- Home
- Domestic appliances
- Climate control
- Weather stations
- Belimo
- LonWorks GMX24-LON
- Quick start Guide
Belimo LonWorks GMX24-LON Quick start manual
Add to my manuals
4 Pages
Belimo LonWorks GMX24-LON is a direct-coupled actuator for proportional modulation of dampers in HVAC systems, featuring electronic overload protection, adjustable end positions, a visual position indicator, and manual override. It supports LonWorks networking, enabling integration with compatible LON systems and control via any LON system. Utilize the universal clamp for direct mounting on air dampers, or employ the crank arm and mounting brackets for indirect coupling. Add auxiliary switches or feedback potentiometers for signaling and switching functions.
advertisement
GMX24-LON
LonWorks
®
, Non-Spring Return, 24 V
Technical Data GMX24-LON
Power supply 24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
4.5 W (1.5 W) Power consumption
Transformer sizing
Electrical connection
Overload protection
Angle of rotation
7 VA (Class 2 power source)
18 GA plenum rated cable
1/2” conduit connector protected NEMA 2 (IP54)
3 ft [1m] electronic throughout 0 to 95° rotation max. 95°, adjustable with mechanical stop electronically variable
360 in-lb [40 Nm] Torque
Direction of rotation reversible with reflective visual indicator (snap-on) external push button switch
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Servicing
150 seconds (default)
5 to 95% RH non condensing (EN 60730-1)
-22°F to +122°F [-30°C to +50°C]
-40°F to +176°F [-40°C to +80°C]
NEMA 2, IP54, UL enclosure type 2
UL94-5VA cULus acc. to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02,
CE acc. to 2004/108/EEC and 2006/95/EC
<45dB(A) maintenance free
Quality standard
Weight
ISO 9001
3.4 lbs [1.55 kg]
† Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
LonWorks
®
Certified
Processor
Transceiver
Functional profile according to LonMARK ® 3.3
Neuron 3120
FTT-10A, compatible with LPT-10 according to LonMARK ® Damper actuator object #8110 open loop sensor object #1
LNS plug-in for actuator/sensor can be run with any LNS based integration tool (min. for LNS 3.x)
Service button and status LED according to LonMARK ® guidelines
Conductors, cables conductor lengths, cable specifications and topology of the LonWorks ® network according to the Echelon ® directives
LonWorks and LonMARK © 2007-2009 LonMark International
i i lb f l f d f f
Application
Direct coupled actuators for direct link to LonWorks network. Actuators are easily installed by direct shaft mounting on air dampers in ventilation and air conditioning systems. Actuator can be controlled by any compatible LON system.
For proportional modulation of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer’s specifications.
The actuator is mounted directly to a damper shaft up to 1.05” in diameter by means of its universal clamp. A crank arm and several mounting brackets are available for applications where the actuator cannot be direct coupled to the damper shaft.
Operation
The actuator is not provided with and does not require any limit switches, but is electronically protected against overload. The anti-rotation strap supplied with the actuator will prevent lateral movement.
The GMX24-LON series provides 95° of rotation and a visual indicator indicates position of the actuator. When reaching the damper or actuator end position, the actuator automatically stops. The gears can be manually disengaged with a button on the actuator cover.
The GMX24-LON actuators use a brushless DC motor, which is controlled by an actuator’s rotation and provides a digital rotation sensing (DRS) function to prevent damage to the actuator in a stall condition. Power consumption is reduced in holding mode.
the actuator body for signaling and switching functions.
Dimensions (Inches [mm])
1/2” to 1.05” [12.7 to 26.67]
2/5” to 1.05” [10 to 26.67]
5.37” [136.4]
7.02” [178.4]
To center of mounting slot.
1.42”
[36]
5.6” [142.4] 2” [50.8]
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
207
GMX24-LON
LonWorks
®
, Non-Spring Return, 24 V
Accessories
K-GM20
ZG-102
ZG-GMA
3/4" [20 mm] Shaft Clamp
Multiple Actuator Mounting Bracket
Crank arm Adaptor Kit
ZG-JSA (-1, 2, 3) Jackshaft Adaptors for Hollow Jackshafts
ZS-100 Weather Shield - Steel
ZS-150
ZS-260
Weather Shield - Polycarbonate
Explosion Proof Housing
ZS-300 (-1) (-5)
Tool-07
PS-100
S1A, S2A
P370
P…A
SGA24
SGF24
ADS-100
NEMA 4X Housing
13 mm Wrench
Actuator Power Supply Simulator
Auxiliary Switch (es)
Shaft Mount Auxiliary Switch
Feedback Potentiometers
Min positioners in NEMA 4 housing
Min positioners for flush panel mounting
Analog to Digital Switch
NSV24 US
ZG-X40
Battery Back-Up Module
Transformer
NOTE: When using GMX24-LON actuators, only use accessories listed on this page.
Typical Specification
Proportional control damper actuators shall be electronic direct-coupled type, which require no crank arm and linkage and be capable of direct mounting to a shaft up to
1.05” diameter. Actuators shall have brushless DC motor technology and be protected from overload at all angles of rotation. Actuators shall have reversing switch and manual override on the cover. Run time shall be constant and independent of torque.
ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo.
Wiring Diagrams
–
T
+
~
V
–
T
1 2
+
~
3 5 6 7
Connection without Sensor
V
Possible connection of a voltmeter for checking the position feedback U.
–
T
+
~
–
T
1 2
+
~
3 5 6 7
Sensor scaling:
The sensors can be scaled with the sensor plug-in (sensor table).
Sensor
Ni1000
PT1000
NTC
Temperature range
–28 ... +98°C
–35 ... +155°C
–10 ... +160°C
(depending on type)
Resistance range
850 ... 1600
850 ... 1600
Ω
Ω
200 ... 60 k
Ω
Resolution
1
Ω
1
Ω
1
Ω
Connection with Passive Sensor, e.g. Pt1000, Ni1000, NTC
–
T
+
~
Requirements for switching contact:
The switching contact must be able to accurately switch a current of 16 mA @ 24 V.
1
T
– +
~
2 3 5 6 7
Connection with Switching Contact, e.g.
Δp-monitor
–
T
+
~
–
T
1
+
~
2 3 5 6 7
Possible input voltage range:
0 ... 32 V (resolution 30 mV)
Sensor scaling:
The sensors can be scaled with the sensor plug-in (sensor table)
Connection with Active Sensor, e.g. 0...10 V @ 0...50° C
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
208
GMX24-LON
LonWorks
®
, Non-Spring Return, 24 V
K
®
The LON-capable damper actuator is certified by LonMARK ® . The actuator functions are supplied with the LonWorks ® network as standardized network variables according to LonMARK ® . The Node Object #0, the Damper Actuator Object #8110 and the Open Loop SensorObject #1 are implemented in the actuator.
Node object #0
The node object contains the object status and object request functions.
nviRequest SNVT_obj_request
Input variable for requesting the status of a particular object in the node.
nvoStatus SNVT_obj_status
Output variable that outputs the current status of a particular object in the node.
nvoFileDirectory SNVT_address
Output variable that shows information in the address range of the Neuron chip.
Damper actuator object #8110
The actuator object is used to map the functions of the MP actuators to the
LONWORKS® network.
nviRelStpt SNVT_lev_percent
The nominal position is assigned to the actuator via this input variable. This variable is normally linked to the output variable of an HVAC controller.
nviActuateState SNVT_switch
A preset position is assigned to the actuator via this input variable. Note on priority:
The last variable that was active, either nviActuatorState or nviRelStpt, has priority.
nviManOvrd SNVT_hvac_overid
These input variables can be used to manually override the actuator into a particular position.
nvoActualValue SNVT_lev_percent
This output variable shows the current actual position of the actuator and can be used for control circuit feedback or for displaying positions.
nvoAbsAngle SNVT_angle_deg
This output variable shows the current angle of rotation of the actuator or the valve and can be used to display the position or for service purposes.
nvoAbsAirFlow SNVT_flow
This output variable is inactive with the SR24ALON-5 rotary actuator and shows a constant value of 65535 (this variable is only active in conjunction with LON-capable
VAV controllers).
Open loop sensor object #1
A sensor can be connected to the rotary actuator. A passive resistance sensor (e.g.
Ni1000), an active sensor (output 0 ... 32 V) or a switch (on/off) can be connected. The open loop sensor object transfers the measured sensor values to the LONWORKS® network.
nvoSensorValue SNVT_xxx
This output variable shows the current sensor value. Depending on the connected sensor, the output variable can be configured via the sensor plug-in and specifically adapted to the system.
The SNVT_... can be configured as:
SNVT_temp_p SNVT_lev_percent
SNVT_temp
SNVT_switch
SNVT_flow
SNVT_flow_p
SNVT_abs_humid
SNVT_enthalpy
SNVT_ppm
SNVT_rpm
SNVT_lux
SNVT_press_p
SNVT_smo_obscur
SNVT_power
SNVT_elec_kwh
Notes
Detailed information on the functional profiles can be found on the website of
LonMARK ®
209
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
4
5
1
2
3
GMX24-LON
LonWorks
®
, Non-Spring Return, 24 V
1 Direction of rotation switch
Switching over Direction of rotation changes
2 Pushbutton and green LED display
Off No voltage supply or malfunction
Green, on
Press button
Operation
Switches on angle of rotation adaption followed by standard operation
3 Service button for commissioning LONWORKS ® and yellow LED display for the LON status
Off The SR24ALON-5 rotary actuator is connected and ready for operation in the
LONWORKS®network.
Yellow, on
Yellow, flashing
(flashing interval 2 seconds)
No application software is loaded in the
SR24ALON-5.
The SR24ALON-5 is ready for operation but not integrated in the LONWORKS ® network
(unconfigured).
Other flashing codes
Press button
A fault is present in the SR24ALON-5.
Service Pin Message is sent to the
LONWORKS ® network.
4 Gear disengagement switch
Press button
Release button
Gear disengaged, motor stops, manual operation possible
Gear engaged, synchronisation starts, followed by standard operation
5 Service plug
For connecting MFT parameterizing and service tools
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA