- Home
- Domestic appliances
- Climate control
- Viessmann
- Vitotronic 200 KO1B
- Operating instructions
- 64 Pages
Viessmann Vitotronic 200 KO1B, KO2B, KW6B Heating system Operating instructions
Below you will find brief information for Heating system Vitotronic 200 KO1B, Heating system Vitotronic 200 KO2B, Heating system Vitotronic 200 KW6B. This document describes the operation of the heating system, including how to start and shut down the system, set the temperature, and program the heating schedule. It also includes information on how to use the various comfort and energy-saving functions, such as party mode, economy mode, and holiday program.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Operating instructions
for the system user
VIESMANN
Heating system with weather-compensated control unit
Vitotronic 200, type KO1B, KO2B or KW6B
VITOTRONIC 200
5592 667 GB 1/2011
Please keep safe.
2
Safety instructions
For your safety
Please follow these safety instructions closely to prevent accidents and material losses.
Safety instructions explained
Danger
This symbol warns against the risk of injury.
!
Please note
This symbol warns against the risk of material losses and environmental pollution.
Danger
Incorrectly executed work on the heating system can lead to lifethreatening accidents.
■ Work on gas appliances must only be carried out by a registered gas fitter.
■ Work on electrical equipment must only be carried out by a qualified electrician.
Note
Details identified by the word "Note" contain additional information.
Target group
These operating instructions are for the heating system user.
This unit is not designed to be used by persons (including children) with limited bodily, sensory or mental capacities, or lacking experience and/or lacking knowledge, unless they are supervised by a person responsible for their safety, or have received instructions from such a person as to how to use the unit.
!
Please note
Children should be supervised.
Ensure that children do not play with the unit.
If you smell gas
Danger
Escaping gas can lead to explosions which may result in serious injury.
■ Do not smoke. Prevent naked flames and sparks. Never switch lights or electrical appliances ON or OFF.
■ Close the gas shut-off valve.
■ Open windows and doors.
■ Remove all people from the danger zone.
■ Notify your gas or electricity supplier and your heating contractor from outside the building.
■ Shut off the electricity supply to the building from a safe place
(outside the building).
Safety instructions
For your safety
(cont.)
If you smell flue gas
Danger
Flue gas can lead to life-threatening poisoning.
■ Shut down the heating system.
■ Ventilate the boiler room.
■ Close all doors in the living space.
In case of fire
Danger
Fire creates the risk of burning and explosions.
■ Shut down the heating system.
■ Close the shut-off valves of the fuel lines.
■ Use a tested fire extinguisher, class ABC.
Boiler room requirements
!
Please note
Incorrect ambient conditions can lead to damage to the heating system and put the safe operation at risk.
■ Ensure ambient temperatures above 0 ºC and below 35 ºC.
■ Prevent air contamination by halogenated hydrocarbons
(e.g. as contained in paints, solvents or cleaning fluids) and excessive dust (e.g. through grinding/polishing work).
■ Avoid continuously high humidity levels (e.g. through frequent drying of washing).
■ Never close existing ventilation apertures.
Ancillary components, spare and wearing parts
!
Please note
Components that are not tested with the heating system may lead to damage to the heating system, or may affect their various functions.
Installation or replacement work must only be carried out by qualified personnel.
3
Index
Index
■ Without frost protection monitoring (shutdown)................................................ 19
■ Setting the room temperature for standard heating mode................................ 22
■ Setting the room temperature for reduced heating mode (night setback)........ 22
Comfort and energy saving functions
Selecting energy saving function "Economy mode"............................................. 28
Selecting energy saving function "Holiday program"............................................ 29
Setting the heating program for DHW heating..................................................... 31
■ Heating system with DHW circulation pump..................................................... 33
4
Index
Index
(cont.)
Repair work......................................................................................................... 48
5
Introductory information
Commissioning
The commissioning and matching of the control unit to local conditions and building characteristics, as well as instructing the user in the operation of the system, must be carried out by your heating contractor.
As the user of new combustion equipment, you may be obliged to notify your local flue gas inspector of the installation
[check local regulations]. Your local flue gas inspector will also inform you [where appropriate] about work he may be required to perform on your combustion equipment (e.g. regular checks, cleaning).
Your system is preset at the factory
The control unit is factory-set to "Heat-
ing and DHW".
Your heating system is therefore ready for use:
Central heating
■ Between 6:00 and 22:00 h, the rooms are heated at 20 °C "Set room tem-
perature" (standard heating mode).
■ Between 22:00 and 6:00 h, the rooms are heated at 3 °C "Set reduced room
temp" (reduced heating mode, frost protection).
■ Your heating contractor can make further settings for you during commissioning.
You can change any settings individually at any time to suit your requirements (see chapter "Central heating").
DHW heating
■ Between 5:30 and 22:00 h, the DHW is heated to 50 °C "Set DHW temper-
ature". Any installed DHW circulation pump is ON.
■ Between 22:00 and 05:30 h, the DHW cylinder temperature will not be reheated. Any installed DHW circulation pump is OFF.
■ Your heating contractor can make further settings for you during commissioning.
You can change any settings individually at any time to suit your requirements (see chapter "DHW heating").
Frost protection
■ Your boiler and DHW cylinder are protected against frost.
Wintertime/summertime changeover
■ This changeover is automatic.
Time and date
■ The day and time were set by your heating contractor during commissioning.
6
Your system is preset at the factory
(cont.)
Introductory information
Power failure
■ All data is saved if there is a power failure.
Terminology
To provide you with a better understanding of the functions of your control unit, the appendix contains the chapter "Ter-
Tips on saving energy
Utilise the setting options for the control unit and remote control (if installed):
■ Never overheat your rooms. Every degree by which the room temperature is reduced saves up to 6% on heating costs.
Never set your room temperature
higher than 20 °C (see page 22).
■ Never set the DHW temperature too
■ Only activate the DHW circulation pump at times when DHW is drawn off.
Set the time program for this (see
■ Select the heating program that meets your current requirements:
– For short absences (e.g. shopping trips), select "Economy mode"
As long as economy mode is activated, the room temperature is reduced.
– If you are going away, set the "Hol-
As long as the holiday program is activated, the room temperature is reduced and DHW heating is off.
– In summer, when you don't want to heat any rooms but do need DHW, select the heating program "Only
7
Introductory information
Tips on saving energy
(cont.)
In conjunction with a solar thermal system:
DHW heating is set at the factory to start at 05:30 h. On sunny days, the
DHW cylinder receives sufficient heat from the solar thermal system so that the DHW temperature is still high enough the next morning. You can program DHW heating to start at
10:00 h, for example.
– If you don't want to heat the rooms and you don't require DHW for an extended period, select the heating program "Standby mode" (see
For additional control unit energy saving functions, please contact your heating contractor.
Further recommendations:
■ Correct ventilation/airing.
Briefly open windows fully and at the same time close the thermostatic valves.
■ Close roller shutters (if installed) at dusk.
■ Set thermostatic valves correctly.
■ Never cover radiators or thermostatic valves.
■ Controlled DHW consumption: A shower generally uses less energy than a full bath.
8
Operation
You can change any settings on your heating system centrally at the programming unit of the control unit.
If remote control units are installed in your rooms, you can also adjust the settings at the remote control units.
Opening the control unit
The control unit may look different depending on the control unit type.
Vitotronic 200, type KO1B
Operation
Remote control operating instructions
A
C B
A Top part of control unit with programming unit
B Cover flap
C Short operating guide on the inside of the cover
9
Operation
Operation
(cont.)
Vitotronic 200, type KO2B
A B
A Cover flap
B Short operating guide on the inside of the cover
Vitotronic 200, type KW6B
Note
You will find a short operating guide in the "Technical documentation".
BA
A Top part of control unit with programming unit
B Pushbutton for changing the angle
10
Operation
Operation
(cont.)
Programming unit
HC1
14°C
21°C
Boiler temperature 48 °C
Takes you to the previous step in the menu or cancels a setting that has been started.
Cursor keys
To scroll in the menu or to set values.
"Help"
Displays explanations about operation in the form of a short guide.
OK Confirms your selection or saves the setting.
Calls up "Help" (see the following chapter) or additional information on the selected menu.
Calls up the extended menu.
Call up the "Help" as follows:
■ If the screen saver is active (see
Press .
■ If you are somewhere in the menu:
Press the button until the standard menu is shown (see the following chapter).
Press .
Menu
There are two control levels available, the "Standard menu" and the "Extended menu".
11
A
B
C
Operation
Menu
(cont.)
Standard menu
Call up the standard menu as follows:
■ If the screen saver is active (see
Press OK.
■ If you are somewhere in the menu:
Keep pressing the button until the standard menu appears.
D
In the standard menu, you can adjust and scan the most frequently used settings for the heating circuit shown in
the header:
■ Set room temperature
■ Heating program
HC1
14 °C
21 °C
Boiler temperature 48 °C
A Header (shows the heating program for the heating circuit displayed
D)
B Current outside temperature
C Set room temperature
Selecting the set room temperature
Press the following keys:
/ for the required value.
OK to confirm.
Setting the heating program
Press the following keys:
/ for the required heating program.
OK to confirm.
D Only with more than one heating circuit:
Heating circuit selected for operation in the standard menu (see chapter "Changing the standard
Heating programs:
Standby mode with frost protection
Only DHW
Heating and DHW
12
Operation
Menu
(cont.)
Note
The settings for the displayed heating circuit can also be found in the Extended
menu.
The settings for any other connected heating circuits can only be found in the extended menu.
Symbols on the display
These symbols are not always displayed, but appear subject to the system version and the operating state.
Heating program
Standby mode with frost protection monitoring
Only DHW
Heating and DHW
Displays
HC1 (2, 3) If your heating system has 2 or 3 heating circuits:
To display the heating circuit selected in the standard menu.
To change this, see
Frost protection monitoring
Extended menu
Call up the extended menu as follows:
■ If the screen saver is active (see
Press OK and then .
■ If you are somewhere in the menu:
Press .
Central heating with standard room temperature
Central heating with reduced room temperature
Party mode enabled
Economy mode enabled
In conjunction with a solar thermal system:
Solar circuit pump runs
Burner in operation
Messages
Service message
Fault message
Note
Your heating contractor can block operation for the extended menu. In this case, you can only scan fault and service messages.
In the extended menu, you can adjust and scan the settings from the control unit's range of functions used less fre-
quently, e.g. time programs and holiday programs.
13
Operation
Menu
(cont.)
The menu overview can be found on
E
Menu
Heating
DHW
Solar energy
Test mode
Continue with OK
E Dialogue line
How to use the controls
The screen saver will become active if you have not adjusted any settings on the programming unit for a few minutes.
The display brightness is reduced.
B
C
14 °C
21 °C
B Current outside temperature
1. Press OK. This takes you to the
14
C Set room temperature
2. Press . This takes you to the
Operation
How to use the controls
(cont.)
The selected menu option is highlighted in white.
The dialogue line E (see diagram on
page 14) then shows the necessary
instructions.
The following diagram shows how to make settings with different dialogue lines, using the set room temperature setting as an example.
15
Operation
How to use the controls
(cont.)
HC1
14°C
21°C
Boiler temperature 48°C
Menu
Heating
DHW
Solar energy
Test mode
Continue with
OK
Heating circuit 1
Party mode
Economy mode
Set room temperature
Set reduced room temp
Continue with
OK
HC1
Ú
ê
ê
Ú
Htg circ. selection
Ù
HC2
Ú
Heating circuit 2
OK Was selected
Heating circuit 1
Party mode
Economy mode
Set room temperature
OK
Set reduced room temp
Continue with
OK
Set room temperature
20°C
HC1
ê
ê
OK
HC1
Change with
Set room temperature
V or
( v
HC1
22°C
Adopt with
Set room temperature
OK
OK
HC1
22°C
Adopted
Heating circuit 2
Party mode
Economy mode
Set room temperature
Set reduced room temp
Continue with
OK
Set room temperature
20°C
HC2
Ú
ê
ê
OK
HC2
Change with
Set room temperature
V or
( v
HC2
22°C
Adopt with
Set room temperature
OK
OK
HC2
22°C
Adopted
16
Starting the heating system
Controls with the cover open
Vitotronic 200, type KO1B
14 °C
21 °C
Start-up/shutdown
A B C
A Fault indicator (red)
B ON indicator (green)
C TEST key
(only for service purposes)
D E FG
D Temperature controller
E Excess temperature reset
F ON/OFF switch
G Cover flap
17
Start-up/shutdown
Starting the heating system
(cont.)
Vitotronic 200, type KO2B
A B C D
A Fault indicator (red)
B ON indicator (green)
Vitotronic 200, type KW6B
14 °C
21 °C
C ON/OFF switch
D Excess temperature reset
R
A B C D
A Fault indicator (red)
B ON indicator (green)
Ask your heating contractor about the following:
■ Boiler and relevant control unit type
■ Level of the required system pressure
■ Position of the pressure gauge, shutoff valve, gas shut-off valve, ventilation apertures
1. Check the heating system pressure at the pressure gauge. If the pressure of the heating system is too low, top up the water or notify your heating contractor.
C Reset button
D ON/OFF switch
2. In boilers for open flue operation:
Check that the ventilation apertures of the installation room are open and unrestricted.
Note
With open flue operation, the combustion air is drawn from the installation room.
3. Open the shut-off valves in the oil lines (at the tank and filter) or open the gas shut-off valve.
18
Start-up/shutdown
Starting the heating system
(cont.)
4. Switch ON the power supply, e.g. at a separate MCB/fuse or a mains isolator.
5. Switch ON the ON/OFF switch (see
After a short time, the standard menu
is displayed (see page 12) and the
green ON indicator illuminates. Your heating system and, if installed, your remote control unit are now ready for use.
Shutting down the heating system
With frost protection monitoring
For every heating circuit, select the heating program "Standby mode".
■ No central heating.
■ No DHW heating.
■ Frost protection for the boiler and the
DHW cylinder is enabled.
For the heating circuit displayed in the header
Standard menu
1. / for the heating program
"Standby mode" (frost protection monitoring).
2. OK to confirm.
For the other heating circuits
3. Select the heating circuit, if necessary
4. "Heating program"
5. "Standby mode" (frost protection monitoring).
Note
The circulation pumps are briefly started every 24 hours to prevent them from seizing up.
End the heating program "Standby mode"
Select another heating program.
Extended menu
1.
2. "Heating"
Without frost protection monitoring (shutdown)
1. Switch OFF the ON/OFF switch (see
2. Close the shut-off valves in the oil lines (at the tank and filter) or close the gas shut-off valve.
19
Start-up/shutdown
Shutting down the heating system
(cont.)
3. Isolate the heating system from its main power supply, e.g. at a separate
MCB/fuse or a mains isolator.
4. Where outside temperatures of below 3 °C are anticipated, please take suitable measures to protect the heating system against frost. If necessary, contact your heating contractor.
Information on a prolonged shutdown
■ Circulation pumps may seize up as they are not supplied with power.
■ It may be necessary to reset the date
20
Central heating
Required settings (central heating)
If you want central heating, check the following points:
■ Have you selected the heating circuit?
For settings, see the next chapter.
■ Have you set the required room temperature?
■ Have you set the correct heating program?
■ Have you set the required time program?
Note
Your heating contractor can, for example, enable the "Screed function" for your new installation or fitting for building drying. Your settings for central heating have no effect for the duration of the building drying. For a more detailed explanation of building drying/screed function, see chapter "Terminology" in the appendix.
In the extended menu, you can scan the selected heating program under "Infor-
mation" (see chapter "Scanning information", "Heating circuit ..." group).
Selecting a heating circuit
The heating of all rooms can, if necessary, be split over several heating circuits.
■ In the case of heating systems with several heating circuits, for all central heating settings, first select the heating circuit where you want to make a change.
■ This selection is not possible in heating systems with only one heating circuit.
Example:
■ "Heating circuit 1" is the heating circuit for the rooms occupied by you.
■ "Heating circuit 2" is the heating circuit for the rooms of a separate apartment.
The heating circuits are marked at the factory as "Heating circuit 1" (HC1),
"Heating circuit 2" (HC2) and "Heating
circuit 3" (HC3).
If you or your heating contractor have renamed the heating circuits (e.g. as
"Apartment", etc.), the name is displayed instead of "Heating circuit ..." (see
Extended menu
1.
2. "Heating"
Menu
Heating
DHW
Solar energy
Test mode
Continue with OK
3. / for the required heating circuit.
21
Central heating
Selecting a heating circuit
(cont.)
Heating circuit 1
Party mode
Economy mode
Set room temperature
Set reduced room temp
Continue with OK
HC1
Ú
ê
ê
Ú
Note
If you return to the standard menu with
, the header will again display "HC1"
For changes to the heating circuit display
in the standard menu, see page 36.
Htg circ. selection
Ù Ú
Heating circuit 2
Was selected
Setting the room temperature
Setting the room temperature for standard heating mode
Factory setting: 20 °C
For the heating circuit displayed in the header
Proceed as described on page 12.
For the other heating circuits
3. Select the heating circuit, if necessary
4. "Set room temperature"
5. Set the required value.
Extended menu
1.
2. "Heating"
Setting the room temperature for reduced heating mode (night setback)
Factory setting: 3 °C Extended menu
1.
2. "Heating"
22
Central heating
Setting the room temperature
(cont.)
3. Select the heating circuit, if necessary
4. "Set reduced room temp"
5. Set the required value.
The rooms are heated to this temperature:
■ Between the time phases for standard
■ In the holiday program (see
Setting the heating program for central heating
Factory setting: "Heating and DHW"
For the heating circuit displayed in the header
Proceed as described on page 12.
For the other heating circuits
Extended menu
1.
2. "Heating"
3. Select the heating circuit, if necessary
4. "Heating program"
5. "Heating and DHW"
■ The rooms of the selected heating circuit are heated in accordance with the room temperature and time program settings.
■ DHW is reheated in accordance with the set DHW temperature and time program (see chapter "DHW heating").
23
Central heating
Setting the time program for central heating
■ The time program for central heating is made up of time phases. One time phase from 6:00 to 22:00 h for every
day of the week is set at the factory.
■ You can set the time program individ-
ually, to be the same for every day of the week or different:
You can select up to 4 time phases per day for standard heating mode. Set the start and end points for each time phase. Between these time phases, the rooms are heated with the reduced room temperature (see chapter "Setting the room temperature for reduced heating mode").
■ When setting, bear in mind that your heating system requires some time to heat the rooms to the required temperature.
■ In the extended menu, you can scan the current time program under "Infor-
mation" (see chapter "Scanning information", "Heating circuit ..." group).
Extended menu:
1.
2. "Heating"
3. Select the heating circuit if necessary.
4. "Heating time program"
5. Select part of the week or a day.
6. Select the time phase !, ?, § or
$.
7. Set the start and end points for the relevant time phase.
Example shown:
■ Time program for Monday to Friday
("Mo-Fr")
■ Time phase !:
From 05:00 to 08:30 h
■ Time phase ?:
From 16:30 to 23:00 h
Heating
!
Mo-Fr
?
HC1
0 2 4 6 8 10 12 14 16 18 20 22 24
!
05:00 - 08:30 u
?
16:30 - 23:00 u
Normal
Normal
Select with
(
Example:
You want to set the same time program for every day except Monday:
Select the period "Monday–Sunday" and set the time program.
Then select "Monday" and set the time program for this.
Note
If you want to terminate the setting process prematurely, keep pressing until the required display appears.
24
Central heating
Setting the time program for central heating
(cont.)
Deleting a time phase
Set the time for the end point to the same time that was set for the start point. The display shows the selected time phase
"- - : - -".
Heating Mo-Fr
HC1
0 2 4 6 8 10 12 14 16 18 20 22 24
?
§
- -:- - - - -:- -
- -:- - - - -:- u u
Normal
Normal
Adopt with OK
Changing the heating curve
Your system's heating characteristics are affected by the slope and the level of the selected heating curve. Further information about the heating curve can be found under "Terminology" on
Factory setting:
■ Heating curve "Slope": 1.4
■ Heating curve "Level": 0
■ "Set room temperature": 20 ºC
■ "Set reduced room temp": 3 ºC
Extended menu:
1.
2. "Heating"
3. Select the heating circuit, if necessary
4. "Heating curve"
5. "Slope" or "Level"
Note
Tips on when and how to change the heating curve slope and level are displayed by pressing ?.
6. Set the required value.
Example:
Change the heating curve slope to 1.5.
A graph clearly shows the change in the heating curve as soon as you alter the value for the slope or level.
25
Central heating
Changing the heating curve
(cont.)
Heating curve
HC1
100°C
23°C
41°C
20
Slope
10 0
Change with
55°C
-10
68°C
-20
81°C
(
-30
1.5
Depending on various outside temperatures (shown on the horizontal axis), the assigned set flow temperatures for the heating circuit are highlighted white.
Switching OFF central heating
For the heating circuit displayed in the header
Standard menu
1. / for the heating program
"Only DHW" (summer mode, no central heating) or
"Standby mode" (frost protection monitoring).
2. OK to confirm.
For the other heating circuits
Extended menu
1.
2. "Heating"
3. Select the heating circuit, if necessary
4. "Heating program"
5. "Only DHW" (summer mode, no central heating) or
"Standby mode" (frost protection monitoring).
26
Comfort and energy saving functions
Selecting comfort function "Party mode"
With this function, you can change the room temperature for several hours, e.g.
if guests unexpectedly stay longer in the evening. You do not have to change any existing control settings. The DHW is boosted in this function to the specified set temperature.
Extended menu
1.
2. "Heating"
3. Select the heating circuit, if necessary
4. "Party mode"
Heating circuit 1
Party mode
Economy mode
Set room temperature
Set reduced room temp
Continue with
Ù
HC1
OK
Ú
ê
ê
Display in the standard menu
14°C
21°C
Boiler temperature
HC1
48°C
Note
The display of the selected set room temperature does not change.
■ The rooms are heated to the required temperature.
■ DHW is reheated to the selected set temperature.
■ The DHW circulation pump is switched
ON (if installed).
5. Set the required room temperature during party mode.
Party mode
HC1
23 °C
Change with
(
27
Comfort and energy saving functions
Selecting comfort function "Party mode"
(cont.)
Ending party mode
■ Automatically when the system switches to standard heating mode in accordance with the time program.
or
■ In the extended menu, set "Party
mode" to "OFF".
Selecting energy saving function "Economy mode"
To save energy, you can reduce the room temperature in standard heating
mode. For example, if you want to leave your home for a few hours.
Extended menu
1.
2. "Heating"
3. Select the heating circuit, if necessary
4. "Economy mode"
Heating circuit 1
Party mode
Economy mode
Set room temperature
Set reduced room temp
Continue with
Ù
HC1
Ú
OK
ê
ê
Display in the standard menu
Note
14°C
21°C
Boiler temperature
HC1
48°C
The display of the selected set room temperature does not change.
28
Comfort and energy saving functions
Selecting energy saving function "Economy mode"
(cont.)
Ending economy mode
■ Automatically when the system switches to reduced heating mode in accordance with the time program.
or
■ In the extended menu, set "Economy
mode" to "OFF".
Selecting energy saving function "Holiday program"
To save energy, for example over long holidays, you can activate the "Holiday
program".
Note
The control unit is set so that the holiday program can only be selected for one heating circuit. However, it affects all heating circuits. If you want to make changes, contact your local heating contractor.
The holiday program has the following effect on the heating circuits and DHW heating:
■ Central heating:
– For heating circuits in the heating program "Heating and DHW": in these heating circuits, the rooms are heated to the selected reduced
room temperature (see page 22).
– For heating circuits in the heating program "Only DHW":
No central heating in these heating circuits.
If the heating program "Only
DHW" is selected for all heating circuits, frost protection monitoring is
only enabled for the boiler and DHW cylinder.
■ DHW heating:
DHW heating is switched OFF; frost protection monitoring for the DHW cylinder is active.
The holiday program starts at 00:00 h the day following your departure and ends at
00:00 h on the day of your return. This means the selected time program is active on the days of departure and
29
Comfort and energy saving functions
Selecting energy saving function "Holiday program"
(cont.)
Extended menu:
1.
2. "Heating"
3. "Holiday program"
Heating circuit 1
Heating program
Heating time program
Holiday program
Heating curve
Continue with
Ù
HC1
Ú
OK
ê
Display in the standard menu
The enabled holiday program is not displayed in the standard menu.
Display in the extended menu
In the extended menu, you can scan the selected holiday program under "Infor-
mation" (see chapter "Scanning information", "Heating circuit ..." group).
4. Set the required departure and return dates.
Holiday program
Leaving date:
Date
Return date:
Date
Select with
HC1
Tu 21/12/2010
We 22/12/2010
(
Terminating or deleting a holiday program
Extended menu
1.
2. "Heating"
3. "Holiday program"
4. "Delete program"
30
DHW heating
Required settings (DHW heating)
If you want DHW heating, check the following points:
■ Have you set the required DHW temperature?
For settings, see the next chapter.
■ Have you set the correct heating program?
■ Have you set the required time program?
Note
The control unit is set up so that DHW heating applies to all heating circuits. If you want to make changes, contact your local heating contractor.
Setting the DHW temperature
Extended menu
1.
2. "DHW"
Menu
Heating
DHW
Solar energy
Test mode
Continue with OK
3. "Set DHW temperature"
4. Set the required value.
Setting the heating program for DHW heating
Extended menu
1.
2. "Heating"
3. Select the heating circuit, if necessary
4. "Heating program"
5. "Heating and DHW" (with central heating) or
"Only DHW" (summer mode, no central heating)
31
DHW heating
Setting the time program for DHW heating
■ The time program for DHW heating is made up of time phases. One time phase from 5:30 to 22:00 h for every
day of the week is set at the factory.
■ Automatic mode is set at the factory for DHW heating. This means that, in standard heating mode, the DHW is reheated to the set temperature. To ensure that hot water is available at the start of standard heating mode, the time phase for DHW heating begins automatically half an hour earlier than the time phase for standard heating mode.
■ If you don't want the automatic mode, you can select up to 4 individual time phases per day for DHW heating, which can be the same for every day of the week or different. Set the start and end points for each time phase.
■ When setting, bear in mind that your heating system requires some time to heat the DHW to the required temperature.
■ In the "Extended menu", you can scan the current time program under "Infor-
mation" (see chapter "Scanning information", "DHW" group).
Extended menu:
1.
2. "DHW"
3. "DHW time prog"
4. "Individual"
5. Select part of the week or a day.
6. Select the time phase !, ?, § or
$.
7. Set the start and end points for the relevant time phase.
Example shown:
■ Time program for Monday to Friday
("Mo-Fr")
■ Time phase !:
From 04:30 to 06:30 h
■ Time phase ?:
From 15:30 to 20:30 h
DHW
!
Mo-Fr
?
HC1
0 2 4 6 8 10 12 14 16 18 20 22 24
!
04:30 - 06:30 u
?
15:30 - 20:30 u
ON
ON
Select with
(
Example:
You want to set the same time program for every day except Monday:
Select the period "Monday–Sunday" and set the time program.
Then select "Monday" and set the time program for this.
Note
If you want to terminate the setting process prematurely, keep pressing until the required display appears.
32
DHW heating
Setting the time program for DHW heating
(cont.)
Deleting a time phase
Set the time for the end point to the same time that was set for the start point. The display shows the selected time phase
"- - : - -".
DHW heating once, no longer in the time program
Note
At least one heating circuit of your system must not be in standby mode.
DHW Mo-Fr
HC1
0 2 4 6 8 10 12 14 16 18 20 22 24
?
§
- -:- - - - -:- -
- -:- - - - -:- u u
ON
---
Adopt with OK
Extended menu
1.
2. "Heating"
3. Select the heating circuit if necessary.
4. "Party mode"
5. Disable "Party mode" again with
"OFF", to prevent unintentional central heating with standard room temperature.
Heating system with DHW circulation pump
Further information about the DHW circulation pump can be found under "Ter-
■ Automatic mode is set for the DHW circulation pump time program. In other words, the DHW circulation pump operates in parallel to the DHW heating time program.
■ If you don't want the automatic mode, you can select up to 4 individual time phases per day for the DHW circulation pump, which can be the same for every day of the week or different. Set the start and end points for each time phase.
■ In the "Information" menu, you can scan the current time program (see chapter "Scanning information",
"DHW" group).
Note
Activating the DHW circulation pump is only advisable for those times when
DHW is actually drawn.
Extended menu:
1.
2. "DHW"
3. "DHW circ time prog"
4. "Individual"
5. Select part of the week or a day.
6. Select the time phase !, ?, § or
$.
7. Set the start and end points for the relevant time phase.
Note
If you want to terminate the setting process prematurely, keep pressing until the required display appears.
33
DHW heating
Setting the time program for DHW heating
(cont.)
Deleting a time phase for DHW circulation pump
Set the time for the end point to the same time that was set for the start point. The display shows the selected time phase
"- - : - -".
DHW circulation
Mo-Fr
HC1
0 2 4 6 8 10 12 14 16 18 20 22 24
?
- -:- - - - -:- u
---
§
- -:- - - - -:- u
---
Adopt with OK
Switching OFF DHW heating
You do not want to have DHW or heat your rooms.
For the heating circuit displayed in the header
Standard menu
1. / for the heating program "Standby
mode" (frost protection monitoring).
2. OK to confirm.
For the other heating circuits
Extended menu
1.
2. Select the heating circuit, if necessary
3. "Heating"
4. "Heating program"
5. "Standby mode" (frost protection monitoring).
34
You do not want DHW, but do want to heat the rooms.
Extended menu
1.
2. Select the heating circuit, if necessary
3. "Heating"
4. "Heating program"
5. "Heating and DHW"
6.
until the menu is displayed.
7. "DHW"
8. "Set DHW temperature"
9. Select 10 °C.
Further adjustments
Setting the display contrast
Extended menu
1.
2. "Settings"
3. "Contrast"
4. Set the required contrast.
Setting the display brightness
If you would like the texts in the menu to be more clearly legible, change the brightness for "Control".
You can also alter the screen saver brightness.
Extended menu
1.
2. "Settings"
3. "Brightness"
4. "Control" or "Screen saver"
5. Set the required brightness.
Entering names for the heating circuits
You can give heating circuits 1, 2 and 3
("HC1", "HC2" and "HC3") individual names. The abbreviations "HC1",
"HC2" and "HC3" will be retained.
Extended menu
1.
2. "Settings"
3. "Name for heating circ."
4. "Heating circuit 1", "Heating circuit
2" or "Heating circuit 3"
5. "Change?"
6. You can select the required symbol with / .
7. / takes you to the next character.
8. Press OK to accept all entered characters at once and simultaneously exit this menu.
Note
The entered term is deleted with
"Reset?"; "Heating circuit 1" will then be shown again.
Example:
Name for "Heating circuit 2": Apartment
35
Further adjustments
Entering names for the heating circuits
(cont.)
HC2
The menu shows "Apartment" for "Heat-
ing circuit 2".
Heating circuit 2 f g e d c
Change with
Heating circuit 2
(
HC2
Ù
HC2
Ú
Party mode
Economy mode
Set room temperature
22 °C
ß
Set red. Set room temp. temp
Select with
(
Apartment
Adopted
Changing the standard menu
If your heating system has several heating circuits, you can select the heating circuit to be displayed in the standard
Note
If your heating system only has one heating circuit, this menu is not available.
No heating circuit name "HC..." is shown in the header.
Extended menu
1.
2. "Settings"
3. "Standard menu"
4. Select the heating circuit:
■ "Heating circuit 1"
Display in the header: "HC1"
■ "Heating circuit 2"
Display in the header: "HC2"
■ "Heating circuit 3"
Display in the header: "HC3"
36
Further adjustments
Setting the time and date
The time and date are factory-set. If your heating system has been shut down for a long time, it may be necessary to set the time and date.
Extended menu
1.
2. "Settings"
3. "Time/Date"
4. Set the time and date.
Language selection
Extended menu
1.
2. "Settings"
3. "Language"
4. Select the required language.
Setting the temperature unit (°C/°F)
Factory setting: °C
Extended menu
1.
2. "Settings"
3. "Temperature unit"
4. Select the temperature unit "°C" or
"°F".
Restoring factory settings
You can restore the factory settings for each heating circuit separately.
Extended menu
1.
2. "Settings"
3. "Standard setting"
4. "Heating circuit 1", "Heating circuit
2" or "Heating circuit 3"
The following settings and values are reset:
■ Set room temperature
■ Set reduced room temperature
■ Heating program
■ Set DHW temperature
■ Time program for central heating
■ Time program for DHW heating
■ Time program for DHW circulation pump
■ Heating curve slope and level
37
Further adjustments
Restoring factory settings
(cont.)
Party mode, economy mode and holiday program are deleted.
38
Scanning
Scanning information
Subject to the connected components and settings made, you can scan current temperatures and operating conditions.
The extended menu splits the information into groups:
■ "General"
■ "Heating circuit 1"
■ "Heating circuit 2"
■ "Heating circuit 3"
■ "DHW"
■ "Solar"
■ "Reset data"
Note
If heating circuits have been given names, the name is displayed (see chapter "Entering names for the heating circuits").
For detailed scanning options for the individual groups, see chapter "Scanning options in the extended menu".
Extended menu
1.
2. "Information"
3. Select the category.
4. Select the required scan.
Scanning in conjunction with solar thermal systems
Extended menu
1.
2. "Solar energy"
The solar energy yield for the past 7 days is displayed on a graph.
The flashing line on the graph indicates that the current day is not yet over.
Solar energy
4.0
0
We Th Fr Sa Su Mo Tu We kWh Su 03.10.10
Select with
1.3
Note
Further scanning options, e.g. for the solar circuit pump hours run, can be found in the extended menu under
"Information" in the "Solar" group.
Resetting data
You can reset the following data:
■ Burner hours run.
■ Fuel consumption, if set by your heating contractor.
■ In conjunction with a solar thermal system:
Solar energy yield, solar circuit pump hours run and hours run output 22.
■ All the above data simultaneously.
Extended menu
1.
2. "Information"
3. "Reset data"
39
Scanning
Scanning the service messages
If your heating system is due for a service, the symbol flashes in the display, and "Service" appears.
1. You can call up the reason for the service with OK.
Service
Burner
Service
05500 h
Continue with OK
Acknowledge with OK
2. Pressing calls up information on the service that is due.
3. If you want to acknowledge the service message, follow the instructions in the menu.
Contact your local heating contractor.
The service message is transferred to the menu.
Display in the standard menu
HC1
14°C
21°C
Boiler temperature 48°C
40
Scanning
Scanning the service messages
(cont.)
Display in the extended menu
Menu
Service
Heating
DHW
Solar energy
Select with
ë
Note
If the service can only be carried out at a later date, the service message is displayed again the following Monday.
Calling up an acknowledged service message
Extended menu
1.
2. "Service"
Scanning fault messages
If any faults have occurred in your heating system, the symbol flashes in the display, and "Fault" appears. The red fault indicator also flashes (see chapter
"Starting the heating system").
1. You can call up the cause of the fault with OK.
Fault
Outside temp sensor
Fault
18
A2
Fault
Acknowledge with OK
Continue with OK
2. Pressing ? calls up information on the heating system performance.
Tips on which measures you can take yourself before notifying your heating contractor are also displayed.
41
Scanning
Scanning fault messages
(cont.)
3. Make a note of the cause of the fault and the fault code next to it on the right. In this example: "Outside temp
sensor 18" and "Fault A2".
This enables the heating contractor to be better prepared for the service call and may save additional travelling costs.
4. If you want to acknowledge the fault message, follow the instructions in the menu.
The fault message is transferred to the menu.
Display in the standard menu
HC1
Note
■ If you have connected up signalling equipment (e.g. a buzzer) for fault messages, this is deactivated when the fault message is acknowledged.
■ If the fault can only be rectified at a later date, the fault message will be displayed again the next day and the signalling equipment will be switched on again.
Calling up an acknowledged fault message
Extended menu
1.
2. "Fault"
14°C
21°C
Boiler temperature 48°C
Display in the extended menu
Menu
Fault
Heating
DHW
Solar energy
Continue with
ã
OK
42
Emissions test mode
Emissions test mode
Emissions test mode should only be activated by your flue gas inspector during the annual inspection.
Extended menu
1.
2. "Test mode"
3. "Flue gas test ON"
Note
You can also enable emissions test mode if the controls are locked out by your heating contractor.
Test mode
Boiler temperature 62°C
Terminate with OK
If the burner is on, the symbol is shown.
Ending emissions test mode
■ Automatically after 30 min.
■ Press OK.
43
What to do if...
Rooms are too cold
Cause
The heating system is off.
Control unit or remote control incorrectly adjusted.
Remedy
■ Switch the ON/OFF switch ON (see dia-
■ Switch ON the mains isolator, if installed (outside the boiler room).
■ Reset the MCB in the power distribution board (main domestic MCB).
Check settings and correct if required:
■ "Heating and DHW" must be selected
■ Room temperature (see page 22).
■ Check the settings at the remote control (if available).
Separate operating instructions
Only when operating with DHW heating:
DHW priority is enabled.
No fuel.
Only with the Vitotronic 200, type KW6B:
"Combustion controller" is shown on the display.
"Fault" is displayed, and the red fault indicator flashes.
Burner start faulty.
"Fault" is displayed and the red fault indicator on the burner is illuminated.
Wait until the DHW cylinder has been heated up.
With oil/LPG:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with your gas supply utility.
Press R (see diagram on page 18).
Acknowledge the fault (see page 42).
Notify your heating contractor if this fault recurs.
The fault message is displayed until the cause is rectified.
Scan and acknowledge the type of fault
(see page 42). If necessary, notify your
heating contractor.
Press the reset button on the burner. If there is no reset button, switch the ON/
OFF switch (see diagrams from page 17)
first OFF and then ON again.
Contact your local heating contractor if the burner still fails to start.
44
What to do if...
Rooms are too cold
(cont.)
Cause
Vitoair draught stabiliser faulty.
Remedy
Contact your local heating contractor.
Press the rotary selector on the motor and rotate it past this position A as far as it will go.
A
Mixer motor faulty.
Adjust the mixer manually.
Rooms are too hot
Cause
Control unit or remote control is incorrectly adjusted.
"Fault" is displayed, and the red fault indicator flashes.
Mixer motor faulty.
Remedy
Check settings and correct if required:
■ Room temperature (see page 22).
■ Check the settings at the remote control (if available).
Separate operating instructions
Scan and acknowledge the type of fault
(see page 42). If necessary, notify your
heating contractor.
Adjust the mixer manually.
45
What to do if...
There is no hot water
Cause
The heating system is OFF.
Control unit or remote control incorrectly adjusted.
Remedy
■ Switch the ON/OFF switch ON (see dia-
■ Switch ON the mains isolator, if installed (outside the boiler room).
■ Reset the MCB in the power distribution board (main domestic MCB).
Check settings and correct if required:
■ DHW heating must be enabled (see
■ DHW temperature (see page 31)
■ Check the settings at the remote control (if available).
Separate operating instructions
No fuel.
Vitoair draught stabiliser faulty.
With oil/LPG:
Check the fuel reserves and re-order if required.
With natural gas:
Open the gas shut-off valve. If necessary, check with your gas supply utility.
Contact your local heating contractor.
Press the rotary selector on the motor and rotate it past this position A as far as it will go.
A
"Fault" is displayed, and the red fault indicator flashes.
Scan and acknowledge the type of fault
(see page 42). If necessary, notify your
heating contractor.
46
What to do if...
The DHW is too hot
Cause Remedy
The control unit is incorrectly adjusted.
Check and correct the DHW temperature,
ã
flashes and "Fault" is displayed
Cause
Heating system fault.
Remedy
Proceed as described on page 41.
ë
flashes and "Service" is displayed
Cause
The time for a service, as specified by your heating contractor, has arrived.
Remedy
Proceed as described on page 40.
"Controls locked out" is displayed
Cause
This function is disabled.
Remedy
Your heating contractor can lift this block.
"External hook-up" is displayed
Cause
The heating program set at the control unit was changed by an external device, e.g. extension EA1.
Remedy
No remedy is required.
"External program" is displayed
Cause
The heating program set at the control unit was changed over by the Vitocom communication interface.
Remedy
You can change the heating program.
47
Repair work
Repair work
Cleaning
All equipment can be cleaned with a commercially available domestic cleaning agent (non-scouring). Clean the surface of the programming unit with a microfibre cloth.
Inspection and maintenance
Inspection and maintenance of your heating system is prescribed by the
Energy Savings Order and DIN 4755,
DVGW-TRGI 2008 and DIN 1988-8.
Regular maintenance ensures troublefree, energy efficient, environmentally responsible and safe heating. Your heating system must be serviced by an authorised contractor at least every
2 years. For this, we advise you to arrange an inspection and maintenance contract with your local heating contractor.
Boiler
Increasing boiler contamination raises the flue gas temperature and thereby increases energy losses. For that reason, all boilers should be cleaned annually.
DHW cylinder (if installed)
The DIN 1988-8 and EN 806 specify that maintenance and cleaning should be carried out no later than two years after commissioning and thereafter as required.
Only a qualified heating contractor should clean the inside of a DHW cylinder and the DHW connections.
Refill any water treatment equipment
(e.g. a lock or injection system) in good time, if such equipment is installed in the cold water supply of the DHW cylinder.
Observe the manufacturer's instructions.
Additionally for a Vitocell 100:
We recommend that the correct function of the sacrificial anode is checked annually by your heating contractor.
The anode function can be checked without interrupting the system operation.
The heating contractor will check the earth current with an anode tester.
Safety valve (DHW cylinder)
The safety valve function should be checked every six months by venting, either by the system user or the local heating contractor. The valve seat may become contaminated (see the valve manufacturer's instructions).
48
Repair work
(cont.)
Potable water filter (if installed)
To maintain high hygienic standards, proceed as follows:
■ Replace filter element on non-back flushing filters every six months (visual inspection every two months).
■ On back flushing filters, back flush every two months.
Repair work
49
Appendix
Ordering fuel oil
Fuel oil quality
Vitoladens appliances are approved for the combustion of low sulphur fuel oil to
DIN 51603-EL-1 (max. sulphur content
50 ppm).
A condensate neutralising system is not required (according to Code of Practice
ATV-DVWK-A 251 [Germany]) when using this low sulphur fuel.
Fuel oil additives
Fuel oil additives are materials that can be used providing they offer the following characteristics:
■ Improvement of stability during fuel storage.
■ Increase in the thermal stability of the fuel.
■ Reduction of odour development during filling.
!
Please note
Fuel oil additives can create residues and impair the safe operation of your heating system.
The use of fuel oil additives that leave residues is not permissible.
Combustion improvers
Combustion improvers are additives for optimising fuel oil combustion.
Viessmann oil burners do not require combustion improvers, as these burners operate with clean and efficient combustion.
!
Please note
Combustion improvers can create residues and impair the safe operation of your heating system.
The use of combustion improvers that leave residues is not permissible.
Biofuels
Biofuels are made from vegetable oil, e.g. sunflower or rape seed oil.
!
Please note
Biofuels can lead to damage on
Viessmann oil burners.
Their use is not acceptable.
If in doubt refer to your local heating contractor.
Menu overview
Extended menu
50
Appendix
Menu overview
(cont.)
Party mode Economy mode Heating time program Holiday program Heating curve
Heating and DHW Only DHW Standby mode
Set DHW temperature DHW time prog
Detailed scan options see following page
General Heating circuit 1 HC1 Heating circuit 2 HC2 DHW Solar
Time / Date Language DE Brightness Temperature unit Name for heating circ. Standard menu
51
Appendix
Menu overview
(cont.)
Scanning options in the extended menu
Note
Subject to the actual heating system equipment level, not all of the scans listed here may be available.
You can view more details on information marked .
General
"Outside temp"
"Boiler temperature"
"Flue gas temp"
"Sensor 9"
"Burner"
"Hours run"
"Burner stage 1"
"Hours run"
"Burner stage 2"
"Hours run"
"Fuel consumpt."
"Feed pump"
"Block 3rd pty dev"
"Central fault mess."
"Subscriber no."
"Input ext. EA1"
"Time"
"Date"
"Radio clock signal"
Heating circuit 1 (HC1)
"Heating program"
■ "Screed function"
■ "External hook-up"
■ "Holiday program"
■ "External program"
■ "Party mode"
■ "Economy mode"
■ "Heating and DHW"
■ "Only DHW"
■ "Standby mode"
"Operating status:"
■ "Standard heating mode"
■ "Reduced mode"
■ "Standby mode"
"Time program"
"Set room temperature"
"Room temperature"
"Set reduced room temp"
"Set ext. room temp"
"Set party temp"
"Slope"
"Level"
"Heating circ pump"
"Holiday program"
52
Appendix
Menu overview
(cont.)
Heating circuit 2, 3 (HC2, HC3)
"Heating program"
■ "Screed function"
■ "External hook-up"
■ "Holiday program"
■ "External program"
■ "Party mode"
■ "Economy mode"
■ "Heating and DHW"
■ "Only DHW"
■ "Standby mode"
"Operating status:"
■ "Standard heating mode"
■ "Reduced mode"
■ "Standby mode"
"Time program"
"Set room temperature"
"Room temperature"
"Set reduced room temp"
"Set ext. room temp"
"Set party temp"
"Slope"
"Level"
"Heating circ pump"
"Mixer"
"Flow temperature"
"Holiday program"
Terminology
Setback mode (reduced heating mode)
See "Reduced heating mode".
DHW
"DHW time prog"
"DHW circ time prog"
"DHW temperature"
"Cylinder prim pump"
"DHW circ pump"
Solar
"Collector temp"
"Solar DHW"
"Solar circuit pump"
"Solar energy history"
"Solar energy"
"Solar circuit pump"
"Solar circ pump speed"
"Heating suppr. DHW"
"SM1 output 22"
"SM1 output 22"
"Sensor 7"
"Sensor 10"
"Heat suppr. heating"
Building drying
Your heating contractor can, for example, enable the "Screed function" for your new installation or fitting for building drying. With the screed function, your screed is dried in line with the building material according to a fixed time program (temperature/time profile).
53
Appendix
Terminology
(cont.)
The screed function affects the heating circuits with a mixer:
■ All rooms are heated according to the temperature/time profile.
Your settings for central heating have no effect for the duration of the building drying.
■ DHW heating is carried out (but priority control is cancelled).
Heating program
The heating program determines whether you heat your rooms and DHW, or only heat DHW, or whether you shut down your heating system with frost protection monitoring.
You can select the following heating programs:
■ "Heating and DHW"
The rooms are heated and DHW is provided (winter mode).
■ "Only DHW"
DHW is provided but there is no central heating (summer mode).
■ "Standby mode"
Frost protection for the boiler and the
DHW cylinder is enabled, no central heating, no DHW heating.
Note
No heating program is available for central heating without DHW heating. When you want central heating, hot water is generally also required (winter mode).
If you do want just central heating, select the heating program "Heating and
DHW" and set the DHW temperature to
10 °C (see chapter "Setting the DHW temperature"). This means that you will not heat DHW unnecessarily but the
DHW cylinder is protected against frost.
54
Operating status
In the heating program "Heating and
DHW", the operating status changes from "Standard heating mode" (see
page 56) to the operating status
"Reduced heating mode" (see
page 57) and vice versa. The times for
the operating status change are defined when the time program is set.
Extension kit for heating circuit with mixer
Assembly (accessory) for controlling a heating circuit with mixer.
See "Mixer".
Heating curve
Heating curves illustrate the relationship between the outside temperature, room temperature (set value) and boiler water or (heating circuit) flow temperature. The lower the outside temperature, the higher the boiler water temperature or heating circuit flow temperature.
In order to guarantee sufficient heat and minimum fuel consumption at any outside temperature, the conditions of your building and your heating system must be taken into consideration. The heating curve is set by your heating contractor for this purpose.
Note
If your heating system includes heating circuits with mixers, then the flow temperature for the heating circuit without mixer is higher by a selected differential than the flow temperature for the heating circuits with mixer.
Appendix
Terminology
(cont.)
The illustrated heating curves apply with the following settings:
■ Heating curve level = 0
■ Standard room temperature (set value) = 20 ºC
35
Slope
110
100
50
Boiler water or flow temperature in °C
40
30
90
80
70
60
20
15
10
10
5
5
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
C
B
A
0 -5 -10 -15 -20 -25 -30
Outside temperature in °C
Example:
For outside temperature
−14 °C:
A Underfloor heating system, slope
0.2 to 0.8
B Low temperature heating system, slope 0.8 to 1.6
C Heating system with a boiler water temperature in excess of 75 °C, slope 1.6 to 2.0
55
Appendix
Terminology
(cont.)
Factory settings: slope = 1.4 and level =
0.
110
3.5
Boiler water or flow temperature in °C
+20
A
-20
B
Outside temperature in °C
1.4
0.2
A Changing the slope:
The steepness of the heating curve changes.
B Changing the level:
The heating curves are shifted in parallel in a vertical direction.
Heating circuit
A heating circuit is a sealed circuit between the boiler and radiators, in which the heating water circulates.
A heating system may comprise several heating circuits. For example, one heating circuit for the rooms occupied by you and one heating circuit for the rooms of a separate apartment.
Heating circuit pump
Circulation pump for the circulation of the heating water in the heating circuit.
Actual temperature
Current temperature at the time of the scan; e.g. actual DHW temperature.
Mixer
A mixer mixes the water heated in the boiler with the cooled water returning from the heating circuit. The water, heated to the right temperature in line with demand, is delivered to the heating circuit by the heating circuit pump. The control unit adjusts the heating circuit flow temperature via the mixer to the various conditions, e.g. different outside temperature.
Night setback
See "Reduced heating mode".
Standard heating mode
When you are in the house during the day, you can heat the rooms in standard heating mode. Set the periods using the time program for central heating. During these times, the rooms are heated to the standard room temperature.
Standard room temperature
Set the standard room temperature when you are at home during the day
(see chapter "Setting the room temperature").
Open flue operation
The combustion air is drawn from the room where the boiler is installed.
56
Appendix
Terminology
(cont.)
Balanced flue operation
The combustion air is drawn from outside the building.
Reduced heating mode
When you are out or during the night, you can heat the rooms in reduced heating mode (setback mode). Set the periods using the time program for central heating. During these times, the rooms are heated to a reduced room temperature.
Reduced room temperature
When you are out or during the night, set the reduced room temperature (see chapter "Setting the room temperature").
See also "Reduced heating mode".
Safety valve
A safety device that must be installed by your heating contractor in the cold water pipe. The safety valve opens automatically to prevent excess pressure in the
DHW cylinder.
Solar circuit pump
In conjunction with solar thermal systems.
The solar circuit pump delivers the cooled heat transfer medium from the
DHW cylinder indirect coil to the collectors.
Set temperature
Default temperature that should be reached; e.g. set DHW temperature.
Summer mode
Heating program "Only DHW".
At warmer times of the year, i.e. when the rooms do not have to be heated, you can disable heating mode. The boiler remains enabled for DHW heating.
Cylinder primary pump
Circulation pump for heating the DHW in the DHW cylinder.
Potable water filter
A device that removes solids from the water. The drinking water filter is installed in the cold water pipe upstream of the
DHW cylinder or the instantaneous water heater.
Weather-compensated mode
In weather-compensated mode, the heating flow temperature is controlled according to the outside temperature.
This means that no unnecessary heat is generated in order to heat the rooms to the set room temperature you selected.
The outside temperature is captured and transmitted to the control unit by a sensor fitted outside the building.
DHW circulation pump
The DHW circulation pump transfers the hot water around a circuit between the
DHW cylinder and the draw-off points
(e.g. hot tap). This makes hot water available quickly at the draw-off point.
57
Keyword index
Keyword index
A
Activating
■ Standby mode................................26
■ Summer mode................................26
Actual temperature.............................56
Additives for fuel oil............................50
B
Balanced flue operation.....................57
Biofuels..............................................50
Building drying.............................21, 53
C
Central heating
■ Deleting a time phase.....................25
■ Disabling.........................................26
■ Factory setting..................................6
■ Heating program.......................12, 23
■ Required settings............................21
■ Room temperature....................12, 22
■ Selecting a heating circuit...............21
■ Start................................................21
■ Starting...........................................12
■ Time program.................................24
Cleaning.............................................48
Cleaning information..........................48
Cold rooms.........................................44
Combustion improvers.......................50
Comfort function.................................27
Commissioning..............................6, 19
Controls................................................9
■ Type KO1B.....................................17
■ Type KO2B.....................................18
■ Type KW6B....................................18
Controls locked out............................47
Controls with the cover open.............17
Cylinder primary pump.......................57
D
Date...............................................6, 37
Day temperature (standard room temperature)........................................6, 12
DHW circulation pump
■ Deleting a time phase.....................34
■ Time program.................................33
DHW heating
■ DHW temperature...........................31
■ Factory setting..................................6
■ Heating program.............................31
■ Required settings............................31
■ Starting...........................................31
■ Switching off...................................34
■ Time program.................................32
■ Time program, DHW circulation pump...............................................33
DHW heating outside of the time program...................................................33
Display elements................................13
■ Type KO1B.....................................17
■ Type KO2B.....................................18
■ Type KW6B....................................18
Display illumination............................35
E
Economy mode
■ Ending............................................29
■ Starting...........................................28
Emissions test mode..........................43
Ending
■ DHW heating..................................34
■ Economy mode...............................29
■ Holiday program.............................30
Extended menu
■ Control............................................13
■ Menu structure................................50
Extension kit.......................................54
External hook-up................................47
External program...............................47
F
Factory setting.....................................6
Fault display.......................................13
58
Keyword index
Keyword index
(cont.)
Fault message
■ Acknowledging...............................41
■ Calling up (acknowledged).............42
■ Display............................................47
■ Scanning.........................................41
Filter...................................................57
Frost protection monitoring................................6, 13, 19, 26, 34
Fuel oil
■ Additives.........................................50
■ Ordering..........................................50
■ Quality............................................50
Further settings..................................37
G
Glossary.............................................53
H
Heating and DHW................................6
Heating circuit....................................56
Heating circuit designation.................35
Heating circuit pump..........................56
Heating circuit with mixer...................54
Heating curve
■ Explanation.....................................54
■ Setting............................................25
Heating mode
■ Reduced...................................22, 57
■ Setting......................................12, 23
■ Standard...................................22, 56
Heating only.......................................34
Heating program
■ Central heating.........................12, 23
■ DHW heating..................................31
■ DHW only.......................................57
■ Heating and DHW...........................12
■ Only DHW.......................................12
■ Standby mode................................12
■ Terminology....................................54
Heating system
■ Shutting down.................................19
■ Starting...........................................18
Heating times.....................................24
Heating without DHW heating............34
Holiday program
■ Deleting..........................................30
■ Starting...........................................29
■ Terminating.....................................30
Hot rooms..........................................45
Hot water............................................47
How to use the controls.....................14
I
Inspection...........................................48
K
Keys...................................................11
L
Language selection............................37
Level............................................25, 54
M
Maintenance......................................48
Maintenance contract.........................48
Menu
■ Extended menu..............................13
■ Standard menu...............................12
■ Structure.........................................50
■ Where to find the controls...............11
Mixer..................................................56
Modifying the boiler heating characteristics......................................................25
N
Names for the heating circuits...........35
Night setback.....................................56
Night temperature (reduced room temperature)..............................................6
No hot water.......................................46
Notice of completion............................6
O
ON/OFF switch..................................19
Open flue operation...........................56
Opening the control unit.......................9
59
Keyword index
Keyword index
(cont.)
Operating procedure..........................14
Operating status.................................54
Operation.............................................9
■ Controls............................................9
■ Menu...............................................11
■ Sequence.......................................14
Ordering oil........................................50
P
Party mode
■ Ending............................................28
■ Starting...........................................27
Potable water filter.............................57
Power failure........................................7
Pressure gauge..................................18
Programming unit.................................9
Pump
■ Cylinder..........................................57
■ DHW circulation..............................57
■ Heating circuit.................................56
■ Solar circuit.....................................57
R
Reduced heating mode..................6, 57
Reduced room temperature.........22, 57
Remote control.....................................9
Repair work........................................48
Reset..................................................37
Resetting data....................................39
Resetting fuel consumption................39
Resetting hours run............................39
Restoring factory settings..................37
Rooms too cold..................................44
Rooms too hot....................................45
Room temperature
■ Setting for standard heating mode. 12
S
Safety valve.......................................57
Saving energy
■ Economy mode...............................28
■ Holiday program.............................29
■ Tips...................................................7
60
Scan
■ Fault message................................41
■ Information......................................39
■ Operating conditions.......................39
■ Service message............................40
■ Solar thermal system......................39
■ Temperatures.................................39
Scanning information.........................39
Scanning operating conditions...........39
Scanning the actual temperature.......39
Screed function............................21, 53
Screen saver......................................14
Selecting a heating circuit..................21
Service display...................................13
Service message
■ Acknowledging...............................40
■ Calling up (acknowledged).............41
■ Display............................................47
■ Scanning.........................................40
Setback mode..............................53, 57
Set temperature.................................57
Setting programs
■ For central heating..........................24
■ For DHW circulation pump.............33
■ For DHW heating............................32
Settings
■ For central heating....................12, 21
■ For DHW heating............................31
Setting the brightness........................35
Setting the contrast............................35
Setting the DHW temperature............31
Setting the room temperature
■ For reduced heating mode.............22
■ For standard heating mode............22
Shutdown...........................................19
Shutting down
■ Heating system with frost protection monitoring.......................................19
■ Heating system without frost protection monitoring................................19
Slope............................................25, 54
Solar circuit pump..............................57
Solar energy.......................................39
Keyword index
Keyword index
(cont.)
Standard heating mode............6, 22, 56
Standard menu
■ Changing........................................36
■ Control............................................12
Standard room temperature (day temperature)..................................6, 12, 22
Standard settings...............................37
Standby mode..................19, 26, 34, 54
Start
■ Central heating...............................21
Starting
■ Central heating...............................12
■ Comfort function (party mode)........27
■ DHW heating..................................31
■ Energy saving function...................29
■ Energy saving function (economy mode).............................................28
■ Frost protection monitoring.............19
■ Heating system...............................17
■ Standby mode................................19
Starting the appliance........................18
Summer mode.......................26, 54, 57
Summertime changeover.....................6
Switching off
■ Comfort function.............................28
■ DHW heating..................................34
■ Economy mode...............................29
■ Holiday program.............................30
Switching OFF
■ Central heating...............................26
Symbols on the display......................13
T
Temperature
■ Actual temperature.........................56
■ DHW...............................................31
■ Reduced room temperature............22
■ Scanning.........................................39
■ Set temperature..............................57
■ Standard room temperature.....12, 22
Temperature unit................................37
Terminology.......................................53
Test mode..........................................43
Time...............................................6, 37
■ DHW circulation pump....................33
■ DHW heating..................................32
■ Heating times..................................24
Time phase
■ Central heating, deleting.................25
■ DHW circulation pump, deleting.....34
■ DHW heating, deleting....................33
■ Setting central heating....................24
■ Setting DHW heating......................32
■ Setting the DHW circulation pump..33
Time program
■ For central heating............................6
■ For DHW circulation pump...............6
■ For DHW heating..............................6
■ Setting central heating....................24
■ Setting DHW heating......................32
■ Setting the DHW circulation pump..33
Troubleshooting.................................44
W
Water too cold....................................46
Water too hot.....................................47
Weather-compensated mode.............57
Where to find the controls....................9
Winter mode.......................................54
Wintertime/summertime changeover...6
Wintertime changeover........................6
61
62
63
Applicability
Serial No.:
7441800
Your contact
7441802 7452520
Contact your local contractor if you have any questions regarding the maintenance and repair of your system. You may, for example, find local contractors on the internet under www.viessmann.com.
Viessmann Werke GmbH&Co KG
D-35107 Allendorf
Telephone: +49 6452 70-0
Fax: +49 6452 70-2780 www.viessmann.com
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Telephone: +44 1952 675000
Fax: +44 1952 675040
E-mail: [email protected]
64
advertisement
Key Features
- Weather-compensated control
- Central heating & DHW
- Programmable heating schedule
- Comfort and energy saving functions (Economy, Party, Holiday)
- Frost protection
- Remote control (optional)
Frequently Answers and Questions
How do I start the heating system?
How do I set the room temperature?
How do I program the heating schedule?
What are the comfort and energy-saving functions?
How do I protect the system from frost?
Related manuals
advertisement
Table of contents
- 1 Operating instructions
- 1 Vitotronic 200
- 2 Safety instructions
- 4 Index
- 6 Introductory information
- 6 Commissioning
- 6 Your system is preset at the factory
- 7 Terminology
- 7 Tips on saving energy
- 9 Operation
- 9 Operation
- 9 Opening the control unit
- 11 Programming unit
- 11 Menu
- 12 Standard menu
- 13 Extended menu
- 14 How to use the controls
- 17 Start-up/shutdown
- 17 Starting the heating system
- 19 Shutting down the heating system
- 19 With frost protection monitoring
- 19 Without frost protection monitoring (shutdown)
- 21 Central heating
- 21 Required settings (central heating)
- 21 Selecting a heating circuit
- 22 Setting the room temperature
- 22 Setting the room temperature for standard heating mode
- 22 Setting the room temperature for reduced heating mode (night setback)
- 23 Setting the heating program for central heating
- 24 Setting the time program for central heating
- 25 Changing the heating curve
- 26 Switching OFF central heating
- 27 Comfort and energy saving functions
- 27 Selecting comfort function "Party mode"
- 28 Selecting energy saving function "Economy mode"
- 29 Selecting energy saving function "Holiday program"
- 31 DHW heating
- 31 Required settings (DHW heating)
- 31 Setting the DHW temperature
- 31 Setting the heating program for DHW heating
- 32 Setting the time program for DHW heating
- 33 Heating system with DHW circulation pump
- 34 Switching OFF DHW heating
- 35 Further adjustments
- 35 Setting the display contrast
- 35 Setting the display brightness
- 35 Entering names for the heating circuits
- 36 Changing the standard menu
- 37 Setting the time and date
- 37 Language selection
- 37 Setting the temperature unit (°C/°F)
- 37 Restoring factory settings
- 39 Scanning
- 39 Scanning information
- 40 Scanning the service messages
- 41 Scanning fault messages
- 43 Emissions test mode
- 44 What to do if...
- 44 Rooms are too cold
- 45 Rooms are too hot
- 46 There is no hot water
- 47 The DHW is too hot
- 47 ã flashes and "Fault" is displayed
- 47 ë flashes and "Service" is displayed
- 47 "Controls locked out" is displayed
- 47 "External hook-up" is displayed
- 47 "External program" is displayed
- 48 Repair work
- 50 Appendix
- 50 Ordering fuel oil
- 50 Menu overview
- 50 Extended menu
- 52 Scanning options in the extended menu
- 53 Terminology
- 58 Keyword index