Azbil KUX113 I/P Converter User's Manual

Azbil KUX113 I/P Converter User's Manual
Add to My manuals

The KUX113 is a field installation type of instrument that converts an electric current signal of 4 to 20mA DC into a pneumatic pressure signal of 0.2 - 1.0 kgf/cm2 (or other unit of measure). It can be installed on a 2-inch pipe stanchion using a standard type of mounting bracket.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Azbil KUX113 Field-Type I/P Converter User's Manual | Manualzz

Field-Type I/P Converter

Model : KUX113

User's Manual

OM2-5900-1130

Copyright, Notices and Trademarks

1994-2012 Azbil Corporation All Rights Reserved.

While this information is presented in good faith and believed to be accurate,

Azbil Corporation disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customer.

In no event is Azbil Corporation liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.

Table of Contents

Chapter 1 : General

External view.................................................................................................................................. 1-1

Accessories.................................................................................................................................... 1-1

1-1 : Description............................................................................................................................. 1-2

1-2 : Structure and Features .......................................................................................................... 1-2

Chapter 2 : Specifications

2-1 : Performance Specifications ................................................................................................... 2-1

2-2 : Model Number Table ............................................................................................................. 2-2

2-3 : Dimension Drawings.............................................................................................................. 2-3

Chapter 3 : Operating Principle

Chapter 4 : Installation

4-1 : Installation Method................................................................................................................. 4-1

4-2 : Environmental Conditions...................................................................................................... 4-2

4-3 : Customer Connections .......................................................................................................... 4-2

Electrical Connections ....................................................................................................... 4-2

Air Connections ................................................................................................................. 4-2

Chapter 5 : Operation Procedure

Chapter 6 : Calibration

Chapter 7 : Maintenance

7-1 : Cleaning the Pilot Relay Port and Seat ................................................................................. 7-1

7-2 : Cleaning the Restriction for Nozzle Back-pressure ............................................................... 7-2

7-3 : Notes on Installing the Pilot Relay ......................................................................................... 7-2

7-4 : Cleaning the Nozzle............................................................................................................... 7-2

Chapter 8 : Bypass Manifold

8-1 : A/M Switching ........................................................................................................................ 8-2

8-2 : Switchover Procedures and Functions .................................................................................. 8-2

Switchover from Auto (A) to Manual (M)............................................................................ 8-2

Service Position ................................................................................................................. 8-2

Switchover from Manual (M) to Auto (A)............................................................................ 8-2

Chapter 9 : Handling Procedure for A/M Switch (Pipingless type)

9-1 : Setting the A/M Switch........................................................................................................... 9-1

9-2 : Verifying the A/M Switch........................................................................................................ 9-1

List of Figure

Figure 1-1

Figure 1-2

Figure 2-1

Figure 3-1

Figure 4-1

Figure 4-2

Figure 4-3

Figure 6-1

Figure 6-2

Figure 6-3

Figure 7-1

Figure 7-2

Figure 7-3

Figure 8-1

Figure 8-2

Figure 9-1

External view ............................................................................................................... 1-1

Accessories .................................................................................................................. 1-1

Dimension drawings .................................................................................................... 2-3

Block diagram of I/P converter.................................................................................... 3-1

Examples of installation positions ............................................................................... 4-1

Location of exhaust port .............................................................................................. 4-1

Locations of air connectors .......................................................................................... 4-2

Layout of components.................................................................................................. 6-1

Calibration setup .......................................................................................................... 6-1

Location of ZERO control hole ................................................................................... 6-2

Removing the pilot relay.............................................................................................. 7-1

Port and seat of pilot relay ........................................................................................... 7-1

Location of the restriction ............................................................................................ 7-2

Bypass setup................................................................................................................. 8-1

Bypass mechanism....................................................................................................... 8-1

...................................................................................................................................... 9-1

Azbil Corporation

Chapter 1 : General

External view

Pilot relay (rear panel)

Casing

Accessories

Hole for U-bolt

Bracket

Mounting holes for meter body

Terminal box

Figure 1-1 External view

U-bolt

L-wrench

Nut

Bolts

Figure 1-2 Accessories

Mounting bracket (1),

U-shape bolt (1), bolts (4), nuts (2)

KUX113 - Field-Type I/P Converter 1-1

General Azbil Corporation

1-1 : Description

The model KUX113 Field-type I/P Converter is a field installation type of instrument

(to be installed on a 2-inch pipe stanchion). It converts an electric current signal of 4 -

20mA DC into a pneumatic pressure signal of 0.2 - 1.0 kgf/cm

2

(or other unit of measure).

1-2 : Structure and Features

The KUX113 I/P Converter is comprised of a casing (in which the converter mechanism is directly installed), a pilot relay and a cover. The KUX113 can be installed on a

2-inch pipe stanchion employing a standard type of mounting bracket (which is identical to those used for other DSTJ3000 filed-type instruments).

The protective feature of a water splashproof casing, a flameproof enclosure, or of an intrinsic safety barrier.

The water splashproof casing complies with of JIS F8001 Class 3 requirements.

For the flameproof type, frameproof structure consists of the terminal box and magnet unit. These structures allow you to open the cover of the casing to maintain even while the instrument is operating in a hazardous area.

The intrinsic safety barrier type of instrument employs two spark killer diodes connected in parallel to the coil in the magnet section, in conjunction with a barrier.

If a bypass manifold is provided, the Converter can use manually produced signals as its outputs.

1-2 KUX113 - Field-Type I/P Converter

Azbil Corporation

Chapter 2 : Specifications

2-1 : Performance Specifications

Table 2-1 Performance specifications

Item Specifications

Input signal

4 to 20mA DC (Maximum allowable current approx.

30mA.)

250 ohms maximum

Input resistance

Output signal

20 to 100 kPa, 3 to 15 psi, 0.2 to 1.0 bar, 0.2 to 1.0 kgf/cm

2

(Maximum allowable pressure 200kPa)

Air supply pressure

140 kPa {1.4 kgf/cm

2

} ±10%

Air consumption

4 l/min(N) (With output 50% balanced)

Maximum air supply capacity

110 l/min(N)

Maximum air exhaust capacity 110 l/min(N)

Minimum load capacity

I.D. 4 mm copper tube × 3 m + 20 cc

AIr piping connections

Rc1/4, 1/4NPT internal thread

Electrical conduit connection

G1/2 internal thread

Material of major components Aluminum alloy

Operating temperature range

Waterproof, dust proof type: -30 to +80°C

Operating humidity range

Accuracy

Linearity

(with reference to zero)

Flame-proof type explosionproof type: -10 to +70°C

Intrinsic-safety explosionproof type: -10 to +60°C

10 to 90% RH

± 0.5% F.S.

± 0.2% F.S.

Hysteresis error

Reproducibility

Dead band

Temperature effect

Mounting

Net weight

Finish and color

< 0.5% F.S.

< 0.4% F.S.

< 0.05% F.S.

Zero shift: ±3% F.S. /30°C (Maximum)

Span shift: ±2% F.S. /30°C (Maximum)

2-inch pipe (Horizontal of vertical)

Approx. 3 kg

Finish: Acrylic baked finish

Construction

Color: Case; Dark beige, Cover; Black PPS resin, Terminal box cover; Light beige

Waterproof, dust proof type: JIS C 0920 Watertight, JIS F

8001 Class 3 Splashproof

Flame-proof type explosionproof type: JIS C 0903, d2G4

(Operating temperature -10 to +70°C)

Intrinsic-safety explosionproof type: JIS C 0903, i3aG5

(Operating temperature: -10 to +60°C, signal power supply: 23 to 27.5V DC)

KUX113 - Field-Type I/P Converter 2-1

Specifications

2-2 : Model Number Table

Selections

Basic model no.

KUX113

-X

W

E

H

1

Azbil Corporation

Description

3

4

1

2

A

B

B

D

X

A

Filed-type I/P converter not necessary

Waterproof (JIS)

Flame-proof type explosionproof (JIS)

Intrinsic-safety explosionproof (JIS)

Input 4 to 20mA DC

Output 0.2 to 1.0 kgf/cm2

Output 3 to 15 psi

Output 0.2 to 1.0 bar

Output 20 to 100 kPa

Air pressure connections Rc1/4

Air pressure connections 1/4NPT

Standard

Corrosion-resistant paint

Heavy-corrosion-resistant paint

Silver finish

-X

No options

-P

With flameproof-packing-type cable connecting adapter

-G

With output air pressure gauge

-6

With by-pass set (on special order)

-7

WIth air set

-J

With elbow for flame-proof type explosionproof

2-2 KUX113 - Field-Type I/P Converter

Azbil Corporation

2-3 : Dimension Drawings

Specifications

Figure 2-1 Dimension drawings

KUX113 - Field-Type I/P Converter 2-3

Specifications Azbil Corporation

2-4 KUX113 - Field-Type I/P Converter

Azbil Corporation

Chapter 3 : Operating Principle

The electrical input signal (current signal) is converted by the magnet unit into a mechanical force which causes the beam position to change. The change in beam position is converted by the nozzle/flapper mechanism into a pneumatic signal, which is boosted by the pilot relay into the pneumatic output signal. The pneumatic output signal is fed back via the feedback bellows to the beam, thereby attaining a state of equilibrium. Thus, the electrical input signal is converted into a pneumatic output signal, which is directly proportional to the input signal.

Air supply

Input

Magnet unit

Force

+

-

Beam

Position

Nozzle/ flapper

Pneumatic pressure

Bellows

Figure 3-1 Block diagram of I/P converter

Pilot relay

Pneumatic pressure

Output

KUX113 - Field-Type I/P Converter 3-1

Operating Principle Azbil Corporation

3-2 KUX113 - Field-Type I/P Converter

Azbil Corporation

Chapter 4 : Installation

4-1 : Installation Method

(1) The mounting holes are drilled through the rear panel of the casing as shown in

Figure 4-2. Fix the bracket (supplied) to the casing with the four bolts. Select an

appropriate mounting position according to the direction of the 2-inch pipe stanchion.

(2) Hook the U-shape bolt onto the 2-inch pipe stanchion and pass its ends through the bracket holes and fix the ends securely with the nuts.

.

Figure 4-1 Examples of installation positions

(3) The I/P Converter should be installed vertically as shown in Figure 2-1. Note that

the exhaust port of the pilot relay must face downward. To position the exhaust port downward, loosen the screw of the cover and rotate the cover. The location of the exhaust port is labelled on the surface of the cover.

Hole for bolt

Marking

Exhaust port

Figure 4-2 Location of exhaust port

KUX113 - Field-Type I/P Converter 4-1

Installation Azbil Corporation

4-2 : Environmental Conditions

The place of installation must be within the specified temperature and humidity range

(See Chapter 2 :Specifications) and must be reasonably free from mechanical vibra-

tion.

For an explosionproof type of instrument, fasten the terminal box cover with the lock screw after installing the cover. Install the instrument observing all applicable explosionproof instrument installation standards and recommendations.

4-3 : Customer Connections

Electrical Connections

Connect the electrical input signal to the “+” and “-” terminals in the terminal box. The terminals have binding screws (M4, 6mm). For earth grounding, connect the “-” terminal to the “E” terminal.

The instrument has no internal fuse or switch. Provide them externally (if possible a wiring block should be used).

Air Connections

Two air connectors (Rc1/4 or 1/4NPT internal thread) are provided near the pilot valve. Remove the caps and connect the air supply piping to the SUP connector and the output air pressure piping to the OUT connector.

The supply air must be clean. Provide it via an Airset (a regulator and a filter). The air supply pressure must be 140 kPa {1.4 kgf/cm

2

}

OUT

SUP

Figure 4-3 Locations of air connectors

4-2 KUX113 - Field-Type I/P Converter

Azbil Corporation

Chapter 5 : Operation Procedure

After the I/P Converter has been installed and electrical wiring and air piping have been completed, it is ready for operation. Provide the air supply.

KUX113 - Field-Type I/P Converter 5-1

Operation Procedure Azbil Corporation

5-2 KUX113 - Field-Type I/P Converter

Azbil Corporation

Chapter 6 : Calibration

Nozzle block clamping-screws

Zero control wheel

Beam

Nozzle

Flapper Magnet unit

Feedback bellows

Span control slit

Figure 6-1 Layout of components

(1) Connect an air supply to the SUP connector and a precision air pressure gauge to the OUTPUT connector.

(2) Connect a precision electrical signal source (4 - 20mA DC) to the electrical input terminals.

I/P Converter

OUT SUP

Constant-current source (4 - 20mA DC)

IN

140 kPa

Airset

Air supply

Precision pressure gauge

20 cc

Volume tank

Figure 6-2 Calibration setup

KUX113 - Field-Type I/P Converter 6-1

Calibration Azbil Corporation

(3) Feed a current signal of 4mA from the constant-current source. Adjust the ZERO control wheel so that the output pressure become 20 kPa {0.2 kgf/cm

2

}±0.25%.

The output pressure rises as you turn the wheel couterclockwise as viewed from

the top in the attitude shown in Figure 6-1.

(4) Feed a current signal of 20mA from the constant-current source. Adjust the SPAN control by inserting a screwdriver into the SPAN control slit so that the output pressure becomes 100 kPa {1.0 kgf/cm2} 0.25%. The output span becomes wider

as you move the screw driver to the right as viewed in the attitude shown in Figure

6-1.

(5) Repeat step (3) and (4) until the required zero and span accuracies are obtained.

The ZERO control is also adjustable externally.

Hole for control

Hole for zero control

Screws

6-2

Figure 6-3 Location of ZERO control hole

To gain access to the ZERO control hole, loosen the two screws of the cap near the nameplate on the casing, then side it downward.

~Note

If you have removed the cap by mistake, exercise care not to misplace the

O-ring of the ZERO control hole.

KUX113 - Field-Type I/P Converter

Azbil Corporation

Chapter 7 : Maintenance

Normally the I/P Converter requires no maintenance service. However, if the I/P Converter is operated in adverse conditions (such as in environments prone to dust), disassemble the pilot relay and clean the restriction hole (employing a steel wire of 0.27 mm dia.) and the port and seat (employing a soft cloth). If the output pressure has become abnormally high and cannot be lowered, clean the nozzle with a steel wire of

0.6 mm dia. To do this, remove the nozzle block. (See Figure 6-1)

7-1 : Cleaning the Pilot Relay Port and Seat

(1) Remove the pilot relay cover by loosening its screws.

Pilot relay clamping-screws

(three)

Plate

(Gasket on both sides*)

*: Mark “C” is visible at gasket indent.

Figure 7-1 Removing the pilot relay

(2) Detach the pilot relay by removing its three clamping-screws.

Remove the leaf spring from the bottom of the pilot relay by loosening its two screws, and then take out the port.

Leaf spring

Port

Leaf spring

Screws

Figure 7-2 Port and seat of pilot relay

Seat plane

(Another plane deeper inside)

Port seat plane

KUX113 - Field-Type I/P Converter 7-1

Maintenance Azbil Corporation

(3) Clean the seating planes. There are two seating planes to be cleaned - one at the front and another deeper inside the hole. To clean the deeper seat plane, use a cloth formed into a bar shape.

7-2 : Cleaning the Restriction for Nozzle Back-pressure

To gain access to the restriction for the nozzle back-pressure, proceed as follows:

Remove the pilot relay. Now the plate which is sandwiched between the two gaskets is accessible. The restriction is located in the center of the plate.

Gasket

Pilot relay

Figure 7-3 Location of the restriction

Base plate

Restriction

7-3 : Notes on Installing the Pilot Relay

Install the pilot relay by following the two guide pins and exercising care not to damage the two gaskets. Position the gasket so that its indentation is aligned with the “C” mark on the plate. A circlet mark is provided on the side of the pilot relay to facilitate positioning. Align the circlet to the position of the OUT connector.

7-4 : Cleaning the Nozzle

To clean the nozzle, detach the nozzle block by loosening its two clamping-screws

(see Figure 6-1).

7-2 KUX113 - Field-Type I/P Converter

Azbil Corporation

Chapter 8 : Bypass Manifold

This chapter is for the Bypass Manifold which is installed on a I/P Converter. The

Bypass Manifold is comprised of an Airset and an air switching mechanism, and allows the selection between an auto (A) position, a manual (M) position, and a ser-

vice position. A bypass setup is shown in Figure 8-1 and the manifold mechanism is shown in Figure 8-2.

Figure 8-1 Bypass setup

KUX113 - Field-Type I/P Converter

Figure 8-2 Bypass mechanism

8-1

Bypass Manifold Azbil Corporation

8-1 : A/M Switching

The bypass manifold is used when it is necessary to drive the control valve manually into the full open state or fully closed state (A/M position change).

When manually operating the control valve, it is recommended to change the manifold to the service position by means of the plug, in addition to the A/M position change.

(This is recommended as this will prevent hunting which could be caused when in the

M mode).

To return to the control valve to the manual mode, set the manifold to the A position.

8-2 : Switchover Procedures and Functions

Switchover from Auto (A) to Manual (M)

(1) Turn the fixing screw counterclockwise at the head of the hex cap nut with a screwdriver.

(2) Remove the hex cap nut by turning it counterclockwise.

(3) Push the plunger shaft into the manifold in the M direction until the shaft touches the stopper.

(4) Replace the hex cap nut at the M position.

When in manual, the I/P converter remains idle. The air supply adjusted by turning the knob of the Airset is fed to the actuator, allowing you to manually drive the control valve.

Service Position

To set the manifold to the service position from the manual (M) state, drive the stopper plug into the manifold with a screwdriver, until the plug touches the stopper. The service position basically is of an M state.

When in the service position, the I/P converter air supply is shut off. The control valve, however, can be driven manually the same as when the manifold is in manual.

Switchover from Manual (M) to Auto (A)

(1) If the stop plug has been set to the service position, rotate the plug by several turns counterclockwise with a screwdriver to allow the air supply to flow.

(2) Turn couterclockwise the fixing screw at the head of the hex cap nut with a screwdriver.

(3) Remove the hex cap nut by turning it counterclockwise.

(4) Push the plunger shaft into the manifold in the A direction until the shaft touches the stopper.

(5) Replace the hex cap nut at the A position.

When in auto the actuator is driven by the output of I/P converter.

The air supply for the converter is fed through the Airset.

Adjust its output pressure to obtain the required value.

8-2 KUX113 - Field-Type I/P Converter

Azbil Corporation

Chapter 9 : Handling Procedure for A/M Switch

(Pipingless type)

9-1 : Setting the A/M Switch

To set the A/M switch to the A (auto) or M (manual) mode, proceed as follows

Figure 9-1

(1) Loosen the clamping-screw of the plate and move the plate to a position where it grants you access to the A/M switch.

(2) If you want to change the A/M switch to the A mode, turn the A/M switch in the

“A” direction (counterclockwise) until it hits the stopper screw.

(3) If you want to change the A/M switch to the M mode, turn the A/M switch in the

“M” direction (clockwise) until it hits the stopper screw.

9-2 : Verifying the A/M Switch

To verify the setting of the A/M switch, proceed as follows:

(A) Verifying the A mode

(1) Be sure that the A/M switch has been set to the A mode.

(2) Set the pressure regulator output to 140 kPa {1.4 kgf/cm

2

}.

(3) Check and adjust overall operation of the I/P converter.

(B) Verifying for the M mode

(1) Be sure that the A/M switch has been set to the M mode.

(2) Set the pressure regulator output to 140 kPa {1.4 kgf/cm

2

}

(3) Check that the I/P converter output can be adjusted between a range of 0 to 140 kPa {1.4 kgf/cm

2

} by changing the pressure regulator output.

After setting and checking for the M mode of operation has been completed, return the

A/M switch to the A mode, and replace the plate to its original position and fix it securely with the clamping-screw. Finally, reset the pressure regulator output to 140 kPa {1.4 kgf/cm

2

}

KUX113 - Field-Type I/P Converter 9-1

Handling Procedure for A/M Switch (Pipingless type) Azbil Corporation

9-2 KUX113 - Field-Type I/P Converter

Document Number:

Document Name:

Date:

Issued/Edited by:

OM2-5900-1130

Field-Type I/P Converter

Model: KUX113

User's Manual

1st edition: Jun. 1994

7th edition: Sep. 2012

Azbil Corporation

advertisement

Key Features

  • Field installation type
  • Converts 4-20mA DC to pneumatic pressure
  • 2-inch pipe stanchion mounting
  • Water splashproof casing
  • Flameproof or intrinsic safety barrier options
  • Bypass manifold for manual operation
  • Accuracy: ±0.5% F.S.
  • Linearity: ±0.2% F.S.
  • Operating temperature: -30 to +80°C (waterproof type)

Frequently Answers and Questions

What is the input signal range of the KUX113 I/P Converter?
The input signal range is 4 to 20mA DC.
What is the output signal range of the KUX113 I/P Converter?
The output signal range is 0.2 to 1.0 kgf/cm2 (or other unit of measure).
How do I install the KUX113 I/P Converter?
The KUX113 can be installed on a 2-inch pipe stanchion using a standard type of mounting bracket. Refer to Chapter 4 of the User's Manual for detailed installation instructions.
How do I calibrate the KUX113 I/P Converter?
Refer to Chapter 6 of the User's Manual for detailed calibration instructions.
What are the environmental conditions for operating the KUX113 I/P Converter?
The operating temperature range is -30 to +80°C for the waterproof type, and -10 to +70°C for the flameproof type. The operating humidity range is 10 to 90% RH.