S R I/O M /S

S R I/O M /S
DL405 Remote I/O
SERIAL REMOTE I/O MASTER/SLAVE MODULES
Remote master
Remote I/O
Master Module
D4-RM
Remote I/O
Slave Module
3300ft
(1000m)
Max.
Remote slaves
Maximum of seven
remote bases per
channel
1 - 80 0 - 633 - 0405
D4-RS
D4-RSDC
Remote slave
Remote master
Overview
The DL405 offers full-size remote I/O.
The goal of remote I/O is to reduce wiring
costs, by allowing I/O points to be located
near the devices they are controlling. The
chart at the bottom of this page shows the
capacity for each CPU. The D4-450 has
the D4-RM functionality built into the
25-pin port directly on the CPU.
However, you can also choose to use the
D4-RM discussed here. Here’s how it
works: A special module called the Remote
Master is placed in the CPU base. This
Master module controls up to seven
Remote Slaves. The Remote Slaves are
connected to the Master in a daisy-chain
manner over a twisted pair communication cable (maximum length of 3300 feet
or 1000m). Each Remote Slave attaches to
a DL405 base (any size). Standard DL405
562
PLC and PC Products
Maximum number of remote masters supported
Maximum I/O points supported
Maximum I/O points supported per channel
Maximum number of remote I/O bases per channel
D4-450
D4-440
D4-430
3*
2
2
1536
1024
512
512
512
512
7
7
7
*max. of 2 D4-RM, 1 channel is via 25-pin CPU port
modules populate the remote bases.
You can assign normal input and output
addresses to the remote points, or you can
assign special remote I/O addresses. The
Remote Master sends the remote I/O
information to the CPU. The communication between the Remote Master and
the CPU is asynchronous to the CPU
scan. For this reason, remote I/O applications should be limited to those that do
not require the remote I/O points to be
updated with every CPU scan.
DL405 Remote I/O
PLC/PC
SERIAL REMOTE I/O
Remote Slave
Remote Master
RE MOTE I/O MAS TE R
P WR
R UN
D4--R S 110/220VAC R E MOTE I/O
PAR
LINK
DIAG
I/O
MS TR
D4--R M
UNIT
ADRS
PWR
I/O
RUN
PAR
DIAG
LINK
Run relay
24V auxiliary
Power
T
1
Logic ground
2
Chassis ground
T
Remote Channel Connector
1
AC power
G
2
110/220
voltage
select
30VDC 1A
CLAS S 2
3
G
D4--RM
Remote Slave Specifications
Remote Master Specifications
Module Type
Intelligent device
Number of Master
per CPU
Two maximum for D4-430 and
D4-440
Three maximum for D4-450
(max. number must include
both Remote Master modules
and Slice Master modules)
Maximum Slaves
Supported
Seven slaves per channel
Communication to
Slaves
Recommended
Cable
Transmission
Distance
Terminal Type
RS485 via twisted pair with
shield @ 38.4K baud
Operating
Environment
0°C to 60°C (32°F to 140°F),
5% to 95% humidity
(non-condensing)
Internal Power
Consumption
Manufacturer
for D4-430
Maximum Slave Points per 512
1024 for D4-440
CPU
1536 for D4-450
I/O Addresses Used
I/O modules in slave bases do not automatically consume any standard input and output
points. They consume remote I/O points at a rate equal to the number of I/O points in
each base. However, you can choose to use standard I/O addresses as an option
Terminal Type
Operating Environment
Fixed
Power required
110 VAC/220 VAC (D4-RS)
24VDC (D4-RSDC)
Manufacturer
Koyo Electronics
0°C to 60°C (32°F to 140°F), 5% to 95% humidity (non-condensing)
w w w. a u to m at i o n d i re c t . c o m / d l 405
3
UNIT
ADRS
Belden 9841 or equivalent
3,300 ft. maximum
Fixed
300 mA maximum
Koyo Electronics