Johnson Controls DGA A, DGA H gas furnace User’s Information, Maintenance and Service Manual
Below you will find brief information for gas furnace DGA DGAA, gas furnace DGA DGAH. This manual contains important information about the installation, operation, and maintenance of your new gas furnace. It also includes troubleshooting tips to help you resolve common problems. Read through the manual carefully to ensure you get the most out of your furnace!
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
USER’S INFORMATION,
MAINTENANCE AND
SERVICE MANUAL
HIGH EFFICIENCY SEALED COMBUSTION
GAS FURNACE
MODELS: DGAA and DGAH SERIES
(Single Stage Downflow Only)
For Installation In:
1. Manufactured (Mobile) Homes
2. Recreational Vehicles & Park Models
3. Modular Homes & Buildings
TABLE OF CONTENTS
CONTACT INFORMATION FOR USA . . . . . . . . . . . . . . . . . . . . . . . 1
CONTACT INFORMATION FOR CANADA . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
While you are away . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SEASONAL SERVICE INFORMATION . . . . . . . . . . . . . . . . . . . . . . 2
Your Service Technician . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
WARRANTY AND RESPONSIBILITIES . . . . . . . . . . . . . . . . . . . . . 2
GAS SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Natural Gas Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Propane Gas Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTRUCTIONS FOR EXAMINING THE
FURNACE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Observing Burner Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
If Furnace Fails to Operate Properly . . . . . . . . . . . . . . . . . . . . . . . 3
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . . 4
IF FURNACE FAILS TO OPERATE PROPERLY . . . . . . . . . . . . . . 4
When You Call For Service Assistance . . . . . . . . . . . . . . . . . . . . . 4
To Contact Your Serviceman . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Read the Instructions Below Before Trying to Start the Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . . 4
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . .5
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . .6
SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . .6
Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
THE FURNACE CONTROLS AND THEIR FUNCTION . . . . . . . . . .6
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Continuous Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Heating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . .8
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
CONTACT INFORMATION FOR USA
• Contact us by mail:
DISTRIBUTED BY:
Style Crest Inc.
Drawer A
Fremont, OH 43420
• Manufacturer:
Johnson Controls,
Unitary Products
CONTACT INFORMATION FOR CANADA
• Go to website at www.york.com click on “contact”, then click on
“contact form” and follow the instructions.
• Contact us by mail:
Johnson Controls Unitary Products
Consumer Relations
5005 York Drive
Norman, OK 73069
The manufacturer recommends that the user read all sections of this manual and keep the manual for future reference.
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage.
FIRE OR EXPLOSION HAZARD - Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
—Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
—WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone (including cell phone) in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Johnson Controls Unitary Products 129099-BUM-K-0613
129099-BUM-K-0613
1. The furnace area must be kept clear and free of combustible materials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be kept free and clear of insulating materials. The furnace area must be examined when installed in an insulated space or when insulation is added to be sure that the insulation material has been kept away from the furnace.
3. Follow the instructions exactly as shown on the OPERATING
INSTRUCTION LABEL or the Start-up and Shutdown Instructions on Page 4 of this manual when lighting the furnace or turning the furnace off.
4. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
5. Do not use this furnace if any part has been under water. A flooddamaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
6. NEVER … Store flammable materials of any kind near your furnace.
Gasoline, solvents, and other volatile liquids should be stored only in approved containers outside your home. These materials vaporize easily and are extremely dangerous.
7. NEVER
…
Store cleaning materials near your furnace. Materials such as bleaches, detergents, powdered cleansers, etc., can cause corrosion of the heat exchangers.
8. NEVER
…
Use the area around your furnace as a storage area for items which could block the normal flow of air. This flow of air is required for ventilation of the various furnace components.
Your Service Technician
Your furnace's best friend is your qualified service technician. If the unit gives any indication of improper operation, call your service technician.
If the service technician is allowed to perform the normal routine care of your furnace, he can many times detect potential difficulties and make corrections before trouble develops. Preventative maintenance of this type will allow you to operate the unit with a minimum of concern, and at the same time will pay for itself in added years of comfort.
DESCRIPTION
This furnace shall be installed in the downflow position. Figure 1 shows a typical model in the downflow position. The furnace is equipped with an induced-draft vent blower and atmospheric burner. Combustion air is drawn through the roof jack and pushed into the burner box. Flue gas is forced from the heat exchanger by the vent blower and discharged through the flue pipe to the outside atmosphere.
This is a forced air furnace. The furnace circulating air blower draws cool air from the house, passes it over the hot furnace heat exchanger and circulates the warmed air through the ductwork to the house.
The furnace is equipped with the controls necessary for proper operation. The various components referred to in this manual and on the furnace rating plate are identified in Figure 1.
VENT PIPE
FLUE
COLLAR
BLOWER
BLOWER MOTOR
CAPACITOR
BLOWER
MOTOR
PRESSURE
SWITCH
CONTROL
BOARD
SILICONE
TUBE
COMBUSTION
AIR PIPE
SAFETY SHUTOFF
SWITCH
BOOSTER DRAFT
ASSEMBLY
GAS VALVE
FIRE OR EXPLOSION HAZARD
This furnace is designed and approved for use with Natural Gas and (LP) Propane Gas ONLY. DO NOT BURN ANY LIQUID FUEL
OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the furnace heat exchanger, which could result in Fire, Personal Injury, and/or Property
Damage.
While you are away
Your furnace is equipped with a safety device which will shut off the supply of gas to the burner in case of malfunction. For this reason it is never practical to assume that the furnace will operate unattended for a long period of time, especially if there is a possibility of damage to your property because of freezing. So, if you plan to be away from home, arrange for someone to check your house every day.
SEASONAL SERVICE INFORMATION
During extreme cold weather, ice may form on the furnace roof jack crown. Small amounts of ice forming on the roof jack will present no problem to proper furnace operation. However, excessive ice formation could restrict the combustion air supply to the burner causing inefficient burner operation.
When the temperature is very cold, near zero or below, it is recommended that the roof jack be inspected every day or more frequently if required. If ice has started to collect on the roof jack crown, it should be carefully broken off.
GAS BURNER
ASSEMBLY
AIR CONDITIONING
COIL PANELS
FIGURE 1: Component Locations
WARRANTY AND RESPONSIBILITIES
It is the sole responsibility of the home owner to make certain that the gas furnace has been correctly set up and converted to the proper fuel
(Propane or Natural gas) and adjusted to operate properly.
The manufacturer warrants the furnace to be free from defects in material or workmanship for the stated time in the warranty agreement (see warranty certificate packed with the furnace).
However, the manufacturer will not be responsible for any repair costs to correct problems due to improper set-up, improper installation, furnace adjustments, improper operating procedure by the user, etc.
It is also the sole responsibility of the home owner to make sure that the home if located above 2,000 ft. altitude be derated.
2 Johnson Controls Unitary Products
Some specific examples of service calls which cannot be included in warranty payments are:
1. Converting the furnace to use another type of fuel.
2. Correcting faulty duct work in the home.
3. Correcting wiring problems in the electrical circuit to the furnace.
4. Resetting circuit breakers or other switches.
5. Adjusting the burner air shutter or service calls made to correct problems caused by improper air adjustment.
6. Correcting problems caused by improper gas supply pressure to the furnace.
7. Instructional training on how to light and operate furnace.
8. Furnace problems caused by installation of air conditioner, heat pump, or other air quality device.
9. Problems caused by improper installation of the furnace flue assembly (roof jack).
10. Adding a roof jack extension because of unusual wind conditions or snow conditions.
11. Adjusting thermostats.
12. Problems caused by construction debris which has fallen into the flue or combustion air openings.
13. Replacement of fuses.
14. Problems caused by plugged or restricted orifices by any means.
You should establish a firm understanding of these responsibilities with your manufactured housing dealer, service company or gas supplier so there will be no misunderstanding at a later time.
GAS SUPPLY
The gas supply to your home will either be Natural Gas or Propane gas.
Your furnace will be factory equipped to operate on only one of these two different gases.
A small metal tag secured to the furnace next to the gas valve will specify the type of gas your furnace is equipped to use.
If the gas is different from that specified on the metal tag, the furnace can be converted by following the instructions on the furnace safety label inside lower front panel. Parts for conversion are contained in the small bag attached to the gas valve. Be sure the proper size orifice is used, as specified on the furnace name plate.
129099-BUM-K-0613
2. Examine the vent pipe making sure it is firmly in place, and is physically sound without holes and all of the connections are secure.
3. Examine return connections for Modular or Manufactured (Mobile)
Homes.
4. Examine the return air filter rack connections to make sure they are physically sound, sealed to the furnace door.
5. Examine the furnace casing making sure the physical support is sound without sagging, cracks or gaps. Examine the furnace base making sure it is physically sound without cracks, gaps or sagging and has a good seal.
6. Examine the furnace casing for obvious signs of deterioration.
7. Examine the burner flames to make sure the burner look like they are operating properly. The burner flames for natural gas should appear blue with a few yellow tips. The burner flames for propane gas should appear blue with moderate yellow tips. The flame should appear cylindrical in shape and should extend from the end of the burner into the heat exchanger.
NATURAL GAS
LIGHT BLUE
WITH YELLOW TIPS
DARK BLUE
BLUE TIPS JUST
STARTING TO
BECOME
PRONOUNCED
PROPANE GAS
FIGURE 2: Burner Flame Appearance
WHITISH YELLOW
TO LIGHT YELLOW
LIGHT BLUE
BLUE TIPS JUST
STARTING TO
BECOME
PRONOUNCED
Observing Burner Operation
1. Observe burner to make sure it ignites. Observe color of flame. On natural gas the flame will burn blue with appreciably yellow tips. On
Propane gas a yellow flame may be expected. If flame is not the proper color call a qualified service technician for service.
2. Let furnace heat until blower cycles on.
3. Turn thermostat down.
4. Observe burner to make sure it shuts off.
5. Let the furnace cool and blower cycle off.
The furnace must be converted by a qualified technician. Improper conversion can cause unsafe operation, explosion, and/or fire or asphyxiation.
Natural Gas Operation
The furnace is designed for 7" W.C. inlet pressure. Pressure is reduced to 3-1/2” W.C. by the pressure regulator in the gas valve.
Propane Gas Operation
Inlet pressure to the gas valve must be 11" W.C. When properly converted to Propane gas, the pressure is regulated at 10" W.C.
INSTRUCTIONS FOR EXAMINING THE FURNACE
INSTALLATION
It is the owner’s responsibility to ensure that an annual inspection of the entire heating portion of the unit is made by a qualified service agency.
Examine the furnace as outlined below in steps “1 - 6” before each heating season.
1. Examine the heat exchanger, through an access panel located on the supply air plenum. Visually examine the exterior sections of the vent/combustion air piping and the vent connectors to be sure that they are physically sound without holes or excessive corrosion.
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the furnace and allow blower to run until furnace cools down and blower shuts off before shutting off the electrical supply.
If any abnormalities are observed when checking for correct operation, such as burner failing to ignite or to turn off, sooty flame, etc., call your nearest authorized service technician as shown in the Service Center
List included in the home owner envelope with the furnace.
If Furnace Fails to Operate Properly
1. Check setting of thermostat - and position of HEAT/COOL switch if air conditioning is installed. If a set-back type thermostat is employed be sure that the thermostat is in the correct operating mode.
2. Check to see that electrical power is ON.
3. Check to see that the knob or switch on the gas control valve is in the full ON position.
4. Make sure filters are clean, return grilles are not obstructed, and supply registers are open.
5. Be sure that furnace flue piping is open and unobstructed.
If the cause for the failure to operate is not obvious, do not attempt to service the furnace yourself. Call a qualified service agency or your gas supplier.
Johnson Controls Unitary Products 3
4
129099-BUM-K-0613
2. Examine Filter Door
4. Examine Burner Door
1. Examine Vent Pipe
3. Remove Filter
Door to Examine
Combustion Air Pipe
7. Remove Burner
Door to Examine
Burner Flame
All appliances need maintenance by serviceman at the beginning of each heating season. Call your nearest authorized service technician to:
1. Replace filters. Clean all lint and dust from around furnace.
2. Remove fan and clean all dust and lint from unit with stiff bristle brush.
3. Inspect combustion chamber, the transition into the blower compartment, flue collar, and roof jack.
4. Check the gas valve and line connections for leaks.
5. Make any adjustments necessary for good operation.
NOTICE
The coil panel provides a good removable access for inspecting inside the furnace casing. Smoke or reflected light inside the casing indicates the presence of leaks in the heat exchanger.
SAFETY INFORMATION
Read the Instructions Below Before Trying to Start the
Furnace
5. Remove Burner
Door to Examine
Furnace Base and
Air Conditioning
Coil Panels
FIGURE 3: Furnace Examination Checkpoints
HOW YOUR GAS FURNACE WORKS
Your furnace is a very easy appliance to take for granted. Season after season, it sits there in your home, keeping you warm and comfortable.
For this reason, you may never have given much thought to the way your furnace operates. In order to get the safest and most efficient operation from your furnace, you should understand how your furnace does its job.
When you set your thermostat to provide more heat in your home, you are starting the heating cycle of the furnace. First, the inducer motor starts to purge the heat exchanger of any remaining gases. Next, the hot surface ignitor glows and after a warm-up period the gas valve opens and ignition occurs. A short time later, the blower starts and distributes the warm air throughout the home. When the temperature setting on your thermostat is reached, the gas valve closes, the main burner is turned off, and the blower continues to run until the remaining warm air in the system is distributed. When the blower stops, the heating cycle has ended.
IF FURNACE FAILS TO OPERATE PROPERLY
1. Check setting of thermostat - and position of heat/cool switch if air conditioning is installed. If a set-back type thermostat is employed be sure that the thermostat is in the correct operating mode.
2. Check to see that electrical power is “ON”.
3. Check to see that the lever or switch on the gas control valve is in the full “ON” position.
4. Make sure filters are clean, return grilles are not obstructed, and supply registers are open.
5. Be sure that furnace flue piping is open and unobstructed.
When You Call For Service Assistance
Very often time can be saved if you will give the service agency the
MODEL and SERIAL NUMBER of your furnace. This will enable him to determine the specific components used, and perhaps to better identify the possible problem and be better prepared if a service call is required.
To Contact Your Serviceman
(fill in)
COMPANY: ______________________________________________
ADDRESS: ______________________________________________
TELPHONE: _____________________________________________
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, and/or loss of life.
1. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
2. BEFORE OPERATING; smell all around the appliance area for gas.
Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
3. Use only your hand to push the gas control switch to the “on” position. Never use tools. If the switch will not operate by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
4. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
START-UP AND SHUTDOWN INSTRUCTIONS
Operating Instructions:
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove furnace door.
5. Move gas control switch to the “OFF” position. Do not force. See
Figure 4.
6. Wait five (5) minutes to clear out any gas. If you then smell gas,
STOP! Follow Step 2 (refer to Safety Information on Page 4). If you don’t smell gas, go to next step.
7. Move gas control switch to the “ON” position. Do not force. See Figure 4.
8. Replace burner door.
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate follow the instructions, “TO TURN OFF THE APPLIANCE” and call your service technician or gas supplier.
Johnson Controls Unitary Products
129099-BUM-K-0613
To Turn Off the Appliance:
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove burner access panel.
4. Move gas control switch to the “OFF” position. See Figure 4.
5. Replace burner access panel.
Should overheating occur, or the gas valve fail to shut off, turn the external manual gas valve in the gas supply line to the furnace to the
“off” position and let the furnace cool off before shutting off the electrical power supply. Refer to Figure 5.
OUTLET (MANIFOLD)
PRESSURE TAP
MAIN REGULATOR
ADJUSTMENT
90°
FLANGE
INLET
SUPPLY
PRESSURE
TAP
ELECTRICAL
CONNECTIONS
FIGURE 4: Gas Valve
ON/OFF SWITCH
(shown in OFF position) OUTLET
MANUAL
SHUT-OFF
VALVE
GAS
PIPE
DRIP
LEG
GAS
BURNER
GAS
VALVE
DRIP
LEG
FIGURE 5: Gas Piping
FURNACE USER MAINTENANCE
GAS
PIPE
MANUAL
SHUT-OFF
VALVE
Before proceeding, be sure the area is well ventilated. Turn the thermostat OFF. If the blower is running, wait until it stops automatically.
Turn OFF the gas and electrical power supplies to the furnace. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.
Every time the filters are changed the following items should be visually inspected:
• Check roof jack assembly for blockage or leakage.
• Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.
• Check the evaporator coil drain lines to make sure there are no cracks or leaks.
• Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the furnace and its components must be done by a qualified service professional.
If, during the inspection of your furnace, you find any of the following conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Do not operate the furnace, and call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the front panels. Follow the operating instructions to place the furnace in operation.
Air Filters
Dirty filters greatly restrict the flow of air and may cause damage to the moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation.
The filters should be checked every 3 months (DO NOT USE PLEATED
FILTER in this furnace). On new construction, check the filters every week for the first four weeks and every three weeks after that, especially if the indoor fan is running continuously. When replacing the filter(s) you must use filters that are the same size and type as those in the furnace (2 - 16 x 20 x1).
Removing Filters
Internally Mounted Air Filters
The air filter is in a rack that is attached to the door of the furnace.
To remove the filter you must do the following:
1. Before proceeding, be sure the area is well ventilated. Follow instruction “To turn off the appliance”. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.
2. Remove the filter door.
3. Remove the air filter by sliding it down the track. The air filter will slide out of the rack.
4. Replace throw away filter(s) with the same size new filter(s). Throw away filter(s) may be replaced with cleanable filter(s) at this time.
Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described in these instructions.
To replace the filter after cleaning you must do the following:
1. Slide filter into place. If the filter has been cleaned, make sure it is dry before re-installing it.
2. Replace the door or cover panel.
3. Make sure the door snaps into the retaining clips.
4. Follow the Operating Instructions to place the furnace back in operation.
Johnson Controls Unitary Products 5
6
129099-BUM-K-0613
Blower Care
Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vacuum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then call a qualified service agency. Only a qualified service agency can perform this service.
Make sure you DO NOT move the clip on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not require periodic oiling.
SECTION II: SERVICE AND MAINTENANCE
MANUAL
SAFETY SECTION
This section has been designed to assist a qualified service agency in performing service and maintenance on this appliance. The homeowners and/or end user must never attempt to perform any service or maintenance on the appliance especially when it involves the removal or adjustment of any parts and/or components.
The following safety rules must be followed when servicing the furnace.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, and death or property damage.
• Before servicing, disconnect all electrical power to the furnace.
• When servicing controls, label all wires prior to disconnecting.
Reconnect wires correctly.
• Verify proper operation after servicing.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.
1. The roof cap (if applicable).
2. The furnace vent pipe. Should it be necessary to service the vent/air intake system, the manufacturer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.
3. The furnace burner, ignitor and flame sensor.
FURNACE CLEANING SECTION
NOTICE
The cleaning operations listed below must be performed only by a qualified service agency.
Burner Removal/Cleaning
The main burner should be checked periodically for dirt accumulation. If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the upper access panel.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner assembly to the combustion air box and remove the assembly.
6. Remove burner from the burner assembly.
7. Rinsing in hot water may clean burners.
8. Reassemble in the reverse order.
Cleaning the Heat Exchanger
NOTICE
It is recommended that replacement gaskets be available before removing burner assembly and combustion air box.
Lower Heat Exchanger Access
1. Turn off the electrical power to the unit and turn off gas supply at the shutoff valve.
2. Remove the blower and burner compartment access doors. Disconnect the gas supply piping at the union to permit removal of the entire burner and gas control assembly from the vestibule panel.
Use the wrench boss on the gas valve when removing or installing this piping.
3. Unplug the igniter from the wire harness. Disconnect sensor wires.
Identify and note the location of all leads for ease of reinstallation.
4. Remove the screws holding the burner assembly to the vestibule panel and remove this assembly. Handle the assembly carefully since it contains the igniter, which is fragile and easily broken. The lower portion of the heat exchanger will now be exposed. Remove any soot and scale. Vacuum loose soot, scale and dirt from the heat exchanger.
5. After cleaning is complete, replace all components in reverse order.
Re-gasket all surfaces which required a gasket. Reconnect all wiring. Reattach vent pipe and gas supply lines before restoring service to furnace. Restore electrical power, check gas supply piping for leaks, and then verify furnace operation.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
THE FURNACE CONTROLS AND THEIR FUNCTION
1. Limit Control - This furnace is protected by two (2) high temperature limit switches. The lower limit switch is an automatic reset type.
2. Upper Limit Control - The upper limit switch near left side of blower is a manual reset type limit switch. If burner does not function, turn system switch to “OFF” and push reset button in center of limit switch.
3. Gas Valve - The gas valve is 100% shut-off type and will fail safe if for some reason the gas is turned off. It is also of the snap opening type which opens to fire position.
Johnson Controls Unitary Products
129099-BUM-K-0613
SEQUENCE OF OPERATION
Continuous Blower
On cooling/heating thermostats with fan switch, when the fan switch is set in the ON position, a circuit is completed between terminals R and G of the thermostat. The blower motor is energized through the cool fan terminal on the ignition control module.
Intermittent Blower - Cooling
On cooling/heating thermostats with fan switch, when the fan switch is set in the auto position and the thermostat calls for cooling, a circuit is completed between the R, Y and G terminals. The motor is energized through the cool fan terminal and runs on the selected speed. The fan off setting is fixed at 60 seconds for SEER enhancement.
Heating Cycle
When the system switch is set on HEAT and the fan is set on AUTO, and the room thermostat calls for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, a pressure switch activates the ignition control.
The ignition control provides a 30-second warm-up period. The gas valve then opens for 10 seconds. If the flame is not detected within 2 seconds of the gas valve opening, the gas valve is shut off and a retry operation begins. If the flame is lost for 2 seconds during the 10 second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation the ventor starts a 15 second interpurge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition, during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been corrected the furnace will again lockout after three retries.
A momentary loss of gas supply, flame blowout, or a faulty flame probe circuit will result in a disruption in the flame and be sensed within 0.8
seconds. The gas valve will de-energize and the control will begin a recycle operation. A normal ignition sequence will begin after a 15 second inter-purge. If during the three recycles the gas supply does not return, or the fault condition is not corrected the ignition control will lockout for 60 minutes.
During burner operation, a momentary loss of power for 50 milliseconds or longer will de-energize the gas valve. When the power is restored, the gas valve will remain de-energized and the ignition sequence will immediately restart.
As the gas starts to flow and ignition occurs, the flame sensor begins its sensing function. If a flame is detected during the 10 second flame stabilization period the circulating blower will energize 30 seconds after the gas valve opens (20 seconds after the flame stabilization period ends).
Normal furnace operation will continue until the thermostat circuit between R and W is opened. When the thermostat circuit opens, the ignition control is de-energized. When the ignition control is de-energized, the gas flow stops, and the burner flames are extinguished. The ventor continues to operate for 15 seconds after the gas flow stops.
The blower motor continues to operate for the amount of time set by the fan-off delay “Jumper” located on the ignition control board. Refer to
Figure 6. The heating cycle is complete, and the furnace is ready for the start of the next heating cycle.
FAN OFF
JUMPER
FAN ON
ADJUSTMENT
JUMPER
FIGURE 6: Furnace Control Board
Hot Surface Ignition System
TRANSFORMER
LINE VOLTAGE
BLACK - HIGH SPEED
RED -LOW SPEED
FUSE 3A
HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1. Check to see that the power to the furnace and the ignition control module is ON.
2. The manual shut-off valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.
Never bypass pressure switch to allow furnace operation. To do so will allow furnace to operate under potentially hazardous conditions.
Do not try to repair controls. Replace defective controls with
UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
Johnson Controls Unitary Products 7
8
129099-BUM-K-0613
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self diagnostic capability. If a system problem occurs, a fault code is shown by a blinking green LED. It is located behind a clear view port in the blower compartment door. DO NOT turn off furnace power as this action will clear the control's memory of the fault.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced as the control is not field repairable.
Flash sequence codes 1 through 6 are as follows: LED will turn “on” for one second and “off” for one second. This pattern will be repeated the number of times equal to the code. For example, six “on” flashes equals a number 6 fault code.
All flash code sequences are broken by a 2 second “off” period.
IGNITION CONTROL
Normal flame sense current is approximately
3.7 microamps DC (
a)
Low flame signal control lockout point is
0.9 microamps DC (
a)
1 FLASH: Ignition failure.
2 FLASH: Combustion air pressure switch closed, this indicates that the normally open pressure switch contacts are stuck in the closed position.
The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or mis-wiring.
3 FLASH: Combustion air pressure switch failed to close, this indicates the normally open pressure switch contact did not close at the beginning of the heat cycle. This could be caused by a number of problems; faulty inducer, blocked vent pipe, broken pressure switch hose or faulty pressure switch.
4 FLASH: Limit Switch Open, this indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.
5 FLASH: Gas flow with no call for heat. Check gas valve and gas valve wiring.
RAPID FLASHES: Reverse Polarity, reverse polarity indicates reverse line voltage polarity. Both heating and cooling will be affected. Check polarity of both.
STEADY ON: Normal Operation.
60 MINUTE AUTOMATIC RESET FROM LOCKOUT: This control includes a “watchdog” type circuit that will reset from a lockout condition after 60 minutes. Operational faults 1, 3, 4 and Steady On will be reset.
This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the “watchdog” would restart the unit and provide heat for the house.
NOTICE
If a flame is detected the control flashes the LED for 1/8 of a second and then enters a flame stabilization period.
Thermostat Satisfied
(Seconds) 0 5
Thermostat Calling for Heat
32
Fan on Delay
12 Seconds
0
ON
THERMOSTAT
OFF
INDUCER
OFF
ON
ON
IGNITOR
MAIN VALVE
OFF
OFF
CIRCULATING
BLOWER OFF
FIGURE 7: Furnace Event Control Schedule
OFF
OFF
ON
OFF
15 Sec.
Post
Purge
OFF
OFF
OFF
60, 90, 120, 180 SEC.
Selectable Fan Off Delay
OFF
Johnson Controls Unitary Products
129099-BUM-K-0613
SECTION III: REPLACEMENT PARTS LIST
All components, assemblies, accessories, and replacement parts for this furnace are available through your qualified service installer or refer to the service center list in your booklet. It is not recommended that the homeowner purchase, install, or replace any components of this furnace. Contact your local contactor, dealer, or service provider for additional information.
ITEM DESCRIPTION
15
16
17
18
8
9
10
11
12
13
5
6
7
1
2
3
4
Switch, Pressure
Tubing Silicone (2’ Req’d)
Limit Switch, Manual (Upper)
Assembly, Booster (w/Motor)
Control Board, Integrated
Valve, Gas
Bracket, Mounting (Gas Valve)
14
19
Exchanger, Heat (w/Gaskets)
Sensor, Flame
Switch, System
Transformer (115-24V, 40 VA)
Switch, Limit
Burner Assembly, Auto Ignition
(Includes items 10 & 15)
Ignitor, Hot Surface
Filter (2 Req’d) (16x20x1)
Panel, Door (Upper)
Panel, Door (Lower, Tall)
Motor (See Note 2) (old-see note 4)
Motor (new-see note 4)
20
21
Assembly, Motor Mount (See Note 2)
Plug, Connector
Capacitor, Run (See Note 3) (Old-see note 4)
22 Capacitor (New-see note 4)
Capacitor (Units built on/after 8/11/2008)
23 Wheel, Blower
24* Top, Casing
25* Diagram, Wiring
26* Strike, Door
27* Latch, Door
28* Housing, Blower
29* Gasket, Combustion Air Box
30* Gasket, Burner
31* Gasket, Booster Assembly
32* Gasket, Heat Exchanger
DGAA
DGAA056BDTB
S1-32435972000
S1-02812499000
S1-02535358000
S1-37319801821
S1-03101932002
S1-02543267000
S1-07319801064
S1-37319804651
S1-02535354000
S1-7681-3301
S1-2940A3541
S1-02535380000
S1-37319801403
S1-02541021000
S1-1214-2511
7900-7611
S1-1468-220P
S1-02435603000
S1-37319806100
S1-02521192000
S1-02420063000
S1-02435602000
S1-02435813000
S1-02619654003
S1-07319801342
155887
S1-02118364000
S1-02118365000
S1-37323864001
S1-01006900005
S1-01006742000
S1-01006900015
S1-01006900001
DGAA070BDTB
S1-32435972000
S1-02812499000
S1-02535358000
S1-37319801821
S1-03101932002
S1-02543267000
S1-07319801064
S1-37323792001
S1-02535354000
S1-7681-3301
S1-2940A3541
S1-02535380000
S1-37319801403
DGAA077BDTB
S1-32435972000
S1-02812499000
S1-02535358000
S1-37319801821
S1-03101932002
S1-02543267000
S1-07319801064
S1-37323792002
S1-02535354000
S1-7681-3301
S1-2940A3541
S1-02535381000
S1-37319801403
S1-02541021000
S1-1214-2511
S1-02541021000
S1-1214-2511
Accessory (See Page 4)
7900-7611
S1-1468-220P
S1-02435603000
7900-7611
S1-1468-220P
S1-02435603000
S1-37319806100
S1-02521192000
S1-02420063000
S1-02435602000
S1-02435813000
S1-02619654003
S1-07319801342
155887
S1-37319806100
S1-02521192000
S1-02420063000
S1-02435602000
S1-02435813000
S1-02619654003
S1-07319801342
155887
S1-02118364000
S1-02118365000
S1-37323864001
S1-01006900005
S1-01006742000
S1-01006900015
S1-01006900001
S1-02118364000
S1-02118365000
S1-37323864001
S1-01006900005
S1-01006742000
S1-01006900015
S1-01006900001
DGAA090BDTB
S1-32435972000 <
S1-02812499000
S1-02535358000
S1-37319801821
S1-03101932002
S1-02543267000
S1-07319801064 <
S1-37323792003
S1-02535354000
S1-7681-3301
S1-2940A3541
S1-02535381000
S1-37319801403
S1-02541021000
S1-1214-2511
7900-7611
S1-1468-220P
S1-02435603000
S1-37319806100
S1-02521192000
S1-02420063000
S1-02435602000
S1-02435813000
S1-02619654003
S1-07319801342
155887
S1-02118364000
S1-02118365000
S1-37323864001
S1-01006900005
S1-01006742000
S1-01006900015
S1-01006900001
NOTE: *Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 1/12.
Major components and suggested stocking items are shown with shaded item number.
“<“Across from row indicates a change in that row.
--- Not applicable to specified model.
2. For Serial Numbers lower then 001207164- Replacement DGAA motors also require Motor Mount
Assembly 373-19806-100 if replaced motor has integral, flex-arm motor mount.
3. DGAA with 5-Ton Blowers are provided as an accessory item and are not standard equipment from the factory. See Page 4
4. The “old” motor must use the “old” run capacitor. The “new” motor can use either capacitor.
Serial No. W0F6528688 and above were built with the new motor.
Johnson Controls Unitary Products 9
129099-BUM-K-0613
WIRING DIAGRAM
DGAH
26*
27*
28*
29*
22
23
24*
25*
18
19
20
21
15
16
17
30*
31*
32*
6
7
4
5
1
2
3
ITEM DESCRIPTION
Switch, Pressure
Tubing Silicone (2’ Req’d)
Limit Switch, Manual (Upper)
12
13
14
8
9
10
11
Assembly, Booster (w/Motor)
Control Board, Integrated
Valve, Gas
Bracket, Mounting (Gas Valve)
Exchanger, Heat (w/Gaskets)
Sensor, Flame
Switch, System
Transformer (115-24V, 40 VA)
Switch, Limit
DGAH056BBSB
S1-32435972000
S1-02812499000
S1-02535358000
S1-37319801821
S1-03101932002
S1-02543267000
S1-07319801064
DGAH077BBSB
S1-32435972000
S1-02812499000
S1-02535358000
S1-37319801821
S1-03101932002
S1-02543267000
S1-07319801064
Burner Assembly, Auto Ignition
(Includes items 10 & 15)
Ignitor, Hot Surface
Filter (2 Req’d) (16x20x1)
Panel, Door (Upper)
S1-02541021000
S1-1214-2511
Panel, Door (Lower, Short) 7900-7671
Motor S1-02431948000
S1-02541021000
S1-1214-2511
Accessory (See Page 4)
7900-7671
S1-02431948000
Assembly, Motor Mount
Plug, Connector
Capacitor, Run
Wheel, Blower
Top, Casing
Diagram, Wiring
Strike, Door
Latch, Door
Housing, Blower
Gasket, Combustion Air Box
Gasket, Burner
Gasket, Booster Assembly
Gasket, Heat Exchanger
S1-37319804651
S1-02535354000
S1-7681-3301
S1-2940A3541
S1-02535380000
S1-37319801403
---
S1-02521192000
---
S1-02619654003
S1-07319801342
157953
S1-02118364000
S1-02118365000
S1-37323864001
S1-01006900005
S1-01006742000
S1-01006900015
S1-01006900001
S1-37323792002
S1-02535354000
S1-7681-3301
S1-2940A3541
S1-02535381000
S1-37319801403
---
S1-02521192000
---
S1-02619654003
S1-07319801342
157953
S1-02118364000
S1-02118365000
S1-37323864001
S1-01006900005
S1-01006742000
S1-01006900015
S1-01006900001
NOTE: *Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 1/12.
Major components and suggested stocking items are shown with shaded item number.
“<“Across from row indicates a change in that row.
--- Not applicable to specified model.
3. DGAH with 5-Ton Blowers are provided as an accessory item and are not standard equipment from the factory. See page 4.
MODEL
NATURAL GAS
LP GAS
BURNER ORIFICE CHART (Normal Altitude Only, See Note 5)
056
S1-9951-1361
S1-9951-0821
070
S1-9951-1541
S1-9951-0931
077
S1-9951-1611
S1-9951-0981
090
S1-9951-1771
S1-9951-1061
<
<
ACCESSORY
ACCESSORY PARTS LIST
DESCRIPTION DGAA DGAH
10
5-Ton Blower Ass’y
7900-7751
Door Panel (Upper)
Motor
Run Capacitor (20 MFD)
Motor Mount
Blower Wheel
7900-7631 7900-7631
S1-02431975000 S1-02431975000
S1-02420051000 S1-02420051000
S1-37319802930 S1-37319802930
S1-1472-2761 S1-1472-2761
NOTES
5 Contact Customer Service for installations at altitudes over 2000 feet above sea level.
“<“Across from row indicates a change in that row.
--- Not Applicable to specified model.
Johnson Controls Unitary Products
129099-BUM-K-0613
FIGURE 8: Wiring Diagram - DGAA
Johnson Controls Unitary Products 11
129099-BUM-K-0613
FIGURE 9: Wiring Diagram - DGAH
12 Johnson Controls Unitary Products
129099-BUM-K-0613
Limited Warranty
Manufactured Housing Furnaces
WARRANTY TERMS: Johnson Controls Unitary Products (hereinafter “Company”) warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts, without charge, subject to the exclusions below, that prove to have such defects according to the terms outlined in this warranty. Company reserves the right, at its sole discretion, to provide a replacement unit in the place of repair parts, in which case the warranty period for the replacement unit is limited to the remainder of the original warranty period. Alternatively, Company may, at its option, extend a replacement allowance to be applied toward the purchase of a new unit marketed by
Company. The exact amount of the allowance will be determined at the discretion of Company, based upon current market conditions, but in no case shall this allowance exceed thirty (30) percent of the original consumer purchase price of the unit excluding such items as ductwork, wiring, piping, and installation costs. The warranty period for repair or replacement parts or unit provided hereunder shall not extend beyond the warranty period stated below. Company shall have no responsibility hereunder for installation, shipping, handling, or other charges except as specifically provided herein.
This warranty covers only the equipment described by the Product Model Number and Unit Serial Number on the equipment or listed on the Warranty Registration Card, and applies only to products installed in the United States, Canada, or Puerto Rico. Tampering, altering, defacing, or removing the product serial number will serve to void this warranty. This warranty extends only to the original consumer purchaser and is nontransferable.
For this warranty to apply, the product must be installed according to Company recommendations and specifications, and in accordance with all local, state, and national codes; and the product or residence must not be removed from its place of original installation. This warranty does not apply to any unit sold over the Internet, by telephone or other electronic means unless the dealer that buys or sells a unit over the Internet, by telephone or other electronic means also installs the unit. In the absence of a recorded Warranty Registration Card, the warranty period will begin upon product shipment from Company. If you are unaware of the date the warranty became effective, contact Company at (877) 874-7378 or visit www.upgproductregistration.com.
ADDITIONAL CONDITIONS FOR HEAT EXCHANGER WARRANTY: This warranty shall cover the heat exchanger (primary and/or secondary, if applicable) only if:
1. The product has not been operated with an input rate in excess of the rating plate attached to the product.
2. The product has not been allowed to operate without the use of the proper automatic limit control on the maximum warm air temperature and/or without adequate circulation.
3. The product is installed so that the combustion air is not contaminated by compounds of chlorine, fluorine, or other damaging chemicals
(or vapors).
4. The product is installed such that the heat exchangers are not exposed to return air temperatures below stated ratings.
FOR PRODUCT REGISTRATION: For your benefit and protection, register your product with Company promptly after installation. This will initiate the warranty period and allow us to contact you, should it become necessary. You can register your product online at www.upgproductregistration.com or by returning the Warranty Registration Card on the back page of this packet.
Product Model Number: ____________________________________ Installation Date: __________________________________________
Unit Serial Number: _______________________________________ Installing Dealer: __________________________________________
FOR WARRANTY SERVICE OR REPAIR: Consult the Authorized Service Center List packed with the unit installed in the manufactured home or contact your installing or servicing dealer. The Authorized Service Center List is also available online at http://www.stylecrestinc.com/manufacturedhousing-products/hvac-service-documents/
Or, look in the Yellow Pages of the telephone book under Mobile Homes or Manufactured Housing Repair and Service for the name and telephone number of the nearest authorized manufactured housing service center. If local authorized service cannot be obtained, or you are unable to contact your installing dealer, contact the authorized distributor in your area. If you are unable to contact an authorized servicer, please contact StyleCrest
Inc., at 1-800-231-4822. If there is no distributor in your area, and you cannot obtain proper service under the terms of the warranty, please write:
Johnson Controls Unitary Products, Consumer Relations, 5005 York Drive, Norman, OK 73069.
WARRANTY PERIOD: The warranty period in years, depending on the part, is as shown in the chart below.
Furnace Model
FURNACE MODELS
Heat Exchanger Parts Coverage
Labor and Trip Coverage *
DGAA, DGAH
NOTES:
10 years 2 years 1 year
*
The warranty period for any replacement heat exchanger or part provided here under shall not extend beyond the warranty period stated above. The heat exchanger warranty is on a parts only basis: no labor, freight or other service charges are allowed.
The warranty period will begin on the purchase date of the residence when the product is installed as original equipment, or the installation date when installed in a residence previously purchased by the consumer.
MAINTENANCE: Company strongly recommends regular periodic preventive maintenance on this equipment. The person most familiar with the equipment in your HVAC system is a Participating Dealer. The Participating Dealer can ensure that your maintenance program meets the “Company
Warranty” conditions, maximize the equipment efficiency, and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere.
Johnson Controls Unitary Products 13
EXCLUSIONS: This warranty does not cover any:
1. Shipping, labor, or material charges or damages resulting from transportation, installation, or servicing.
2. Damage or repairs required as a consequence of mishandling, faulty installation, misapplication, abuse, improper servicing, unauthorized alteration, or improper operation.
3. Damages or failure to start resulting from improper voltage conditions, blown fuses, open circuit breakers, or other inadequacy or interruption of electrical service or fuel supply.
4. Fuses, either internal or external to the product.
5. Labor or other costs incurred for diagnosing, repairing, removing, installing, shipping, servicing, or handling of either defective parts or replacement parts.
6. Products removed from their original location for reinstallation purposes.
7. Damages resulting from accident, abuse, fire, flood, alteration, or acts of God.
8. Damages resulting from use of the product in a corrosive atmosphere.
9. Normal maintenance, or damages resulting from failure to perform normal maintenance, as outlined in the installation and servicing instructions or owner's manual.
10. Cleaning or replacement of filters, nozzles, or orifices.
11. Damages resulting from operation with inadequate supply of air or water; Damages resulting from failure to properly and regularly clean air and/ or water side of condenser and evaporator.
12. Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water;
(IV) fouling or restriction of the water circuit by foreign material or like causes.
13. Damages caused by improper parts, components or accessories not suitable for use in or with the unit. For a list of parts that are known to be compatible please reference the equipment renewal parts list, contact a Participating Dealer for assistance, or call 1-877-874-7378.
14. Electricity or fuel costs, or increases in fuel or electric costs, for any reason including additional or unusual use of supplemental electric heat.
This warranty is in lieu of all other express warranties. All implied warranties, including the implied warranty of merchantability and fitness for a particular purpose are limited in duration to the actual warranty period applicable to the part. Some states do not allow the disclaimer of implied warranties, so the above disclaimer may not apply to you. In addition, some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. In no event, whether as a result of breach of warranty or contract, tort (including negligence), strict liability, or otherwise, shall Company be liable for special, incidental, or consequential damages or expenses, including but not limited to loss of use of the equipment or associated equipment, lost revenues or profits, cost of substitute equipment, or cost of fuel or electricity.
The above limitations shall inure to the benefit of Company's suppliers and subcontractors. The above limitation on consequential damages shall not apply to injuries to persons in the case of consumer goods. Company does not assume, or authorize any other person to assume for Company, any other liability for the sale of this product. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you. This warranty gives you specific legal rights. You may also have other rights which vary from state to state.
Subject to change without notice. Published in U.S.A.
Copyright © 2013 by Johnson Controls, Inc. All rights reserved.
York International Corp.
3110 N. Mead
Wichita, KS 67219
129099-BUM-K-0613
Supersedes: 129099-BUM-J-0112
advertisement
Key Features
- High efficiency sealed combustion
- Downflow furnace
- Automatic ignition
- Continuous blower
- Safety shutoff switch
- Filter replacement
Frequently Answers and Questions
How do I turn off the appliance?
How often should I replace the air filters?
What should I do if the furnace fails to operate properly?
How do I clean the burner?
How do I clean the heat exchanger?
Related manuals
advertisement
Table of contents
- 1 CONTACT INFORMATION FOR USA
- 1 CONTACT INFORMATION FOR CANADA
- 1 SAFETY
- 2 While you are away
- 2 SEASONAL SERVICE INFORMATION
- 2 Your Service Technician
- 2 DESCRIPTION
- 2 WARRANTY AND RESPONSIBILITIES
- 3 GAS SUPPLY
- 3 Natural Gas Operation
- 3 Propane Gas Operation
- 3 FURNACE INSTALLATION
- 3 Observing Burner Operation
- 3 If Furnace Fails to Operate Properly
- 4 HOW YOUR GAS FURNACE WORKS
- 4 IF FURNACE FAILS TO OPERATE PROPERLY
- 4 When You Call For Service Assistance
- 4 To Contact Your Serviceman
- 4 SAFETY INFORMATION
- 4 to Start the Furnace
- 4 START-UP AND SHUTDOWN INSTRUCTIONS
- 4 Operating Instructions
- 5 To Turn Off the Appliance
- 5 FURNACE USER MAINTENANCE
- 5 Air Filters
- 5 Removing Filters
- 6 Blower Care
- 6 Motor Lubrication
- 6 SERVICE AND MAINTENANCE MANUAL
- 6 SAFETY SECTION
- 6 FURNACE MAINTENANCE SECTION
- 6 FURNACE CLEANING SECTION
- 6 Burner Removal/Cleaning
- 6 Cleaning the Heat Exchanger
- 6 THE FURNACE CONTROLS AND THEIR FUNCTION
- 7 SEQUENCE OF OPERATION
- 7 Continuous Blower
- 7 Heating Cycle
- 7 Hot Surface Ignition System
- 7 TROUBLESHOOTING
- 8 FURNACE CONTROL DIAGNOSTICS
- 9 REPLACEMENT PARTS LIST
- 11 WIRING DIAGRAM
- 13 LIMITED WARRANTY