- No category
advertisement
Timers
Delay on Release
Types DBA52
• Time range 0.1 s to 100 h
• Knob selection of time range
• Knob-adjustable time setting
• Repeatability:
≤
0.2%
• Output: 8 A SPDT relay
• For mounting on DIN-rail in accordance with DIN/EN
50 022
• 17.5 mm DIN-rail housing
• Combined AC and DC power supply
• LED indication for relay status and power supply ON
Product Description
Multi-voltage delay on release timer with 7 knob selectable time ranges within 0.1s and 100h. For mounting on DIN-rail.
Ordering Key
Housing
Function
Type
Item number
Output
Power supply
DBA 52 C M24
Type Selection
Mounting Output
DIN-rail SPDT
Housing
D-Housing
Supply: 24 VDC and 24 to 240 VAC
DBA 52 C M24
Time Specifications
Time ranges
Knob Selectable
Setting accuracy
Repeatability
0.1 to 1 s
1 to 10 s
6 to 60 s
60 to 600 s
0.1 to 1 h
1 to 10 h
10 to 100h
≤
5%
≤
0.2%
Time variation
Within rated power supply
≤
0.05%/V
Within ambient temperature
≤
0.2%/ºC
Reset
Manual reset of time and/or relay Close the trigger contact
Pulse duration
Power supply interruption between pins A1 and Y1
≥
100 ms
≥
200 ms
Output Specifications
Output
Rated insulation voltage
SPDT relay
250 VAC (rms)
Contact Ratings (AgSnO
Resistive loads
Mechanical life
Electrical life
2
)
AC 1
DC 12
Small inductive loads AC 15
DC 13
µ
5 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥
30 x 10 6 operations
≥
10 5 operations
(at 5 A, 250 V, cos ϕ
= 1)
< 7200 operations/h Operating frequency
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand volt.
2.5 kV (1.2/50 µs)
Supply Specifications
Power supply
Rated operational voltage through terminals:
A1, A2
Overvoltage cat. II
(IEC 60664, IEC 60038)
24 VDC ±15% and
24 to 240 VAC
+10%/-15%, 45 to 65 Hz
≤
10 ms Voltage interruption
Rated operational power
AC supply
DC supply
4 VA
1.5 W
Specifications are subject to change without notice (18.10.02) 1
DBA52
Function and Time Setting
Centre knob:
Time setting on relative scale: 1 to 10 with respect to the chosen range.
Lower knob:
Setting of time range.
Mode of Operation
The relay operates as soon as the trigger contact is closed. The time period begins when the trigger contact is opened. The relay releases at the end of the set delay time or when the power supply is disconnected. The relay operates again when the input contact is closed again. If it is closed before the end of the delay time the relay keeps ON, a new time period begins as soon as the trigger contact is opened again.
Additional Load
It's possible to wire an additional load (i.e. a relay) between pins Y1 and A2 driven by the trigger contact without damaging the device (see wiring diagram).
Yellow LED working mode
Timing: Slow blinking
Relay ON: See operation diagrams
Incorrect knobs position:
Fast blinking
General Specifications
≤
100 ms Power ON delay
Indication for
Power supply status
Output status
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Screw terminals
Tightening torque
LED, green
LED, yellow
(flashing when timing)
(EN 60529)
IP 20
2 (IEC 60664)
-20° to +60°C, R.H.<95%
-30° to +80°C, R.H. < 95%
Approx. 75 g
Approvals
CE Marking
EMC
Immunity
Emission
Timer Specifications
Max. 0.5 Nm according to
IEC EN 60947
UL
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 50081-1
According to EN 61812-1
Wiring Diagrams
DBA52
A1
L(+)
16 ϕ
18
S
Y1
A2
N(-)
15
Operating Diagram
ON
OFF
2 Specifications are subject to change without notice (18.10.02)