Eaton-Williams | ICU80 | QLC Brochure - Eaton

QUALITAIR
QLC
LOW TEMPERATURE
CASSETTE RANGE
■ Air conditioning style combined
with lower temperature control.
■ Stylish split system.
■ R407c or R404a system.
■ Controls down to 8°C.
■ Low velocity four way air
distribution.
Qualitair is maintaining the tradition
of listening to the industry and
developing products in conjunction
with specifiers and installers.
The EEC directives and legislation on
food preparation and storage are
many and difficult to understand.
However, we do know that certain
food preparation areas should be
maintained at lower temperatures
than can be achieved with standard
air conditioning. These are the areas
the Qualitair QLC low temperature
cassette was specifically designed for.
Q
■ Wipe clean low profile fascia.
■ Easy access for maintenance.
■ Electric heater (optional).
Whatever the directive or legislation
the QLC will control your
environment to between 8°C and
21°C depending on the set point
chosen.
The QLC provides low velocity air
when compared with traditional
coolers and it also has the benefit of
four way air distribution ensuring an
even temperature in the
working area.
The Qualitair ICU outdoor
unit has a small footprint
and can be installed on the
roof, at ground level, or
with brackets, on the wall.
The units can also be
stacked if required.
Rotary compressor fitted on
the ICU40 model and scroll
compressors on the other units in
the range ensure low noise levels,
reduced starting currents and
increased reliability.
QLC
RANGE
Food Preparation
& Storage
TECHNICAL SPECIFICATIONS
QLC (indoor unit), ICU (outdoor unit) capacities and dimension data
Capacity
Model
QLC10
Btu/hr
2.93
10000
0.31
59
1245
650
60
5/8"
1/4"
0.45
42
720
610
250
5/8"
1/4"
0.54
83
1245
850
60
5/8"
1/4"
0.45
60
800
765
320
5/8"
1/4"
0.56
83
1245
850
60
3/4"
3/8"
0.70
64
800
765
320
3/4"
3/8"
4.40
15000
ICU55
QLC20
Valve Connections
kW
ICU40
QLC15
QLC Fascia and ICU Dimensions mm
Airflow
m3/s
5.95
20300
ICU80
Weight
kg
A
B
C
Suction o/d
Liquid o/d
Cooling capacities based on 12ºC 75% RH indoors and 35ºC db ambient outdoors.
QLC
Electrical data
Model
OPTIONS
Electrical Supply
Indoor
Outdoor
V/ph/Hz
Lrc
Flc
Fuse
Heater
Current
Heater
Fuse
QLC10
ICU40
230/1/50
28
7.5
10
12
16
QLC15
ICU55
230/1/50
53
12
16
17
20
QLC20
ICU80
230/1/50
82
16.5
20
17
20
QLC20
ICU80
400/3/50
33/ph
6.7/ph
10/ph
6/ph
10/ph
Heater Kit
Fresh Air Kit
Decorative Surround
Condensate Lift Pump
Electrical Isolator
Wall Mounting Kit
QLC10/15/20 ceiling cassette
BMS Interface
1165mm
QLC10 (299mm)
QLC15/20 (349mm)
Operation with PACS
Full technical data sheets available with
options part numbers.
QLC
A Fascia
ICU outdoor unit
QLC10 (535mm)
QLC15/20 (735mm)
Airflow
B
C Fascia
B Fascia
A
Eaton-Williams Air Conditioning
Oldfields Business Park
Birrell Street, Fenton
Stoke-on-Trent ST4 3ES
Telephone: +44 (0)1782 597124
Facsimile: +44 (0)1782 316633
www.eaton-williams.com
C
130mm
Minimum
distance
from wall
We reserve the right to alter specifications without
notice and products will sometimes be supplied with
modifications which do not strictly comply with the
descriptions and illustrations in this publication.