THE WALL-MOUNT™ GAS/ELECTRIC

Add to my manuals
16 Pages

advertisement

THE WALL-MOUNT™ GAS/ELECTRIC | Manualzz

THE WALL-MOUNT™ GAS/ELECTRIC

Models: W24G3 to W60G3 Up to 10.5 EER

26,000 to 57,500 BTUH Cooling Capacity

34,000 to 102,500 BTUH Heating Capacity

G reen

r efriGerant r-410a

The Bard Wall-Mount Electric Air Conditioner with gas fired heating is a self-contained energy efficient system which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space.

This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, portable structures, correctional facilities, retail stores or other commercial applications. Factory or field installed accessories are available to meet specific job requirements.

Engineered Features

Air Conditioner Compressor:

Scroll compressors are used on all models and no crankcase heaters are required.

R-410A Refrigerant:

Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.

Pre-Painted 20 Gauge Zinc Coated

Steel Cabinet:

Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.

High & Low Pressure Switches are Auto-

Reset:

Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor.

16 Gauge Zinc Coated Unit Base.

Liquid Line Filter Drier:

Protects system against moisture.

Aluminum Finned Copper Coils:

Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.

Compressor Control Module:

Standard on all units. Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls.

Alarm output for alarm relay.

Heat Exchanger:

Heavy duty 18-gauge stainless steel tubular heat exchanger. Mechanically joined construction. Ten-year warranty.

In-Shot Burners:

Advanced burner design, quiet operation.

Built-in Circuit Breakers:

Standard on all single (230/208 volt) and three phase (230/208 volt) equipment. Toggle disconnects are standard on all three phase (460 volt) equipment.

Air Filters:

Two-inch pleated air filters are standard equipment.

Optional 1-inch washable filter available.

Factory or field installed.

Barometric Fresh Air Damper:

Standard on all units. Allows up to 25% outside fresh air.

Integrated DSI Control:

Direct spark ignition control and remote sensor delivers smooth, proven ignition sequence. Timed blower control and diagnostics are also features of integrated control.

Ventilation Options:

Several ventilation options are available and can be factory or field installed.

Slope Top:

Standard feature for water run-off.

Phase Rotation Monitor:

Standard on all 3 phase scroll compressors.

Protects against reverse rotation if power supply is not properly connected.

Twin Blowers:

Move air quietly. All models feature multispeed blower motors providing airflow adjustment for high and low static operation.

Electrical Components:

Are easily accessible for routine inspection and maintenance through a right side service panel opening. Features a lockable, hinged access cover to the circuit breaker.

Gas Controls:

Honeywell gas valve and burner orifices are factory standard for natural gas.

High altitude kits available. Field convertible to LP gas with certified conversion kit.

Filter Service Door:

Separate service door provides easy access for filter change.

Condenser Fan and Motor Shroud

Assembly:

Slides out for easy access.

Top Rain Flashing:

Standard feature on all models.

Full Length Mounting Brackets:

Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.

Evaporator Freezestat:

Standard on dehumidification models.

Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2010.

Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).

Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL

1995/CSA 22.2 No. 236-05, Fourth Edition.

Intertek ETL Listed to Standard for Gas-Fired Central Furnaces ANSI Z21.47-2006,

CSA 2.3-2006 Fifth Edition, Addenda A dated 10-01-2007, Addenda B dated 06-01-2008.

Commercial Product - Not intended for Residential application.

Form No.

Supersedes

Page

S3500-615

NEW

1 of 16

Specifications 2 Ton through 3 Ton

MODELS

Electrical Rating – 60 Hz

Operating Voltage Range

Minimum Circuit Ampacity

*Field Wire Size

Ground Wire Size

** Delay Fuse - Max.

Compressor

Voltage

Rated Load Amps

Branch Circuit

Selection Current

Lock Rotor Amps

Compressor Type

Fan Motor & Condenser

Fan Motor--HP--RPM-SPD

Fan Motor--Amps

Fan--DIA/CFM

Blower Motor & Evap.

Blower Motor--HP-RPM-SPD

Blower Motor--Amps

CFM Cooling & E.S.P.

Filter Size

Shipping Weight --LBS.

W24G3-A W24G3-B

230/208 - 1 230/208 - 3

197-253

21

10

10

30

187-253

16

12

12

25

230/208

9.9/10.9

12.8

64/64

Scroll

230/208

6.4/7.1

8.3

58/58

Scroll

W24G3-C

460 - 3

414-506

10

14

14

15

460

3.9

5.1

28

Scroll

W30G3-A W30G3-B

230/208 - 1 230/208 - 3

197-253

23

10

10

35

187-253

17

12

12

25

230/208

11.8/12.9

14.1

77/77

Scroll

230/208

7.5/8.2

9

71/71

Scroll

W30G3-C

460 - 3

414-506

11

14

14

15

460

4.7

5.6

38

Scroll

W36G3-A W36G3-B

230/208 - 1 230/208 - 3

197-253

27

8

10

40

187-253

20

10

10

25

230/208

12.4/14.0

16.7

79/79

Scroll

230/208

7.8/8.8

10.5

73/73

Scroll

W36G3-C

460 - 3

414-506

11

14

14

15

460

4.9

5.8

38

Scroll

1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1 1/5-1050-1

1.5

1.5

.8

1.5

1.5

.8

1.5

1.5

.8

20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400 20" - 2400

1/4-950-3

1.8

1/4-950-3

1.8

1/4-950-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3 1/3-1075-3

.8

2.2

2.2

1.1

2.2

2.2

1.1

800 - .15

800 - .15

800 - .15

1000 - .35

1000 - .35

1000 - .35

1100 - .25

1100 - .25

1100 - .25

20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2 20 x 25 x 2

500 500 500 530 530 530 530 530 530

Specifications 3.5 Ton through 5 Ton

MODELS

Electrical Rating – 60 Hz

Operating Voltage Range

Minimum Circuit Ampacity

*Field Wire Size

Ground Wire Size

** Delay Fuse - Max.

Compressor

Voltage

Rated Load Amps

Branch Circuit

Selection Current

Lock Rotor Amps

Compressor Type

Fan Motor & Condenser

Fan Motor--HP--RPM-SPD

Fan Motor--Amps

Fan--DIA/CFM

Blower Motor & Evap.

Blower Motor--HP-RPM-SPD

Blower Motor--Amps

CFM Cooling & E.S.P.

Filter Size

Shipping Weight --LBS.

W42G3-A W42G3-B

230/208 - 1 230/208 - 3

197-253

33

8

10

50

187-253

25

8

10

35

230/208

16/17.9

19.9

109/109

Scroll

230/208

10.6/11.8

13.1

83/83

Scroll

W42G3-C

460 - 3

414-506

12

14

14

15

460

5.5

6.1

41

Scroll

W48G3-A W48G3-B

230/208 - 1 230/208 - 3

197-253

36

8

10

50

187-253

26

8

10

35

230/208

15.9/18.9

21.8

117/117

Scroll

230/208

10.0/11.9

13.8

83/83

Scroll

W48G3-C

460 - 3

414-506

12

14

14

15

460

5.4

6.3

41

Scroll

W60G3-A W60G3-B

230/208 - 1 230/208 - 3

197-253

41

8

10

60

187-253

27

8

10

40

230/208

23.2/26.3

26.3

134/134

Scroll

230/208

14.0/16.6

16.6

110/110

Scroll

W60G3-C

460 - 3

414-506

14

12

12

20

460

7.8

7.8

52

Scroll

1/3 - 825 - 2 1/3 - 825 - 2 1/3 - 825 - 1 1/3 - 825 - 2 1/3 - 825 - 2 1/3 - 825 - 1 1/3 - 825 - 2 1/3 - 825 - 2 1/3 - 825 - 1

2.5

2.5

1.3

2.5

2.5

1.3

2.5

2.5

1.3

24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050 24" - 3050

1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3 1/2-1050-3

3.4

3.4

1.5

3.4

3.4

1.5

3.4

3.4

1.5

1300 - .35

1300 - .35

1300 - .35

1550 - .38

1550 - .38

1550 - .38

1650 - .30

1650 - .30

1650 - .30

20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2 20 x 30 x 2

700 700 700 710 710 710 725 725 725

*Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.

**Maximum time delay fuse or HACR type circuit breaker.

Form No. S3500-615

Supersedes

NEW

Page 2 of 16

Cooling System Capacity, Efficiency & Airflow Ratings and Available Heating Inputs

Models

W24G3 W30G3 W36G3 W42G3 W48G3 W60G3

Cooling Capacity BTUH 

EER 

Rated CFM

Acceptable Airflow Range

Available Heating Inputs 

26,000

10.0

800

680 - 920

90,000

68,000

45,000

32,000

10.0

1000

850 - 1150

90,000

68,000

45,000

35,000

10.2

1100

935 - 1265

90,000

68,000

45,000

42,000

10.0

1300

1030 - 1500

125,000

100,000

75,000

48,000

10.5

1550

1280 - 1750

125,000

100,000

75,000

57,500

10.1

1650

1340 - 1910

125,000

100,000

75,000

Capacity is certified in accordance with ANSI/ARI Standard 390-2003.

EER = Energy Efficiency Ratio and is certified in accordance with ARI Standard 390-2003.

All ratings based on fresh air intake being 100% closed (no outside air introduction).

Any one of the heating inputs shown is available for each basic cooling model as indicated. Each input can be field derated 10% from factory standard and main

burner orifices are included with each unit to accomplish this. See table below for additional information.

Heating System Capacity, Efficiency, Derate & Airflow Ratings W24G, W30G, W36G

Input

Output

Thermal Efficiency (T.E.)

Temp. Rise Range

Mid-Rise Range Airflow

Acceptable Airflow Range

Factory Standard

90,000

74,000

82.0

50 - 80

1040

845 - 1350

Heating ratings certified in accordance with ANSI Z21.47-2006.

Field Derate

81,000

66,500

82.0

50 - 80

940

765 - 1220

Factory Standard

68,000

55,500

82.0

40 - 70

925

730 - 1275

Field Derate

61,000

50,000

82.0

40 - 70

825

650 - 1135

Factory Standard

45,000

37,000

82.0

25 - 55

830

610 - 1330

Field Derate

41,000

34,000

82.0

25 - 55

740

540 - 1185

Heating System Capacity, Efficiency, Derate & Airflow Ratings W42G, W48G, W60G

Factory Standard

Input

Output

Thermal Efficiency (T.E.)

Temp. Rise Range

Mid-Rise Range Airflow

Acceptable Airflow Range

125,000

102,500

82.0

50 - 80

1410

1145 - 1830

Heating ratings certified in accordance with ANSI Z21.47-2006.

Field Derate

113,000

93,000

82.0

50 - 80

1270

1030 - 1650

Factory Standard

100,000

82,000

82.0

40 - 70

1365

1075 - 1875

Field Derate

90,000

74,000

82.0

40 - 70

1230

965 - 1700

Factory Standard

75,000

61,500

82.0

30 - 60

1250

940 - 1875

Field Derate

68,000

56,000

82.0

30 - 60

1135

850 - 1700

Indoor Blower Performance Factory Connected Speeds

SPEED

W24G cooling airflow is rated 800 CFM @ .15 ESP, and wet coil range is 700 - 910 CFM.

See Heating Airflow Ratings Chart for heating details.

ESP

Inches

H

2

0

.10

.20

.30

.40

.50

.60

Cooling Mode

Wet Coil

High Med

MANUAL FAN and HEATING MODE

90,000 BTU Input

Low High

Med

820 1260 1060

Low

81,000 BTU Input

High Med

1060

Low

870

950

880

770

700

1200 1010

1120

1200 1010

1120 940

910

800

790

710

1030 1030

950

840

860

W30G cooling airflow is rated 1000 CFM @ .35 ESP, and wet coil range is 880 - 1150 CFM.

See Heating Airflow Ratings Chart for heating details.

ESP

Inches

H

2

0

.10

.20

.30

Cooling Mode

Wet Coil

High

Med

Low

1000

MANUAL FAN and HEATING MODE

90,000 BTU Input 81,000 BTU Input

High

Med

Low

1260 1060

High Med Low

1260 1060

1160 950 1370 1200 1010

1080 880 1290 1120 940

1200 1010

1120 940

.40

1150 990

.50

1050 910

.60

940

1190 1030

1090 950

980

1190 1030 860

1090 950

980 840

ESP

Inches

H

2

0

.10

.20

.30

.40

.50

.60

Cooling Mode

Wet Coil

High Med

MANUAL FAN and HEATING MODE

68,000 BTU Input

Low High

Med Low

820 1260 1060 870

61,000 BTU Input

High Med

1060

Low

870

950 770 1200 1010 1010 810

910

800

880

790

710

700 1120

1030

950

910 1120 940

1030 860

950

840

780

ESP

Inches

H

2

0

.10

Cooling Mode

Wet Coil

High Med

MANUAL FAN and HEATING MODE

45,000 BTU Input

Low High

Med Low

820 1260 1060 870

41,000 BTU Input

High Med

1060

Low

870

.20

.30

950

880

770 1200 1010 810 1200 1010 810

700 1120 910 1120 940 750

.40

.50

910

790

710

1030

950

860

780

1030

950

860

780

680

.60

800 840 840

Voltage adjustment - Reduce airflow by 100 CFM for 208 Volt

Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment - Increase airflow by 50 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 100 CFM for SG-3 and RG-3 installations

ESP

Inches

H

2

0

.10

.20

Cooling Mode

Wet Coil

High

Med

Low

1000

1160 950

.30

1080 880

.40

1150 990

.50

1050 910

.60

940

MANUAL FAN and HEATING MODE

68,000 BTU Input 61,000 BTU Input

High

Med

Low

1260 1060

High Med Low

1060

1200 1010 1010

1120 940

1190 1030 860

1090 950

980 840

780 1090

980

1120

1030

950

840

940

860

780

660

ESP

Inches

H

2

0

.10

Cooling Mode

Wet Coil

High

Med

Low

1000

MANUAL FAN and HEATING MODE

45,000 BTU Input 41,000 BTU Input

High

Med

Low

1260 1060

High Med Low

1060

.20

.30

1160 950 1200 1010

1080 880 1290 1120 940

.40

1150 990

.50

1050 910

1190 1030

1090 950

860

780 1090

1200 1010

1120

1030

950

940

860

780

.60

940 980 840 660 980 840 660

Voltage adjustment - Reduce airflow by 100 CFM for 208 Volt

Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment - Increase airflow by 50 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 100 CFM for SG-3 and RG-3 installations

Form No.

Supersedes

Page

S3500-615

NEW

3 of 16

Indoor Blower Performance Factory Connected Speeds

W36G cooling airflow is rated 1100 CFM @ .25 ESP, and wet coil range is 940 - 1250 CFM.

See Heating Airflow Ratings Chart for heating details.

ESP

Inches

H

2

0

.10

.20

Cooling Mode

Wet Coil

High

Med

Low

1220 1000

High

MANUAL FAN and HEATING MODE

90,000 BTU Input

Med

Low

1260 1060

1160 950 1370 1200 1010

81,000 BTU Input

High Med Low

1260 1060

1200 1010

SPEED

W42G cooling airflow is rated 1300 CFM @ .35 ESP, and wet coil range is 1030 - 1480 CFM.

See Heating Airflow Ratings Chart for heating details.

ESP

Inches

H

2

0

.10

.20

Cooling Mode

Wet Coil

High

Med

Low

1520 1110

MANUAL FAN and HEATING MODE

125,000 BTU Input

High

Med

1450 1050 1880 1510

Low

1580 1180

113,000 BTU Input

High Med Low

1580 1180

1510 1090

.30

1250 1080

.40

1150 990

.50

1050

.60

940

1290 1120 940

1190 1030

1090 950

980

1120 940

1190 1030 860

1090 950

980 840

.30

1400

.40

1480 1290

.50

1390

.60

1270

1760 1460

1670 1340

1560 1240

1430

1460

1670 1340

1560 1240

1430 1130

ESP

Inches

H

2

0

.10

Cooling Mode

Wet Coil

High

Med

Low

1220 1000

.20

1160 950

.30

1250 1080

.40

1150 990

.50

1050

.60

940

MANUAL FAN and HEATING MODE

68,000 BTU Input 61,000 BTU Input

High

Med

Low

1260 1060

High Med Low

1060

1200 1010

1120 940

1010

1120 940

1190 1030 860

1090 950 780 1090

1030

950

860

780

980 840 980 840 660

ESP

Inches

H

2

0

Cooling Mode

Wet Coil

High

Med

Low

1220 1000 .10

.20

1160 950

.30

1250 1080

.40

1150 990

.50

1050

MANUAL FAN and HEATING MODE

45,000 BTU Input

High

Med

Low

1260 1060

41,000 BTU Input

High Med Low

1200 1010

1290 1120

1090 950

940

1190 1030 860

780 1090

1060

1200 1010

1120 940

1030

950

860

780

.60

940 980 840 660 980 840 660

Voltage adjustment - Reduce airflow by 100 CFM for 208 Volt

Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment - Increase airflow by 50 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 100 CFM for SG-3 and RG-3 installations

W48G cooling airflow is rated 1550 CFM @ .20 ESP, and wet coil range is 1250 - 1780 CFM.

See Heating Airflow Ratings Chart for heating details.

ESP

Inches

H

2

0

.10

Cooling Mode

High

Wet Coil

Med

1520

.20

1710 1450

Low

MANUAL FAN and HEATING MODE

125,000 BTU Input 113,000 BTU Input

High

Med

Low

1580 1180

High Med Low

1580 1180

1880 1510 1510 1110

.30

1600 1400

.40

1480 1290

.50

1390

.60

1270

1760 1460

1670 1340

1560 1240

1430

1460 1090

1670 1340

1560 1240

1430 1130

ESP

Inches

H

2

0

.10

Cooling Mode

Wet Coil

High

Med

1560

.20

1760 1490

Low

.30

1630 1440

.40

1530 1330

.50

1440 1210

.60

1320

100,000 BTU Input

High

MANUAL FAN and HEATING MODE

Med

1630 1230

1560 1160

1810 1510 1140

1720 1390

1610 1290

Low

90,000 BTU Input

High Med Low

1630 1230

1560 1160

1510 1140

1720 1390 1020

1610 1290

1480 1180 1480 1180

ESP

Inches

H

2

0

.10

Cooling Mode

Wet Coil

High

Med

1600

.20

1805 1530

Low

.30

1680 1480

High

MANUAL FAN and HEATING MODE

75,000 BTU Input

Med

Low

68,000 BTU Input

High Med Low

1680 1280 1680 1280

1610 1210

1860 1560 1190

1610 1210

1560 1190

.40

1580 1360

.50

1490 1280

1770 1440 1070

1660 1340

1440 1070

1660 1340 970

.60

1370 1530 1230 1530 1230

Voltage adjustment - Reduce airflow by 130 CFM for 208 Volt

Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment - Increase airflow by 65 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 170 CFM for SG-5 and RG-5 installations

Form No. S3500-615

Supersedes

NEW

Page 4 of 16

ESP

Inches

H

2

0

.10

Cooling Mode

Wet Coil

High

Med

Low

1560 1160

MANUAL FAN and HEATING MODE

100,000 BTU Input 90,000 BTU Input

High

Med

Low

1630 1230

High Med Low

1630 1230

.20

.30

.60

1320

1490 1090 1560 1160

1440 1070 1810 1510 1140

.40

1530 1330

.50

1440 1210

1720 1390

1610 1290

1480 1180

1560 1160

1510 1140

1720 1390 1020

1610 1290

1480 1180

ESP

Inches

H

2

0

Cooling Mode

Wet Coil

High

Med

Low

1600 1260

MANUAL FAN and HEATING MODE

75,000 BTU Input

High

Med

Low

1680 1280 .10

.20

.30

.40

1530 1190 1610 1210

1480 1120 1860 1560 1190

1360 1100 1770 1440 1070

.50

1490 1280 1660 1340

68,000 BTU Input

High Med

1680 1280

1610 1210

1560 1190

1440 1070

1660 1340

Low

970

.60

1370 1530 1230 1530 1230

Voltage adjustment - Reduce airflow by 130 CFM for 208 Volt

Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment - Increase airflow by 65 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 170 CFM for SG-5 and RG-5 installations

W60G cooling airflow is rated 1650 CFM @ .30 ESP, and wet coil range is 1360 - 1850 CFM.

See Heating Airflow Ratings Chart for heating details.

ESP

Inches

H

2

0

High

Cooling Mode

Wet Coil

Med

.10

1800 1520

Low

MANUAL FAN and HEATING MODE

125,000 BTU Input

High

Med

Low

1950 1580 1180

113,000 BTU Input

High Med Low

1580 1180

.20

1710 1450

.30

1600 1400

.40

1480

.50

1390

.60

1880 1510

1760 1460

1670 1340

1560 1240

1430

1880 1510 1110

1760 1460 1090

1670 1340

1560 1240

1430 1130

ESP

Inches

H

2

0

High

Cooling Mode

Wet Coil

Med

.10

1860 1560

Low

.20

1760 1490

.30

1630 1440

.40

1530 1330

.50

1440

.60

1320

100,000 BTU Input

High

MANUAL FAN and HEATING MODE

Med

1630 1230

1930 1560 1160

1810 1510 1140

1720 1390

1610 1290

Low

90,000 BTU Input

High Med Low

1630 1230

1560 1160

1510 1140

1720 1390 1020

1610 1290

1480 1180 1480 1180

ESP

Inches

H

2

0

High

Cooling Mode

Wet Coil

Med Low

.10

1910 1600

.20

1805 1530

.30

1680 1480

MANUAL FAN and HEATING MODE

75,000 BTU Input

High

Med

Low

68,000 BTU Input

High Med Low

1680 1280 1680 1280

1980 1610 1210

1860 1560 1190

1610 1210

1560 1190

.40

1580 1360

.50

1490

1770 1440 1070

1660 1340

1440 1070

1660 1340 970

.60

1370 1530 1230 1530 1230

Voltage adjustment - Reduce airflow by 130 CFM for 208 Volt

Dehumidification coil adjustment - Reduce airflow by 35 CFM for dehumidification coil installed

Top outlet adjustment - Increase airflow by 65 CFM for top outlet models

SG-3, RG-3, non-ducted application adjustment - Reduce airflow by 170 CFM for SG-5 and RG-5 installations

Important Information Concerning Altitude Impact on Heating Input Ratings

Heating input, and thus heating output, decreases with altitude. No orifice change is required up to 6,000 feet elevation and derate occurs naturally due to altitude impact.

Natural gas models may require orifice change based on BTU content of gas. See Natural Gas Orifice and Altitude Tables on next page

for details. For Propane Gas see the Propane Gas Conversion Table below.

Above 6,000 feet elevation orifice changes are required, and capacity reductions are a function of altitude impact and orifice change. Pressure switch change is required above 6,000 feet elevation. For Natural Gas see the Orifice and Altitude Tables on next page. For Propane Gas see the Propane Gas

Conversion Table below

.

NATURAL GAS DERATE CAPACITIES

W**G Rated Input Sea Level 1000

41,000

45,000

41,000

45,000

39,204

43,560

61,000

68,000

58,806

65,340

61,000

68,000

75,000

81,000

90,000

100,000

113,000

125,000

75,000

81,000

90,000

100,000

113,000

125,000

72,600

78,408

87,120

96,800

108,900

121,000

2000

37,908

42,120

56,862

63,180

70,200

75,816

84,240

93,600

105,300

117,000

3000

36,612

40,680

54,918

61,020

67,800

73,224

81,360

90,400

101,700

113,000

4000

35,640

39,600

53,460

59,400

66,000

71,280

79,200

88,000

99,000

110,000

5000

34,992

38,880

52,488

58,320

64,800

69,984

77,760

86,400

97,200

108,000

6000

34,182

37,980

51,273

56,970

63,300

68,364

75,960

84,400

94,950

105,500

7000

33,696

37,440

50,544

56,160

62,400

67,392

74,880

83,200

93,600

104,000

8000

33,048

36,720

49,572

55,080

61,200

66,096

73,440

81,600

91,800

102,000

9000

32,643

36,270

48,965

54,405

60,450

65,286

72,540

80,600

90,675

100,750

10,000

32,076

35,640

48,114

53,460

59,400

64,152

71,280

79,200

89,100

99,000

PROPANE (LP) DERATE CAPACITIES

W**G Rated Input Sea Level 1000

41,000

45,000

41,000

45,000

39,852

44,280

61,000

68,000

61,000

68,000

59,778

66,420

2000

39,528

43,920

3000

39,204

43,560

4000

38,556

42,840

5000

38,232

42,480

6000

37,584

41,760

7000

36,612

40,680

8000

35,640

39,600

9000

34,344

38,160

10,000

32,724

36,360

59,292

65,880

58,806

65,340

57,834

64,260

57,348

63,720

56,376

62,640

54,918

61,020

53,460

59,400

51,516

57,240

49,086

54,540

75,000

81,000

90,000

100,000

113,000

125,000

75,000

81,000

90,000

100,000

113,000

125,000

73,800

79,704

88,560

98,400

110,700

123,000

73,200

79,056

87,840

97,600

109,800

122,000

72,600

78,408

87,120

96,800

108,900

121,000

71,400

77,112

85,680

95,200

107,100

119,000

70,800

76,464

84,960

94,400

106,200

118,000

69,600

75,168

83,520

92,800

104,400

116,000

67,800

73,224

81,360

90,400

101,700

113,000

66,000

71,280

79,200

88,000

99,000

110,000

63,600

68,688

76,320

84,800

95,400

106,000

60,600

65,448

72,720

80,800

90,900

101,000

Gas Pressure Inches W.C.

Minimum permissible gas supply pressure for purpose of input adjustment:

Maximum permissible gas supply pressure for purpose of input adjustment:

Manifold Pressure:

Natural 4.5 LP 11.0

Natural 11.0 LP 13.0

Natural 3.5 LP 10.0

Propane Gas Conversion Kits -- Fits All WG-Series Models

PROPANE (LP) GAS -- Use Gas Conversion Kits As Indicated

MODELS Propane Gas Conversion Kit Use WGCK-1

W24G

W30G

W36G

Factory

Standard

Input

22,500 - 22,650 BTU

Per Burner

Optional

10% Field

Converted

Derate

20,250 - 20,500 BTU

Per Burner

Gas

Heat

Value

BTU/Cu. Ft.

2500

Pressure Switch

Gas

Heat

Value

BTU/Cu. Ft.

2500

Pressure Switch

Up to 6000 Feet

Install Orifice

1.45

Standard (.55)

Up to 6000 Feet

Install Orifice

1.35

Standard (.55)

Use WGCK-2

6001 to 8000 Feet

Requires Pressure

Switch Change and

Orifice as Shown

8001 to 10,000 Feet

Requires Pressure

Switch Change and

Orifice as Shown

1.45

1.40

Pressure Switch (.42) Included in Conversion Kit

6001 to 8000 Feet

Requires Pressure

Switch Change and

Orifice as Shown

8001 to 10,000 Feet

Requires Pressure

Switch Change and

Orifice as Shown

1.35

1.30

Pressure Switch (.42) Included in Conversion Kit

PROPANE (LP) GAS -- Use Gas Conversion Kits As Indicated

MODELS Propane Gas Conversion Kit

W42G

W48G

Factory

Standard

Input

25,000 BTU

Per Burner

Gas

Heat

Value

BTU/Cu. Ft.

2500

Pressure Switch

W60G

Optional

10% Field

Converted

Derate

22,500 - 22,650 BTU

Per Burner

Gas

Heat

Value

BTU/Cu. Ft.

2500

Pressure Switch

All orifice sizes shown are millimeters (mm).

Use WGCK-1

Up to 6000 Feet

Install Orifice

1.50

Standard (.55)

Up to 6000 Feet

Install Orifice

1.45

Standard (.55)

Use WGCK-2

6001 to 8000 Feet

Requires Pressure

Switch Change and

Orifice as Shown

8001 to 10,000 Feet

Requires Pressure

Switch Change and

Orifice as Shown

1.50

1.45

Pressure Switch (.42) Included in Conversion Kit

6001 to 8000 Feet

Requires Pressure

Switch Change and

Orifice as Shown

8001 to 10,000 Feet

Requires Pressure

Switch Change and

Orifice as Shown

1.45

1.40

Pressure Switch (.42) Included in Conversion Kit

Form No.

Supersedes

Page

S3500-615

NEW

5 of 16

Natural Gas Orifice and Altitude Tables

NATURAL GAS -- W24G, W30G, W36G Models

Factory

Standard

Input

22,500 to

22,650

BTU

Per Burner

W24G

W30G

W36G

Gas

Heat*

Value

BTU/Cu. Ft.

700-749

750-799

800-849

850-899

900-949

950-999

1000-1049**

1050-1100

Pressure Switch

Up to 6000 Feet

No Changes

Except

For BTU Content

2.75

2.70

2.60

2.50

2.45

2.35

(2.30)

2.25

Standard (.55)

6001 to 8000 Feet

Requires Pressure Switch

Change and Orifice Change

Based on BTU Content

2.70

2.60

2.50

2.40

2.35

(2.30)

2.25

[2.20]

8001 to 10,000 Feet

Requires Pressure Switch

Change and Orifice Change

Basesd on BTU Content

2.60

2.50

2.45

2.35

(2.30)

2.25

[2.20]

2.15

Order 8620-189 High Altitude Pressure Switch Kit (.42)

(2.30) is the standard factory installed orifice size.

[2.20] orifices are shipped with the unit for field installed optional 10% derate.

All other orifice sizes shown are available as individual items, see orifice chart below for part numbers.

Optional

10% Field

Converted

Derate

Gas

Heat*

Value

BTU/Cu. Ft.

Up to 6000 Feet

No Changes

Except

For BTU Content

6001 to 8000 Feet

Requires Pressure Switch

Change and Orifice Change

Based on BTU Content

8001 to 10,000 Feet

Requires Pressure Switch

Change and Orifice Change

Basesd on BTU Content

20,250 to

20,500

BTU

Per Burner

W24G

700-749

750-799

800-849

850-899

900-949

950-999

1000-1049**

1050-1100

2.60

2.50

2.45

2.40

(2.30)

2.25

[2.20]

2.15

2.50

2.45

2.40

(2.30)

2.25

[2.20]

2.15

2.15

2.45

2.40

(2.30)

2.25

[2.20]

2.15

2.10

2.10

[2.20] orifices are shipped with the unit for field installed optional 10% input derate.

(2.30) is the factory installed orifice size for full rated input.

W30G

All other orifice sizes shown are available as individual items, see orifice chart below for part numbers.

W36G

Pressure Switch Standard (.55) Order 8620-189 High Altitude Pressure Switch Kit (.42)

* At standard conditions: 30.00 Inches Mercury, 60F, Saturated, .60 Specific Gravity

** All Natural Gas factory orifice sizing and standard input ratings based on nominal 1025 BTU per cubic foot gas and sea level conditions.

NATURAL GAS -- W42G, W48G, W60G Models

Factory

Standard

Input

25,000

BTU

Per Burner

W42G

W48G

W60G

Gas

Heat*

Value

BTU/Cu. Ft.

700-749

750-799

800-849

850-899

900-949

950-999

1000-1049**

1050-1100

Pressure Switch

Up to 6000 Feet

No Changes

Except

For BTU Content

2.90

2.80

2.70

2.60

2.50

2.45

(2.40)

[2.30]

Standard (.55)

6001 to 8000 Feet

Requires Pressure Switch

Change and Orifice Change

Based on BTU Content

8001 to 10,000 Feet

Requires Pressure Switch

Change and Orifice Change

Basesd on BTU Content

2.80

2.70

2.60

2.70

2.60

2.50

2.50

2.45

2.45

(2.40)

(2.40)

2.35

2.25

2.35

[2.30]

2.20

Order 8620-189 High Altitude Pressure Switch Kit (.42)

(2.40) is the standard factory installed orifice size.

[2.30] orifices are shipped with the unit for field installed optional 10% derate.

All other orifice sizes shown are available as individual items, see orifice chart below for part numbers.

Optional

10% Field

Converted

Derate

Gas

Heat*

Value

BTU/Cu. Ft.

Up to 6000 Feet

No Changes

Except

For BTU Content

6001 to 8000 Feet

Requires Pressure Switch

Change and Orifice Change

Based on BTU Content

8001 to 10,000 Feet

Requires Pressure Switch

Change and Orifice Change

Basesd on BTU Content

22,500 to

22,650

BTU

Per Burner

W42G

W48G

700-749

750-799

800-849

850-899

900-949

950-999

1000-1049**

1050-1100

2.75

2.70

2.60

2.50

(2.40)

2.35

[2.30]

2.25

2.70

2.60

2.50

2.45

2.35

[2.30]

2.25

2.25

2.60

2.50

2.45

(2.40)

[2.30]

2.25

2.20

2.20

[2.30] orifices are shipped with the unit for field installed optional 10% input derate.

(2.40) is the factory installed orifice size for full rated input.

All other orifice sizes shown are available as individual items, see orifice chart below for part numbers.

W60G

Pressure Switch Standard (.55) Order 8620-189 High Altitude Pressure Switch Kit (.42)

* At standard conditions: 30.00 Inches Mercury, 60F, Saturated, .60 Specific Gravity

** All Natural Gas factory orifice sizing and standard input ratings based on nominal 1025 BTU per cubic foot gas and sea level conditions.

Bard

Part No.

9010-092

9010-088

9010-087

9010-086

9010-082

9010-085

9010-079

9010-084

9010-093

9010-094

9010-095

9010-096

9010-097

9010-098

Orifice

Size (mm)

2.10

2.15

2.20

2.25

2.30

2.35

2.40

2.45

2.50

2.60

2.70

2.75

2.80

2.90

Orifice

Diameter

0.0826

0.0846

0.0866

0.0885

0.0905

0.0925

0.0945

0.0964

0.0984

0.1024

0.1063

0.1082

0.1102

0.1142

All orifice sizes shown are in millimeters (mm).

Form No. S3500-615

Supersedes

NEW

Page 6 of 16

No. of Orifices Required

Based on Unit Input Rating

41,000 (2)

45,000 (2)

61,000 (3)

68,000 (3)

75,000 (3)

81,000 (4)

90,000 (4)

100,000 (4)

113,000 (5)

125,000 (5)

Ventilation System Packages

Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements.

All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory, or field-installed at a later date.

BAROMETRIC FRESH AIR DAMPER - WGBFAD STANDARD

The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.

BAROMETRIC FRESH AIR DAMPER

BLANK OFF PLATE - WGBOP OPTIONAL

A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.

MOTORIZED FRESH AIR DAMPER - WGMFAD OPTIONAL

The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a

24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.

MOTORIZED FRESH AIR DAMPER

COMMERCIAL ROOM VENTILATOR

ECONOMIZER

ENERGY RECOVERY VENTILATOR

NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.

COMMERCIAL ROOM VENTILATOR - WGCRV OPTIONAL

The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper.

The commercial room ventilator (WGCRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the WGCRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The WGCRV can be controlled by indoor blower operation or field controlled based on room occupancy. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.

Two Models Available:

WGCRVS - spring return on power loss or deactivation

WGCRVP - power return (will not close on power loss)

ECONOMIZER - WGJIFM OPTIONAL

The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.

Standard Features:

• One Piece Construction - Easy to install with no mechanical linkage adjustment required.

• Exhaust Air Damper - Built in with positive closed position. Provides exhaust air capability to prevent pressurization

of tight buildings.

• Actuator Motor - 24 volt, power open, spring return with built in torque limiting switch.

• Proportioning Type Control - for maximum “free cooling” economy and comfort.

• Moisture Eliminator & Prefilter - permanent, washable aluminum construction.

• Enthalpy Control - adjustable to monitor outdoor temperature and humidity.

• Honeywell JADE™ electronic economizer module with precision settings and diagnostics.

• Mixed Air Sensor - to monitor outside and return air to automatically modulate damper position.

WALL-MOUNT ENERGY RECOVERY VENTILATOR - WGERV OPTIONAL

The wall-mount energy recovery ventilator (WGERV) is a highly innovative approach to address indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The WGERV allows up to 450 CFM (depending upon speed setting) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels.

In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat transfer efficiency is up to 74% during summer and 80% during winter conditions.

The WGERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only.

The WGERV is designed to be internally mounted behind the service door in the WG Gas/Electric units. It can be builtin at the factory or field installed as an option. WGERV can be independently adjusted for intake and exhaust rates.

NOTE: See Page 8 for WGERV Performance Data and Page 9 for WGCRV Performance Data

Form No.

Supersedes

Page

S3500-615

NEW

7 of 16

Form No. S3500-615

Supersedes

NEW

Page 8 of 16

W24G CRV Airflow Versus Position - Low Speed

600

550

500

450

400

350

300

250

200

150

100

50

0 closed A B C

Damper Position

D Open

Free Blow

.15" ESP

.30" ESP

W24G CRV Airflow Versus Position - Medium Speed

700

650

600

550

500

450

400

350

300

250

200

150

100

50

0 closed A B C

Damper Position

D Open

Free Blow

.15" ESP

.30" ESP

W24G CRV Airflow Versus Position - High Speed

750

700

650

600

550

500

450

400

350

300

250

200

150

100

50

0 closed A B C

Damper Position

D Open

Free Blow

.15" ESP

.30" ESP

Form No.

Supersedes

Page

S3500-615

NEW

9 of 16

Form No. S3500-615

Supersedes

NEW

Page 10 of 16

W30-36G CRV Airflow Versus Position - Low Speed

400

350

300

250

200

150

100

50

0

650

600

550

500

450 closed A B C

Damper Position

D Open

Free Blow

.15" ESP

.30" ESP

W30-36G CRV Airflow Versus Position - Medium

Speed

450

400

350

300

250

200

150

100

50

0

750

700

650

600

550

500 closed A B C

Damper Position

D Open

Free Blow

.15" ESP

.30" ESP

W30-36G CRV Airflow Versus Position - High Speed

400

350

300

250

200

150

100

50

0

800

750

700

650

600

550

500

450 closed A B C

Damper Position

D Open

Free Blow

.15" ESP

.30" ESP

W42-60G CRV Airflow Versus Position - Low Speed

650

600

550

500

450

400

350

300

250

200

150

100

50

0 closed A B C

Damper Position

D Open

Free Blow

0.15" ESP

0.30" ESP

W42-60G CRV Airflow Versus Position - Medium

Speed

800

750

700

650

600

550

500

450

400

350

300

250

200

150

100

50

0 closed A B C

Damper Position

D Open

Free Blow

0.15" ESP

0.30" ESP

W42-60G CRV Airflow Versus Position - High Speed

900

850

800

750

700

650

600

550

500

450

400

350

300

250

200

150

100

50

0 closed A B C

Damper Position

D Open

Free Blow

0.15" ESP

0.30" ESP

Form No.

Supersedes

Page

S3500-615

NEW

11 of 16

W24G3D Application Performance Data

Indoor

Conditions

Outdoor

Conditions

System Capacity

DB/WB % RH DB Total Sensible Latent S/T

65/63

65/63

90

90

75/62.5

50

75/62.5

50

75/65.5

60

75/65.5

60

75/68 70

75/68

80/67

80/67

70

50

50

65

65

75

75

75

75

75

75

95

95

27,900 11,900 16,000

-0(800) 13,050

28,750 19,750 7,000

9,650 3,700 5,950

28,550 17,550 11,000

10,950 2,000 8,950

29,650 15,450 14,200

11,850 350

26,000 18,900

-0(2,500)

11,500

7,100

6,000

W30G3D Application Performance Data

Indoor

Conditions

Outdoor

Conditions

System Capacity

.43

-0-

.69

.38

.62

.18

.52

.03

.73

-0-

DB/WB % RH DB Total Sensible Latent S/T

65/63

65/63

90

90

75/62.5

50

75/62.5

50

75/65.5

60

75/65.5

60

75/68 70

75/68

80/67

70

50

80/67

Form No. S3500-615

Supersedes

NEW

Page 12 of 16

50

65/63

65/63

90

90

75/62.5

50

75/62.5

50

75/65.5

60

75/65.5

60

75/68

75/68

70

70

80/67

80/67

50

50

75

75

75

75

65

65

75

75

95

95

35,650 15,550 20,100

-0(950) 16,200

33,050 25,300

10,300 4,200

7,750

6,100

34,950 22,200 12,750

11,900 2,450 9,450

36,400 19,550 16,850

13,300 700 12,600

32,000 24,350

-0(2,200)

7,650

6,350

W36G3D Application Performance Data

Indoor

Conditions

Outdoor

Conditions

System Capacity

DB/WB % RH DB Total Sensible Latent S/T

.64

.21

.54

.05

.43

-0-

.76

.41

.76

-0-

65

65

75

75

75

75

75

75

95

95

35,050 15,350 19,700

11,600 (2,450) 14,050

33,800 26,250 7,550

7,150 1,500 5,650

34,900 22,550 12,350

8,850 (100) 8,950

36,100 19,600 16,500

10,250 (1,350) 11,600

34,500 26,600 7,900

300 (5,500) 5,800

.44

-0-

.78

.21

.65

-0-

.54

-0-

.77

-0-

Pounds of

Water/Hour

Lbs.

15.1

12.3

6.6

5.6

10.4

8.5

13.4

10.8

6.7

5.7

Evaporator

Airflow

CFM

800

800

800

800

800

800

800

800

800

800

Approximate

Supply Air

Mode

DB/WB

51.6 / 51.1

A/C vs.

Dehum

A/C

66.0 / 58.2

Dehum

52.5 / 50.8

A/C

70.8 / 58.5

Dehum

54.9 / 53.7

A/C

72.9 / 61.3

Dehum

57.4 / 56.5

A/C

74.7 / 63.8

Dehum

58.8 / 56.8

A/C

82.9 / 65.8

Dehum

Pounds of

Water/Hour

Lbs.

19.0

15.3

7.3

5.8

12.0

8.9

15.9

11.9

7.2

6.0

Evaporator

Airflow

CFM

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

Approximate

Supply Air

Mode

DB/WB

51.1 / 50.8

A/C vs.

Dehum

A/C

65.9 / 58.1

Dehum

52.1 / 50.9

A/C

71.1 / 59.2

Dehum

54.8 / 53.9

A/C

72.8 / 61.8

Dehum

57.2 / 56.5

A/C

74.3 / 64.1

Dehum

58.0 / 56.8

82.1 /65.8

A/C

Dehum

Pounds of

Water/Hour

Lbs.

18.6

13.3

7.1

5.3

11.6

8.5

15.5

11.0

7.5

5.5

Evaporator

Airflow

CFM

1100

1100

1100

1100

1100

1100

1100

1100

1100

1100

Approximate

Supply Air

Mode

DB/WB

52.1 / 52.1

A/C vs.

Dehum

A/C

67.2 / 59.8

Dehum

53.7 / 51.9

A/C

73.9 / 62.5

Dehum

56.6 / 55.3

A/C

75.2 / 65.6

Dehum

58.8 / 58.0

A/C

76.2 / 65.3

Dehum

57.9 / 57.1

A/C

84.7 / 67.0

Dehum

W42G3D Application Performance Data

Indoor

Conditions

Outdoor

Conditions

System Capacity

DB/WB % RH DB Total Sensible Latent S/T

65/63

65/63

90

90

75/62.5

50

75/62.5

50

75/65.5

60

75/65.5

60

75/68

75/68

80/67

80/67

70

70

50

50

75

75

75

75

95

95

65

65

75

75

46,800 20,700 26,100

23,450 (900) 24,350

44,050 34,700

17,650 9,750

9,350

7,900

46,500 30,350 16,150

20,550 6,200 14,350

49,000 26,850 22,150

23,100 3,150

42,000 32,400

9,700 1,800

19,950

9,600

7,900

W48G3D Application Performance Data

Indoor

Conditions

Outdoor

Conditions

System Capacity

.65

.30

.55

.14

.77

.18

.44

-0-

.79

.55

DB/WB % RH DB Total Sensible Latent S/T

65/63 90

65/63 90

75/62.5

50

75/62.5

50

75/65.5

60

75/65.5

60

75/68

75/68

70

70

80/67

80/67

50

50

75

75

75

95

95

65

65

75

75

75

52,550 22,300 30,250

24,350 (2,050) 26,400

50,200 38,600 11,600

17,800 8,300 9,500

52,750 33,350 19,400

20,650 5,250 15,400

55,600 29,200 26,400

23,050 1,650 21,400

48,000 36,400 11,600

7,200 150 7,050

W60G3D Application Performance Data

Indoor

Conditions

Outdoor

Conditions

System Capacity

.26

.53

.07

.76

.02

.42

-0-

.77

.46

.63

DB/WB % RH DB Total Sensible Latent S/T

65/63

65/63

90

90

75/62.5

50

75/62.5

50

75/65.5

60

75/65.5

60

75/68 70

75/68

80/67

80/67

70

50

50

65

65

75

75

75

75

75

75

95

95

63,400 28,150 35,250

31,250 1,550 29,700

60,100 44,400 15,700

24,200 10,100 14,100

63,600 39,400 24,200

27,700 5,950 21,750

66,400 35,150 31,250

30,650 2,300 28,350

57,000 41,700 15,300

13,950 100 13,850

.44

.05

.74

.42

.62

.21

.53

.08

.73

.01

Pounds of

Water/Hour

Lbs.

24.6

23.0

8.8

7.5

15.2

13.5

20.9

18.8

9.1

7.5

Evaporator

Airflow

CFM

1400

1400

1400

1400

1400

1400

1400

1400

1400

1400

Approximate

Supply Air

Mode

DB/WB

52.0 / 51.6

A/C vs.

Dehum

A/C

65.6 / 57.4

Dehum

52.6 / 51.6

A/C

68.8 / 58.5

Dehum

55.5 / 54.8

A/C

71.2 / 61.1

Dehum

58.0 / 57.3

A/C

73.3 / 63.3

Dehum

58.8 / 57.5

A/C

79.0 / 65.1

Dehum

Pounds of

Water/Hour

Lbs.

14.5

24.9

20.2

10.9

6.6

28.6

24.9

11.0

9.0

18.3

Evaporator

Airflow

CFM

1450

1450

1450

1450

1450

1450

1450

1450

1450

1450

Approximate

Supply Air

Mode

DB/WB

51.0 / 50.7

A/C vs.

Dehum

A/C

66.3 / 57.8

Dehum

50.8 / 50.3

A/C

69.0 / 58.6

Dehum

54.1 / 53.6

A/C

71.6 / 61.3

Dehum

56.7 / 56.3

A/C

73.9 / 63.6

Dehum

57.1 / 56.5

A/C

79.9 / 65.6

Dehum

Pounds of

Water/Hour

Lbs.

33.3

28.0

14.8

13.3

22.8

20.5

29.5

26.7

14.4

13.1

Evaporator

Airflow

CFM

1650

1650

1650

1650

1650

1650

1650

1650

1650

1650

Approximate

Supply Air

Mode

DB/WB

49.9 / 49.7

A/C vs.

Dehum

A/C

66.3 / 57.0

Dehum

50.8 / 49.6

A/C

69.6 / 57.8

Dehum

53.7 / 52.8

A/C

72.1 / 60.5

Dehum

56.2 / 55.6

A/C

74.2 / 62.7

Dehum

57.3 / 56.0

A/C

80.2 / 64.6

Dehum

Form No.

Supersedes

Page

S3500-615

NEW

13 of 16

Return Air (DB/WB)

Form No. S3500-615

Supersedes

NEW

Page 14 of 16

DIMENSIONS OF BASIC UNIT

UNIT

W24G-W30G-W36G

W42G-W48G-W60G

A

7.88

9.88

B C D

27.88

13.88

24.25

E

40

29.88

15.88

27.25 43.81

F

14.88

G H

25.63 81.63

31.63

87.5

UNIT

W24G-W30G-W36G

W42G-W48G-W60G

S

12 - 7 HOLES

16 - 6 HOLES

T

3.75

U

2.88

3.88

V

22.9

24.9

W X Y

38 17.84 4.44

42

17.34 8.44

Z

2.25

I

30

AA

11.44

12.19

J K

27.38 27.5

33.38 28.75

L M

14.12 15.44

N

15.31

O

39.25

42.88

BB

3.25

CC

9

10

DD

7.25

EE

36.25

40.25

FF

1.13

GG

1.25

P

4.5

Q

2.5

HH

2

II

0.38

2.75

0.44

R

5.88

3.75

F

G

W

CONDENSER

AIR OUTLET

4 DEG. PITCH IN TOP

VESTIBULE

DOOR

COMBUSTION

AIR EXHAUST

N

P

FRONT DOOR

FILTER

DOOR

CIRCUIT BREAKER/

DISCONNECT ACCESS

PANEL (LOCKABLE)

VENT OPTION

PANEL

1

D

DD

FF

GG

HH II

A

U

M

Z

I

H

GAS

ENTRANCES

Q

X

L

C

AA

HIGH VOLTAGE

ENTRANCES

Y

J K

V

CC

1

E

EE

O

B

SUPPLY OPENING

BB

B

RETURN OPENING

S

S

S

S

R

S

FRONT

RIGHT SIDE

Optional top outlet in place of standard back supply opening, see Nomenclature outlet options (next page).

Standard unit can also be field converted to this configuration using approved top supply outlet conversion kit shown on next page.

BACK

T

MIS-3239 A

Minimum Clearances

INSTALLATION

Installation Wall (from combustible materials)

Outlet Duct (from combustible materials)

W24G - W30G - W36G

0"

1" first 3'

W42G - W48G - W60G

0"

1" first 3'

Vent Terminal (from combustible materials)

Top (from combustible materials)

17"

1" 

16"

0" 

Condenser Air Inlets 20" 20"

1-inch clearance at rear top of unit (at the wall surface). The 4° pitch of top creates 1.688 inch clearance between front top and any

extended overhang above the top of the unit.

0-inch clearance at rear top of unit (at the wall surface). The 4° pitch of top creates .688 inch clearance between front top and any

extended overhang above the top of the unit.

Service Access

ALL MODELS

Burner Service - Right side

Compressor - Right side

Controls - Right side

Condenser Fan - Left side

20"

20"

20"

20"

Form No.

Supersedes

Page

S3500-615

NEW

15 of 16

Air Conditioning Wall-Mount Model Nomenclature

MODEL NUMBER

W 36 G 3 A X B X X X X X

COOLING

CAPACITY

24 - 2 Ton

30 - 2½ Ton

36 - 3 Ton

42 - 3½ Ton

48 - 4 Ton

60 - 5 Ton

GAS /

ELECTRIC

REVISION

CODE

VOLTS & PHASE

A - 230/208-60-1

B - 230/208-60-3

C - 460-60-3

EMISSIONS

X - Standard

FILTER OPTIONS

X - 2-Inch Pleated

(MERV8)

W - 1-Inch Washable

X

CONTROL MODULES

(

See Control Module Options

)

| COIL OPTIONS

X - No Coating

1 - Phenolic Coated Evap.

2 - Phenolic Coated Cond.

3 - Phenolic Coating on both coils

FEATURE CODE

(-) = Standard

C = Canadian Approval

D = Dehumidification

HEATING INPUT

2-3 Ton 3.5 - 5 Ton

A = 45,000 B = 75,000

B = 68,000 C = 100,000

C = 90,000 D = 125,000*

VENT OPTIONS

(See Chart Below)

COLOR OPTIONS

X - Beige

4 - Buckeye Gray

8 - Dark Bronze

OUTLET OPTIONS

X - Front

T - Top

Ventilation Options

Models W24G, W30G, W36G

Description

Barometric Fresh Air Damper - No Exhaust

Blank-Off Plate

Motorized Fresh Air Damper - No Exhaust

Commercial Ventilator - Spring Return w/Exhaust

Factory Installed

Code No.

X

B

M

V

Commercial Ventilator - Power Return w/Exhaust

Economizer (Internal) Fully Modulating  w/Exhaust

Energy Recovery Ventilator - 230 Volt w/Exhaust 

P

E

R

Energy Recovery Ventilator - 460 Volt w/Exhaust 

R

Low ambient control is required with economizer for low temperature compressor operation.

Independent selection of intake and exhaust speeds (rate) with terminal block selection.

â

Color option must be specified to match unit ("X" = Beige; "4" = Buckeye Gray)

Field Installed

Part No.

WGBFAD-3

WGBOP-3

WGMFAD-3A

WGCRVS-3A

WGCRVP-3A

WGJIFM-3

WGERV-A3B-â

WGERV-C3C-â

W42G, W48G, W60G

Factory Installed

Code No.

X

B

P

E

M

V

R

R

Field Installed

Part No.

WGBFAD-5

WGBOP-5

WGMFAD-5A

WGCRVS-5A

WGCRVP-5A

WGJIFM-5

WGERV-A5B-â

WGERV-C5C-â

Top Supply Outlet Conversion Kits-Field Installed (Convert Standard Front Outlet to Top Outlet)

USED WITH MODELS

W24G, W30G, W36G

W42G, W48G, W60G

UNIT COLOR X - BEIGE

TSO-WG3-X

TSO-WG5-X

UNIT COLOR 4 - BUCKEYE GRAY

TSO-WG3-4

TSO-WG5-4

UNIT COLOR 8 - DARK BRONZE

TSO-WG3-8

TSO-WG5-8

Air Conditioning Control Modules

AVAILABLE CONTROL OPTIONS

Factory Installed Code

Standard Unit

Field Installed Code

Dehumidification Unit

Field Installed Code

CCM HPC LPC LAC

STD

STD

STD

STD

STD

STD l

X

H

N/A

CMA-29 n

N/A

CMA-28 o

STD = Standard equipment

CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2-minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high and/or low-pressure controls, and a 2-minute timed bypass for low-pressure control.

HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .

LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .

LAC. Low ambient control permits cooling operation down to 0°F. Evaporator Freezestat is included.

n

CMA-29 Field installed LAC has evaporator Freezestat included.

o

CMA-28 Field installed LAC does not include Freezestat as one is installed as part of the dehumidification base unit.

Optional Field Installed Accessories

DESCRIPTION PART NUMBER

Natural Gas High Altitude Pressure Switch Kit (6000 - 10,000 Feet) 8620-189

Note: Natural Gas Orifice Change May Be Required Depending Upon Altitude and Gas BTU content. See Orifice and Altitude Tables.

Propane Gas Conversion Kit (0 - 6000 Feet Altitude)

Propane Gas Conversion Kit (6000 - 10,000 Feet Altitude)

WGCK-1

WGCK-2

Vertical Vent Kit (Includes all parts for 5 foot vertical vent)

Additional 1 foot vertical vent pipe section for VVK-5A

Additional 2 foot vertical vent pipe section for VVK-5A

Additional 3 foot vertical vent pipe section for VVK-5A

Additional 5 foot vertical vent pipe section for VVK-5A

VVK-5A

8620-201

8620-170

8620-200

8620-171

Form No. S3500-615

Supersedes

NEW

Page 16 of 16

Bard Manufacturing Company, Inc.

Bryan, Ohio 43506 www.bardhvac.com

Due to our continuous product improvement policy, all specifications subject to change without notice.

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.

Form No.

S3500

June, 2015

Supersedes:

NEW