Interlogix 60 660 01 95R install manual
Quik Bridge Loop Receiver Installation
Instructions
•
Support for a piezo (used for RF testing only) which, when
used sounds the number of transmissions received from
learned transmitters.
•
®
Compatibility with X-10 Modules
•
On-board EEPROM that stores sensor IDs and
programming information in non-volatile memory, even if
power is removed.
Transmitter compatibility
All current Learn Mode™ sensors (319.5 MHz), panic button
transmitters, 2- and 4-button Keychain Touchpads.
Control panel compatibility
Product summary
The Quik Bridge Loop Receiver (receiver) allows you to use up
to 16 Learn Mode wireless sensors (two per zone) with any
standard hardwire control panel. In addition, you can use up to
45 Keychain Touchpads and panic button transmitters, for a
total of 61 wireless transmitters.
The receiver monitors the alarm, battery, tamper, and
supervisory status of transmitters learned into the receiver’s
eight zones.
•
The receiver features the following:
•
Spatial-diversity receiver, which enhances reception
•
8 programmable zone outputs (N/C or N/O)
•
Selectable zone supervision (programmable)
•
RF (radio signal) jam detection on zone 7 (optional).
•
Receiver cover/ antenna tamper on zone 8 (optional).
•
8 red zone LEDs, which indicate zone openings and
closings
•
2 yellow trouble LEDs, which indicate sensor low battery
and supervisory conditions
P/N 466-1568 • REV C • 22FEB11
The receiver is compatible with control panels designed with
hardwire loops where the loop negative is ground (commonloop ground).
Caution: The loop receiver is not directly compatible with
powered loops (2-wire smoke detector loops and glass break
detector loops). Connecting the receiver directly to a powered
loop can cause permanent damage to the receiver. You must
install a relay when connecting power loops (see Figure 13 on
page 9).
The following control panels (one or more versions) support a
common-loop ground for one or more of its loops. If your
control panel is not listed below, you can test it for compatibility
(see “Compatibility Testing” section below).
•
•
•
•
•
•
•
•
®
ADT SafeWatch
Ademco® 4110XM, Vista 10, Via 30P
®
C&K System 236
DSC® PC1550, DSC Power 832 PC5010
®
First Alert FA 1330C
®
Moose Z1100e
Napco® Magnum Alert 1008e/M
®
Radionics D9112B
1
Compatibility Testing
Tamper switch function
Typically, hardwire loops have the negative (-) side of the loop
common with ground. If this is true and the loop is nonpowered, the loop should be compatible with the receiver.
Although most control panels are compatible with the
receiver’s open collector outputs, each loop should be tested
for compatibility before connecting receiver outputs to the
control panel loop inputs.
Caution: If the receiver is not directly compatible with a control
panel loop, a relay must be used to avoid permanent damage
to the receiver.
To check if the negative side of the loop is common
to control panel ground, perform the following test:
1.
Turn off or remove control panel power and disconnect the
back-up battery.
2.
Use an ohm meter and measure the resistance between
the negative side of the loop and panel ground. If the
resistance is zero or close to zero, this loop should be
compatible with the loop receiver.
If the resistance is not zero, a relay is required for this
loop.
Perform this compatibility test for all loops that are to be
connected to the receiver.
In Run Mode
If no transmitters are learned into zone 8, the receiver’s tamper
switch is active. Tripping the tamper switch (by removing the
cover) or removing the antenna causes a tamper alarm on
zone 8.
If one or more transmitters are learned into zone 8, the tamper
feature is inactive and does not cause an alarm.
In Program Mode
While in program mode, pressing the tamper switch cycles
through three programming areas:
•
•
•
Learn/Delete Transmitters
Configuring Zone/Trouble Outputs N/O or N/C
Enabling/Disabling Zone Supervision
ADV and SEL Switches
These switches are used only when in program mode.
The ADV (advance) switch lets you cycle to the zone you want
to program.
The SEL (select) switch lets you select the zone or trouble
output for programming.
Outputs
Overview of receiver operation
DIP switch
A single DIP switch on the receiver board (see Figure 1 below)
controls the mode of operation. When the DIP switch is up, the
receiver is in program mode. When the DIP switch is down, the
receiver is in run mode.
The receiver uses open-collector transistors for the zone and
trouble outputs (see Figure 2 below). The outputs can be open
(high impedance) or closed (shorted to ground), which can be
configured to be normally closed (N/C) or normally open (N/O).
Each output can be wired to the control panel
Figure 2: Receiver terminal strip
Figure 1: Main components of the receiver
1
2
3
4
5
6
7
8
B
S
T GND GND +12V
Antenna
terminal block
Antenna
terminal
block
Select switch
Advance switch
Tamper switch
DIP switch
LEDs
Receiver
terminal strip
2
Zone Outputs
There are eight zone outputs labeled 1 through 8. When a
learned transmitter is activated, the corresponding zone output
switches to the alarm state and remains in alarm for at least 3
seconds, until the transmitter is restored to its non-alarm state.
(If the control panel connected to the receiver is armed, the
panel activates an alarm in response to the zone output
transition.)
Quik Bridge Loop Receiver Installation Instructions
Zone 7—Receiver Jam Detect: If no transmitters are learned
into zone 7, this output trips whenever the receiver detects a
jam condition. Receiver jamming occurs when the receiver
detects a constant signal for 30 seconds. The receiver jam
detect feature is disabled automatically if transmitters are
learned into zone 7.
Zone 8—Receiver Cover/Antenna Tamper: If no transmitters
are learned into zone 8, this output trips whenever the receiver
cover or the antenna is removed. When transmitters are
learned into zone 8, these tamper features are disabled.
Power LED/Self-Tests
Table 1 below describes the power LED states. The power
LED turns on after power is applied to the receiver and the
self-tests are passed. The LED blinks once each time a signal
is received from a transmitter.
If the receiver fails the self-tests, the power LED does not turn
on. Instead, the trouble LEDs flash alternately for a failed selftest.
Table 1: Power LED states
Trouble Outputs
Power LED
Indicates
There are two trouble outputs labeled B (low battery summary)
and S (supervisory failure summary).
On steady
Receiver has power and is
functioning normally.
Off (and all other LEDS off)
Receiver is not properly wired or has
a power failure.
Off (and yellow LEDs blinking)
Receiver failed power-up test.
Blinks off momentarily
Receiver received an RF signal,
whether learned or not.
B - Low Battery: When a learned transmitter sends a low
battery signal, this output switches to, and remains in the alarm
state until the receiver receives a signal from the same
transmitter with a good battery.
S - Supervisory: If a learned supervised transmitter fails to
report for four hours, this output switches to the alarm state
until the failed or unreporting transmitters have reported to the
receiver.
Test Output
Run Mode LED Indications
In run mode, the LEDs indicate 3 conditions: alarm, low
battery, and supervisory failure.
To diagnose alarm/tamper status conditions:
T - Test/Piezo: This output momentarily supplies 5 VDC each
time a transmitter sends an alarm signal to the receiver.
Connect a piezo (optional) to this output only when testing RF
transmitter response.
LED Indicators
The receiver has 11 LEDs: 8 red zone LEDs (bottom row), a
green Power LED, a yellow Low Battery LED, and a yellow
Supervisory LED (see Figure 3 below).
Figure 3: Receiver LEDs
When the trouble LEDs are both off, the zone LEDs indicate
alarm/tamper information.
The zone LEDs turn on for zones that are open (in
alarm/tamper). Zone LEDs remain off for zones that are closed
or not used.
To diagnose transmitter low battery conditions:
The yellow low battery LED indicates when one or more
transmitters have reported a low battery condition. After a low
battery report, the low battery LED will flash or blink once every
three seconds, in sync with at least one zone LED. Check the
corresponding zone’s transmitter(s) for low battery conditions.
To diagnose transmitter supervisory conditions:
Supervisory LED
Power LED
Low battery LED
Zone LEDs
The yellow supervisory LED indicates when one or more
transmitters have failed to report to the receiver for at least four
hours. When a supervisory condition exists, the supervisory
LED will flash or blink once every three seconds, in sync with
at least one zone LED. Check the corresponding zone’s
transmitter(s) for supervisory conditions.
Figure 4 shows the alarm, low battery and supervisory run
mode LED indications.
on page 4
In run mode, the LEDs indicate alarm and trouble conditions. In
program mode, the LEDs indicate programming conditions.
Quik Bridge Loop Receiver Installation Instructions
3
Figure 4: Run mode LED indications
Installing the Receiver
Alarm
Display if there is an
alarm on a zone 2
transmitter.
Mounting the Receiver
Low battery
Display if there is a
low battery on a zone
5 transmitter.
Supervisory
Display if there is a
supervisory on a zone
7 transmitter.
Caution: You must be free of static electricity before handling
circuit boards. Touch a bare metal surface or wear a grounding
strap to discharge yourself.
1.
Y
Remove the receiver’s cover by pressing down on the top
center of the cover (see Figure 6 below).
Figure 6: Removing the receiver’s cover
Press down here
Tools and Accessories Needed
Included with Receiver
•
•
•
Mounting screws and anchors
Spring for tamper switch
1 antenna
Not Included with Receiver
•
•
•
•
•
•
Phillips screwdriver
Small standard screwdriver
12-22 gauge stranded wire
Optional piezo for sensor testing (30-006)
12 VDC power supply (typically supplied by panel)
EOL Resistors (typically supplied with panel)
2.
Press down on the lower right corner of the base until the
lower right latch releases the circuit board (see Figure 7
below).
3.
Remove the circuit board by pulling it away from the top
two latches and set it aside.
4.
Hold the base against the mounting surface and mark the
three mounting holes (see Figure 7 below). Leave at least
10" above the base for the antenna.
Installation Guidelines
Observe the following guidelines when installing the receiver:
•
•
•
Figure 7: Base mounting hole locations
Leave 10” above the receiver for the antenna.
Avoid areas that may expose the receiver to moisture.
Avoid areas with excessive metal or electrical wiring,
including furnace and utility rooms.
Mounting hole
Top latch
Top latch
If unavoidable, mount on metal with the antenna extending
above the metallic surface (see Figure 5 below).
Figure 5: When mounting on metal is unavoidable
Metal
4
Metal
Mounting hole
Lower right latch
Mounting hole
5.
Remove the base and install the anchors provided, if studs
are not present.
6.
Mount the base on the wall with the screws provided.
Quik Bridge Loop Receiver Installation Instructions
7.
Replace the circuit board on the base by sliding the top of
the circuit board under the top two latches, then press on
the bottom of the circuit board until it snaps under the
lower right latch.
Connecting the Antenna to the Receiver
To connect the antenna to the receiver:
1.
Loosen the inside terminals of the left and right antenna
terminal blocks.
2.
Insert an antenna end into each inside terminal.
3.
Tighten the terminal screws.
Powering
To connect power to the receiver:
1.
2.
Turn off or remove power from the panel and disconnect
the battery.
Wire receiver terminals (GND) and (+12V) to a nonswitched 12V supply output on the control panel. Make
sure you observe the correct polarity (see Figure 8 below).
Figure 8: Connecting panel power to the receiver
3.
Note: All Keychain Touchpads learned into the receiver control
the same zone outputs. For example, if Keychain Touchpad #1
is learned into zone 1 and Keychain Touchpad #2 is learned
into zone 2, both Keychain Touchpads control both zones.
Zone 1: Lock & Unlock Buttons Together—This
simultaneous keypress can be learned only into zone 1
and still allows you to learn 2 additional sensors into zone
1. When learned, this keypress causes a momentary
alarm on zone 1.
Note: Both panic button transmitters and this keypress
can be learned into zone 1 together; however, the total
number of panic buttons and Keychain Touchpads learned
into zone 1 cannot exceed 45.
For zones 2 through 6, keychain touchpads and other sensors
cannot be learned into the same zone.
Zone 2: Lock or Unlock Button—When learned into zone
2, both of these keypresses work together to provide a
maintained (toggle) output response (only one of these
buttons needs to be learned for both to work).
Typically, this output would be used for a maintained
keyswitch on the control panel for arming/disarming (refer
to the control panel instructions for this application).
+VDC
-NEG
(GND)
Suggested applications include panic button, momentary or
maintained (toggle on/off) control panel activation for
arming/disarming, or momentary activation for a garage door
opener. Maintained output applications also include X-10 light
control (see “X-10 Applications”).
To panel’s
12 V supply
Turn on or apply power to the panel.
Zone Planning
Before programming, it’s a good idea to write down how you
plan to use the transmitters with each zone.
The following guidelines describe the receiver zone
capabilities. Use these guidelines to help you complete Table 2
on page 6 for recording the wireless devices used for each
zone.
When learned, pressing the lock button arms the system
and pressing the unlock button disarms the system.
Zone 3: Lights Button—This keypress can be learned only
into zone 3. When learned, pressing this button switches
the zone 3 output. The output can be configured to switch
momentarily (default) or maintained (toggle on/off for each
press) (See Configuring Touchpad Zone Output
Responses).
Zone 4: Star Button—This keypress can be learned only
into zone 4. When learned, pressing this button switches
the zone 4 output. The output can be configured to switch
momentarily (default) or maintained (toggle) (See
Configuring Touchpad Zone Output Responses).
Keychain Touchpads
Zone 5: Lock Button—This keypress can be learned into
zone 2 (as detailed above) or zone 5. When learned into
zone 5, pressing this button switches the zone 5 output.
The output can be configured to switch momentarily
(default) or maintained (toggle) (See Configuring
Touchpad Zone Output Responses).
The receiver can learn up to 45 Keychain Touchpads. The
following describes the Keychain Touchpad button functions.
Zone 6: Unlock Button—This keypress can be learned into
zone 2 (as above) or zone 6. When learned into zone 6,
Zone Planning Guidelines
Quik Bridge Loop Receiver Installation Instructions
5
pressing this button switches the zone 6 output. The
output can be configured to switch momentarily (default)
or maintained (toggle) (See Configuring Touchpad Zone
Output Responses).
Tamper and Trouble Conditions
7 (RF jam
detect
________________
__________________
8
(Tamper
detect)
________________
__________________
B
Zone 7: RF jam detection is set up to automatically
monitor for radio signals that can jam the receiver.
However, once a transmitter is learned into zone 7, the RF
jam detection is disabled.
S
Zone 8: Cover/Antenna tamper is set up to automatically
monitor cover and antenna removal. However, once a
transmitter is learned into zone 8, the cover/antenna
tamper is disabled.
This section describes the following programming procedures:
Low Battery—Receiver terminal B activates whenever the
receiver gets a signal from a transmitter with a low battery.
To monitor for low transmitter battery conditions, connect
the receiver’s B output to a control panel zone input.
RF Supervision—Receiver terminal S activates whenever
the receiver goes four hours without receiving a signal
from a supervised transmitter. To monitor for RF
supervision, connect the receiver’s S output to a control
panel zone input.
Panic Buttons and Wireless Sensors
Panic Buttons—Use zone 1 for up to 45 unsupervised
panic button transmitters. Use zones 2 - 8 for supervised
panic button transmitters (2 per zone).
Wireless Sensors—Learn wireless sensors into
remaining unused zones (2 per zone). Make sure that both
sensors learned into the same zone have the same
expected response type at the control panel (i.e. delay,
instant, interior, 24-hour)
Programming the Receiver
•
•
•
•
•
•
•
Learning Wireless Transmitters
Deleting Wireless Transmitters
Configuring Zone/Trouble Outputs N/O or N/C
Configuring RF Supervision
Configuring Keychain Touchpad Zone Output Responses
Garage Door Opener Control
X-10 Applications (Light Control and Garage Door Opener
Control)
Learning Wireless Transmitters
To learn a transmitter into a zone:
1.
Enter program mode by sliding the DIP switch up. The low
battery and supervisory LEDs blink back and forth. Zone
LEDs turn on if sensors are already learned into those
zones.
2.
Press and release the ADV switch until the desired zone
LED turns on. (Pressing and holding the ADV switch
advances to the next zone and causes the zone LED to
flicker.)
3.
Press and release the SEL switch once to select this zone
for learning transmitters. The zone LED remains on and
the low battery and supervisory LEDs stop flashing.
4.
Trip the transmitter(s):
For sensors with tamper switches, activate the sensor’s
tamper switch by removing the cover.
For sensors without tamper switches, put the sensor in
alarm.
Table 2: Transmitter zone assignments
Recvr
Zone
Panel
zone
Transmitter
Function
1
_______________
__________________
2
_______________
__________________
3
_______________
__________________
4
________________
__________________
5
________________
__________________
6
________________
__________________
6
Each time the receiver learns a sensor, the selected zone
LED blinks once.
For Keychain Touchpads:
Zone 1, press the lock and unlock buttons together.
Zone 2, press the lock or unlock button.
Zone 3, press the lights button.
Zone 4, press the star button.
Zone 5, press the lock button.
Zone 6, press the unlock button.
Each time the receiver learns a Keychain Touchpad
Quik Bridge Loop Receiver Installation Instructions
5.
button, all zone LEDs with learned Keychain Touchpads
blink once.
3.
Press and release the ADV switch until all zone LEDs are
off (nine presses), to select the trouble outputs.
To stop learning transmitters in the selected zone, slide
the DIP switch down.
4.
Press and release the SEL switch to change the trouble
output configuration to the desired setting (low battery
LED on = N/C, low battery LED flashing = N/O).
5.
Slide the DIP switch down to return to run mode.
Repeat steps 1-4 to learn transmitters into other zones.
Deleting Wireless Transmitters
Configuring RF Supervision
To delete all transmitters from a zone:
1.
Enter program mode sliding the DIP switch up.
2.
Press and release the ADV switch until the desired zone
LED turns on.
3.
Press and hold the SEL switch for five seconds to delete
all transmitters from this zone. The zone LED should turn
off.
4.
Slide the dip switch down to put the receiver in run mode.
To delete a Keychain Touchpad from the receiver:
Repeat steps 1 - 4, for each button on a Keychain Touchpad
button that is learned into a zone. A Keychain Touchpad is
deleted only when all learned buttons are deleted from their
respective zones.
All 8 zones default to be RF supervised, and can be changed
to be unsupervised.
To enable or disable RF supervision on a zone:
1.
Enter program mode by sliding the DIP switch up.
2.
Press the tamper switch twice to gain access to
configuring zone supervision.
3.
Press and release the ADV switch until the desired zone
LED turns on.
4.
Press and release the SEL switch to change the RF
supervision configuration to the desired setting (zone LED
on = supervised, zone LED off = unsupervised).
5.
Repeat steps 3 and 4 for each zone configuration change.
6.
Slide the DIP switch down to return to run mode.
Configuring Zone/Trouble Outputs N/O or N/C
Note: Keychain Touchpads are not supervised. Panic
Button transmitters learned into zone 1 are not supervised.
All 8 zones and both trouble outputs default to N/C, and can be
changed to N/O.
To program a zone output N/O or N/C:
1.
Enter program mode by sliding the DIP switch up.
2.
Press the tamper switch once to gain access to
configuring zone outputs. The low battery LED should turn
on or flash.
3.
Press and release the ADV switch until the desired zone
LED turns on.
4.
Press and release the SEL switch to change the output
configuration to the desired setting
(zone LED on = N/C, zone LED off = N/O).
5.
Repeat steps 3 and 4 for each zone configuration change.
6.
Slide the DIP switch down to return to run mode.
Configuring Keychain Touchpad Zone Output
Responses
Zone outputs 3 through 6 can be set up to respond by
switching momentarily or to maintain (toggle on/off for each
activation).
To change the zone output response to momentary
or maintained:
1.
Enter program mode sliding the DIP switch up.
2.
Press the tamper switch once to gain access to
configuring zone outputs.
3.
Press and release the ADV switch until the desired zone
LED (3 - 6) turns on.
4.
Press and release the SEL switch to change the zone
output response to the desired setting. The selected
zone’s LED should turn off (maintained) or on
(momentary), indicating the current configuration.
5.
Advance to another programmable option or exit program
mode by sliding the DIP switch down.
To program both trouble outputs N/O or N/C:
1.
Enter program mode by sliding the DIP switch up.
2.
Press the tamper switch once to gain access to
configuring zone outputs.
Quik Bridge Loop Receiver Installation Instructions
7
Light Control
Garage Door Opener Control
This section describes how to set up a zone with a relay to
control a garage door opener.
To set up garage door opener control using a relay:
1.
Learn the star button of a 4-Button Keychain Touchpad
into a zone (3-6).
2.
Configure the zone output as N/O, momentary.
3.
Connect a relay to the zone output (see Figure 9 below).
Figure 9: Connecting a relay for garage door opener control
Receiver terminals
To set up light control:
1.
Learn the lights button of a 4-Button Keychain Touchpad
into zone 3.
2.
Configure zone 3 for N/O if you want the zone 3 LED to
turn on when lights are on,
or - configure zone 3 for N/C if you want the zone 3 LED to
turn on when lights are off.
3.
Configure zone 3 output as maintained (see Configuring
Keychain Touchpad Zone Output Responses).
4.
Set the unit code and house code dials on the Powerflash
Interface Module to match those on the Lamp Module(s).
5.
Set the Powerflash Interface Module input switch to B and
the mode switch to 3.
6.
Connect receiver terminal 3 to the Powerflash Interface
Module’s negative (-) terminal.
7.
Connect the receiver GND terminal to the Powerflash
Interface Module’s positive (+) terminal.
8.
Plug in the Powerflash Interface Module and all Lamp
Modules.
Panel terminals
Panel +12V
Panel GND
Return
Zone 1
Coil
NC
Coil
COM
NO
4.
Connect the relay COM and N/O contacts to the garage
door opener activation terminals.
X-10 Applications
Garage Door Opener Control
To set up garage door opener control using X-10
modules:
1.
Learn the star button of a 4-Button Keychain Touchpad
into a zone (3-6).
2.
Configure the zone as N/O, momentary.
3.
Set the unit code and house code dials on the Powerflash
Interface Module to match those on the Universal Module.
4.
Set the Powerflash Interface Module input switch to B and
the mode switch to 3.
5.
On the Universal Module, set the lower-left switch to
momentary and the lower-right switch to relay only.
6.
Connect the zone output terminal to the Powerflash
Interface Module’s positive (+) terminal.
7.
Connect the receiver GND terminal to the Powerflash
Interface Module’s negative (-) terminal.
8.
Plug in the Powerflash Interface Module and Universal
Module.
9.
Connect the garage door opener wires to the N/O relay
connection on the Universal Module.
There are two ways to use X-10 devices:
•
•
8
Light Control—using an X-10 Powerflash Interface Module
(13-058) and X-10 Lamp Modules (13-204), the lights
button on a 4-Button Keychain Touchpad can be used to
control lights.
Garage Door Opener Control—using an X-10 Powerflash
Interface Module (13-058) and an X-10 Universal Module
(13-399), the star button on a 4-Button Keychain
Touchpad can be used to control a garage door opener.
Quik Bridge Loop Receiver Installation Instructions
Connecting the Receiver to a Control Panel
Figure 13: Wiring diagram when using a relay
There are four ways to wire the loop receiver to the control
panel. Refer to Figures 10 through 13 for panel connections.
Receiver terminals
Figure 10: Wiring diagram for a supervised N/O loop
Panel terminals
Panel +12V
Panel GND
Return
Zone 1
Receiver terminals
Panel terminals
EOL resister
Panel +12V
Panel GND
Return
Zone 1
Coil
NC
Coil
COM
NO
Note: You can connect multiple normally open loop receiver
zone outputs in parallel to panel zone inputs.
Figure 11: Wiring diagram for a N/C loop
Testing RF Reception
Receiver terminals
Panel terminals
You can test the receiver two ways: (1) counting the LED
flashes when transmitters are tripped or (2) counting the beeps
emitted by an attached piezo beeper (optional).
To test the system using the receiver’s LED:
EOL resister
Panel +12V
Panel GND
Return
Zone 1
Figure 12: Wiring diagram for a non-supervised loop
Receiver terminals
1.
Make sure the DIP switch is down (normal operation/run
mode).
2.
Trip all sensors in the system.
3.
After each trip, watch for the correct number of LED
flashes (see Table 3 on page 10).
To test the system using a piezo beeper:
1.
Panel terminals
Panel +12V
Panel GND
Return
Zone 1
Connect a piezo (30-006) beeper between the test output
(T) and ground (GND) (see Figure 14 below).
Figure 14: Piezo status beeper connections
Receiver terminals
Red
Black
Piezo
beeper
Quik Bridge Loop Receiver Installation Instructions
9
2.
Make sure the dip switch is down (normal operation/run
mode).
3.
Trip all sensors in the system.
4.
After each trip, listen for the correct number of beeps from
the piezo beeper (see Table 3 below).
Table 3: LED/Piezo test responses
Transmitter
Should cause
Sensors
7–8 beeps and LED flashes
Keychain
touchpads
1-button press
2 beeps and LED flashes
2-button press
8 beeps and LED flashes
Specifications
Compatibility
Control panels with common-loop ground
hardwire loops.
Power requirements
10.0 – 14.0 VDC
Current draw
60 mA maximum
Open collector outputs
(1-8, B, S)
maximum applied voltage = 16 VDC
maximum sink current = 50 mA (typical)
15 mA (minimum)
Operating temperature
range
40° to 120°F
Dimensions
4.125” x 5.25” x 1” (L x W x H), excluding
antenna.
Regulatory information
Manufacturer
UTC Fire & Security Americas Corporation, Inc.
1275 Red Fox Rd., Arden Hills, MN 55112-6943,
USA
FCC compliance:
This equipment has been tested and found to comply with the limits
for a class B digital device, pursuant to part 15 of the FCC rules.
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment
generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or
more of the following measures:
• Install a quality radio or television outdoor antenna if the indoor
antenna is not adequate.
• Reorient or relocate the panel.
• Move the panel away from the affected equipment.
• Move the panel away from any wire runs to the affected equipment.
• Connect the affected equipment and the panel to separate outlets,
on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
Send for the FCC booklet How to Identify and Resolve Radio-TV
Interference Problems, available from the U.S. Government Printing
Office, Washington, D.C. 20402.
Stock Number: 004-000-00345-4.
This device complies with FCC Rules Part 15. Operation is subject to
the following two conditions:
This device may not cause harmful interference.
This device must accept any interference that may be received,
including interference that may cause undesired operation.
Changes or modifications not expressly approved by Interactive
Technologies, Inc. can void the user’s authority to operate the
equipment.
Contact information
www.utcfireandsecurity.com or www.interlogix.com
For customer support, see www.interlogix.com/customersupport
Copyright © 2011 UTC Fire & Security Company. All rights
reserved.
10
Quik Bridge Loop Receiver Installation Instructions
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement