F2-04AD-1 4-Channel 4-20mA Analog In
$207.00
This module can be powered by either a 12 VDC or 24 VDC power supply, and is a direct
replacement for F2-04AD-1L modules.
Number of Channels
4, single ended (1 common)
Input Ranges
4 to 20 mA current
Resolution
Maximum Inaccuracy
±.5% @ 77ºF (25ºC)
±.65% 32º to 140ºF (0º to 60ºC)
12-bit (1 in 4096)
Accuracy vs.Temperature
±50 ppm/ºC maximum full scale
(including max. offset change)
Active Low-pass Filtering
-3 dB at 120 Hz,2 poles
(-12 dB per octave)
Recommended Fuse
0.032 A, Series 217 fast-acting, current inputs
Input Impedance
250 ±0.1%, 1/2W current input
Digital Input Points Required 2 channel ID bits, 2 diagnostic bits)
Absolute Maximum Ratings
-40 mA to +40 mA, current input
Base Power Required 5 VDC 100 mA
Converter Type
Successive approximation
External Power Supply
5 mA maximum, +10 to +30 VDC
Conversion Time
(PLC Update Rate)
1 channel per scan maximum (D230 CPU);
4 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158°F (-20º to 70ºC)
Linearity Error (End to End)
±1 count (0.025% of full scale) maximum
Relative Humidity
5 to 95% (non-condensing)
Input Stability
Full Scale Calibration Error
(offset error not included)
Offset Calibration Error
±1 count
Environmental Air
No corrosive gases permitted
±12 counts max., @ 20 mA current input
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Step Response
4.9 ms to 95% of F.S. change
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
16 (X) input points (12 binary data bits,
±7 counts max.,@ 4mA current input
See Wiring Solutions for part numbers of ZIPLink
cables and connection modules compatible with
this I/O module.
One count in the specification table is equal to one least significant bit of the
analog data value (1 in 4096).
Note 1: Shields should be grounded at the signal source
IN
Internal
Module
Wiring
S ee NOTE 1
0 VDC
-+
-CH1
4--wire
4--20mA +
Trans mitter
CH1--
250
DC to DC
Converter
+24 VDC
+5V
+15V
0V
--15V
CH1+
CH2--
CH3--
250
CH3+
-CH3
2-wire
4--20mA +
Trans mitter
CH4--
250
CH4+
F2-04AD-1
18-26.4VDC
5mA
0V
250
CH2+
Analog S witch
+
-CH2
3--wire
4--20mA +
Trans mitter
ANALOG
ANA
4CH
A to D
Converter
+24V
CH1–
CH1+
CH2–
CH2+
CH3–
CH3+
CH4–
-CH4
2-wire
4--20mA +
Trans mitter
CH4+
ANALOG IN
4-20mA
+
Optional
E xternal
P /S
-+
-24VDC
OV
More than one external power supply can be used provided all the power supply commons are connected. A Series 217, 0.032A, fast-acting fuse is recommended for
4-20 mA current loops. If the power supply common of an external power supply is not connected to 0VDC on the module, then the output of the external transmitter
must be isolated. To avoid “ground loop” errors, recommended 4-20 mA transmitter types are:
2 or 3 wire: Isolation between input signal and power supply.
4 wire: Isolation between input signal, power supply, and 4-20 mA output
Book 1 (14.1)
eD2-98
DL205 PLCs
1 - 80 0 - 633 - 0405
Analog Current Input Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-08AD-1 8-Channel 4-20mA Analog In $255.00
Company
Information
Maximum Inaccuracy
±.1% @ 77ºF (25ºC)
±.25% 32º to 140ºF (0º to 60ºC)
Control Systems
Overview
CLICK PLC
Number of Channels
8, single ended (1 common)
Input Ranges
4 to 20 mA current
Accuracy vs.Temperature
±50 ppm/ºC maximum full scale
(including max. offset change of two counts)
Resolution
12 bit (1 in 4096)
Recommended Fuse
0.032A, Series 217 fast-acting, current inputs
Low-pass Filtering
-3dB at 200 Hz, (-6dB per octave)
Input Impedance
250 ±0.1%, 1/2W current input
Absolute Maximum Ratings
-45 mA to +45 mA
Base Power Required 5VDC
100 mA
Converter Type
Successive approximation
External Power Supply
5 mA maximum, +10 to +30 VDC
Conversion Time (PLC
Update Rate)
(D2-230 CPU) 1 channel per scan maximum
(D2-240, D2-250(-1) and D2-260 CPUs) 8
channels per scan maximum
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Linearity Error (End to End)
±1 count (0.025% of full scale) maximum
Relative Humidity
5 to 95% (non-condensing)
Input Stability
Full Scale Calibration Error
(offset error not included)
Offset Calibration Error
±1 count
Environmental Air
No corrosive gases permitted
±5 counts max., @ 20 mA current input
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Step Response
1 ms to 95% of F.S. change
Terminal Type (included)
Removable; D2-8IOCON
16 (X) input points
Digital Input Points Required (12 binary data bits, 3 channel ID bits, 1 broken
transmitter bit)
±2 counts max., @ 4mA current input
See Wiring Solutions for part numbers of ZIPLink
cables and connection modules compatible with this
I/O module.
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
Controller
Overview
Productivity
3000
Universal
Field I/O
One count in the specification table is equal to one least
significant bit of the analog data value (1 in 4096).
Note 1: Shields should be grounded at the signal source.
S e e NOTE 1
DC to DC
C onve rte r
0 VDC
+24 VDC
--
IN
Inte rna l
Module
Wiring
+
-C H1
4 -- wire
+
4 -- 20mA
Tra ns mitte r
0V
CH2+
250
CH6+
-C H6
2-wire
4 -- 20mA
+
Tra ns mitte r
CH7+
250
Other HMI
A to D
C onve rte r
+24V
Communications
CH2+
Appendix
Book 1
CH4+
Terms and
Conditions
CH1+
CH3+
CH5+
CH6+
CH8+
--
C H8
2-wire
+
4 -- 20mA
Tra ns mitte r
250
CH7+
CH8+
ANALOG IN
4-20mA
+
Optiona l
E xte rna l
P /S
Ana log S witch
CH4+
CH5+
-+
-24VDC
OV
More than one external power supply can be used provided all the power supply commons are connected. A Series 217, 0.032A, fast-acting fuse is recommended for
4-20 mA current loops. If the power supply common of an external power supply is not connected to 0 VDC on the module, then the output of the external transmitter
must be isolated. To avoid "ground loop" errors, recommended 4-20 mA transmitter types are:
2 or 3 wire: Isolation between input signal and power supply.
4 wire: Isolation between input signal, power supply, and 4-20 mA output
Book 1 (14.1)
w w w. a u to m a t i o n d i re c t . c o m / d l 205
C-More
HMI
ViewMarq
Industrial
Marquees
0V
CH3+
+
+
C H4
3 -- wire
-4 -- 20mA
Tra ns mitte r
F2-08AD-1
10-30VDC
5mA
250
Software
C-More Micro
HMI
+5V
+15V
-- 15V
CH1+
ANALOG
ANA
8CH
DL205 PLCs
eD2-99
Analog Voltage Input Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-04AD-2 4-Channel Voltage Analog In $228.00
This module can be powered by either a 12 VDC or 24 VDC power supply, and is a direct
replacement for F2-04AD-2L modules.
Maximum Inaccuracy
±.1% @ 77ºF (25ºC)
±.3% 32º to 140ºF (0º to 60ºC)
Accuracy vs.Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change )
Number of Channels
4, single ended (1 common)
Input Ranges
0 to 5V, 0 to 10 V, ±5V, ±10 V
Resolution
12 bit (1 in 4096)
16(x) input points
Digital Input Points Required (12
binary data bits, 2 channel ID bits)
Active Low-pass Filtering
-3 dB at 80 Hz, 2 poles (-12 dB per octave)
Base Power Required 5VDC
110 mA
Input Impedance
>20 M
External Power Supply
5 mA maximum, +10 to +30 VDC
Absolute Maximum Ratings
-75 to +75 VDC
Operating Temperature
32º to 140ºF (0 to 60ºC)
Converter Type
Successive approximation
Storage Temperature
-4º to 158°F (-20º to 70ºC)
Conversion Time
(PLC Update Rate)
1 channel per scan maximum (D2-230 CPU)
4 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Linearity Error (End to End)
±1 count (0.025% of full scale) maximum
±2 counts maximum (bi-polar)
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
Input Stability
Full Scale Calibration Error
(offset error not included)
Offset Calibration Error
±1 count
Step Response
8.2 ms to 95% of F.S change
±3 counts maximum
±1 count maximum (0V input)
See Wiring Solutions for part numbers of ZIPLink
the analog data value (1 in 4096).
Notes:
1. Shields
should
be grounded
cables
and connection
modules
compatible
with at the signal source.
Note 1: Shields should be grounded at the signal source.
this I/O module.
2. Unused inputs should be jumpered together (i.e. Ch4-- to Ch4+).
One count in the specification table is equal to one least significant bit of
Note 2: Unused inputs should be jumpered together (i.e. CH4- to CH4+).
3. More than one external power supply can be used provided
the
Note 3: More than one external power supply can be used provided the
commons are connected together.
commons are connected together.
4. F2-04AD-2L requires 10--15 VDC input supply.
Module Supply
See NOTE 3
10-30 VDC
+ 18--26.4VDC
--
Typical User Wiring
Typical Us er Wiring
+
See
S eeNOTE
NOTE11
0 0VDC
VDC
0 0V V
+24
VDC
+24
VDC
--
--
2424V V
CH1-CH1-
-+
0V
0V
CH1
CH1
CH2-CH2CH2+
CH2+
CH2
CH2
CH3-CH3-
+
CH3+
CH3+
+
-CH3 +
-Voltage
CH3
+
Transmitter
Voltage
+
Trans mitter
CH3
CH3
CH4-CH4CH4+
CH4+
CH4
CH4
+
-CH4 +
-Voltage
CH4
+
Transmitter
Voltage
+
Trans mitter
Analog S witch
Analog Switch
+
F2-04AD-2
F2--04AD--2
10-30VDC
5mA
0V
10--30VDC
5mA
---
ANALOG
ANA
4CH
ANALOG
4CH
+5V
+5V
+15V
+15V
--15V
--15V
CH1+
CH1+
+
IN
DC to DC
DC to DC
Converter
Converter
+
-+
CH1
Voltage
CH1
Transmitter
Voltage
Trans mitter
+
CH2 +
Voltage
CH2
Transmitter
Voltage
Trans mitter
IN
Internal
Internal
Module
Module
Wiring
Wiring
--
A to D
Converter
A to D
Converter
0V+24V
+24V
CH1–
CH1-CH1+
CH1+
CH2–
CH2-CH2+
CH2+
CH3–
CH3-CH3+
CH3+
CH4–
CH4-CH4+
CH4+
ANALOG IN
0--5, 0--10VDC
+/--5,+/--10VDC
+
ANALOG IN
0-5, 0 -10VDC
- 10VDC
+/-5, +/-10VDC
-5-12VDC
See NOTE 3
Supply
OV
OV
Transmitter Supply
24 volts model shown, but wiring is
the same for 12 volts model.
Book 1 (14.1)
eD2-100
DL205 PLCs
1 - 80 0 - 633 - 0405
Analog Voltage Input Modules
Prices as of April 16, 2014. Check Web site for most current prices.
Company
Information
Control Systems
Overview
F2-08AD-2 8-Channel Voltage Analog In $274.00
Number of Channels
8, single ended (1 common)
Input Ranges
0 to 5V, 0 to 10 V, ±5V, ±10 VDC
CLICK PLC
Maximum Inaccuracy
±.1% @ 77ºF (25ºC)
±.3% 32º to 140ºF (0º to 60ºC)
Resolution
12 bit (1 in 4095) uni-polar
13 bit (-4095 to 4095) bi-polar
Accuracy vs.Temperature
±50 ppm/ºC maximum full scale
(including max. offset change of 2 counts)
Active Low-pass Filtering
-3dB at 200 Hz,
(-6dB per octave)
Digital Input Points Required (12 binary data bits, 3 channel ID bits, 1 sign bit,
Input Impedance
>20 M
Base Power Required 5VDC
100 mA
Absolute Maximum Ratings
-75 to +75 VDC
External Power Supply
5 mA maximum, +10 to +30 VDC
Converter Type
Successive approximation
Operating Temperature
32º to 140ºF (0º to 60ºC)
Conversion Time (PLC
Update Rate)
1 channel per scan maximum (D2-230 CPU)
8 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Linearity Error (End to End)
±1 count (0.025% of full scale) maximum
Environmental Air
No corrosive gases permitted
Input Stability
Full Scale Calibration Error
(offset error not included)
Offset Calibration Error
±1 count
Vibration
MIL STD 810C 514.2
±3 counts maximum
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Step Response
Removable; D2-8IOCON
1 ms to 95% of F.S. change
Terminal Type (included)
16 (X) input points,
1 diagnostic bit)
±1 count maximum (0V input)
One count in the specification table is equal to one least significant bit of the analog data value (1 in
4096). Includes circuitry to automatically detect broken or open transmitters.
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
See Wiring Solutions for part
numbers of Z IPLink cables and
connection modules compatible
with this I/O module.
Note 1: Shields should be grounded at the signal source.
Note 2: Connect all external power supply commons.
Note 3: Connect unused channels (CH5+, CH6+, CH7+, CH8+ in this example) to 0VDC.
DirectLOGIC
DL405
Productivity
Controller
Overview
Productivity
3000
Universal
Field I/O
Software
C-More
HMI
24VDC
+
IN
ANA
ANALOG
8CH
0 VDC
24VDC
C H1
+
3-wire
+
Volta g e
Tra ns mitte r -
CH4
+
3-wire
+
Volta g e
Tra ns mitte r -
C H3+
C H4+
C H5+
C H6+
C H7+
C H8 +
Communications
Appendix
Book 1
10-30VDC
5mA
0V
Terms and
Conditions
+24V
AD C
CH3
+
4-wire
+ Volta g e
- Tra ns mitte r
C H2+
CH1+
CH2+
CH3+
CH4+
CH5+
CH6+
CH7+
CH8+
ANALOG IN
0-5.0 --10VDC
10VDC
+/-5, +/-10VDC
Book 1 (14.1)
w w w. a u to m a t i o n d i re c t . c o m / d l 205
DL205 PLCs
ViewMarq
Industrial
Marquees
Other HMI
F2-08AD-2
C H1+
Analog Multiplexer
CH2
+
2-wire
Volta g e
Tra ns mitte r -
0V
C-More Micro
HMI
eD2-101
Temperature Input Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-04RTD 4-Channel RTD In
$310.00
Number of Channels
4
Input Ranges
Type Pt100: -200.0/850.0ºC,
-328/1562ºF
Type Pt1000: -200.0/595.0ºC,
-328/1103ºF
Type jPt100: -38.0/450.0ºC,
-36/842ºF
Type CU-10/25ž: -200.0/260.0ºC,
-328/500ºF
Resolution
Display Resolution
RTD Excitation Current
Input Type
16 bit (1 in 65535)
Notch Filter
>100 db notches at 50/60 Hz
-3db=13.1Hz
Maximum Setting Time
Common Mode Range
Absolute Maximum
Ratings
Sampling Rate
100ms (full-scale step input)
Converter Type
Charge Balancing
Linearity Error
±.05ºC maximum, ±.01ºC typical
Maximum Inaccuracy
±1ºC
PLC Update Rate
4 channel/scan max., 240/250(-1)/D2-260CPUs
1 channel per scan max., 230 CPU
32 input points (16 binary data bits,
Digital Input Points Required 2 channel ID bits, 4 fault bits)
Base Power Required 5VDC
90 mA
Operating Temperature
32° to 140°F (0° to 60°C)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Temperature Drift
None (self-calibrating)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
0-5 VDC
Vibration
MIL STD 810C 514.2
Fault protected inputs to ±50 VDC
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
±0.1ºC, ±0.1ºF (±3276.7)
200 µA
Differential
160 ms per channel
Notes:
1. The three wires connecting the RTD to the module must be the same type and
length. Do not use the shield or drain wire for the third connection.
2. If an RTD sensor has four wires, the plus sense wire should be left unconnected
as shown.
3. This module is not compatible with the ZIPLink wiring systems.
Note 1
IN
Ch1 Ch1 +
Ch2 Ch2 +
Note 2
Ch3 -Ch3 +
Ch4 -Ch4 +
x
Analog Multiplexer
C
C
200 A
Current
S ource
RTD
TEMP
F2-04RTD
RTD
INPUT
R ef.
Adj.
CH1–
CH1+
CH2–
+
A/D
-
CH2+
COM
COM
CH3–
0V
200 A
Current
S ource
CH3+
CH4–
CH4+
F2-04RTD
Book 1 (14.1)
eD2-102
DL205 PLCs
1 - 80 0 - 633 - 0405
Temperature Input Modules
Prices as of April 16, 2014. Check Web site for most current prices.
Company
Information
Control Systems
Overview
F2-04THM 4-Channel Thermocouple In $310.00
General Specifications
CLICK PLC
Thermocouple Specifications
Number of Channels
4, differential
Common Mode Range
±5 VDC
Common Mode Rejection
90 dB min. @ DC, 150 dB min. @ 50/60 Hz.
Input Impedance
1 M
Absolute Maximum Ratings
Fault-protected inputs to ±50 VDC
Accuracy vs. Temperature
±5 ppm/ºC maximum full scale calibration
(including maximum offset change)
PLC Update Rate
4 channels per scan max.
D2-240/250(-1)/D2-260 CPU, H2-EBC(-F);
1 chan. per scan max. D2-230 CPU
Type J -190 to 760ºC
Type E -210 to 1000ºC
Type K -150 to 1372ºC
Type R 65 to 1768ºC
Type S 65 to 1768ºC
Type T -230 to 400ºC
Type B 529 to 1820ºC
Type N -70 to 1300ºC
Type C 65 to 2320ºC
Input Ranges
Display Resolution
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
(X) input points (16 binary data bits,
Digital Input Points Required 232channel
ID bits, 4 diagnostic bits)
Warm-Up Time
30 minutes typically ± 1ºC repeatability
External Power Supply
60 mA maximum, 18 to 26.4 VDC
Linearity Error (End to End)
±.05ºC maximum, ±.01ºC typical
Base Power Required 5VDC
110 mA
Maximum Inaccuracy
±3ºC (excluding thermocouple error)
Operating Temperature
32º to 140ºF (0º to 60ºC)
Voltage Input Specifications
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Voltage Ranges
0-5V, ±5V, 0-156.25 mV, ±156.25 mVDC
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Resolution
Full Scale Calibration Error
(Offset Error Included)
Offset Calibration Error
16 bit (1 in 65535)
No corrosive gases permitted
Noise Immunity
Linearity Error (End to End)
±1 count maximum
NEMA ICS3-304
Terminal Type (included)
±.02% @ 25ºC (77ºF)
Non-removable
Maximum Inaccuracy
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
Controller
Overview
±13 counts typical ±33 maximum
±1 count maximum, @ 0V input
Productivity
3000
Universal
Field I/O
Notes:
1: Terminate shields at the respective signal source.
CPU Firmware Required
Software
Firmware Required
2: Connect unused channels to a common terminal (0V, CH4+, CH4).
V1.06
V2.5
V1.06
All firmware versions work
3: When using 0-156 mV and 5V ranges, connect (-) or (0) volts terminal to 0V to
ensure common mode range acceptance.
4. This module is not compatible with the ZIPLink wiring system.
Thermocouple input wiring diagram
TEMP
VOLT
See Notes 2 and 3
C H1+
C H1
F2-04THM
C H1
THERMOCOUPLE mV
0-5, -5-+5VDC
C H2+
C H4+
Module S upply
C H4
24
VDC
+24VDC
C H3+
Volta g e
Tra ns mitte r
Tra ns mitte r
S upply
C H3
+
--
ADC
C H3
C H2
Ana log Mux
C H3+
C H2+
Volta g e
Tra ns mitte r
ADC
Ana log Mux
C H2
C H4+
C H4
0V
24
VDC
0V
Module S upply
+24VDC
0V
0V
CH1 +
CH1
CH2 +
CH2
CH3 +
CH3
CH4 +
CH4
+24V
0v
18-26.4VDC, 60mA
Book 1 (14.1)
w w w. a u to m a t i o n d i re c t . c o m / d l 205
ViewMarq
Industrial
Marquees
Other HMI
Communications
C H1+
Volta g e
Tra ns mitte r
C-More
HMI
C-More Micro
HMI
IN
Voltage input wiring diagram
See Notes 1 and 2
Examples of grounded
thermocouple wiring
Do-More T1H
PLC
Cold Junction Compensation Automatic
100 ms per channel
Examples of differential
thermocouple wiring
Do-More H2
PLC
±0.1ºC or ±0.1ºF
Conversion Time
CPU
D2-230
D2-240
D2-250
D2-250-1, D2-260
Do-More
PLCs Overview
-310 to 1400ºF
-346 to 1832ºF
-238 to 2502ºF
149 to 3214ºF
149 to 3214ºF
-382 to 752ºF
984 to 3308ºF
-94 to 2372ºF
149 to 4208ºF
DL205 PLCs
eD2-103
Appendix
Book 1
Terms and
Conditions
Analog Current Output Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-02DA-1 2-Channel 4-20 mA Analog Output $162.00
This module requires a 24 VDC user power supply for operation. See the F2-02DA-1L on
the next page if you want to use a 12 VDC supply. All other specifications are the same.
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
0.1% @ 77ºF (25ºC)
0.3% @ 32º to 140ºF (0º to 60ºC)
Number of Channels
2
Output Ranges
4 to 20 mA
Resolution
12 bit (1 in 4096)
Base Power Required 5VDC
40 mA
Output Type
Digital Output Points
Required
Maximum Loop Supply
Single ended, one common
External Power Supply
18 to 30 VDC, 60 mA.
(add 20 mA for each current loop used)
16 (Y) output points
(12 binary data bits, 2 channel ID bits)
Operating Temperature
32º to 140ºF (0º to 60ºC)
30 VDC
Storage Temperature
-4 to 158ºF(-20 to 70ºC)
40 VDC
(clamped by transient voltage suppressor)
Relative Humidity
5% to 95% (non-condensing)
Peak Output Voltage
Environmental Air
No corrosive gases permitted
Load Impedance
Maximum Load/Power
Supply
0 minimum
Vibration
MIL STD 810C 514.2
620 /18 V, 910 /24 V, 1200 / 30V
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
PLC Update Rate
1 channel per scan maximum D2-230 CPU
2 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Linearity Error (end to end)
±1 count (±0.025% of full scale) maximum
Conversion Settling Time
Full Scale Calibration Error
(offset error included)
Offset Calibration Error
100 µs maximum (full scale change)
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).
NOTE 1: Shields should be connected to the 0V of the module or the OV of the R/S.
NOTE 2: Unused current outputs should remain open (no connections) for minimum
power consumption.
± 5 counts max., 20 mA @77ºF (25ºC)
± 3 counts max., 4 mA @ 77ºF (25Cº)
See Wiring Solutions for part numbers of ZIPLink
cables and connection modules compatible with this
I/O module.
Internal
Module
Wiring
0 VDC
See
NOTE 1
Ch 1 load
250Ω typical
CH1-CH2-N/C
Ch 2 load
250Ω typical
N/C
+
24 VDC
Maximum user load is dependent upon loop power
supply
Loop power supply
30 VDC
24 VDC
18 VDC
Load range
0 to 1200
0 to 910
0 to 620
+24 VDC
DC to DC
Converter
60m A
Typical user wiring
CH1+
OUT
+5V
+15V
F2-02DA-1
0V
-- 15V
D to A
Converter
CH2+
Ch 1
Current sinking
N/C
D to A
Converter
Ch 2
Current sinking
N/C
Transient protected
precision digital to analog
converter output circuits
--
ANALOG
ANA
2CH
18-30VDC
60mA
ANALOG OUT
4-20mA
0V
+24V
CH1–
CH1+
CH2–
CH2+
NC
NC
NC
NC
F2-02DA1
OV
Book 1 (14.1)
eD2-104
DL205 PLCs
1 - 80 0 - 633 - 0405
Analog Current Output Modules
Prices as of April 16, 2014. Check Web site for most current prices.
Company
Information
Control Systems
Overview
F2-02DA-1L 2-Ch 4-20mA Analog Output $155.00
This module requires a 12 VDC user power supply for operation. See the F2-02DA-1 on the
previous page if you want to use a 24 VDC supply. All other specifications are the same.
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
+0.1% @ 77ºF (25ºC)
±0.3% @ 32 to 140°F (0 to 60°C)
Number of Channels
2
Output Ranges
4 to 20 mA
Resolution
12 bit (1 in 4096)
Base Power Required 5VDC
40 mA
Output Type
Digital Output Points
Required
Maximum Loop Supply
Single ended, 1 common
External Power Supply
10 to 15 VDC, 70 mA
(add 20 mA for each current loop used)
16(Y) output points
(12 binary data bits, 2 channel ID bits)
Operating Temperature
32º to 140ºF (0º to 60ºC)
30 VDC
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
40 VDC
(clamped by transient voltage suppressor)
Relative Humidity
5 to 95% (non-condensing)
Peak Output Voltage
Environmental Air
No corrosive gases permitted
Load Impedance
Maximum Load/Power
Supply
0 minimum
Vibration
MIL STD 810C 514.2
620/18V, 910/24V, 1200/30V
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
2 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Linearity Error (end to end)
±1 count (0.025% of full scale) maximum
Conversion Settling Time
Full Scale Calibration Error
(offset error included)
Offset Calibration Error
100 µs maximum (full scale change)
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
NOTE 1: Shields should be connected to the 0V of the module or the OV of the P/S.
NOTE 2: Unused current outputs should remain open (no connections) for minimum
power consumption.
±3 counts max., 4mA @ 77ºF (25ºC)
0 VDC
DC to DC
C onve rte r
+12 VDC
CH1--
OUT
ANALOG
ANA
2CH
+5V
+15V
F2-02DA-1L
0V
-- 15V
S ee
NOTE 1
CH1+
CH2--
D to A
C onve rte r
CH2+
Ch 1
C urre nt s inking
N/C
N/C
Ch 2 load
250Ω typical
D to A
C onve rte r
N/C
Ch 2
C urre nt s inking
N/C
Transient protected
precision digital to analog
converter output circuits
--
10-15VDC
70mA
ANALOG OUT
4-20mA
Other HMI
CH1+
Terms and
Conditions
CH1–
CH2–
CH2+
NC
NC
NC
NC
OV
DL205 PLCs
ViewMarq
Industrial
Marquees
Appendix
Book 1
Book 1 (14.1)
w w w. a u to m a t i o n d i re c t . c o m / d l 205
C-More Micro
HMI
+12V
Maximum user load is dependent upon loop power supply.
Load range (ohm)
0 to 450
0 to 300
0 to 200
C-More
HMI
Communications
0V
F2-02DA-1L
12 VDC
Loop power supply
15 VDC
12 VDC
10 VDC
Productivity
Controller
Overview
Software
70m A + 20m A
for e a c h loop
+
DirectLOGIC
DL405
Universal
Field I/O
Internal
Module
Wiring
Ch 1 load
250Ω typical
DirectLOGIC
DL305
Productivity
3000
See Wiring Solutions for part numbers of ZIPLink
cables and connection modules compatible with
this I/O module.
Typical User Wiring
Do-More
PLCs Overview
Do-More H2
PLC
One count in the specification table is equal to one least significant bit of the analog
data value (1 in 4096).
±5 counts max., 20 mA @ 77ºF (25ºC)
CLICK PLC
eD2-105
Analog Current Output Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-02DAS-1 2-Channel Isolated 4-20mA Analog Output
$228.00
Linearity Error (end to end)
±10 count (±0.015% of full scale) maximum
Gain Calibration Error
±32 counts (±0.05%)
Offset Calibration Error
±13 counts (±0.02%)
Output Drift
50 ppm/ºC
32 (Y) output points
(16 binary data bits, 2 channel ID bits,
1 output enable bit)
Maximum Inaccuracy
0.07% @ 25ºC (77ºF)
0.18% 0 to 60ºC (32º to 140ºF)
Operating Temperature
0º to 60ºC (32º to 140ºF)
Isolation Voltage
±750 V continuous, channel to channel,
channel to logic
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Base Power Required 5VDC
Relative Humidity
5 to 95% (non-condensing)
100 mA
Loop Supply
Environmental air
No corrosive gases permitted
18-32 VDC
External Power Supply
MIL STD 810C 514.2
18-32 VDC @ 50 mA per channel
Vibration
Output Loop Compliance
Shock
MIL STD 810C 516.2
Vin - 2.5V
Load Impedance
Maximum Load/ Power
Supply
0-1375 (@ 32 V)
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
Number of Channels
2, isolated
Output Ranges
4 to 20 mA
Resolution
16 bit (1 in 65536)
Output Type
Current sourcing
Digital Output Points
Required
375 /12 V, 975 /24 V, 1375 /32 V
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
2 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Conversion Settling Time
3ms to 0.1% of full scale
One count in the specification table is equal to one least significant bit of the
analog data value (1 in 65536).
NOTE 1: Shields should be connected to the 0V terminal of the module.
NOTE 2: Load must be within compliance voltage.
NOTE 3: For non-isolated outputs, connect all 0V’s together (0V1…0V2) and
connect all +V’s together (+V1…+V2).
See Wiring Solutions for part numbers of ZIPLink
cables and connection modules compatible with this
I/O module.
Internal module
wiring
OUT
Typical user wiring
ANALOG
ANA
2CH
0 V1
-Trans mitter
S upply
18--32VDC +
Ch 1 load
0--1375 ohms
NOTE 2
+V1
4--20mAcurrent sourcing
--I1
+I1
D/A
S ee
NOTE 1
N/C
Ch 2 load
0--1375 ohms
NOTE 2
+V1
– I1
+V2
4--20mAcurrent sourcing
+I2
D/A
S ee
NOTE 3
+I1
NC
N/C
--I2
S ee
NOTE 1
12-32VDC
ANALOG OUT
4-20mA
0V1
100 ohms
N/C
0V2
-Trans mitter
S upply
18--32VDC +
F2-02DAS-1
100 ohms
0V2
+V2
– I2
+I2
F2-02DAS-1
Book 1 (14.1)
eD2-106
DL205 PLCs
1 - 80 0 - 633 - 0405
Analog Current Output Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-08DA-1 8-Channel 4-20mA Analog Output
Number of Channels
8, single-ended
Output Ranges
4 to 20 mA
Resolution
12 bit (1 in 4096)
Output Type
Company
Information
Control Systems
Overview
$310.00
CLICK PLC
Linearity Error (end to end)
±2 count (±0.050% of full scale) maximum
Full Scale Calibration Error
Current sinking or current sourcing
± 12 counts max. sinking @ any load
± 12 counts max. sourcing @ 125 load
± 18 counts max. sourcing @ 250 load
± 26 counts max. sourcing @ 400 load
Digital Output Points
Required
16 (Y) output points
(12 binary data bits, 3 channel ID bits, 1 output
enable bit)
Offset Calibration Error
± 9 counts max. sinking @ any load
± 9 counts max. sourcing @ 125 load
± 11 counts max. sourcing @ 250 load
± 13 counts max. sourcing @ 400 load
Base Power Required 5VDC
30 mA
Maximum Loop Voltage
30 VDC
External Power Supply
18 to 30 VDC, 50 mA., class 2
(add 20 mA for each current loop used)
Maximum Full Scale
Inaccuracy @ 60ººC
0.5% sinking (any load) sinking & sourcing @
125 load
0.64% sourcing @ 250 load
0.83% sourcing @ 400 load
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
Source Load
0-400 @ 18-30 VDC
Maximum Full Scale
Inaccuracy @ 25ººC
Sink Load
0-600 /18V, 0-900 /24 V, 0-1200 /30 V
(Incudes all errors and temp drift)
0.3% sinking (any load) sinking & sourcing @
125 load
0.44% sourcing @ 250 load
0.63% sourcing @ 400 load
Total Load (sink + source)
600 /18 V, 900 /24 V, 1200 /30 V
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4 to 158ºF(-20 to 70ºC)
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
8 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Relative Humidity
5% to 95% (non-condensing)
400 µs maximum (full scale change)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-16IOCON
Conversion Settling Time
See Wiring Solutions for part numbers of ZIPLink
cables and connection modules compatible with
this I/O module.
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
Controller
Overview
Productivity
3000
Universal
Field I/O
Software
NOTE 1: Shields should be connected to the 0V of the module.
ANALOG
OUT
8 CHANNEL
F2-08DA-1
18-26.4VDC
80mA
4-20mA
SNK-SRC
1-O
2-O
3-O
4-O
5-O
6-O
7-O
8-O
0V
DL205 PLCs
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
Communications
1-I
Appendix
Book 1
2-I
3-I
4-I
Terms and
Conditions
5-I
6-I
7-I
8-I
N/C
24V
Book 1 (14.1)
w w w. a u to m a t i o n d i re c t . c o m / d l 205
C-More
HMI
eD2-107
Analog Voltage Output Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-02DA-2 2-Channel Voltage Analog Output $169.00
This module requires a 24 VDC user power supply for operation. See the F2-02DA-2L on
the next page if you want to use a 12 VDC supply. All other specifications are the same.
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change (including maximum offset change of 2 counts)
Maximum Inaccuracy
+0.3% unipolar ranges @ 77ºF (25ºC)
±0.45% unipolar ranges >77ºF (25ºC)
±0.4% bipolar ranges @77ºF (25ºC)
±0.55% bipolar ranges >77ºF (25ºC)
Base Power Required 5VDC
40 mA
External Power Supply
18 to 30 VDC, 60 mA (outputs fully loaded)
Operating Temperature
32º to 140ºF (0º to 60ºC)
Number of Channels
2
Output Ranges
0 to 5V, 0 to 10 V, ±5V, ±10 V
Resolution
12 bit (1 in 4096)
Output Type
Digital Output Points
Required
Single ended, 1 common
Peak Output Voltage
15 VDC (clamped by transient voltage suppressor)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Load Impedance
2000 minimum
Relative Humidity
5 to 95% (non-condensing)
Load Capacitance
.01 µF maximum
Environmental Air
No corrosive gases permitted
PLC Update Rate
1 channel per scan maximum D2-230 CPU
2 channels per scan maximum (D2-240, D2250(-1) and D2-260 CPUs)
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Linearity Error (end to end)
±1 count (0.025% of full scale) maximum
Noise Immunity
NEMA ICS3-304
Conversion Settling Time
Full Scale Calibration Error
(offset error included)
5µs maximum (full scale change)
Terminal Type (included)
Removable; D2-8IOCON
Offset Calibration Error
±3 counts max., unipolar @ 77ºF (25ºC)
±8 counts max., bipolar @ 77ºF (25ºC)
16 (Y) output points
(12 binary data bits, 2 channel ID bits)
±12 counts max. unipolar @ 77ºF (25ºC)
±16 counts max. bipolar @ 77ºF (25ºC)
See Wiring Solutions for part numbers of ZIPLink
cables and connection modules compatible with
this I/O module.
One count in the specification table is equal to one least significant bit of the
analog data value (1 in 4096).
NOTE 1: Shields should be connected to the 0V of the module or the OV of the
R/S.
NOTE 2: Unused voltage outputs should remain open (no connections) for minimum power consumption.
Internal
Internal module
Module
wiring
Wiring
24 VDC
+
Typical Us
usererwiring
Typical
Wiring
0 VDC
Ch 1 load
2K
minimum
DC to DC
Converter
S ee
NOTE 1
OUT
--
+24 VDC
60mA
CH1--
+5V
+15V
0V
--15V
CH1+
Ch 1
Voltage s ink/s ource
CH2--
Ch 2 load
2K
minimum
D to A
Converter
CH2+
N/C
Ch 2
Voltage s ink/s ource
N/C
D to A
Converter
N/C
ANALOG
ANA
2CH
N/C
Transient
protected
precision
digital
Trans ient
protected
precis
ion to
analog to
converter
circuits
digital
analogoutput
converter
output circuits
F2-02DA-2
18-30VDC
60mA
ANALOG OUT
0-5VDC
-5-+5VDC
0V
+24V
CH1–
CH1+
CH2–
CH2+
NC
NC
NC
NC
0-10VDC
-10-+10VDC
F2-02DA-2
OV
Book 1 (14.1)
eD2-108
DL205 PLCs
1 - 80 0 - 633 - 0405
Analog Voltage Output Modules
Prices as of April 16, 2014. Check Web site for most current prices.
Company
Information
F2-02DA-2L 2-Channel Voltage Analog Output $161.00
This module requires a 12 VDC user power supply for operation. See the F2-02DA-2 on the
previous page if you want to use a 24 VDC supply. All other specifications are the same.
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
+0.3% unipolar ranges @ 77ºF (25ºC)
±0.45% unipolar ranges >77ºF (25ºC)
±0.4% bipolar ranges @77ºF (25ºC)
±0.55% bipolar ranges >77ºF (25ºC)
Number of Channels
2
Output Ranges
0 to 5V, 0 to 10 V, ±5V, ±10 V
Resolution
12 bit (1 in 4096)
Base Power Required 5VDC
40 mA
Output Type
Digital Output Points
Required
Single ended, 1 common
External Power Supply
10 to 15 VDC, 70 mA (outputs fully loaded)
16 (Y) output points
(12 binary data bits, 2 channel ID bits)
Operating Temperature
32º to 140ºF (0º to 60ºC)
15 VDC
(clamped by transient voltage suppressor)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Peak Output Voltage
Relative Humidity
5 to 95% (non-condensing)
Load Impedance
2000 minimum
Environmental Air
No corrosive gases permitted
Load Capacitance
.01 µF maximum
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
2 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Noise Immunity
NEMA ICS3-304
Linearity Error (end to end)
±1 count (0.025% of full scale) maximum
Terminal Type (included)
Removable; D2-8IOCON
Conversion Settling Time
Full Scale Calibration Error
(offset error included)
5 µs maximum (full scale change)
Offset Calibration Error
±3 counts max., unipolar @ 77ºF (25ºC)
±8 counts max., bipolar @ 77ºF (25ºC)
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
Controller
Overview
Productivity
3000
Universal
Field I/O
Software
C-More
HMI
Internal
Internal
module
Module
wiring
Wiring
12 VDC
OUT
--
0 VDC
DC to DC
Converter
Ch 2 load
2K
minimum
Do-More T1H
PLC
DirectLOGIC
DL205
NOTE 1: Shields should be connected to the 0V of the module or the OV of the P/S.
NOTE 2: Unused voltage outputs should remain open (no connections) for minimum power consumption.
Ch 1 load
2K
minimum
Do-More H2
PLC
DirectLOGIC
DL105
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).
S ee
NOTE 1
Do-More
PLCs Overview
DirectLOGIC
DL05/06
±12 counts max. unipolar @ 77ºF (25ºC)
±16 counts max. bipolar @ 77ºF (25ºC)
+
CLICK PLC
DirectLOGIC
PLCs Overview
See Wiring Solutions for part numbers of
ZIPLink cables and connection modules
compatible with this I/O module.
Typical user wiring
Control Systems
Overview
+12 VDC
70mA
CH1--
+5V
+15V
0V
--15V
CH1+
Ch 1
Voltage s ink/s ource
CH2-D to A
Converter
CH2+
N/C
Ch 2
Voltage s ink/s ource
N/C
D to A
Converter
N/C
ANALOG
ANA
2CH
N/C
Transient
precision
Trans
ientprotected
protected
precisdigital
ion
todigital
analogtoconverter
circuits
analog output
converter
output circuits
Communications
10-15VDC
70mA
ANALOG OUT
0-5VDC
-5+5VDC
Appendix
Book 1
0V
+12V
Terms and
Conditions
CH1–
CH1+
CH2–
CH2+
NC
NC
NC
NC
OV
Book 1 (14.1)
DL205 PLCs
ViewMarq
Industrial
Marquees
Other HMI
F2-02DA-2L
F2-02DA-2L
w w w. a u to m a t i o n d i re c t . c o m / d l 205
C-More Micro
HMI
eD2-109
Analog Voltage Output Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-02DAS-2 2-Channel 0-5V, 0-10V Isolated
Analog Output $255.00
Linearity Error (end to end)
±10 count (±0.015% of full scale) maximum
Gain Calibration Error
±32 counts (±0.05%)
Offset Calibration Error
±13 counts (±0.02%)
Output Drift
50 ppm/ºC
Maximum Inaccuracy
0.07% @ 25ºC (77ºF)
0.18% 0 to 60ºC (32º to 140ºF)
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
60 mA
Relative Humidity
5 to 95% (non-condensing)
21.6-26.4 VDC @ 60 mA per channel
Environmental air
No corrosive gases permitted
Load Impedance
2 k min
Vibration
MIL STD 810C 514.2
1 channel per scan maximum (D2-230 CPU)
2 channels per scan maximum (D2-240, D2250(-1) and D2-260 CPUs)
Shock
MIL STD 810C 516.2
PLC Update Rate
Noise Immunity
NEMA ICS3-304
Conversion Settling Time
3ms to 0.1% of full scale
Terminal Type (included)
Removable; D2-8IOCON
Number of Channels
2, isolated
Output Ranges
0-5V, 0-10V
Resolution
16 bit (1 in 65536)
Output Type
Digital Output Points
Required
Sourced through external loop supply
Isolation Voltage
±750 V continuous, channel to channel,
channel to logic
Base Power Required 5VDC
External Power Supply
32 (Y) output points
(16 binary data bits, 2 channel ID bits)
See Wiring Solutions for part numbers of
ZIPLink cables and connection modules
compatible with this I/O module.
NOTE 1: Shields should be connected to the 0V of the module or the OV of the P/S.
Internal
Module
Wiring
OUT
ANALOG
ANA
2CH
0 V1
-Trans mitter
S upply
24 VDC +
+V1
F2-02DAS-2
CH1-V
Ch 1 load
2kohms
NOTE 2
CH1+V
S ee
NOTE 1
N/C
D/A
0V1
IN
+V1
IN
CH1
-V
CH1
+V
100 ohms
N/C
Voltage Source
0V2
-Trans mitter
S upply
24 VDC +
+V2
N/C
CH2-V
Ch 2 load
2kohms
NOTE 2
21.6-26.4 VDC
60 mA CH
ANALOG OUT
CH2+V
D/A
100 ohms
Voltage Source
N/C
0V2
IN
+V2
IN
CH2
-V
CH2
+V
0-10VDC
0-5VDC
F2-02DAS-2
Book 1 (14.1)
eD2-110
DL205 PLCs
1 - 80 0 - 633 - 0405
Analog Voltage Output Modules
Prices as of April 16, 2014. Check Web site for most current prices.
F2-08DA-2 8-Channel Voltage Analog Output
Company
Information
Control Systems
Overview
$279.00
Number of Channels
8, single-ended, 1 common
Linearity Error (end to end)
±1 count (±0.025% of full scale) maximum
Output Ranges
0 to 5V, 0 to 10V
Full Scale Calibration Error
±12 counts max. unipolar @ 25ºC (77ºF)
Resolution
12 bit (1 in 4096)
Offset Calibration Error
±3 counts max., unipolar @ 25ºC (77ºF)
Output Type
Voltage sourcing
Accuracy vs. Temperature
Digital Output Points
Required
16 (Y) output points
(12 binary data bits, 3 channel ID bits,
1 output enable bit)
±57 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
±0.3% @ 25ºC (77ºF)
±0.45% @ 0-60ºC (32-140ºF)
Base Power Required 5VDC
60 mA
Operating Temperature
0º to 60ºC (32º to 140°F)
External Power Supply
21.6-26.4 VDC, 140 mA (outputs fully loaded)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Peak Output Voltage
15 VDC
(clamped by transient voltage suppressor)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
Load Impedance
1-10 k
Load Capacitance
0.01 µF maximum
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
8 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Conversion Settling Time
400 µs maximum (full scale change)
4.5 ms to 9ms for digital out to analog out
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
One count in the specification table is equal to one least significant bit of the
analog data value (1 in 4096).
See Wiring Solutions for part numbers of
ZIPLink cables and connection modules
compatible with this I/O module.
CLICK PLC
DirectLOGIC
DL405
Productivity
Controller
Overview
Productivity
3000
Universal
Field I/O
NOTE 1: Shields should be connected to the 0V of the module.
Software
Internal
Internal module
Module
wiring
Wiring
18--30VDC
@ 90mA
+
OUT
--
ANALOG
ANA
8CH
Typical user wiring
0 VDC
S ee
NOTE 1
Ch 1 load
1K--10K ohms
minimum
+V1
DC to DC
Converter
+24 VDC
0V
--15V
+V2
Ch 1
Voltage s ource
+V3
+V4
D to A
Converter
+V7
Ch 8 load
1K--10K ohms
minimum
+V8
Other HMI
Communications
0V
Appendix
Book 1
+24V
+V2
Terms and
Conditions
+V3
+V6
S ee
NOTE 1
F2-08DA-2
18-30VDC
80mA
ANALOG OUT
0-5VDC
0-10VDC
+V1
+V5
Ch 8
Voltage s ource
D to A
Converter
+V4
+V5
+V6
+V7
+V8
F2-08DA-2
Book 1 (14.1)
w w w. a u to m a t i o n d i re c t . c o m / d l 205
DL205 PLCs
C-More Micro
HMI
ViewMarq
Industrial
Marquees
+5V
+15V
C-More
HMI
eD2-111
Analog In/Out Combination Module
Prices as of April 16, 2014. Check Web site for most current prices.
F2-4AD2DA 4-Channel Analog Input /
2-Channel Analog Output $290.00
Number of Input Channels
4, single-ended (1 common)
Number of Output Channels
2, single-ended (1 common)
Ranges
4 to 20 mA current (current sinking)
Resolution
12 bit (1 in 4096)
Peak Withstanding Voltage
Maximum Continuous
Overload
75 VDC, current outputs
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change)
Maximum Inaccuracy
±0.1% @ 77ºF (25ºC)
±0.3% @ 32 to 140ºF (0 to 60ºC)
Digital Input and Output
Points Required
16 (X) input points (12 binary data bits,
2 channel ID bits, 2 diagnostic bits)
16 (Y) output points (12 binary data bits,
2 channel enable bits)
PLC Update Rate
4 channels per scan maximum:
(D2-240, D2-250(-1) and D2-260 CPUs)
2 output channels per scan maximum:
(D2-240, D2-250(-1) and D2-260 CPUs)
1 input and 1 output channel per scan maximum:
(D2-230 CPU)
-40 to +40 mA, each current output
Input Impedance
250 , ±0.1%, 1/2 W,
25 ppm/ºC current input resistance
External Load Resistance
0 minimum, current outputs
Maximum Loop Supply
30 VDC
Recommended Fuse
0.032 A, series 217 fast-acting, current inputs
Maximum Load/Power
Supply
Active Low-pass Filter
910 /24 V, current outputs
620 /18 V, 1200 /30 V
Linearity Error (best fit)
±1 count (±0.025% of full scale) maximum
Output Settling Time
100 µs maximum (full scale change)
-3 dB @ 20 Hz, 2 poles (-12 dB per octave)
See Wiring Solutions for part numbers of ZIPLink
cables and connection modules compatible with this
I/O module.
Base Power Required 5VDC
External Power Supply
Requirement
90 mA
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON
18-26.4 VDC @ 80 mA
20 mA per loop
One count in the specification table is equal to one least significant bit of the analog
data value (1 in 4096).
Note 6: If an analog channel is connected backwards, then
erroneous data values will be returned for that channel.
Note 1: Shields should be connected at their respective signal source.
Note 7: To avoid small errors due to terminal block losses,
connect 0 VDC, IN-, and OUT- on the terminal block as
shown. The module’s internal connection alone of these
nodes is not sufficient to permit module performance up
to the accuracy specifications.
Note 2: Unused channel should remain open for minimum power consumption.
Note 3: More than one external power supply can be used provided the power supply commons are
connected.
Note 4: A Series 217, 0.032A fast-acting fuse is recommended for 4-20 mA current input loops.
Note 8: Choose an output transducer resistance according to the
maximum load/power listed in the Output Specifications.
Note 5: If the power supply common of an external power supply is not connected to 0 VDC on the
module, then the output of the external transmitter must be isolated. To avoid "ground
loop" errors, recommended 4-20 mA transmitter types are:
2 or 3 wire: isolation between Input signal and power supply
4 wire: Isolation between input signal, power supply, and 4-20 mA output.
Typical user wiring
Module S upply
IN/
OUT
24VDC
S ee NOTE 1
+
Internal
module
Internal
Module
wiring
--
ANA
ANALOG
Wiring
--
+
-CH1
4--wire
4--20mA +
Trans mitter
DC to DC
Converter
0 VDC
+24 VDC
IN--
+
-CH2
3--wire
+
4--20mA
Trans mitter
+5V
+15V
0V
--15V
IN1+
CH3
2-wire
4--20mA +
Trans mitter
-CH4
2-wire
4--20mA +
Trans mitter
250
A to D
Converter
250
OUT--
F us e
IN
250
OUT1+
D to A
Converter
Ch 1
Current s inking
OUT2+
Ch 1 load
0--910
(@ 24V)
D to A
Converter
Ch 2
Current s inking
--
S ee NOTE 8
+
IN
IN4+
F us e
Ch 2 load
0--910
(@ 24V)
+24V
250
IN3+
F us e
--
18-26.4VDC
80mA
ANALOG
4 IN/2 OUT
4-20mA
0V
IN2+
F us e
F2-4AD2DA
Loop S upply
CH1+
CH2+
CH3+
CH4+
OUT-
CH1+
CH2+
F2-4AD2DA
0V
S ee NOTE 1
Book 1 (14.1)
eD2-112
DL205 PLCs
1 - 80 0 - 633 - 0405
Analog In/Out Combination Module
Prices as of April 16, 2014. Check Web site for most current prices.
Company
Information
Control Systems
Overview
REQUIRES D2-250-1 OR D2-260 CPU AND DIRECTSOFT 4.0 OR LATER PROGRAMMING SOFTWARE.
CLICK PLC
F2-8AD4DA-1 8-Channel Analog Current Input / 4-Channel
Analog Current Output $363.00
Output Channels per Module 4
Output Range
4 to 20 mA
Input Channels per Module
8, single ended (one common)
Resolution
16-bit, 0.244 mA/bit
Input Range
0 to 20 mA
Output Type
Current sourcing at 20 mA max.
Resolution
12, 14, 16-bit selectable
Load Impedance
0-750 0.25% of range
External DC Power Required 100 mA @ 18-26.4 VDC
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
Max. Continuous Overload
±45 mA
Input Impedance
100 0.1% 1/4W
Max. Inaccuracy
Max. Full Scale Calibration
Error (not incl. offset error)
Filter Characteristics
Active low pass, -3dB @ 80 Hz
Max. Offset Calibration Error ±0.1% of range max.
Conversion Time
12-bit = 1.5 ms per channel
14-bit = 6 ms per channel
16-bit = 25 ms per channel
Accuracy vs. Temperature
±25 ppm/ °C max. full scale calibration change
(± 0.0025% of range / °C)
Conversion Method
Over sampling successive approximation
-70 dB, 1 LSB
Accuracy vs. Temperature
±25 ppm / °C Max.
Max. Crosstalk at DC,
50/60Hz
Maximum Inaccuracy
0.1% of range
Linearity Error (End to End)
±1 count max. (±0.025% of full scale)
Monotonic with no missing codes
Linearity Error
(End to End)
12-bit = ±2 count max. (±0.06% of range)
14-bit = ±10 count max. (±0.06% of range)
16-bit = ±20 count max. (±0.06% of range)
Monotonic with no missing codes
Output Stability
and Repeatability
Output Ripple
±0.07% of range max.
Output Settling Time
0.5 ms max., 5 µs min. (full scale change)
Max. Continuous Overload
Outputs open circuit protected
Electronically current limited to 20 mA or
less
Full Scale Calibration Error
(not including offset error)
Offset Calibration Error
±0.03% of range max.
±0.075% of range max.
DirectLOGIC
PLCs Overview
DirectLOGIC
DL305
DirectLOGIC
DL405
0.005% of full scale
0.032A, Littelfuse Series 217 fast-acting
Type of Output Protection
Base Power Required 5VDC
35 mA
Output Signal at
Power-up and Power-down
Terminal Type (included)
DirectLOGIC
DL105
DirectLOGIC
DL205
±1 LSB after 10 min. warm-up typical
Rec. Fuse (external)
DirectLOGIC
DL05/06
4 mA
Productivity
Controller
Overview
Productivity
3000
Universal
Field I/O
Removable; D2-16IOCON
Software
C-More
HMI
Internal module wiring
+
-+
-+
-+
-3--wire 4--20mA +
transmitter
4--20mA output
Channel 1
I3+
I4+
COM
4--20mA output
Channel 4
CH3 DAC
CH4 DAC
100Ω
See Note 2
COM
I3+
100Ω
100Ω
4--20mA transmitter
shield, Channel 3
See Note 1
0.032A
4--20mA transmitter
shield, Channel 5
COM
100Ω
COM
Transmitter power
100Ω
I5+
I8+
AC or DC
4--wire 4--20mA
transmitter
CH2 DAC
COM
4--20mA output
Channel 3
See Note 2
CH1 DAC
100Ω
100Ω
100Ω
CH1 ADC
CH2 ADC
F2-8AD4DA-1
18-26.4VDC 100mA
8 INPUTS
0-20mA
4 OUTPUTS
4-20mA
0V
OUT2
OUT3
CH3 ADC
CH4 ADC
CH5 ADC
CH6 ADC
CH7 ADC
CH8 ADC
0V
IN2
IN3
0V
IN6
IN7
0V
OUT4
IN1
0V
IN4
IN5
0V
IN8
Isolated analog
circuit common
Note 1: A Littlefuse Series 217, 0.032A fast--acting fuse is recommended for all 4--20mA current loop inputs.
Note 2: Connect shields to the 0V of the module; do not connect both ends of shield.
Book 1 (14.1)
w w w. a u to m a t i o n d i re c t . c o m / d l 205
DL205 PLCs
Other HMI
Communications
Appendix
Book 1
Terms and
Conditions
24V
OUT1
4--20mA transmitter
shield, Channel 8
See Note 2
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Isolated analog
circuit power
I1+
I2+
4--20mA output
Channel 2
See Note 2
2--wire 4--20mA
transmitter
User 24VDC
supply
24VDC+
0VDC--
ANALOG
IN/
OUT
eD2-113
Analog In/Out Combination Module
Prices as of April 16, 2014. Check Web site for most current prices.
REQUIRES D2-250-1 OR D2-260 CPU AND DIRECTSOFT 4.0 OR LATER PROGRAMMING SOFTWARE.
F2-8AD4DA-2 8-Channel Analog Voltage Input / 4-Channel
Analog Voltage Output $363.00
Output Channels per Module 4
Output Range
0 - 5V, 0 - 10V
Input Channels per Module
8, single ended (one common)
Resolution
0 to 5V at 15-bit, 0 to10V at 16-bit, 152 µV/bit
Input Range
0 to 10 V
Output Type
Voltage sourcing/sinking at 10 mA max.
Resolution
12, 14, 16-bit selectable
Load Impedance
>1000 External DC Power Required 80 mA @ 18-26.4 VDC
0.15% of range
Max. Inaccuracy
Max. Full Scale Calibration ±0.075% of range max.
Error (not incl. offset error)
Max. Offset Calibration Error ±0.025% of range max.
Max. Continuous Overload
±100 V
Input Impedance
>10 M
Filter Characteristics
Active low pass, -3 dB @ 80Hz
Conversion Time
12-bit = 1.5 ms per channel
14-bit = 6 ms per channel
16-bit = 25 ms per channel
Conversion Method
Over sampling successive approximation
Accuracy vs. Temperature
±50 ppm / °C Max.
Maximim Inaccuracy
0.1% of range
Linearity Error (End to End)
12-bit = ±1 count max. (±0.025% of range)
14-bit = ±4 count max. (±0.025% of range)
16-bit = ±16 count max. (±0.025% of range)
Monotonic with no missing codes
Full Scale Calibration Error
(not including offset error)
Offset Calibration Error
Base Power Required 5VDC
±0.075% of range max.
±0.025% of range max.
Accuracy vs. Temperature
±50 ppm/ °C max. full scale calibration change
(± 0.005% of range / °C)
Max. Crosstalk
@ DC, 50/60Hz
-70 dB, 1 LSB
Linearity Error (End to End)
±1 count max. (±0.025% of full scale)
Monotonic with no missing codes
Output Stability and
Repeatability
Output Ripple
±1 LSB after 10 min. warm-up typical
0.005% of full scale
Output Settling Time
0.5 ms max., 5µs min. (full scale change)
Max. Continuous Overload
Outputs current limited to 15 mA typical
Type of Output Protection
1 VDC peak output voltage
(clamped by transient voltage suppressor)
35 mA
Output Signal at
Power-up and Power-down
Terminal Type (included)
0V
Removable; D2-16IOCON
+
User 24VDC
supply
24VDC+
0VDC--
Voltage output
Channel 1
-+
V1+
V2+
Voltage output
Channel 2
-+
COM
V3+
V4+
COM
Voltage output
Channel 3
-+
--
See Note 1
3--wire voltage
transmitter
+
Voltage transmitter
shield, Channel 3
COM
V3+
COM
See Note 1
V5+
2--wire voltage
transmitter
Voltage transmitter
shield, Channel 5
See Note 1
COM
Transmitter power
V8+
AC or DC
4--wire voltage
transmitter
Isolated analog
circuit power
CH1 DAC
CH2 DAC
CH3 DAC
CH4 DAC
CH1 ADC
Voltage output
Channel 4
ANALOG
IN/
OUT
Internal module wiring
CH2 ADC
F2-8AD4DA-2
18-26.4VDC 80mA
8 INPUTS
0-5/0-10VDC
4 OUTPUTS
0-5/0-10VDC
0V
OUT2
OUT3
CH3 ADC
CH4 ADC
CH5 ADC
CH6 ADC
CH7 ADC
CH8 ADC
0V
IN2
IN3
0V
IN6
IN7
24V
OUT1
0V
OUT4
IN1
0V
IN4
IN5
0V
IN8
Voltage transmitter
shield, Channel 8
Isolated analog
circuit common
See Note 1
Note 1: Connect shields to the 0V of the module; do not connect both ends of shield.
Book 1 (14.1)
eD2-114
DL205 PLCs
1 - 80 0 - 633 - 0405
Wiring Solutions
Prices as of April 16, 2014. Check Web site for most current prices.
Company
Information
Control Systems
Overview
Wiring Solutions using the ZIPLink Wiring System
ZIPLinks eliminate the normally tedious process of wiring between
devices by utilizing prewired cables and DIN rail mount
connector modules. It's as simple as plugging in a cable
connector at either end or terminating wires at only one end.
Prewired cables keep installation clean and efficient, using half
the space at a fraction of the cost of standard terminal blocks.
There are several wiring solutions available when using the
ZIPLink System ranging from PLC I/O-to-Z
ZI PLink Connector
Modules that are ready for field termination, options for
connecting to third party devices, GS, DuraPulse and SureServo
Drives, and specialty relay, transorb and communications
modules. Pre-printed I/O-specific adhesive label strips for quick
marking of ZIPLink modules are provided with ZIPLink cables.
See the following solutions to help determine the best ZIPLink
system for your application.
Solution 1: DirectLOGIC, CLICK and Productivity3000
I/O Modules to ZIPLink Connector Modules
When looking for quick and easy I/O-to-field termination, a ZIPLink
connector module used in conjunction with a prewired ZIPLink cable,
consisting of an I/O terminal block at one end and a multi-pin
connector at the other end, is the best solution.
Using the PLC I/O Modules to ZIPLink Connector
Modules selector tables located in this section,
1. Locate your I/O module/PLC.
2. Select a ZIPLink Module.
3. Select a corresponding ZIPLink Cable.
CLICK PLC
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
Controller
Overview
Solution 2: DirectLOGIC, CLICK and Productivity3000
I/O Modules to 3rd Party Devices
When wanting to connect I/O to another device within close proximity
of the I/O modules, no extra terminal blocks are necessary when using
the ZIPLink Pigtail Cables. ZIPLink Pigtail Cables are prewired to an I/O
terminal block with color-coded pigtail with soldered-tip wires on the
other end.
Productivity
3000
Universal
Field I/O
Using the I/O Modules to 3rd Party Devices selector tables
located in this section,
1. Locate your PLC I/O module.
2. Select a ZIPLink Pigtail Cable that is compatible
with your 3rd party device.
Software
C-More
HMI
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
Communications
Solution 3: GS Series and DuraPulse Drives
Communication Cables
Need to communicate via Modbus RTU to a drive or a
network of drives?
Appendix
Book 1
Using the Drives Communication selector tables located in
this section,
1. Locate your Drive and type of communications.
2. Select a ZIPLink cable and other associated hardware.
ZI PLink cables are available in a wide range of
configurations for connecting to PLCs and SureServo,
SureStep, Stellar Soft Starter and AC drives. Add a ZIPLink
communications module to quickly and easily set up a
multi-device network.
Book 1 (14.1)
w w w. a u to m a t i o n d i re c t . c o m / d l 205
DL205 PLCs
eD2-77
Terms and
Conditions
Wiring Solutions
Prices as of April 16, 2014. Check Web site for most current prices.
Solution 4: Serial Communications Cables
ZIPLink offers communications cables for use with DirectLOGIC, CLICK,
and Productivity3000 CPUs, that can also be used with other communications devices. Connections include a 6-pin RJ12 or 9-pin, 15-pin and 25pin D-sub connectors which can be used in conjunction with the RJ12 or
D-Sub Feedthrough modules.
Solution 5: Specialty ZIPLink Modules
For additional application solutions, ZIPLink modules are available in a
variety of configurations including stand-alone relays, 24VDC and
120VAC transorb modules, D-sub and RJ12 feedthrough modules,
communication port adapter and distribution modules, and SureServo
50-pin I/O interface connection.
Solution 6: ZIPLink Connector Modules to 3rd Party
Devices
If you need a way to connect your device to terminal blocks without
all that wiring time, then our pigtail cables with color-coded
soldered-tip wires are a good solution. Used in conjunction with any
compatible ZIPLink Connector Modules, a pigtail cable keeps wiring
clean and easy and reduces troubleshooting time.
Using the Serial Communications Cables selector
table located in this section,
1. Locate your connector type
2. Select a cable.
Using the ZIPLink Specialty Module s selector table
located in this section,
1. Locate the type of application.
2. Select a ZIPLink module.
Using the Unive rs al Conne ctor Modules and Pigtail
Cables table located in this section,
1. Select module type.
2. Select the number of pins.
3. Select cable.
Book 1 (14.1)
eD2-78
DL205 PLCs
1 - 80 0 - 633 - 0405
PLC I/O Modules to ZIPLink
Connector Modules - DL205
Prices as of April 16, 2014. Check Web site for most current prices.
DL205 PLC Input Module ZIPLink Selector
ZIPLink
PLC
Input
Module
# of
Terms
D2-08ND3
10
D2-16ND3-2
19
D2-32ND3¹
Part
Component Module
No.
D2-32ND3-2¹
D2-04TD1²
D2-08TD1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
D2-08TD2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
D2-16TD1-2
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Fuse
ZL-RFU205
ZL-D2-CBL19*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
D2-16TD2-2
19
Fuse
ZL-RFU205
ZL-D2-CBL19*
Relay
ZL-RRL16-24-2
ZL-D2-CBL19*
F2-16TD1P
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
F2-16TD2P
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Feedthrough
ZL-RTB40
Fuse
ZL-RFU405
Feedthrough
ZL-RTB40
Fuse
ZL-RFU405
ZL-D2-CBL10*
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Sensor
ZL-LTB16-24
ZL-D2-CBL19*
Feedthrough
ZL-RTB40
Sensor
ZL-LTB32-24
Feedthrough
ZL-RTB40
Sensor
ZL-LTB32-24
ZL-D24-CBL40*
ZL-D24-CBL40*
ZL-D24-CBL40*X
ZL-D24-CBL40*
ZL-D24-CBL40*X
ZL-D24-CBL40*X
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
D2-08NA-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
D2-16NA
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
† X in the part number represents a 45° angle.
10
Feedthrough
F2-04AD-1
# of Terms Component
10
Feedthrough
40
40
ZL-D24-CBL40*
ZL-D24-CBL40*X
ZL-D24-CBL40*
ZL-D24-CBL40*X
ZL-D24-CBL40*
ZL-D24-CBL40*X
ZL-D24-CBL40*
ZL-D24-CBL40*X
D2-08TA
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
Module Part Cable Part
No.
No.
F2-08TA
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
D2-12TA
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
ZL-RTB20
Fuse
ZL-RFU205
ZL-D2-CBL19*
D2-04TRS²
D2-08TR
F2-08TRS²
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
ZL-D2-CBL10*
DL205 PLC Analog Module ZIPLink Selector
ZIPLink
PLC
Analog
Module
D2-32TD1¹
D2-32TD2¹
DL205 PLC Combo In/Out Module ZIPLink Selector
ZIPLink
PLC
D2-08CDR
Module Part Cable Part
No.
No. †
ZL-D24-CBL40*
10
# of Terms Component
# of Terms Component
ZL-D24-CBL40*X
D2-08NA-1
Combo
Module
DL205 PLC Output Module ZIPLink Selector
ZIPLink
PLC
Output
Module
ZL-RTB20
40
Control Systems
Overview
Cable Part
No. †
Feedthrough
40
Company
Information
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Module
Cable
F2-08TR³
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
ZL-RTB20
ZL-D2-CBL10*
D2-12TR
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
Fuse
ZL-RFU205
ZL-D2-CBL19*
F2-04AD-1L
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-08AD-1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-04AD-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-04AD-2L
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-08AD-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
† X in the part number represents a 45° angle plug
F2-02DA-1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-02DA-1L
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
* Select the cable length by replacing the * with: Blank = 0.5m, -1 = 1.0m,
or -2 = 2.0m.
F2-02DAS-1
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
1 To make a custom cable for the 32-point modules, use: Ribbon-style Connector
F2-08DA-1
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
F2-02DA-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
ZL-D24-CON-R, Solder-style 180° connector ZL-D24-CON or Solder-style 45°
connector ZL-D24-CON-X
F2-02DA-2L
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-02DAS-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-08DA-2
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-4AD2DA
10
Feedthrough
ZL-RTB20
ZL-D2-CBL10*
F2-8AD4DA-1
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
F2-8AD4DA-2
19
Feedthrough
ZL-RTB20
ZL-D2-CBL19*
F2-04RTD4
Matched Only
See Note 4
F2-04THM4
Matched Only
See Note 4
2 Caution: The D2-04TD1, D2-04TRS, and F2-08TRS outputs are derated not to
exceed module specs 2A per point and 2A per common when used with
the ZIPLink wiring system.
3 The F2-08TR outputs are derated not to exceed 2A per point and 4A per common when used with the ZIPLink wiring system.
4 The F2-04RTD and F2-04THM modules are not supported by the ZIPLink wiring
system.
5 Note: Fuses (5 x 20 mm) are not included. See Edison Electronic Fuse section
for (5 x 20 mm) fuse. S500 and GMA electronic circuit protection for fast-acting
maximum protection. S506 and GMC electronic circuit protection for time-delay
performance. Ideal for inductive circuits.
To ensure proper operation, do not exceed the voltage and current rating of
ZIPLink module. ZL-RFU20 = 2A per circuit; ZL-RFU40 = 400 mA per circuit.
Book 1 (14.1)
DL205 PLCs
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
Controller
Overview
Productivity
3000
Universal
Field I/O
Software
C-More
HMI
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
NOTE: ZIPLINK CONNECTOR MODULES AND ZIPLINK CABLES
SPECIFICATIONS ARE IN THE ZIPLINK CATALOG SECTION.
w w w. a u to m a t i o n d i re c t . c o m / d l 205
CLICK PLC
eD2-79
Communications
Appendix
Book 1
Terms and
Conditions
Prices as of April 16, 2014. Check Web site for most current prices.
Power Requirements
These charts help
determine your power
requirements
This section shows the amount of power
supplied by each of the base power
supplies and the amount of power
consumed by each DL205 device. The
Power Consumed charts list how much
INTERNAL power from each power source
is required for the DL205 devices. Use this
information when calculating the power
budget for your system.
In addition to the internal power sources,
the DL205 bases offer a 24 VDC auxiliary
power supply with external power connections. This auxiliary power supply can
power external devices.
Use ZIPLinks to reduce
power requirements
If your application requires a lot of relay
outputs, consider using the ZIPLink AC or
DC relay output modules. These modules
can switch high current (10A) loads
without putting a load on your base power
budget. Refer to the Terminal Blocks and
Wiring Solutions section in this catalog for
more information.
This logo is placed next to the I/O
modules that are supported by the ZIPLink
connection systems. See the I/O module
specifications at the end of this section.
Device
D2-03B-1
Operator Interface
DV-1000
150
0
C-more MicroGraphic
210
0
5V(mA) 24V Auxiliary
Bases
D2-06BDC1-1
$194.00
2600
None
None
D2-06BDC2-1
$184.00
2600
300
D2-04B-1
300
D2-09B-1
$220.00
2600
300
D2-04BDC1-1 $171.00 2600
None
D2-09BDC1-1
$238.00
2600
None
D2-06B-1
300
D2-09BDC2-1
$238.00
2600
300
$132.00 2600
$143.00 2600
$176.00 2600
Power Consumed
Power Consumed
Device
5V(mA)
24V Auxiliary
Device
5V(mA)
24V Auxiliary
Analog Modules
CPUs
D2-230
120
0
F2-04AD-1
100
5
D2-240
120
0
F2-04AD-2
110
5
D2-250-1
330
0
F2-08AD-1
100
5
D2-260
330
0
F2-08AD-2
100
5
H2-WPLC*-**
680
0
F2-02DA-1
40
60 (note 1)
F2-02DA-1L
40
70 @ 12V (note 1)
0
F2-02DA-2
40
60
40
70 @ 12V
DC Input Modules
D2-08ND3
50
D2-16ND3-2
100
0
F2-02DA-2L
D2-32ND3
25
0
D2-32ND3-2
25
0
F2-02DAS-1
F2-02DAS-2
100
100
50 / channel
60 / channel
F2-08DA-1
30
50 (note 1)
F2-08DA-2
60
140
F2-4AD2DA
60
80 (note 1)
F2-8AD4DA-1
35
100 (note 1)
F2-8AD4DA-2
35
80 (note 1)
F2-04RTD
90
0
F2-04THM
110
60
AC Input Modules
D2-08NA-1
D2-08NA-2
D2-16NA
50
100
100
0
0
0
Input Simulator Module
F2-08SIM
50
0
DC Output Modules
D2-04TD1
60
20
D2-08TD1
100
0
D2-08TD2
100
0
200
200
80
0
F2-16TD1P
70
50
F2-16TD2P
70
50
D2-32TD2
24V Auxiliary
Price
D2-03BDC1-1 $150.00 2600
D2-32TD1
5V(mA)
Device
300
D2-16TD2-2
Device
Power Supplied
Price 5V(mA) 24V Auxiliary
Bases
D2-16TD1-2
Power Consumed
HERE
350
350
0
0
AC Output Modules
D2-08TA
250
0
F2-08TA
250
0
D2-12TA
350
0
Relay Output Modules
D2-04TRS
250
0
D2-08TR
250
0
F2-08TR(S)
670
0
D2-12TR
450
0
Combination In/Out Module
D2-08CDR
200
0
Specialty Modules
D2-CTRINT
50*
0
D2-CM / D2-EM
100/130
0
H2-CTRIO
400
0
H2-CTRIO2
275
0
D2-DCM
300
0
F2-DEVNETS
160
0
F2-SDS-1
160
0
H2-PBC
530
0
H2-EBC100
300
0
H2-EBC-F
640
0
H2-ECOM100
300
0
H2-ECOM-F
640
0
F2-CP128
235
0
H2-ERM100, (-F)
300, (-F: 450)
0
D2-RMSM
200
0
D2-RSSS
150
0
Remote I/O
Programming Devices
D2-HPP
200
0
*requires external 5VDC for outputs
Note 1: Add an additional 20 mA per output loop.
Book 1 (14.1)
eD2-46
DL205 PLCs
1 - 80 0 - 633 - 0405
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement