THE WALL-MOUNT™ GAS/ELECTRIC
Models: W24G3 to W60G3 Up to 10.5 EER
26,000 to 57,500 BTUH Cooling Capacity
34,000 to 102,500 BTUH Heating Capacity
G reen
r efriGerant r-410a
The Bard Wall-Mount Electric Air Conditioner with gas fired heating is a self-contained energy efficient system which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space.
This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, portable structures, correctional facilities, retail stores or other commercial applications. Factory or field installed accessories are available to meet specific job requirements.
Engineered Features
Air Conditioner Compressor:
Scroll compressors are used on all models and no crankcase heaters are required.
R-410A Refrigerant:
Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.
Pre-Painted 20 Gauge Zinc Coated
Steel Cabinet:
Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.
High & Low Pressure Switches are Auto-
Reset:
Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor.
16 Gauge Zinc Coated Unit Base.
Liquid Line Filter Drier:
Protects system against moisture.
Aluminum Finned Copper Coils:
Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.
Compressor Control Module:
Standard on all units. Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls.
Alarm output for alarm relay.
Heat Exchanger:
Heavy duty 18-gauge stainless steel tubular heat exchanger. Mechanically joined construction. Ten-year warranty.
In-Shot Burners:
Advanced burner design, quiet operation.
Built-in Circuit Breakers:
Standard on all single (230/208 volt) and three phase (230/208 volt) equipment. Toggle disconnects are standard on all three phase (460 volt) equipment.
Air Filters:
Two-inch pleated air filters are standard equipment.
Optional 1-inch washable filter available.
Factory or field installed.
Barometric Fresh Air Damper:
Standard on all units. Allows up to 25% outside fresh air.
Integrated DSI Control:
Direct spark ignition control and remote sensor delivers smooth, proven ignition sequence. Timed blower control and diagnostics are also features of integrated control.
Ventilation Options:
Several ventilation options are available and can be factory or field installed.
Slope Top:
Standard feature for water run-off.
Phase Rotation Monitor:
Standard on all 3 phase scroll compressors.
Protects against reverse rotation if power supply is not properly connected.
Twin Blowers:
Move air quietly. All models feature multispeed blower motors providing airflow adjustment for high and low static operation.
Electrical Components:
Are easily accessible for routine inspection and maintenance through a right side service panel opening. Features a lockable, hinged access cover to the circuit breaker.
Gas Controls:
Honeywell gas valve and burner orifices are factory standard for natural gas.
High altitude kits available. Field convertible to LP gas with certified conversion kit.
Filter Service Door:
Separate service door provides easy access for filter change.
Condenser Fan and Motor Shroud
Assembly:
Slides out for easy access.
Top Rain Flashing:
Standard feature on all models.
Full Length Mounting Brackets:
Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.
Evaporator Freezestat:
Standard on dehumidification models.
• Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2010.
• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL
1995/CSA 22.2 No. 236-05, Fourth Edition.
• Intertek ETL Listed to Standard for Gas-Fired Central Furnaces ANSI Z21.47-2006,
CSA 2.3-2006 Fifth Edition, Addenda A dated 10-01-2007, Addenda B dated 06-01-2008.
• Commercial Product - Not intended for Residential application.
Form No.
Supersedes
Page
S3500-615
NEW
1 of 16
Specifications 2 Ton through 3 Ton
MODELS
Electrical Rating – 60 Hz
Operating Voltage Range
Minimum Circuit Ampacity
*Field Wire Size
Ground Wire Size
** Delay Fuse - Max.
Compressor
Voltage
Rated Load Amps
Branch Circuit
Selection Current
Lock Rotor Amps
Compressor Type
Fan Motor & Condenser
Fan Motor--HP--RPM-SPD
Fan Motor--Amps
Fan--DIA/CFM
Blower Motor & Evap.
Blower Motor--HP-RPM-SPD
Blower Motor--Amps
CFM Cooling & E.S.P.
Filter Size
Shipping Weight --LBS.
W24G3-A W24G3-B
230/208 - 1 230/208 - 3
197-253
21
10
10
30
187-253
16
12
12
25
230/208
9.9/10.9
12.8
64/64
Scroll
230/208
6.4/7.1
8.3
58/58
Scroll
W24G3-C
460 - 3
414-506
10
14
14
15
460
3.9
5.1
28
Scroll
W30G3-A W30G3-B
230/208 - 1 230/208 - 3
197-253
23
10
10
35
187-253
17
12
12
25
230/208
11.8/12.9
14.1
77/77
Scroll
230/208
7.5/8.2
9
71/71
Scroll
W30G3-C
460 - 3
414-506
11
14
14
15
460
4.7
5.6
38
Scroll
W36G3-A W36G3-B
230/208 - 1 230/208 - 3
197-253
27
8
10
40
187-253
20
10
10
25
230/208
12.4/14.0
16.7
79/79
Scroll
230/208
7.8/8.8
10.5
73/73
Scroll
W36G3-C
460 - 3
414-506
11
14
14
15
460
4.9
5.8
38
Scroll
1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1
1.5
1.5
.8
1.5
1.5
.8
1.5
1.5
.8
20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400
1/4-950-3
1.8
1/4-950-3
1.8
1/4-950-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3
.8
2.2
2.2
1.1
2.2
2.2
1.1
800 - .15
800 - .15
800 - .15
1000 - .35
1000 - .35
1000 - .35
1100 - .25
1100 - .25
1100 - .25
20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2
500 500 500 530 530 530 530 530 530
Specifications 3.5 Ton through 5 Ton
MODELS
Electrical Rating – 60 Hz
Operating Voltage Range
Minimum Circuit Ampacity
*Field Wire Size
Ground Wire Size
** Delay Fuse - Max.
Compressor
Voltage
Rated Load Amps
Branch Circuit
Selection Current
Lock Rotor Amps
Compressor Type
Fan Motor & Condenser
Fan Motor--HP--RPM-SPD
Fan Motor--Amps
Fan--DIA/CFM
Blower Motor & Evap.
Blower Motor--HP-RPM-SPD
Blower Motor--Amps
CFM Cooling & E.S.P.
Filter Size
Shipping Weight --LBS.
W42G3-A W42G3-B
230/208 - 1 230/208 - 3
197-253
33
8
10
50
187-253
25
8
10
35
230/208
16/17.9
19.9
109/109
Scroll
230/208
10.6/11.8
13.1
83/83
Scroll
W42G3-C
460 - 3
414-506
12
14
14
15
460
5.5
6.1
41
Scroll
W48G3-A W48G3-B
230/208 - 1 230/208 - 3
197-253
36
8
10
50
187-253
26
8
10
35
230/208
15.9/18.9
21.8
117/117
Scroll
230/208
10.0/11.9
13.8
83/83
Scroll
W48G3-C
460 - 3
414-506
12
14
14
15
460
5.4
6.3
41
Scroll
W60G3-A W60G3-B
230/208 - 1 230/208 - 3
197-253
41
8
10
60
187-253
27
8
10
40
230/208
23.2/26.3
26.3
134/134
Scroll
230/208
14.0/16.6
16.6
110/110
Scroll
W60G3-C
460 - 3
414-506
14
12
12
20
460
7.8
7.8
52
Scroll
1/3 - 825 - 2 1/3 - 825 - 2 1/3 - 825 - 1 1/3 - 825 - 2 1/3 - 825 - 2 1/3 - 825 - 1 1/3 - 825 - 2 1/3 - 825 - 2 1/3 - 825 - 1
2.5
2.5
1.3
2.5
2.5
1.3
2.5
2.5
1.3
24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050
1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3
3.4
3.4
1.5
3.4
3.4
1.5
3.4
3.4
1.5
1300 - .35
1300 - .35
1300 - .35
1550 - .38
1550 - .38
1550 - .38
1650 - .30
1650 - .30
1650 - .30
20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2
700 700 700 710 710 710 725 725 725
*Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
**Maximum time delay fuse or HACR type circuit breaker.
Form No. S3500-615
Supersedes
NEW
Page 2 of 16
Cooling System Capacity, Efficiency & Airflow Ratings and Available Heating Inputs
Models
W24G3 W30G3 W36G3 W42G3 W48G3 W60G3
Cooling Capacity BTUH
EER
Rated CFM
Acceptable Airflow Range
Available Heating Inputs
26,000
10.0
800
680 - 920
90,000
68,000
45,000
32,000
10.0
1000
850 - 1150
90,000
68,000
45,000
35,000
10.2
1100
935 - 1265
90,000
68,000
45,000
42,000
10.0
1300
1030 - 1500
125,000
100,000
75,000
48,000
10.5
1550
1280 - 1750
125,000
100,000
75,000
57,500
10.1
1650
1340 - 1910
125,000
100,000
75,000
Capacity is certified in accordance with ANSI/ARI Standard 390-2003.
EER = Energy Efficiency Ratio and is certified in accordance with ARI Standard 390-2003.
All ratings based on fresh air intake being 100% closed (no outside air introduction).
Any one of the heating inputs shown is available for each basic cooling model as indicated. Each input can be field derated 10% from factory standard and main
burner orifices are included with each unit to accomplish this. See table below for additional information.
Heating System Capacity, Efficiency, Derate & Airflow Ratings W24G, W30G, W36G
Input
Output
Thermal Efficiency (T.E.)
Temp. Rise Range
Mid-Rise Range Airflow
Acceptable Airflow Range
Factory Standard
90,000
74,000
82.0
50 - 80
1040
845 - 1350
Heating ratings certified in accordance with ANSI Z21.47-2006.
Field Derate
81,000
66,500
82.0
50 - 80
940
765 - 1220
Factory Standard
68,000
55,500
82.0
40 - 70
925
730 - 1275
Field Derate
61,000
50,000
82.0
40 - 70
825
650 - 1135
Factory Standard
45,000
37,000
82.0
25 - 55
830
610 - 1330
Field Derate
41,000
34,000
82.0
25 - 55
740
540 - 1185
Heating System Capacity, Efficiency, Derate & Airflow Ratings W42G, W48G, W60G
Factory Standard
Input
Output
Thermal Efficiency (T.E.)
Temp. Rise Range
Mid-Rise Range Airflow
Acceptable Airflow Range
125,000
102,500
82.0
50 - 80
1410
1145 - 1830
Heating ratings certified in accordance with ANSI Z21.47-2006.
Field Derate
113,000
93,000
82.0
50 - 80
1270
1030 - 1650
Factory Standard
100,000
82,000
82.0
40 - 70
1365
1075 - 1875
Field Derate
90,000
74,000
82.0
40 - 70
1230
965 - 1700
Factory Standard
75,000
61,500
82.0
30 - 60
1250
940 - 1875
Field Derate
68,000
56,000
82.0
30 - 60
1135
850 - 1700
Indoor Blower Performance Factory Connected Speeds
SPEED
W24G cooling airflow is rated 800 CFM @ .15 ESP, and wet coil range is 700 - 910 CFM.
See Heating Airflow Ratings Chart for heating details.
ESP
Inches
H
2
0
.10
.20
.30
.40
.50
.60
Cooling Mode
Wet Coil
High Med
MANUAL FAN and HEATING MODE
90,000 BTU Input
Low High
Med
820 1260 1060
Low
81,000 BTU Input
High Med
1060
Low
870
950
880
770
700
1200 1010
1120
1200 1010
1120 940
910
800
790
710
1030 1030
950
840
860
W30G cooling airflow is rated 1000 CFM @ .35 ESP, and wet coil range is 880 - 1150 CFM.
See Heating Airflow Ratings Chart for heating details.
ESP
Inches
H
2
0
.10
.20
.30
Cooling Mode
Wet Coil
High
Med
Low
1000
MANUAL FAN and HEATING MODE
90,000 BTU Input 81,000 BTU Input
High
Med
Low
1260 1060
High Med Low
1260 1060
1160 950 1370 1200 1010
1080 880 1290 1120 940
1200 1010
1120 940
.40
1150 990
.50
1050 910
.60
940
1190 1030
1090 950
980
1190 1030 860
1090 950
980 840
ESP
Inches
H
2
0
.10
.20
.30
.40
.50
.60
Cooling Mode
Wet Coil
High Med
MANUAL FAN and HEATING MODE
68,000 BTU Input
Low High
Med Low
820 1260 1060 870
61,000 BTU Input
High Med
1060
Low
870
950 770 1200 1010 1010 810
910
800
880
790
710
700 1120
1030
950
910 1120 940
1030 860
950
840
780
ESP
Inches
H
2
0
.10
Cooling Mode
Wet Coil
High Med
MANUAL FAN and HEATING MODE
45,000 BTU Input
Low High
Med Low
820 1260 1060 870
41,000 BTU Input
High Med
1060
Low
870
.20
.30
950
880
770 1200 1010 810 1200 1010 810
700 1120 910 1120 940 750
.40
.50
910
790
710
1030
950
860
780
1030
950
860
780
680
.60
800 840 840
Voltage adjustment - Reduce airflow by 100 CFM for 208 Volt
Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed
Top outlet adjustment - Increase airflow by 50 CFM for top outlet models
SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 100 CFM for SG-3 and RG-3 installations
ESP
Inches
H
2
0
.10
.20
Cooling Mode
Wet Coil
High
Med
Low
1000
1160 950
.30
1080 880
.40
1150 990
.50
1050 910
.60
940
MANUAL FAN and HEATING MODE
68,000 BTU Input 61,000 BTU Input
High
Med
Low
1260 1060
High Med Low
1060
1200 1010 1010
1120 940
1190 1030 860
1090 950
980 840
780 1090
980
1120
1030
950
840
940
860
780
660
ESP
Inches
H
2
0
.10
Cooling Mode
Wet Coil
High
Med
Low
1000
MANUAL FAN and HEATING MODE
45,000 BTU Input 41,000 BTU Input
High
Med
Low
1260 1060
High Med Low
1060
.20
.30
1160 950 1200 1010
1080 880 1290 1120 940
.40
1150 990
.50
1050 910
1190 1030
1090 950
860
780 1090
1200 1010
1120
1030
950
940
860
780
.60
940 980 840 660 980 840 660
Voltage adjustment - Reduce airflow by 100 CFM for 208 Volt
Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed
Top outlet adjustment - Increase airflow by 50 CFM for top outlet models
SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 100 CFM for SG-3 and RG-3 installations
Form No.
Supersedes
Page
S3500-615
NEW
3 of 16
Indoor Blower Performance Factory Connected Speeds
W36G cooling airflow is rated 1100 CFM @ .25 ESP, and wet coil range is 940 - 1250 CFM.
See Heating Airflow Ratings Chart for heating details.
ESP
Inches
H
2
0
.10
.20
Cooling Mode
Wet Coil
High
Med
Low
1220 1000
High
MANUAL FAN and HEATING MODE
90,000 BTU Input
Med
Low
1260 1060
1160 950 1370 1200 1010
81,000 BTU Input
High Med Low
1260 1060
1200 1010
SPEED
W42G cooling airflow is rated 1300 CFM @ .35 ESP, and wet coil range is 1030 - 1480 CFM.
See Heating Airflow Ratings Chart for heating details.
ESP
Inches
H
2
0
.10
.20
Cooling Mode
Wet Coil
High
Med
Low
1520 1110
MANUAL FAN and HEATING MODE
125,000 BTU Input
High
Med
1450 1050 1880 1510
Low
1580 1180
113,000 BTU Input
High Med Low
1580 1180
1510 1090
.30
1250 1080
.40
1150 990
.50
1050
.60
940
1290 1120 940
1190 1030
1090 950
980
1120 940
1190 1030 860
1090 950
980 840
.30
1400
.40
1480 1290
.50
1390
.60
1270
1760 1460
1670 1340
1560 1240
1430
1460
1670 1340
1560 1240
1430 1130
ESP
Inches
H
2
0
.10
Cooling Mode
Wet Coil
High
Med
Low
1220 1000
.20
1160 950
.30
1250 1080
.40
1150 990
.50
1050
.60
940
MANUAL FAN and HEATING MODE
68,000 BTU Input 61,000 BTU Input
High
Med
Low
1260 1060
High Med Low
1060
1200 1010
1120 940
1010
1120 940
1190 1030 860
1090 950 780 1090
1030
950
860
780
980 840 980 840 660
ESP
Inches
H
2
0
Cooling Mode
Wet Coil
High
Med
Low
1220 1000 .10
.20
1160 950
.30
1250 1080
.40
1150 990
.50
1050
MANUAL FAN and HEATING MODE
45,000 BTU Input
High
Med
Low
1260 1060
41,000 BTU Input
High Med Low
1200 1010
1290 1120
1090 950
940
1190 1030 860
780 1090
1060
1200 1010
1120 940
1030
950
860
780
.60
940 980 840 660 980 840 660
Voltage adjustment - Reduce airflow by 100 CFM for 208 Volt
Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed
Top outlet adjustment - Increase airflow by 50 CFM for top outlet models
SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 100 CFM for SG-3 and RG-3 installations
W48G cooling airflow is rated 1550 CFM @ .20 ESP, and wet coil range is 1250 - 1780 CFM.
See Heating Airflow Ratings Chart for heating details.
ESP
Inches
H
2
0
.10
Cooling Mode
High
Wet Coil
Med
1520
.20
1710 1450
Low
MANUAL FAN and HEATING MODE
125,000 BTU Input 113,000 BTU Input
High
Med
Low
1580 1180
High Med Low
1580 1180
1880 1510 1510 1110
.30
1600 1400
.40
1480 1290
.50
1390
.60
1270
1760 1460
1670 1340
1560 1240
1430
1460 1090
1670 1340
1560 1240
1430 1130
ESP
Inches
H
2
0
.10
Cooling Mode
Wet Coil
High
Med
1560
.20
1760 1490
Low
.30
1630 1440
.40
1530 1330
.50
1440 1210
.60
1320
100,000 BTU Input
High
MANUAL FAN and HEATING MODE
Med
1630 1230
1560 1160
1810 1510 1140
1720 1390
1610 1290
Low
90,000 BTU Input
High Med Low
1630 1230
1560 1160
1510 1140
1720 1390 1020
1610 1290
1480 1180 1480 1180
ESP
Inches
H
2
0
.10
Cooling Mode
Wet Coil
High
Med
1600
.20
1805 1530
Low
.30
1680 1480
High
MANUAL FAN and HEATING MODE
75,000 BTU Input
Med
Low
68,000 BTU Input
High Med Low
1680 1280 1680 1280
1610 1210
1860 1560 1190
1610 1210
1560 1190
.40
1580 1360
.50
1490 1280
1770 1440 1070
1660 1340
1440 1070
1660 1340 970
.60
1370 1530 1230 1530 1230
Voltage adjustment - Reduce airflow by 130 CFM for 208 Volt
Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed
Top outlet adjustment - Increase airflow by 65 CFM for top outlet models
SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 170 CFM for SG-5 and RG-5 installations
Form No. S3500-615
Supersedes
NEW
Page 4 of 16
ESP
Inches
H
2
0
.10
Cooling Mode
Wet Coil
High
Med
Low
1560 1160
MANUAL FAN and HEATING MODE
100,000 BTU Input 90,000 BTU Input
High
Med
Low
1630 1230
High Med Low
1630 1230
.20
.30
.60
1320
1490 1090 1560 1160
1440 1070 1810 1510 1140
.40
1530 1330
.50
1440 1210
1720 1390
1610 1290
1480 1180
1560 1160
1510 1140
1720 1390 1020
1610 1290
1480 1180
ESP
Inches
H
2
0
Cooling Mode
Wet Coil
High
Med
Low
1600 1260
MANUAL FAN and HEATING MODE
75,000 BTU Input
High
Med
Low
1680 1280 .10
.20
.30
.40
1530 1190 1610 1210
1480 1120 1860 1560 1190
1360 1100 1770 1440 1070
.50
1490 1280 1660 1340
68,000 BTU Input
High Med
1680 1280
1610 1210
1560 1190
1440 1070
1660 1340
Low
970
.60
1370 1530 1230 1530 1230
Voltage adjustment - Reduce airflow by 130 CFM for 208 Volt
Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed
Top outlet adjustment - Increase airflow by 65 CFM for top outlet models
SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 170 CFM for SG-5 and RG-5 installations
W60G cooling airflow is rated 1650 CFM @ .30 ESP, and wet coil range is 1360 - 1850 CFM.
See Heating Airflow Ratings Chart for heating details.
ESP
Inches
H
2
0
High
Cooling Mode
Wet Coil
Med
.10
1800 1520
Low
MANUAL FAN and HEATING MODE
125,000 BTU Input
High
Med
Low
1950 1580 1180
113,000 BTU Input
High Med Low
1580 1180
.20
1710 1450
.30
1600 1400
.40
1480
.50
1390
.60
1880 1510
1760 1460
1670 1340
1560 1240
1430
1880 1510 1110
1760 1460 1090
1670 1340
1560 1240
1430 1130
ESP
Inches
H
2
0
High
Cooling Mode
Wet Coil
Med
.10
1860 1560
Low
.20
1760 1490
.30
1630 1440
.40
1530 1330
.50
1440
.60
1320
100,000 BTU Input
High
MANUAL FAN and HEATING MODE
Med
1630 1230
1930 1560 1160
1810 1510 1140
1720 1390
1610 1290
Low
90,000 BTU Input
High Med Low
1630 1230
1560 1160
1510 1140
1720 1390 1020
1610 1290
1480 1180 1480 1180
ESP
Inches
H
2
0
High
Cooling Mode
Wet Coil
Med Low
.10
1910 1600
.20
1805 1530
.30
1680 1480
MANUAL FAN and HEATING MODE
75,000 BTU Input
High
Med
Low
68,000 BTU Input
High Med Low
1680 1280 1680 1280
1980 1610 1210
1860 1560 1190
1610 1210
1560 1190
.40
1580 1360
.50
1490
1770 1440 1070
1660 1340
1440 1070
1660 1340 970
.60
1370 1530 1230 1530 1230
Voltage adjustment - Reduce airflow by 130 CFM for 208 Volt
Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed
Top outlet adjustment - Increase airflow by 65 CFM for top outlet models
SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 170 CFM for SG-5 and RG-5 installations
Important Information Concerning Altitude Impact on Heating Input Ratings
Heating input, and thus heating output, decreases with altitude. No orifice change is required up to 6,000 feet elevation and derate occurs naturally due to altitude impact.
Natural gas models may require orifice change based on BTU content of gas. See Natural Gas Orifice and Altitude Tables on next page
for details. For Propane Gas see the Propane Gas Conversion Table below.
Above 6,000 feet elevation orifice changes are required, and capacity reductions are a function of altitude impact and orifice change. Pressure switch change is required above 6,000 feet elevation. For Natural Gas see the Orifice and Altitude Tables on next page. For Propane Gas see the Propane Gas
Conversion Table below
.
NATURAL GAS DERATE CAPACITIES
W**G Rated Input Sea Level 1000
41,000
45,000
41,000
45,000
39,204
43,560
61,000
68,000
58,806
65,340
61,000
68,000
75,000
81,000
90,000
100,000
113,000
125,000
75,000
81,000
90,000
100,000
113,000
125,000
72,600
78,408
87,120
96,800
108,900
121,000
2000
37,908
42,120
56,862
63,180
70,200
75,816
84,240
93,600
105,300
117,000
3000
36,612
40,680
54,918
61,020
67,800
73,224
81,360
90,400
101,700
113,000
4000
35,640
39,600
53,460
59,400
66,000
71,280
79,200
88,000
99,000
110,000
5000
34,992
38,880
52,488
58,320
64,800
69,984
77,760
86,400
97,200
108,000
6000
34,182
37,980
51,273
56,970
63,300
68,364
75,960
84,400
94,950
105,500
7000
33,696
37,440
50,544
56,160
62,400
67,392
74,880
83,200
93,600
104,000
8000
33,048
36,720
49,572
55,080
61,200
66,096
73,440
81,600
91,800
102,000
9000
32,643
36,270
48,965
54,405
60,450
65,286
72,540
80,600
90,675
100,750
10,000
32,076
35,640
48,114
53,460
59,400
64,152
71,280
79,200
89,100
99,000
PROPANE (LP) DERATE CAPACITIES
W**G Rated Input Sea Level 1000
41,000
45,000
41,000
45,000
39,852
44,280
61,000
68,000
61,000
68,000
59,778
66,420
2000
39,528
43,920
3000
39,204
43,560
4000
38,556
42,840
5000
38,232
42,480
6000
37,584
41,760
7000
36,612
40,680
8000
35,640
39,600
9000
34,344
38,160
10,000
32,724
36,360
59,292
65,880
58,806
65,340
57,834
64,260
57,348
63,720
56,376
62,640
54,918
61,020
53,460
59,400
51,516
57,240
49,086
54,540
75,000
81,000
90,000
100,000
113,000
125,000
75,000
81,000
90,000
100,000
113,000
125,000
73,800
79,704
88,560
98,400
110,700
123,000
73,200
79,056
87,840
97,600
109,800
122,000
72,600
78,408
87,120
96,800
108,900
121,000
71,400
77,112
85,680
95,200
107,100
119,000
70,800
76,464
84,960
94,400
106,200
118,000
69,600
75,168
83,520
92,800
104,400
116,000
67,800
73,224
81,360
90,400
101,700
113,000
66,000
71,280
79,200
88,000
99,000
110,000
63,600
68,688
76,320
84,800
95,400
106,000
60,600
65,448
72,720
80,800
90,900
101,000
Gas Pressure Inches W.C.
Minimum permissible gas supply pressure for purpose of input adjustment:
Maximum permissible gas supply pressure for purpose of input adjustment:
Manifold Pressure:
Natural 4.5 LP 11.0
Natural 11.0 LP 13.0
Natural 3.5 LP 10.0
Propane Gas Conversion Kits -- Fits All WG-Series Models
PROPANE (LP) GAS -- Use Gas Conversion Kits As Indicated
MODELS Propane Gas Conversion Kit Use WGCK-1
W24G
W30G
W36G
Factory
Standard
Input
22,500 - 22,650 BTU
Per Burner
Optional
10% Field
Converted
Derate
20,250 - 20,500 BTU
Per Burner
Gas
Heat
Value
BTU/Cu. Ft.
2500
Pressure Switch
Gas
Heat
Value
BTU/Cu. Ft.
2500
Pressure Switch
Up to 6000 Feet
Install Orifice
1.45
Standard (.55)
Up to 6000 Feet
Install Orifice
1.35
Standard (.55)
Use WGCK-2
6001 to 8000 Feet
Requires Pressure
Switch Change and
Orifice as Shown
8001 to 10,000 Feet
Requires Pressure
Switch Change and
Orifice as Shown
1.45
1.40
Pressure Switch (.42) Included in Conversion Kit
6001 to 8000 Feet
Requires Pressure
Switch Change and
Orifice as Shown
8001 to 10,000 Feet
Requires Pressure
Switch Change and
Orifice as Shown
1.35
1.30
Pressure Switch (.42) Included in Conversion Kit
PROPANE (LP) GAS -- Use Gas Conversion Kits As Indicated
MODELS Propane Gas Conversion Kit
W42G
W48G
Factory
Standard
Input
25,000 BTU
Per Burner
Gas
Heat
Value
BTU/Cu. Ft.
2500
Pressure Switch
W60G
Optional
10% Field
Converted
Derate
22,500 - 22,650 BTU
Per Burner
Gas
Heat
Value
BTU/Cu. Ft.
2500
Pressure Switch
All orifice sizes shown are millimeters (mm).
Use WGCK-1
Up to 6000 Feet
Install Orifice
1.50
Standard (.55)
Up to 6000 Feet
Install Orifice
1.45
Standard (.55)
Use WGCK-2
6001 to 8000 Feet
Requires Pressure
Switch Change and
Orifice as Shown
8001 to 10,000 Feet
Requires Pressure
Switch Change and
Orifice as Shown
1.50
1.45
Pressure Switch (.42) Included in Conversion Kit
6001 to 8000 Feet
Requires Pressure
Switch Change and
Orifice as Shown
8001 to 10,000 Feet
Requires Pressure
Switch Change and
Orifice as Shown
1.45
1.40
Pressure Switch (.42) Included in Conversion Kit
Form No.
Supersedes
Page
S3500-615
NEW
5 of 16
Natural Gas Orifice and Altitude Tables
NATURAL GAS -- W24G, W30G, W36G Models
Factory
Standard
Input
22,500 to
22,650
BTU
Per Burner
W24G
W30G
W36G
Gas
Heat*
Value
BTU/Cu. Ft.
700-749
750-799
800-849
850-899
900-949
950-999
1000-1049**
1050-1100
Pressure Switch
Up to 6000 Feet
No Changes
Except
For BTU Content
2.75
2.70
2.60
2.50
2.45
2.35
(2.30)
2.25
Standard (.55)
6001 to 8000 Feet
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
2.70
2.60
2.50
2.40
2.35
(2.30)
2.25
[2.20]
8001 to 10,000 Feet
Requires Pressure Switch
Change and Orifice Change
Basesd on BTU Content
2.60
2.50
2.45
2.35
(2.30)
2.25
[2.20]
2.15
Order 8620-189 High Altitude Pressure Switch Kit (.42)
(2.30) is the standard factory installed orifice size.
[2.20] orifices are shipped with the unit for field installed optional 10% derate.
All other orifice sizes shown are available as individual items, see orifice chart below for part numbers.
Optional
10% Field
Converted
Derate
Gas
Heat*
Value
BTU/Cu. Ft.
Up to 6000 Feet
No Changes
Except
For BTU Content
6001 to 8000 Feet
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
8001 to 10,000 Feet
Requires Pressure Switch
Change and Orifice Change
Basesd on BTU Content
20,250 to
20,500
BTU
Per Burner
W24G
700-749
750-799
800-849
850-899
900-949
950-999
1000-1049**
1050-1100
2.60
2.50
2.45
2.40
(2.30)
2.25
[2.20]
2.15
2.50
2.45
2.40
(2.30)
2.25
[2.20]
2.15
2.15
2.45
2.40
(2.30)
2.25
[2.20]
2.15
2.10
2.10
[2.20] orifices are shipped with the unit for field installed optional 10% input derate.
(2.30) is the factory installed orifice size for full rated input.
W30G
All other orifice sizes shown are available as individual items, see orifice chart below for part numbers.
W36G
Pressure Switch Standard (.55) Order 8620-189 High Altitude Pressure Switch Kit (.42)
* At standard conditions: 30.00 Inches Mercury, 60F, Saturated, .60 Specific Gravity
** All Natural Gas factory orifice sizing and standard input ratings based on nominal 1025 BTU per cubic foot gas and sea level conditions.
NATURAL GAS -- W42G, W48G, W60G Models
Factory
Standard
Input
25,000
BTU
Per Burner
W42G
W48G
W60G
Gas
Heat*
Value
BTU/Cu. Ft.
700-749
750-799
800-849
850-899
900-949
950-999
1000-1049**
1050-1100
Pressure Switch
Up to 6000 Feet
No Changes
Except
For BTU Content
2.90
2.80
2.70
2.60
2.50
2.45
(2.40)
[2.30]
Standard (.55)
6001 to 8000 Feet
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
8001 to 10,000 Feet
Requires Pressure Switch
Change and Orifice Change
Basesd on BTU Content
2.80
2.70
2.60
2.70
2.60
2.50
2.50
2.45
2.45
(2.40)
(2.40)
2.35
2.25
2.35
[2.30]
2.20
Order 8620-189 High Altitude Pressure Switch Kit (.42)
(2.40) is the standard factory installed orifice size.
[2.30] orifices are shipped with the unit for field installed optional 10% derate.
All other orifice sizes shown are available as individual items, see orifice chart below for part numbers.
Optional
10% Field
Converted
Derate
Gas
Heat*
Value
BTU/Cu. Ft.
Up to 6000 Feet
No Changes
Except
For BTU Content
6001 to 8000 Feet
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
8001 to 10,000 Feet
Requires Pressure Switch
Change and Orifice Change
Basesd on BTU Content
22,500 to
22,650
BTU
Per Burner
W42G
W48G
700-749
750-799
800-849
850-899
900-949
950-999
1000-1049**
1050-1100
2.75
2.70
2.60
2.50
(2.40)
2.35
[2.30]
2.25
2.70
2.60
2.50
2.45
2.35
[2.30]
2.25
2.25
2.60
2.50
2.45
(2.40)
[2.30]
2.25
2.20
2.20
[2.30] orifices are shipped with the unit for field installed optional 10% input derate.
(2.40) is the factory installed orifice size for full rated input.
All other orifice sizes shown are available as individual items, see orifice chart below for part numbers.
W60G
Pressure Switch Standard (.55) Order 8620-189 High Altitude Pressure Switch Kit (.42)
* At standard conditions: 30.00 Inches Mercury, 60F, Saturated, .60 Specific Gravity
** All Natural Gas factory orifice sizing and standard input ratings based on nominal 1025 BTU per cubic foot gas and sea level conditions.
Bard
Part No.
9010-092
9010-088
9010-087
9010-086
9010-082
9010-085
9010-079
9010-084
9010-093
9010-094
9010-095
9010-096
9010-097
9010-098
Orifice
Size (mm)
2.10
2.15
2.20
2.25
2.30
2.35
2.40
2.45
2.50
2.60
2.70
2.75
2.80
2.90
Orifice
Diameter
0.0826
0.0846
0.0866
0.0885
0.0905
0.0925
0.0945
0.0964
0.0984
0.1024
0.1063
0.1082
0.1102
0.1142
All orifice sizes shown are in millimeters (mm).
Form No. S3500-615
Supersedes
NEW
Page 6 of 16
No. of Orifices Required
Based on Unit Input Rating
41,000 (2)
45,000 (2)
61,000 (3)
68,000 (3)
75,000 (3)
81,000 (4)
90,000 (4)
100,000 (4)
113,000 (5)
125,000 (5)
Ventilation System Packages
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements.
All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory, or field-installed at a later date.
BAROMETRIC FRESH AIR DAMPER - WGBFAD STANDARD
The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.
BAROMETRIC FRESH AIR DAMPER
BLANK OFF PLATE - WGBOP OPTIONAL
A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - WGMFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a
24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.
MOTORIZED FRESH AIR DAMPER
COMMERCIAL ROOM VENTILATOR
ECONOMIZER
ENERGY RECOVERY VENTILATOR
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.
COMMERCIAL ROOM VENTILATOR - WGCRV OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper.
The commercial room ventilator (WGCRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the WGCRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The WGCRV can be controlled by indoor blower operation or field controlled based on room occupancy. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.
Two Models Available:
WGCRVS - spring return on power loss or deactivation
WGCRVP - power return (will not close on power loss)
ECONOMIZER - WGJIFM OPTIONAL
The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
Standard Features:
• One Piece Construction - Easy to install with no mechanical linkage adjustment required.
• Exhaust Air Damper - Built in with positive closed position. Provides exhaust air capability to prevent pressurization
of tight buildings.
• Actuator Motor - 24 volt, power open, spring return with built in torque limiting switch.
• Proportioning Type Control - for maximum “free cooling” economy and comfort.
• Moisture Eliminator & Prefilter - permanent, washable aluminum construction.
• Enthalpy Control - adjustable to monitor outdoor temperature and humidity.
• Honeywell JADE™ electronic economizer module with precision settings and diagnostics.
• Mixed Air Sensor - to monitor outside and return air to automatically modulate damper position.
WALL-MOUNT ENERGY RECOVERY VENTILATOR - WGERV OPTIONAL
The wall-mount energy recovery ventilator (WGERV) is a highly innovative approach to address indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The WGERV allows up to 450 CFM (depending upon speed setting) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels.
In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat transfer efficiency is up to 74% during summer and 80% during winter conditions.
The WGERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only.
The WGERV is designed to be internally mounted behind the service door in the WG Gas/Electric units. It can be builtin at the factory or field installed as an option. WGERV can be independently adjusted for intake and exhaust rates.
NOTE: See Page 8 for WGERV Performance Data and Page 9 for WGCRV Performance Data
Form No.
Supersedes
Page
S3500-615
NEW
7 of 16
Form No. S3500-615
Supersedes
NEW
Page 8 of 16
W24G CRV Airflow Versus Position - Low Speed
600
550
500
450
400
350
300
250
200
150
100
50
0 closed A B C
Damper Position
D Open
Free Blow
.15" ESP
.30" ESP
W24G CRV Airflow Versus Position - Medium Speed
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0 closed A B C
Damper Position
D Open
Free Blow
.15" ESP
.30" ESP
W24G CRV Airflow Versus Position - High Speed
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0 closed A B C
Damper Position
D Open
Free Blow
.15" ESP
.30" ESP
Form No.
Supersedes
Page
S3500-615
NEW
9 of 16
Form No. S3500-615
Supersedes
NEW
Page 10 of 16
W30-36G CRV Airflow Versus Position - Low Speed
400
350
300
250
200
150
100
50
0
650
600
550
500
450 closed A B C
Damper Position
D Open
Free Blow
.15" ESP
.30" ESP
W30-36G CRV Airflow Versus Position - Medium
Speed
450
400
350
300
250
200
150
100
50
0
750
700
650
600
550
500 closed A B C
Damper Position
D Open
Free Blow
.15" ESP
.30" ESP
W30-36G CRV Airflow Versus Position - High Speed
400
350
300
250
200
150
100
50
0
800
750
700
650
600
550
500
450 closed A B C
Damper Position
D Open
Free Blow
.15" ESP
.30" ESP
W42-60G CRV Airflow Versus Position - Low Speed
650
600
550
500
450
400
350
300
250
200
150
100
50
0 closed A B C
Damper Position
D Open
Free Blow
0.15" ESP
0.30" ESP
W42-60G CRV Airflow Versus Position - Medium
Speed
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0 closed A B C
Damper Position
D Open
Free Blow
0.15" ESP
0.30" ESP
W42-60G CRV Airflow Versus Position - High Speed
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0 closed A B C
Damper Position
D Open
Free Blow
0.15" ESP
0.30" ESP
Form No.
Supersedes
Page
S3500-615
NEW
11 of 16
W24G3D Application Performance Data
Indoor
Conditions
Outdoor
Conditions
System Capacity
DB/WB % RH DB Total Sensible Latent S/T
65/63
65/63
90
90
75/62.5
50
75/62.5
50
75/65.5
60
75/65.5
60
75/68 70
75/68
80/67
80/67
70
50
50
65
65
75
75
75
75
75
75
95
95
27,900 11,900 16,000
-0(800) 13,050
28,750 19,750 7,000
9,650 3,700 5,950
28,550 17,550 11,000
10,950 2,000 8,950
29,650 15,450 14,200
11,850 350
26,000 18,900
-0(2,500)
11,500
7,100
6,000
W30G3D Application Performance Data
Indoor
Conditions
Outdoor
Conditions
System Capacity
.43
-0-
.69
.38
.62
.18
.52
.03
.73
-0-
DB/WB % RH DB Total Sensible Latent S/T
65/63
65/63
90
90
75/62.5
50
75/62.5
50
75/65.5
60
75/65.5
60
75/68 70
75/68
80/67
70
50
80/67
Form No. S3500-615
Supersedes
NEW
Page 12 of 16
50
65/63
65/63
90
90
75/62.5
50
75/62.5
50
75/65.5
60
75/65.5
60
75/68
75/68
70
70
80/67
80/67
50
50
75
75
75
75
65
65
75
75
95
95
35,650 15,550 20,100
-0(950) 16,200
33,050 25,300
10,300 4,200
7,750
6,100
34,950 22,200 12,750
11,900 2,450 9,450
36,400 19,550 16,850
13,300 700 12,600
32,000 24,350
-0(2,200)
7,650
6,350
W36G3D Application Performance Data
Indoor
Conditions
Outdoor
Conditions
System Capacity
DB/WB % RH DB Total Sensible Latent S/T
.64
.21
.54
.05
.43
-0-
.76
.41
.76
-0-
65
65
75
75
75
75
75
75
95
95
35,050 15,350 19,700
11,600 (2,450) 14,050
33,800 26,250 7,550
7,150 1,500 5,650
34,900 22,550 12,350
8,850 (100) 8,950
36,100 19,600 16,500
10,250 (1,350) 11,600
34,500 26,600 7,900
300 (5,500) 5,800
.44
-0-
.78
.21
.65
-0-
.54
-0-
.77
-0-
Pounds of
Water/Hour
Lbs.
15.1
12.3
6.6
5.6
10.4
8.5
13.4
10.8
6.7
5.7
Evaporator
Airflow
CFM
800
800
800
800
800
800
800
800
800
800
Approximate
Supply Air
Mode
DB/WB
51.6 / 51.1
A/C vs.
Dehum
A/C
66.0 / 58.2
Dehum
52.5 / 50.8
A/C
70.8 / 58.5
Dehum
54.9 / 53.7
A/C
72.9 / 61.3
Dehum
57.4 / 56.5
A/C
74.7 / 63.8
Dehum
58.8 / 56.8
A/C
82.9 / 65.8
Dehum
Pounds of
Water/Hour
Lbs.
19.0
15.3
7.3
5.8
12.0
8.9
15.9
11.9
7.2
6.0
Evaporator
Airflow
CFM
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Approximate
Supply Air
Mode
DB/WB
51.1 / 50.8
A/C vs.
Dehum
A/C
65.9 / 58.1
Dehum
52.1 / 50.9
A/C
71.1 / 59.2
Dehum
54.8 / 53.9
A/C
72.8 / 61.8
Dehum
57.2 / 56.5
A/C
74.3 / 64.1
Dehum
58.0 / 56.8
82.1 /65.8
A/C
Dehum
Pounds of
Water/Hour
Lbs.
18.6
13.3
7.1
5.3
11.6
8.5
15.5
11.0
7.5
5.5
Evaporator
Airflow
CFM
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
Approximate
Supply Air
Mode
DB/WB
52.1 / 52.1
A/C vs.
Dehum
A/C
67.2 / 59.8
Dehum
53.7 / 51.9
A/C
73.9 / 62.5
Dehum
56.6 / 55.3
A/C
75.2 / 65.6
Dehum
58.8 / 58.0
A/C
76.2 / 65.3
Dehum
57.9 / 57.1
A/C
84.7 / 67.0
Dehum
W42G3D Application Performance Data
Indoor
Conditions
Outdoor
Conditions
System Capacity
DB/WB % RH DB Total Sensible Latent S/T
65/63
65/63
90
90
75/62.5
50
75/62.5
50
75/65.5
60
75/65.5
60
75/68
75/68
80/67
80/67
70
70
50
50
75
75
75
75
95
95
65
65
75
75
46,800 20,700 26,100
23,450 (900) 24,350
44,050 34,700
17,650 9,750
9,350
7,900
46,500 30,350 16,150
20,550 6,200 14,350
49,000 26,850 22,150
23,100 3,150
42,000 32,400
9,700 1,800
19,950
9,600
7,900
W48G3D Application Performance Data
Indoor
Conditions
Outdoor
Conditions
System Capacity
.65
.30
.55
.14
.77
.18
.44
-0-
.79
.55
DB/WB % RH DB Total Sensible Latent S/T
65/63 90
65/63 90
75/62.5
50
75/62.5
50
75/65.5
60
75/65.5
60
75/68
75/68
70
70
80/67
80/67
50
50
75
75
75
95
95
65
65
75
75
75
52,550 22,300 30,250
24,350 (2,050) 26,400
50,200 38,600 11,600
17,800 8,300 9,500
52,750 33,350 19,400
20,650 5,250 15,400
55,600 29,200 26,400
23,050 1,650 21,400
48,000 36,400 11,600
7,200 150 7,050
W60G3D Application Performance Data
Indoor
Conditions
Outdoor
Conditions
System Capacity
.26
.53
.07
.76
.02
.42
-0-
.77
.46
.63
DB/WB % RH DB Total Sensible Latent S/T
65/63
65/63
90
90
75/62.5
50
75/62.5
50
75/65.5
60
75/65.5
60
75/68 70
75/68
80/67
80/67
70
50
50
65
65
75
75
75
75
75
75
95
95
63,400 28,150 35,250
31,250 1,550 29,700
60,100 44,400 15,700
24,200 10,100 14,100
63,600 39,400 24,200
27,700 5,950 21,750
66,400 35,150 31,250
30,650 2,300 28,350
57,000 41,700 15,300
13,950 100 13,850
.44
.05
.74
.42
.62
.21
.53
.08
.73
.01
Pounds of
Water/Hour
Lbs.
24.6
23.0
8.8
7.5
15.2
13.5
20.9
18.8
9.1
7.5
Evaporator
Airflow
CFM
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
Approximate
Supply Air
Mode
DB/WB
52.0 / 51.6
A/C vs.
Dehum
A/C
65.6 / 57.4
Dehum
52.6 / 51.6
A/C
68.8 / 58.5
Dehum
55.5 / 54.8
A/C
71.2 / 61.1
Dehum
58.0 / 57.3
A/C
73.3 / 63.3
Dehum
58.8 / 57.5
A/C
79.0 / 65.1
Dehum
Pounds of
Water/Hour
Lbs.
14.5
24.9
20.2
10.9
6.6
28.6
24.9
11.0
9.0
18.3
Evaporator
Airflow
CFM
1450
1450
1450
1450
1450
1450
1450
1450
1450
1450
Approximate
Supply Air
Mode
DB/WB
51.0 / 50.7
A/C vs.
Dehum
A/C
66.3 / 57.8
Dehum
50.8 / 50.3
A/C
69.0 / 58.6
Dehum
54.1 / 53.6
A/C
71.6 / 61.3
Dehum
56.7 / 56.3
A/C
73.9 / 63.6
Dehum
57.1 / 56.5
A/C
79.9 / 65.6
Dehum
Pounds of
Water/Hour
Lbs.
33.3
28.0
14.8
13.3
22.8
20.5
29.5
26.7
14.4
13.1
Evaporator
Airflow
CFM
1650
1650
1650
1650
1650
1650
1650
1650
1650
1650
Approximate
Supply Air
Mode
DB/WB
49.9 / 49.7
A/C vs.
Dehum
A/C
66.3 / 57.0
Dehum
50.8 / 49.6
A/C
69.6 / 57.8
Dehum
53.7 / 52.8
A/C
72.1 / 60.5
Dehum
56.2 / 55.6
A/C
74.2 / 62.7
Dehum
57.3 / 56.0
A/C
80.2 / 64.6
Dehum
Form No.
Supersedes
Page
S3500-615
NEW
13 of 16
Return Air (DB/WB)
Form No. S3500-615
Supersedes
NEW
Page 14 of 16
DIMENSIONS OF BASIC UNIT
UNIT
W24G-W30G-W36G
W42G-W48G-W60G
A
7.88
9.88
B C D
27.88
13.88
24.25
E
40
29.88
15.88
27.25 43.81
F
14.88
G H
25.63 81.63
31.63
87.5
UNIT
W24G-W30G-W36G
W42G-W48G-W60G
S
12 - 7 HOLES
16 - 6 HOLES
T
3.75
U
2.88
3.88
V
22.9
24.9
W X Y
38 17.84 4.44
42
17.34 8.44
Z
2.25
I
30
AA
11.44
12.19
J K
27.38 27.5
33.38 28.75
L M
14.12 15.44
N
15.31
O
39.25
42.88
BB
3.25
CC
9
10
DD
7.25
EE
36.25
40.25
FF
1.13
GG
1.25
P
4.5
Q
2.5
HH
2
II
0.38
2.75
0.44
R
5.88
3.75
F
G
W
CONDENSER
AIR OUTLET
4 DEG. PITCH IN TOP
VESTIBULE
DOOR
COMBUSTION
AIR EXHAUST
N
P
FRONT DOOR
FILTER
DOOR
CIRCUIT BREAKER/
DISCONNECT ACCESS
PANEL (LOCKABLE)
VENT OPTION
PANEL
1
D
DD
FF
GG
HH II
A
U
M
Z
I
H
GAS
ENTRANCES
Q
X
L
C
AA
HIGH VOLTAGE
ENTRANCES
Y
J K
V
CC
1
E
EE
O
B
SUPPLY OPENING
BB
B
RETURN OPENING
S
S
S
S
R
S
FRONT
RIGHT SIDE
Optional top outlet in place of standard back supply opening, see Nomenclature outlet options (next page).
Standard unit can also be field converted to this configuration using approved top supply outlet conversion kit shown on next page.
BACK
T
MIS-3239 A
Minimum Clearances
INSTALLATION
Installation Wall (from combustible materials)
Outlet Duct (from combustible materials)
W24G - W30G - W36G
0"
1" first 3'
W42G - W48G - W60G
0"
1" first 3'
Vent Terminal (from combustible materials)
Top (from combustible materials)
17"
1"
16"
0"
Condenser Air Inlets 20" 20"
1-inch clearance at rear top of unit (at the wall surface). The 4° pitch of top creates 1.688 inch clearance between front top and any
extended overhang above the top of the unit.
0-inch clearance at rear top of unit (at the wall surface). The 4° pitch of top creates .688 inch clearance between front top and any
extended overhang above the top of the unit.
Service Access
ALL MODELS
Burner Service - Right side
Compressor - Right side
Controls - Right side
Condenser Fan - Left side
20"
20"
20"
20"
Form No.
Supersedes
Page
S3500-615
NEW
15 of 16
Air Conditioning Wall-Mount Model Nomenclature
MODEL NUMBER
W 36 G 3 A X B X X X X X
COOLING
CAPACITY
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
GAS /
ELECTRIC
REVISION
CODE
VOLTS & PHASE
A - 230/208-60-1
B - 230/208-60-3
C - 460-60-3
EMISSIONS
X - Standard
FILTER OPTIONS
X - 2-Inch Pleated
(MERV8)
W - 1-Inch Washable
X
CONTROL MODULES
(
See Control Module Options
)
| COIL OPTIONS
X - No Coating
1 - Phenolic Coated Evap.
2 - Phenolic Coated Cond.
3 - Phenolic Coating on both coils
FEATURE CODE
(-) = Standard
C = Canadian Approval
D = Dehumidification
HEATING INPUT
2-3 Ton 3.5 - 5 Ton
A = 45,000 B = 75,000
B = 68,000 C = 100,000
C = 90,000 D = 125,000*
VENT OPTIONS
(See Chart Below)
COLOR OPTIONS
X - Beige
4 - Buckeye Gray
8 - Dark Bronze
OUTLET OPTIONS
X - Front
T - Top
Ventilation Options
Models W24G, W30G, W36G
Description
Barometric Fresh Air Damper - No Exhaust
Blank-Off Plate
Motorized Fresh Air Damper - No Exhaust
Commercial Ventilator - Spring Return w/Exhaust
Factory Installed
Code No.
X
B
M
V
Commercial Ventilator - Power Return w/Exhaust
Economizer (Internal) Fully Modulating w/Exhaust
Energy Recovery Ventilator - 230 Volt w/Exhaust
P
E
R
Energy Recovery Ventilator - 460 Volt w/Exhaust
R
Low ambient control is required with economizer for low temperature compressor operation.
Independent selection of intake and exhaust speeds (rate) with terminal block selection.
â
Color option must be specified to match unit ("X" = Beige; "4" = Buckeye Gray)
Field Installed
Part No.
WGBFAD-3
WGBOP-3
WGMFAD-3A
WGCRVS-3A
WGCRVP-3A
WGJIFM-3
WGERV-A3B-â
WGERV-C3C-â
W42G, W48G, W60G
Factory Installed
Code No.
X
B
P
E
M
V
R
R
Field Installed
Part No.
WGBFAD-5
WGBOP-5
WGMFAD-5A
WGCRVS-5A
WGCRVP-5A
WGJIFM-5
WGERV-A5B-â
WGERV-C5C-â
Top Supply Outlet Conversion Kits-Field Installed (Convert Standard Front Outlet to Top Outlet)
USED WITH MODELS
W24G, W30G, W36G
W42G, W48G, W60G
UNIT COLOR X - BEIGE
TSO-WG3-X
TSO-WG5-X
UNIT COLOR 4 - BUCKEYE GRAY
TSO-WG3-4
TSO-WG5-4
UNIT COLOR 8 - DARK BRONZE
TSO-WG3-8
TSO-WG5-8
Air Conditioning Control Modules
AVAILABLE CONTROL OPTIONS
Factory Installed Code
Standard Unit
Field Installed Code
Dehumidification Unit
Field Installed Code
CCM HPC LPC LAC
STD
STD
STD
STD
STD
STD l
X
H
N/A
CMA-29 n
N/A
CMA-28 o
STD = Standard equipment
CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2-minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high and/or low-pressure controls, and a 2-minute timed bypass for low-pressure control.
HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .
LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .
LAC. Low ambient control permits cooling operation down to 0°F. Evaporator Freezestat is included.
n
CMA-29 Field installed LAC has evaporator Freezestat included.
o
CMA-28 Field installed LAC does not include Freezestat as one is installed as part of the dehumidification base unit.
Optional Field Installed Accessories
DESCRIPTION PART NUMBER
Natural Gas High Altitude Pressure Switch Kit (6000 - 10,000 Feet) 8620-189
Note: Natural Gas Orifice Change May Be Required Depending Upon Altitude and Gas BTU content. See Orifice and Altitude Tables.
Propane Gas Conversion Kit (0 - 6000 Feet Altitude)
Propane Gas Conversion Kit (6000 - 10,000 Feet Altitude)
WGCK-1
WGCK-2
Vertical Vent Kit (Includes all parts for 5 foot vertical vent)
Additional 1 foot vertical vent pipe section for VVK-5A
Additional 2 foot vertical vent pipe section for VVK-5A
Additional 3 foot vertical vent pipe section for VVK-5A
Additional 5 foot vertical vent pipe section for VVK-5A
VVK-5A
8620-201
8620-170
8620-200
8620-171
Form No. S3500-615
Supersedes
NEW
Page 16 of 16
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506 www.bardhvac.com
Due to our continuous product improvement policy, all specifications subject to change without notice.
Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
Form No.
S3500
June, 2015
Supersedes:
NEW