Bloomfield | MOD-500TDM | installation instructions electrical cutout details product dimensions

INSTALLATION INSTRUCTIONS
BUILT-IN FOOD WARMERS
WITH AUTO WATER FILL
MOD-500TDM/AF (1 CONTROL PANEL)
ELECTRICAL
UNIT IS SHIPPED THREE PHASE AND IS FIELD CONVERTIBLE TO SINGLE PHASE.
MODEL
MOD-500TDM/AF
MOD-500TDM/AF
VOLTS
WATTS
208
240
6200
8250
L1
L2
L3
AMPS
SINGLE
PHASE
3 PHASE
1 PHASE
TEMP.
RATING
19.5
22.1
14.6
16.9
14.6
16.9
29.8
34.4
10 AWG Cu
8 AWG Cu
8 AWG Cu
8 AWG Cu
90°C
90°C
AMPS PER LINE 3 PHASE
FIELD WIRING GAUGE
CUTOUT DETAILS
PRODUCT DIMENSIONS
70 3/4
(1797)
TYP
14
(356)
7 3/4
(197)
6
(152)
22 1/2
(572)
23 5/8
(600)
TOP CUTOUT
33 15/16
(862)
2 1/4
(57)
71 1/2
(1816)
3 1/8
(79)
5
(127)
FRONT PANEL CUTOUT
CLEARANCES
1 3/4
(44)
9 3/4
(248)
1/4 INCH
EXTERNAL NPT
WATER LINE
CONNECTION
35 1/16
(890)
6 1/4
(159)
1 INCH
INTERNAL NPT
MANIFOLD EACH END
4. Mount Control Panel onto electrical box using the
screws supplied.
MINIMUM CLEARANCE REQUIRED
UNIT TO THE NEAREST SURFACE
BACK
INCHES
(MM)
SIDE
BOTTOM
FRONT
1
1
6 3/4
6
(25)
(25)
(171)
(152)
INSTALLATION INSTRUCTIONS
INSTALLER MUST MEET CONDITIONS OF ACCEPTABILITY
OUTLINED BELOW UPON INSTALLATION:
1. Required installation clearances:
Wooden and Metal Installation: DO NOT install closer than
6 inches to front wall, 1 inch to back and side walls,
and 6 3/4 inches to surface below the unit. If the control
box is located below the unit, the front clearance may be
1 inch.
2. Unit shall be accessible for servicing from the bottom.
3. If storage is to be used underneath the unit, it is
recommended that a baffle be placed 8 1/2 inches below
the unit to avoid contact with elevated temperatures.
4. For water and waste connections: This appliance is to
be installed to comply with the applicable federal, state, or
local plumbing codes.
TO FABRICATE:
1. Lay out cutout dimensions on countertop and front apron.
TO PLUMB:
1. A drain manifold complete with valve is supplied on all
models except MOD100TD. Location of valve handle is at
the discretion of the fabricator (see drawing).
2. Connect 1" drain connection to suitable drain line.
3. Connect 1/4"NPT water supply to Solenoid valve in
Outlet Box. Note: Maximum pressure 120 psi, maximum
temperature 120°F. A backflow preventor is incorporated
in the unit, between the water fill solenoid and pan. Local
codes may require an additional vacuum break device.
(Not provided by Wells). Device must be installed in
accordance with local codes and authorities having
jurisdiction.
TO WIRE:
1. Final connection is accomplished by bringing proper
power supply leads (see 'WIRING REQUIREMENTS' label)
through conduit knockout to terminal block supplied within
the Master Control Panel. Check nameplates for voltage
and phase.
NOTE: INSTALLATION MUST MEET LOCAL PLUMBING AND
ELECTRICAL CODES.
WARMER FLANGE
TO INSTALL:
IMPORTANT - DO NOT disconnect lead wires from the
Master Control Panel when making installation.
1. Tilt and pass Control Panel and electrical box through
the countertop cutout, then through the apron cutout.
Lower modular section into countertop cutout and position.
RECOMMENDATION: Before final seating of modular section
to countertop, apply a bead of silicone adhesive/sealant
to the underside of gray gasket material supplied on the
mounting flange.
2. From underneath, insert screwdriver into slots in
Wellslock frame and twist ears outward (clockwise) as
required to secure flange tightly to countertop.
3. Mount Control Box to apron cutout as shown in drawing.
COUNTERTOP
GASKET
2. Lay out and fabricate control panel holes in counter
apron using the control box as a template.
3. Cut out holes.
WELLSLOK
SCREWDRIVER
OUTLET BOX
SOLENOID
MASTER
CONTROL
PANEL
IMPORTANT:
MOUNT APPLIANCE SO THAT BOTH THE
MASTER CONTROL PANEL AND DRAIN
MANIFOLD ARE LOCATED TO THE FRONT
OF THE FIXTURE.
WATER SUPPLY
1/4 NPT
WELLS/BLOOMFIELD * VERDI, NV
303570-5 REV (-)