Belimo LonWorks GMX24-LON Quick start manual


Add to my manuals
4 Pages

advertisement

Belimo LonWorks GMX24-LON Quick start manual | Manualzz

GMX24-LON

LonWorks

®

, Non-Spring Return, 24 V

Technical Data GMX24-LON

Power supply 24 VAC ± 20% 50/60 Hz

24 VDC ± 10%

4.5 W (1.5 W) Power consumption

Transformer sizing

Electrical connection

Overload protection

Angle of rotation

7 VA (Class 2 power source)

18 GA plenum rated cable

1/2” conduit connector protected NEMA 2 (IP54)

3 ft [1m] electronic throughout 0 to 95° rotation max. 95°, adjustable with mechanical stop electronically variable

360 in-lb [40 Nm] Torque

Direction of rotation reversible with reflective visual indicator (snap-on) external push button switch

Position indication

Manual override

Running time

Humidity

Ambient temperature

Storage temperature

Housing

Housing material

Agency listings†

Noise level

Servicing

150 seconds (default)

5 to 95% RH non condensing (EN 60730-1)

-22°F to +122°F [-30°C to +50°C]

-40°F to +176°F [-40°C to +80°C]

NEMA 2, IP54, UL enclosure type 2

UL94-5VA cULus acc. to UL 60730-1A/-2-14,

CAN/CSA E60730-1:02,

CE acc. to 2004/108/EEC and 2006/95/EC

<45dB(A) maintenance free

Quality standard

Weight

ISO 9001

3.4 lbs [1.55 kg]

† Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.

LonWorks

®

Certified

Processor

Transceiver

Functional profile according to LonMARK ® 3.3

Neuron 3120

FTT-10A, compatible with LPT-10 according to LonMARK ® Damper actuator object #8110 open loop sensor object #1

LNS plug-in for actuator/sensor can be run with any LNS based integration tool (min. for LNS 3.x)

Service button and status LED according to LonMARK ® guidelines

Conductors, cables conductor lengths, cable specifications and topology of the LonWorks ® network according to the Echelon ® directives

LonWorks and LonMARK © 2007-2009 LonMark International

i i lb f l f d f f

Application

Direct coupled actuators for direct link to LonWorks network. Actuators are easily installed by direct shaft mounting on air dampers in ventilation and air conditioning systems. Actuator can be controlled by any compatible LON system.

For proportional modulation of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer’s specifications.

The actuator is mounted directly to a damper shaft up to 1.05” in diameter by means of its universal clamp. A crank arm and several mounting brackets are available for applications where the actuator cannot be direct coupled to the damper shaft.

Operation

The actuator is not provided with and does not require any limit switches, but is electronically protected against overload. The anti-rotation strap supplied with the actuator will prevent lateral movement.

The GMX24-LON series provides 95° of rotation and a visual indicator indicates position of the actuator. When reaching the damper or actuator end position, the actuator automatically stops. The gears can be manually disengaged with a button on the actuator cover.

The GMX24-LON actuators use a brushless DC motor, which is controlled by an actuator’s rotation and provides a digital rotation sensing (DRS) function to prevent damage to the actuator in a stall condition. Power consumption is reduced in holding mode.

the actuator body for signaling and switching functions.

Dimensions (Inches [mm])

1/2” to 1.05” [12.7 to 26.67]

2/5” to 1.05” [10 to 26.67]

5.37” [136.4]

7.02” [178.4]

To center of mounting slot.

1.42”

[36]

5.6” [142.4] 2” [50.8]

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

207

GMX24-LON

LonWorks

®

, Non-Spring Return, 24 V

Accessories

K-GM20

ZG-102

ZG-GMA

3/4" [20 mm] Shaft Clamp

Multiple Actuator Mounting Bracket

Crank arm Adaptor Kit

ZG-JSA (-1, 2, 3) Jackshaft Adaptors for Hollow Jackshafts

ZS-100 Weather Shield - Steel

ZS-150

ZS-260

Weather Shield - Polycarbonate

Explosion Proof Housing

ZS-300 (-1) (-5)

Tool-07

PS-100

S1A, S2A

P370

P…A

SGA24

SGF24

ADS-100

NEMA 4X Housing

13 mm Wrench

Actuator Power Supply Simulator

Auxiliary Switch (es)

Shaft Mount Auxiliary Switch

Feedback Potentiometers

Min positioners in NEMA 4 housing

Min positioners for flush panel mounting

Analog to Digital Switch

NSV24 US

ZG-X40

Battery Back-Up Module

Transformer

NOTE: When using GMX24-LON actuators, only use accessories listed on this page.

Typical Specification

Proportional control damper actuators shall be electronic direct-coupled type, which require no crank arm and linkage and be capable of direct mounting to a shaft up to

1.05” diameter. Actuators shall have brushless DC motor technology and be protected from overload at all angles of rotation. Actuators shall have reversing switch and manual override on the cover. Run time shall be constant and independent of torque.

ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo.

Wiring Diagrams

T

+

~

V

T

1 2

+

~

3 5 6 7

Connection without Sensor

V

Possible connection of a voltmeter for checking the position feedback U.

T

+

~

T

1 2

+

~

3 5 6 7

Sensor scaling:

The sensors can be scaled with the sensor plug-in (sensor table).

Sensor

Ni1000

PT1000

NTC

Temperature range

–28 ... +98°C

–35 ... +155°C

–10 ... +160°C

(depending on type)

Resistance range

850 ... 1600

850 ... 1600

Ω

Ω

200 ... 60 k

Ω

Resolution

1

Ω

1

Ω

1

Ω

Connection with Passive Sensor, e.g. Pt1000, Ni1000, NTC

T

+

~

Requirements for switching contact:

The switching contact must be able to accurately switch a current of 16 mA @ 24 V.

1

T

– +

~

2 3 5 6 7

Connection with Switching Contact, e.g.

Δp-monitor

T

+

~

T

1

+

~

2 3 5 6 7

Possible input voltage range:

0 ... 32 V (resolution 30 mV)

Sensor scaling:

The sensors can be scaled with the sensor plug-in (sensor table)

Connection with Active Sensor, e.g. 0...10 V @ 0...50° C

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

208

GMX24-LON

LonWorks

®

, Non-Spring Return, 24 V

K

®

The LON-capable damper actuator is certified by LonMARK ® . The actuator functions are supplied with the LonWorks ® network as standardized network variables according to LonMARK ® . The Node Object #0, the Damper Actuator Object #8110 and the Open Loop SensorObject #1 are implemented in the actuator.

Node object #0

The node object contains the object status and object request functions.

nviRequest SNVT_obj_request

Input variable for requesting the status of a particular object in the node.

nvoStatus SNVT_obj_status

Output variable that outputs the current status of a particular object in the node.

nvoFileDirectory SNVT_address

Output variable that shows information in the address range of the Neuron chip.

Damper actuator object #8110

The actuator object is used to map the functions of the MP actuators to the

LONWORKS® network.

nviRelStpt SNVT_lev_percent

The nominal position is assigned to the actuator via this input variable. This variable is normally linked to the output variable of an HVAC controller.

nviActuateState SNVT_switch

A preset position is assigned to the actuator via this input variable. Note on priority:

The last variable that was active, either nviActuatorState or nviRelStpt, has priority.

nviManOvrd SNVT_hvac_overid

These input variables can be used to manually override the actuator into a particular position.

nvoActualValue SNVT_lev_percent

This output variable shows the current actual position of the actuator and can be used for control circuit feedback or for displaying positions.

nvoAbsAngle SNVT_angle_deg

This output variable shows the current angle of rotation of the actuator or the valve and can be used to display the position or for service purposes.

nvoAbsAirFlow SNVT_flow

This output variable is inactive with the SR24ALON-5 rotary actuator and shows a constant value of 65535 (this variable is only active in conjunction with LON-capable

VAV controllers).

Open loop sensor object #1

A sensor can be connected to the rotary actuator. A passive resistance sensor (e.g.

Ni1000), an active sensor (output 0 ... 32 V) or a switch (on/off) can be connected. The open loop sensor object transfers the measured sensor values to the LONWORKS® network.

nvoSensorValue SNVT_xxx

This output variable shows the current sensor value. Depending on the connected sensor, the output variable can be configured via the sensor plug-in and specifically adapted to the system.

The SNVT_... can be configured as:

SNVT_temp_p SNVT_lev_percent

SNVT_temp

SNVT_switch

SNVT_flow

SNVT_flow_p

SNVT_abs_humid

SNVT_enthalpy

SNVT_ppm

SNVT_rpm

SNVT_lux

SNVT_press_p

SNVT_smo_obscur

SNVT_power

SNVT_elec_kwh

Notes

Detailed information on the functional profiles can be found on the website of

LonMARK ®

209

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

4

5

1

2

3

GMX24-LON

LonWorks

®

, Non-Spring Return, 24 V

1 Direction of rotation switch

Switching over Direction of rotation changes

2 Pushbutton and green LED display

Off No voltage supply or malfunction

Green, on

Press button

Operation

Switches on angle of rotation adaption followed by standard operation

3 Service button for commissioning LONWORKS ® and yellow LED display for the LON status

Off The SR24ALON-5 rotary actuator is connected and ready for operation in the

LONWORKS®network.

Yellow, on

Yellow, flashing

(flashing interval 2 seconds)

No application software is loaded in the

SR24ALON-5.

The SR24ALON-5 is ready for operation but not integrated in the LONWORKS ® network

(unconfigured).

Other flashing codes

Press button

A fault is present in the SR24ALON-5.

Service Pin Message is sent to the

LONWORKS ® network.

4 Gear disengagement switch

Press button

Release button

Gear disengaged, motor stops, manual operation possible

Gear engaged, synchronisation starts, followed by standard operation

5 Service plug

For connecting MFT parameterizing and service tools

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA