DPI-C and DPI-E position indicators for BHH/BHHF actuators

DPI-C and DPI-E position indicators for BHH/BHHF actuators
Data sheet
DPI-C and DPI-E
Sheet No.: DPI-C and DPI-E
Date: October 2010
DPI-C and DPI-E position indicators for BHH/BHHF
actuators
Description:
The DPI is designed to fit Bettis quarter turn valve actuators BHH and BHHF for use
within the temperature range from -20° C to +80° C (-4° F to +176° F). The DPI range
consists of the DPI-E (ON/OFF/switches), DPI-C (Continuous/potentiometer) and the
hydraulic DPI-B (Bypass).
For further information about the DPI-B, please see separate data sheet.
Basic design:
The DPI-C and -E can be mounted in different mounting blocks or in LPU, with only
internal wiring.
Valve/actuator position is indicated by means of a precision potentiometer or 2 microswitches. Resistance (commonly used Ω output) increases during opening and decreases during closing the valve/ actuator.
Set point adjustment is performed without dismounting the DPI or cable from the LPU or
block.
DPI mounted in LPU on BHH actuator.
Pin
Yoke
Adjustment with counter-nut
DPI mounted on BHH actuator.
Adjustment, self-locking
X=
X
9.5 mm (.37 in) (closed)
13.5 mm (.53 in) (open)
Mounting and adjustments:
When mounting the DPI-C/-E be sure not to press the DPI too far towards the actuator.
Several misadjustments of the DPI may cause destruction of the DPI.
When the valve/actuator is closed you may adjust the DPI by screwing it towards the
actuator until the...
- DPI-C: potentiometer reaches the desired 300 Ω (1500 Ω), or
- DPI-E: CLOSED switch closes (opens if NC configuration), and then adjust the desired
overlap
(1° - 5°).
Check the indicator signal in open position. When DPI is mounted in a block, make sure that
the locking screw is tightened sufficiently to prevent the DPI from turning. When mounted in
LPU remember to tighten the counter-nut. If correct adjustment is not possible - check the
yoke distance “X” (see enlargement), and the presence of the yoke.
www.Bettis.com
Copyright © Emerson Process Management. The information in this document is subject to change without notice.
Updated data sheets can be obtained from our website www.bettis.com or from your nearest Valve Automation Center.
USA: +1 281 727 5300 Europe: +31 74 256 1010 Asia-Pacific: +65 6501 4600
Data sheet
DPI-C and DPI-E
Sheet No.: DPI-C and DPI-E
Date: October 2010
Potentiometer:
Standard resistance values: Total resistance tolerance: Independent linearity tolerance: Resolution: Output smoothness: Insulation resistance: Dielectric strength:
Resistance temperature coefficient: Operating temperature range:
Temperature cycle:
- Total resistance value variation:
- No mechanical damage
1k Ω, 2k Ω, 10k Ω
Precision class ± 20%
Precision class ± 5%
Essentially infinite
Below 0.1% against input voltage
Over 50 M Ω at 500 V DC
1 minute at 500 V AC
± 400 p.p.m./°C
-55° C to +125° C
5 cycles under -55° C to 125° C
(-67° F to +257° F)
Below ±10%.
Exposure at low temperature:
24 hours at -55° C (-67° F)
Below ± 5%.
Exposure at high temperature:
1,000 hours at 105° C (+221° F)
Below ± 10%.
Vibration:
- Total resistance value variation
- No mechanical and electrical damage
10 Hz to 2,000 Hz 20 G
Below ± 2%.
Shock:
- Total resistance value variation
- No mechanical and electrical damage
50 G 7 mS
Below ± 1%
Moisture resistance:
40° C (+104° F) 95% RH 120 hours
Below ±10%
Over 10 M Ω
Life expectancy: 500,000 cycles
Below ± 10% against initial value
- Total resistance value variation
- No mechanical damage
- Total resistance value variation
- No mechanical and electrical damage
- Total resistance value variation
- Insulation resistance
Total resistance value variation
Switches:
Contact resistance: Switching current: Dielectric strength: Life expectancy: Min. Insulation resistance: Humidity: www.Bettis.com
Max. 100 m Ω
Max. 100 mA at 30 V DC resistive load
1500 V AC to ground 1 minute
100,000 operations
100 M Ω at 500 V DC
Max. 85%
Copyright © Emerson Process Management. The information in this document is subject to change without notice.
Updated data sheets can be obtained from our website www.bettis.com or from your nearest Valve Automation Center.
USA: +1 281 727 5300 Europe: +31 74 256 1010 Asia-Pacific: +65 6501 4600
Data sheet
DPI-C and DPI-E
Sheet No.: DPI-C and DPI-E
Date: October 2010
Terminal layout:
Enclosure rating:
When mounted in block, cavity seals are designed to fulfill demands of enclosure rating
IP 68.
Note: In case of installation where a larger enclosure rating than IP 67 is required, the
connection house should be filled with silicone after wire mounting and test of function.
With each actuator comes a yoke, fit to transfer the mechanical signal from the actuator
to the DPI.
Potentiometer:
The potentiometer incorporated in the DPI-C is a high quality potentiometer that is
extremely reliable as long as the following ratings are observed:
Max. continuous load:
Max. peak load:
The normal output range is at
0.12 W (VA)
1 W(VA)
1 kΩ:
0-500 Ω for 0-90° rotation*
300-1400 Ω for 0-90° rotation*
2 kΩ:
1500-7000 Ω for 0-90° rotation*
10 kΩ:
*Approx. adjustment for open (1400/7000) and close (300/1500) set point.
Analogue signal processing:
LPU is equipped with signal conditioning, with a 2-wire 4-20 mA signal output.
When DPI-C is block mounted we recommend the Bettis isolation amplifier 2204 for
transforming the resistance signal into a standard 4-20 mA signal.
The output can be displayed visually by means of the Bettis meter PQ 48 measuring 48
x 48 mm and scaled: “closed, 1/4, 1/2, 3/4, open”.
Materials:
Housing:
Screws:
Seals:
Fixture:
Brass, MS 58 (CuZn39Pb3)
AISI 304 (Stainless)
NBR ~ Acrylonitrile Butadiene
PPS
Cable gland data:
Cable outer diameter:
Ingress protection:
Thread:
Material:
Seal material:
Cable quality/connection:
ø 6-10.5 or ø 8-15 mm (.24-.39 or .31 .59 in)
IP 68
M 16 or M 20
Nickel plated brass
Perbunan and NBR (Rubber)
Wiring to the terminal: Cross sections 0.5-1.5 mm2 (AWG 22 - 16).
Observe that water intrusion into the terminal housing can take place through the cable even through each individual wire.
The IP tightness is based on correct and careful mounting.
Note: Not Certified dimensional drawings. Such drawings are available on request. Contact factory with correct model designation and serial number.
Important: Due to Emerson’s continuing commitment to engineered product advancement, data presented herin is subject to change.
The contents of the publication are presented for information purposes only, and while effort has been made to ensure their accuracy,
they are not to be construed as warranties or guarantees, expresses or implied, regarding the products or services described herein or their use or applicability.
All sales are governed by our terms and conditions, which are available on request.
We reserve the right to modify or improve the designs or specifications of our products at any time without notice.
www.Bettis.com
Copyright © Emerson Process Management. The information in this document is subject to change without notice.
Updated data sheets can be obtained from our website www.bettis.com or from your nearest Valve Automation Center.
USA: +1 281 727 5300 Europe: +31 74 256 1010 Asia-Pacific: +65 6501 4600
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement