Danfoss MT 018-040, 044-081, 100-160, MTZ 018-040, 044-081, 100-160 reciprocating compressor Selection and application guidelines
MT and MTZ series compressors are of the hermetic reciprocating type and are designed for medium and high evaporating temperature applications. The MT series is designed for use with the “traditional” R22 refrigerant, using Danfoss mineral oil 160P as lubricant. The MTZ series is specifically designed for use with the HFC refrigerants R407C, R134a, R404A, and R507A, using 160PZ polyester oil as lubricant.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
MAKING MODERN LIVING POSSIBLE
Maneurop® reciprocating compressors
MT/MTZ 50 - 60 Hz
R22 - R407C - R134a - R404A / R507A
SELECTION &
APPLICATION GUIDELINES
2
CONTENTS
MANEUROP® RECIPROCATING COMPRESSORS
.................................................................................................
p 3
COMPRESSOR MODEL DESIGNATION
..............................................................................................................................................
p 4
Code numbers
................................................................................................................................................................................................................................
p 4
Compressor reference
........................................................................................................................................................................................................
p 4
Versions
...............................................................................................................................................................................................................................................................
p 4
SPECIFICATIONS
........................................................................................................................................................................................................................................
p 5
Technical specifi cations
..................................................................................................................................................................................................
p 5
Approvals & certifi cates
...................................................................................................................................................................................................
p 5
Nominal performance for R404A and R22
.............................................................................................................................
p 6
Nominal performance for R407C and R134a
....................................................................................................................
p 7
OPERATING ENVELOPES
.......................................................................................................................................................................................................
p 8
OUTLINE DRAWINGS
.................................................................................................................................................................................................................
p 10
1 cylinder
....................................................................................................................................................................................................................................................
p 10
2 cylinders
................................................................................................................................................................................................................................................
p 11
4 cylinders
................................................................................................................................................................................................................................................
p 12
ELECTRICAL CONNECTIONS AND WIRING
............................................................................................................................
p 13
Single phase electrical characteristics
.......................................................................................................................................
p 13
Nominal capacitor values and relays
............................................................................................................................................
p 13
Trickle circuit
.......................................................................................................................................................................................................................................
p 13
PSC wiring
................................................................................................................................................................................................................................................
p 13
CSR wiring
................................................................................................................................................................................................................................................
p 13
Suggested wiring diagrams
..............................................................................................................................................................................
p 14
Three phase electrical characteristics
.........................................................................................................................................
p 15
Motor protection and wiring diagrams
...................................................................................................................................
p 15
Soft starters
...........................................................................................................................................................................................................................................
p 16
Voltage application range
....................................................................................................................................................................................
p 16
IP rating
..........................................................................................................................................................................................................................................................
p 16
REFRIGERANTS AND LUBRICANTS
..........................................................................................................................................................
p 17
General information
.............................................................................................................................................................................................................
p 17
SYSTEM DESIGN RECOMMENDATIONS
........................................................................................................................................
p 19
Piping design
.....................................................................................................................................................................................................................................
p 19
Operating limits
...........................................................................................................................................................................................................................
p 20
Operating voltage & cycle rate
...................................................................................................................................................................
p 21
Liquid refrigerant control & charge limits
..........................................................................................................................
p 22
SOUND AND VIBRATION MANAGEMENT
.................................................................................................................................
p 24
Sound
.................................................................................................................................................................................................................................................................
p 24
Vibration
......................................................................................................................................................................................................................................................
p 25
INSTALLATION AND SERVICE
...............................................................................................................................................................................
p 26
System cleanliness
.................................................................................................................................................................................................................
p 26
Compressor handling, mounting and connection to the system
.................................
p 26
System pressure test
.........................................................................................................................................................................................................
p 27
Leak detection
................................................................................................................................................................................................................................
p 27
Vacuum pull down - moisture removal
...................................................................................................................................
p 28
Start-up
..........................................................................................................................................................................................................................................................
p 28
ACCESSORIES AND SPAREPARTS
................................................................................................................................................................
p 30
Rotolock accessories
.........................................................................................................................................................................................................
p 30
Crankcase heaters
...................................................................................................................................................................................................................
p 30
Acoustic hoods
..............................................................................................................................................................................................................................
p 30
3-phase soft start equipment
.......................................................................................................................................................................
p 31
Single phase PSC starting kits
......................................................................................................................................................................
p 31
Single phase CSR starting kits & starting kits in prewired box
.............................................
p 31
Kickstart kits
.........................................................................................................................................................................................................................................
p 31
Lubricants
.................................................................................................................................................................................................................................................
p 31
ORDERING INFORMATION AND PACKAGING
................................................................................................................
p 32
Ordering information
......................................................................................................................................................................................................
p 32
Packaging
..................................................................................................................................................................................................................................................
p 34
MANEUROP® RECIPROCATING COMPRESSORS
Maneurop® reciprocating compressors from Danfoss Commercial Compressors are specially designed for applications with a wide range of operating conditions. All components are of high quality and precision in order to assure a long product life.
Maneurop® MT and MTZ series compressors are of the hermetic reciprocating type and are designed for medium and high evaporating temperature applications.
The compressor design allows for the motor to be 100% suction-gas cooled.
The positive benefi ts of internal movalve design and high torque motors provide for a quality installation.
The MT series is designed for use with the “traditional” R22 refrigerant, using
Danfoss mineral oil 160P as lubricant.
The MT series can also be applied with several R22 based refrigerant blends (substitute refrigerants), using
160 ABM alkylbenzene as lubricant. The
MTZ series is specifi cally designed for use with the HFC refrigerants R407C,
R134a, R404A, and R507A, using 160PZ polyester oil as lubricant.
MTZ compressors can be used in new installations and also to replace Maneurop® MTE compressors in existing installations.
MT and MTZ compressors have a large internal free volume that protects against the risk of liquid hammering when liquid refrigerant enters the compressor.
MT and MTZ compressors are fully suction-gas cooled. This means that no additional compressor cooling is required and allows the compressors to be insulated with acoustic jackets, to obtain lower sound levels, without the risk of compressor overheating.
MT and MTZ compressors are available in 26 diff erent models with displacement ranging from 30 to 543 cm 3 /rev.
Seven diff erent motor voltage ranges are available for single and three phase power supplies at 50 and 60 Hz. Most compressors exist in two versions:
- standard version
- VE version (oil equalisation + oil sight glass).
3
COMPRESSOR MODEL DESIGNATION
Code numbers
(for ordering)
Compressor reference
(indicated on the compressor nameplate)
Available code numbers are listed on pages 32-33
4
Versions
Models
MT/MTZ018-040 (1 cyl.)
MT/MTZ044-081 (2 cyl.)
MT/MTZ100-160 (4 cyl.)
S version (standard) VE version (optional)
Oil sight glass
Oil equalisation connection
Oil sight glass
Oil equalisation connection
threaded 3/8’’fl are
brazed
-
threaded threaded
3/8’’fl are
3/8’’fl are
SPECIFICATIONS
Technical specifi cations
Displacement
Cyl.
number
Oil charge
Net weight
Available motor voltage codes
Compressor model
MT/MTZ018 JA
MT/MTZ022 JC
MT/MTZ028 JE
MT/MTZ032 JF
MT/MTZ040 JH
MT/MTZ044 HJ
MT/MTZ045 HJ
Code cm
3
/rev
MT/MTZ050 HK
MT/MTZ051 HK
MT/MTZ056 HL
MT/MTZ057 HL
MT/MTZ064 HM
MT/MTZ065 HM
MT/MTZ072 HN
MT/MTZ073 HN
MT/MTZ080 HP
MT/MTZ081 HP
MT/MTZ100 HS
MT/MTZ125 HU
MT/MTZ144 HV
MT/MTZ160 HW
30.23
38.12
48.06
53.86
60.47
67.89
76.22
76.22
85.64
85.64
96.13
96.13
107.71
107.71
120.94
120.94
135.78
135.78
171.26
215.44
241.87
271.55
m 3 /h at
2900 rpm dm
3 kg 1 3 4 5 6 7 9
5.26
6.63
8.36
9.37
10.52
11.81
13.26
13.26
14.90
14.90
16.73
16.73
18.74
18.74
21.04
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
0.95
0.95
0.95
0.95
0.95
0.95
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
21
21
23
24
25
26
35
37
35
37
37
39
37
39
40
● ● ● ● ○
-
● ● ● ● ●
-
●
● ● ● ● ●
-
●
● ● ● ● ● ○ ○
● ● ● ● ● ○ ●
● ● ●
-
●
-
● ● ●
-
● ● ●
-
● ●
-
● ● ● ● ● ● ●
-
● ●
-
● ● ●
-
● ● ●
-
● ●
-
● ● ●
-
●
-
●
-
● ●
-
-
● ●
-
●
-
●
21.04
23.63
23.63
2
2
2
1.8
1.8
1.8
41
40
41 -
-
-
● ●
-
● ●
-
●
-
●
● ●
-
29.80
37.49
42.09
47.25
4
4
4
4
3.9
3.9
3.9
3.9
60
64
67
69 -
-
-
-
● ●
-
● ● ●
● ●
-
● ● ○
● ●
-
● ● ●
● ●
-
● ● ●
●
Available in MT and MTZ
○
Available in MTZ only
Approvals and certifi cates
Maneurop® MT/MTZ compressors comply with the following approvals and certifi cates
Certifi cates are listed on the product datasheets: http://www.danfoss.com/odsg
CE
(European Directive)
UL
(Underwriters Laboratories)
CCC (China Compulsory
Product Certifi cation)
Gost certifi cate (for Russia)
All models
All 60 Hz models
Depending on the model and motor voltage code.
Depending on the model and voltage code.
5
SPECIFICATIONS
6
Nominal performance data for R404A and R22
R404A Refrigeration
Compressor model
MTZ018-4
*
MTZ022-4
*
MTZ028-4
*
MTZ032-4
*
MTZ036-4
*
MTZ040-4
*
MTZ044-4
MTZ045-4
*
MTZ050-4
MTZ051-4
*
MTZ056-4
MTZ057-4
*
MTZ064-4
MTZ065-4
*
MTZ072-4
MTZ073-4
*
MTZ080-4
MTZ081-4
*
MTZ100-4
*
MTZ125-4
*
MTZ144-4
*
MTZ160-4
*
Power input kW
1.21
1.48
1.96
2.16
2.58
2.95
3.16
2.77
3.61
3.22
4.00
3.51
4.54
4.20
4.99
4.69
5.84
5.61
6.76
8.44
9.78
11.08
50 Hz, EN12900 ratings
To = -10 °C, Tc = 45°C, SC = 0 K, SH = 10 K
Cooling capacity
W
1 900
2 620
3 430
3 980
4 670
5 330
5 150
5 370
6 150
6 260
7 000
6 710
8 130
7 980
9 150
8 920
10 520
10 470
12 280
15 710
18 490
20 310
C.O.P.
W/W
Current input
A
2.73
3.06
4.04
4.25
4.95
5.87
6.37
5.35
6.53
5.95
7.07
6.83
8.30
7.82
8.64
8.95
10.12
10.20
12.21
13.79
16.29
18.26
1.93
1.70
1.94
1.75
1.91
1.79
1.90
1.84
1.90
1.58
1.77
1.75
1.84
1.81
1.81
1.63
1.80
1.87
1.82
1.86
1.89
1.83
* 50 Hz, EN12900 data for indicated models are Asercom certifi ed
Power input kW
1.31
1.62
2.14
2.37
2.83
3.24
3.43
3.02
3.92
3.50
4.38
3.85
4.96
4.60
5.45
5.11
6.38
6.14
7.35
9.21
10.65
12.09
50 Hz, ARI ratings
To = -6.7 °C, Tc = 48.9 °C, SC = 0 K, SH = 11.1 K
Cooling capacity
W
2 070
2 830
3 690
4 260
4 990
5 680
5 530
5 780
6 580
6 700
7 500
7 250
8 700
8 590
9 760
9 570
11 200
11 180
13 170
16 800
19 690
21 660
E.E.R.
Btu.h/W
Current input
A
2.86
3.24
4.30
4.56
5.33
6.29
6.66
5.67
6.92
6.33
7.57
7.25
8.84
8.35
9.28
9.50
10.87
10.94
12.94
14.86
17.47
19.64
6.53
5.73
6.54
5.85
6.43
5.99
6.37
6.11
6.39
5.40
5.96
5.88
6.15
6.02
5.97
5.51
5.99
6.22
6.11
6.22
6.31
6.11
Power input kW
1.76
2.05
2.68
2.98
3.33
3.76
4.18
3.85
4.82
4.42
5.44
4.98
6.11
5.67
6.91
6.53
8.03
7.81
8.72
11.37
12.99
14.73
60 Hz, ARI ratings
To = -6.7 °C, Tc = 48.9 °C, SC = 0 K, SH = 11.1 K
Cooling capacity
W
2 630
3 600
4 680
5 110
5 900
6 730
7 100
7 110
8 290
8 360
9 310
9 490
10 580
10 540
11 850
11 960
13 400
13 600
15 480
19 970
23 530
25 570
E.E.R.
Btu.h/W
Current input
A
2.86
3.27
4.23
4.56
5.09
5.88
6.58
5.85
7.04
6.53
7.80
7.52
8.98
8.31
9.76
9.73
11.35
11.35
12.79
15.41
17.93
20.17
6.30
5.87
6.46
5.84
6.50
5.91
6.35
5.85
6.25
5.09
6.00
5.95
5.85
6.04
6.11
5.79
5.70
5.94
6.06
6.00
6.18
5.92
R404A data are also valid for refrigerant R507A
R22 Refrigeration Air Conditioning
MT018-4
MT022-4
MT028-4
MT032-4
MT036-4
MT040-4
MT044-4
MT045-4
MT050-4
MT051-4
MT056-4
MT057-4
MT064-4
MT065-4
MT072-4
MT073-4
MT080-4
MT081-4
MT100-4
MT125-4
MT144-4
MT160-4
50 Hz, EN12900 ratings
To = -10 °C, Tc = 45 °C, SC = 0 K, SH = 10 K
50 Hz, ARI ratings
To = +7.2°C, Tc = 54.4 °C, SC = 8.3 K, SH = 11.1 K
Compressor model
Cooling capacity
W
1 690
2 490
3 730
3 950
4 810
5 220
5 300
4 860
5 810
5 870
6 830
6 440
7 640
7 750
8 520
8 710
9 720
10 360
11 330
15 260
17 270
19 190
Power input kW
1.00
1.29
1.81
2.11
2.35
2.67
2.72
2.46
2.95
2.94
3.44
3.18
3.89
3.64
4.29
4.19
4.84
4.89
5.79
7.55
8.47
9.49
Current input
A
2.27
2.55
3.59
3.73
4.30
4.86
6.03
5.02
5.22
5.53
6.21
6.39
7.06
7.03
7.58
8.48
8.24
9.52
11.82
12.28
17.06
16.81
C.O.P.
W/W
Cooling capacity
W
3 880
5 360
7 380
8 060
9 270
10 480
11 040
10 520
12 320
12 230
13 770
13 750
15 820
15 730
17 120
18 190
19 530
20 730
23 400
30 430
34 340
38 270
1.98
1.97
2.00
1.99
2.03
1.96
2.13
1.99
2.08
1.69
1.94
2.06
1.87
2.04
1.95
1.95
2.01
2.12
1.96
2.02
2.04
2.02
To: Evaporating temperature at dew point (saturated suction temperature)
Tc: Condensing temperature at dew point (saturated discharge temperature)
SC: Subcooling,
SH: Superheat
Power input kW
1.45
1.89
2.55
2.98
3.37
3.86
3.89
3.53
4.32
4.19
5.04
4.58
5.66
5.27
6.31
6.12
7.13
7.08
7.98
10.66
11.95
13.40
E.E.R.
Btu.h/W
10.17
9.74
9.97
9.32
10.24
9.53
10.18
9.26
10.15
9.16
9.69
9.87
9.22
9.38
9.27
9.69
9.36
9.99
10.00
9.74
9.80
9.75
Current input
A
2.73
3.31
4.56
4.97
5.77
6.47
7.37
6.37
8.46
7.20
10.27
8.19
9.54
9.16
10.54
10.98
11.58
12.48
14.59
17.37
22.75
22.16
Current input
A
2.73
3.31
4.56
4.97
5.77
6.47
7.37
6.42
8.46
7.26
10.27
8.23
9.54
9.33
10.54
10.77
11.58
12.34
14.59
17.37
22.75
22.16
Power input kW
1.74
2.27
3.06
3.58
4.05
4.63
4.66
4.32
5.18
5.04
6.05
5.58
6.80
6.32
7.57
7.33
8.55
8.50
9.58
12.80
14.35
16.08
Cooling capacity
W
4 660
6 440
8 850
9 680
11 130
12 570
13 240
12 890
14 790
14 690
16 530
16 520
18 980
18 850
20 550
21 840
23 440
24 880
28 080
36 510
41 210
45 930
60 Hz, ARI ratings
To = +7.2°C, Tc = 54.4 °C, SC = 8.3 K, SH = 11.1 K
E.E.R.
Btu.h/W
ARI capacity and power input data are +/- 5%
Asercom: Association of European Refrigeration Compressor and
Controls Manufacturers
ARI: Air Conditioning and Refrigeration Institute
10.18
9.74
9.95
9.32
10.10
9.53
10.18
9.26
10.16
9.16
9.69
9.87
9.22
9.38
9.27
9.69
9.36
10.00
10.00
9.74
9.80
9.75
SPECIFICATIONS
Nominal performance data for R407C and R134a
R407C Air Conditioning
Compressor model
50 Hz, EN12900 ratings
To = +5 °C, Tc = 50 °C, SC = 0 K, SH = 10 K
Cooling capacity
W
3 470
4 550
5 880
6 650
7 510
8 660
8 940
9 130
10 190
10 420
11 700
11 680
13 180
13 360
14 800
15 320
16 750
17 380
20 480
26 880 9.48
29 770 10.68
34 090 12.40
3.79
3.69
4.32
4.02
4.84
4.61
5.50
5.42
6.29
6.29
7.38
Power input kW
1.27
1.71
2.17
2.43
2.93
3.40
3.34
3.12
C.O.P.
W/W
MTZ018-4
*
MTZ022-4
*
MTZ028-4
*
MTZ032-4
*
MTZ036-4
*
MTZ040-4
*
MTZ044-4
MTZ045-4
*
MTZ050-4
MTZ051-4
*
MTZ056-4
MTZ057-4
*
MTZ064-4
MTZ065-4
*
MTZ072-4
MTZ073-4
*
MTZ080-4
MTZ081-4
*
MTZ100-4
*
MTZ125-4
*
MTZ144-4
*
MTZ160-4
*
* 50 Hz, EN12900 data for indicated models are Asercom certifi ed
6.90
6.51
7.85
7.45
8.79
8.35
9.81
9.85
11.02
11.31
13.05
15.14
17.55
20.08
Current input
A
2.73
3.27
4.30
4.57
5.58
6.46
6.10
5.84
2.73
2.67
2.72
2.74
2.56
2.55
2.67
2.93
2.69
2.83
2.71
2.90
2.72
2.90
2.69
2.83
2.66
2.76
2.78
2.84
2.79
2.75
50 Hz, ARI ratings
To = +7.2 °C, Tc = 54.4 °C, SC = 8.3 K, SH = 11.1 K
Cooling capacity
W
3 850
5 020
6 540
7 330
8 280
9 580
9 870
10 100
11 270
11 530
12 940
13 000
14 590
14 850
16 380
17 050
18 530
19 330
22 700
29 790 10.32
33 070 11.59
37 820 13.46
4.11
4.01
4.69
4.37
5.26
5.02
5.97
5.87
6.83
6.83
8.00
Power input kW
1.38
1.86
2.36
2.65
3.21
3.71
3.63
3.38
7.34
6.95
8.36
7.91
9.35
8.91
10.48
10.48
11.83
12.08
13.83
16.28
18.80
21.50
Current input
A
2.86
3.47
4.57
4.90
5.99
6.92
6.49
6.18
60 Hz, ARI ratings
To = +7.2 °C, Tc = 54.4 °C, SC = 8.3 K, SH = 11.1 K
E.E.R.
Btu.h/W
9.53
9.23
9.45
9.43
8.82
Cooling capacity
W
5 050
6 280
8 220
8 990
9 990
8.81
9.27
11 720
12 600
10.21
12 730
9.34
9.82
14 100
14 110
9.42
15 920
10.16
16 050
9.47
17 700
10.10
18 080
9.36
9.91
9.25
9.67
9.69
9.85
9.74
9.59
19 890
20 780
22 520
22 870
28 220
35 620
40 900
45 220
4.95
4.87
5.66
5.40
6.35
6.14
7.21
7.30
8.24
8.24
9.86
12.83
14.42
16.64
Power input kW
1.73
2.26
2.82
3.20
3.90
4.46
4.36
4.25
E.E.R.
Btu.h/W
7.33
7.06
8.41
8.03
9.47
9.01
10.78
10.61
12.35
11.99
14.22
18.07
19.81
22.46
Current input
A
2.82
3.45
4.41
4.80
5.78
6.69
6.84
6.34
9.98
9.48
9.93
9.61
8.74
8.98
9.85
10.23
9.72
9.89
9.60
10.15
9.50
10.05
9.41
9.72
9.33
9.47
9.77
9.47
9.68
9.27
R134a Air Conditioning
Compressor model
MTZ018-4
MTZ022-4
MTZ028-4
MTZ032-4
MTZ036-4
MTZ040-4
MTZ044-4
MTZ045-4
MTZ050-4
MTZ051-4
MTZ056-4
MTZ057-4
MTZ064-4
MTZ065-4
MTZ072-4
MTZ073-4
MTZ080-4
MTZ081-4
MTZ100-4
MTZ125-4
MTZ144-4
MTZ160-4
50 Hz, EN12900 ratings
To = +5 °C, Tc = 50 °C, SC = 0 K, SH = 10 K
Cooling capacity
W
2 310
3 000
3 730
4 390
5 340
5 700
6 120
6 090
7 170
7 110
8 040
7 680
9 160
8 960
10 540
10 230
12 080
11 750
13 770
16 980
21 030
23 080
Power input kW
0.92
1.11
1.41
1.74
1.97
2.15
2.36
2.06
2.68
2.44
2.99
2.62
3.36
3.02
3.74
3.50
4.31
4.02
4.89
5.84
7.27
7.98
Current input
A
2.12
2.42
3.18
3.80
3.88
4.58
5.51
4.56
5.33
5.02
5.61
5.93
6.66
6.53
6.83
7.66
8.03
8.44
9.84
10.24
13.11
13.90
50 Hz, ARI ratings
To = +7.2 °C, Tc = 54.4 °C, SC = 8.3 K, SH = 11.1 K
C.O.P.
W/W
2.51
2.70
2.65
2.52
2.71
2.66
2.60
2.96
2.67
2.91
2.69
2.93
2.73
10 350
2.96
10 160
2.82
11 850
2.92
11 650
2.80
13 580
2.92
13 320
2.81
15 530
2.91
19 070
2.89
23 620
2.89
25 860
Cooling capacity
W
2 550
3 350
4 210
4 950
6 000
6 400
6 870
6 850
8 070
8 010
9 070
8 720
To: Evaporating temperature at dew point (saturated suction temperature)
Tc: Condensing temperature at dew point (saturated discharge temperature)
SC: Subcooling,
SH: Superheat
Power input kW
0.99
1.20
1.53
1.87
2.13
2.33
2.52
2.22
2.88
2.63
3.21
2.84
3.62
3.26
4.01
3.78
4.64
4.35
5.28
6.29
7.83
8.57
Current input
A
2.19
2.51
3.30
3.94
4.09
4.89
5.65
4.73
5.50
5.20
5.83
6.17
6.96
6.81
7.20
7.99
8.45
8.83
10.24
10.80
13.78
14.67
E.E.R.
Btu.h/W
To = +7.2 °C, Tc = 54.4 °C, SC = 8.3 K, SH = 11.1 K
8.81
9.56
9.40
9.03
9.60
9.36
9.29
10.53
8 820
9.57
10 090
10.39
10 110
9.63
11 130
10.47
11 380
Cooling capacity
W
3 280
4 350
5 640
6 130
7 170
8 160
8 740
9.77
13 260
10.63
13 000
10.09
14 640
10.52
14 640
10.00
16 550
10.44
16 490
60 Hz, ARI ratings
Power input kW
1.22
2.84
3.60
3.29
3.95
3.82
4.68
4.20
5.19
4.81
5.99
5.47
1.54
2.04
2.39
2.75
3.08
3.14
10.04
18 730
10.35
23 110
6.50
7.71
10.30
28 390 9.81
10.29
31 520 10.91
E.E.R.
Btu.h/W
ARI capacity and power input data are +/- 5%
Asercom: Association of European Refrigeration Compressor and
Controls Manufacturers
ARI: Air Conditioning and Refrigeration Institute
Current input
A
2.09
2.56
3.37
3.89
4.20
4.72
5.47
4.70
5.36
5.33
5.92
6.37
7.11
6.77
7.59
7.88
8.79
8.68
10.11
11.09
14.28
15.54
9.20
9.63
9.43
8.76
8.91
9.03
9.51
10.59
9.57
10.48
9.62
10.16
9.67
10.56
9.64
10.39
9.42
10.29
9.84
10.23
9.87
9.86
7
8
OPERATING ENVELOPES
MT
R22
MTZ
R407C at DEW point
MTZ
R134a
50
45
40
70
65
60
55
35
30
-30 -25
S.H. = 11.1 K
-20 -15 -10
-5
0
Evaporating temperature (°C)
5
S.H. = 30 K
10 15 20
80
75
70
65
60
55
50
45
40
35
-20
S.H. = 11.1 K
-15 -10
S.H. = 30 K
-5 0 5
Evaporating temperature (°C)
10 15 20 25
MTZ
R404A/R507A
OPERATING ENVELOPES
Zeotropic refrigerant mixtures
Phase shift
Temperature glide
Refrigerant mixtures can be either zeotropic or azeotropic.
An azeotropic mixture (like R502 or
R507A) behaves like a pure refrigerant.
During a phase transition (from vapour to liquid or from liquid to vapour) the composition of vapour and liquid stays the same.
In a zeotropic mixture (like R407C) on the other hand the composition of vapour and liquid changes during the phase transition. When the eff ect of this phase transition is very small, the mixture is often called a near-azeotropic mixture. R404A is such a nearazeotropic mixture.
The composition change causes phase shift and temperature glide.
In system components where both vapour and liquid phase are present
(evaporator, condenser, liquid receiver), the liquid phase and vapour phase do not have the same composition.
In fact both phases form two diff erent refrigerants. Therefore zeotropic refrigerants need some special attention.
Zeotropic refrigerants must always be charged in liquid phase. Flooded evaporators and suction accumulators should not be applied in systems with zeotropic refrigerants. This also applies to near-azeotropic mixtures.
During the evaporating process and the condensing process at constant pressure, the refrigerant temperature will decrease in the condenser and rise in the evaporator. Therefore when speaking about evaporating and condensing temperatures, it is important to indicate whether this is a dew point temperature or a mean point value. In the fi gure below, the dotted lines are lines of constant temperature.
They do not correspond to the lines of constant pressure.
Points A and B are dew point values.
These are temperatures on the saturated vapour line.
Points C and D are mean point values.
These are temperatures which correspond more or less with the average temperature during the evaporating and condensing process. For the same
R407C cycle, mean point temperatures are typically about 2 to 3°C lower than dew point temperatures. According to
Asercom recommendations, Danfoss
Commercial Compressors uses dew point temperatures for selection tables and application envelopes etc.
To obtain exact capacity data at mean point temperatures, the mean point temperatures must be converted to dew point temperatures with help of refrigerant data tables from the refrigerant manufacturer.
Dew temperature and mean temperature for R407C
9
OUTLINE DRAWINGS
1 cylinder
Terminal box
Spade connectors
1/4” AMP-AWE
Earth M4-12
IP rating: 55 (with cable gland)
Ø 21 mm
Knock-out Ø 21 mm
Silent block
10
(1) MTZ 18 , 22-3/4/5/6/7/9 , 28-3/4/5/6/7/9
(2) MTZ 22-1 , 28-1 , 32 , 36 , 40
MT/MTZ018
MT/MTZ022 - 3/4/5/6
MT/MTZ028 - 3/4/5/6
MT/MTZ022 - 1
MT/MTZ028 - 1
MT/MTZ032
MT/MTZ036
MT/MTZ040
Rotolock connections size
Suction Discharge
1” 1”
1”1/4 1”
1”1/4 1”
Suction
Pipe sizing
Discharge
1/2” 3/8”
5/8” 3/8”
5/8” 1/2”
Rotolock valve
Suction Discharge
V06 V01
V09 V01
V09 V06
OUTLINE DRAWINGS
2 cylinders
Terminal box for model (1)
Spade connectors
1/4” AMP-AWE
Earth M4-12
IP rating: 55 (with cable gland)
Ø 21 mm
Knock-out Ø 21 mm
Terminal box for model (2)
Screw
10-32 UNF x 9,5
Earth M4-12
Knock-out
Ø 29 mm
Ø 29 mm
IP rating: 54 (with cable gland)
Silent block
(1) MTZ 44-1, all code 3 except 80-3 & 81-3, all code 4, 7, 9
(2) MTZ 50-1, 56-1, 64-1, 80-3, 81-3, all code 6
Rotolock connections size
Suction Discharge
MT/MTZ044
MT/MTZ045
MT/MTZ050
MT/MTZ051
MT/MTZ056
MT/MTZ057
MT/MTZ064
MT/MTZ065
MT/MTZ072
MT/MTZ073
MT/MTZ080
MT/MTZ081
1”3/4
1”3/4
1”1/4
1”1/4
Suction
Pipe sizing
Discharge
Rotolock valve
Suction Discharge
7/8”
1”1/8”
3/4”
3/4”
V07
V02
V04
V04
11
OUTLINE DRAWINGS
4 cylinders
Terminal box
Screw
10-32 UNF x 9,5
Earth M4-12
Knock-out
Ø 29 mm
Ø 29 mm
IP rating: 54
(with cable gland)
Silent block
12
(1) MTZ 100 , 125
(2) MTZ 144 , 160
MT/MTZ100
MT/MTZ125
MT/MTZ144
MT/MTZ160
Rotolock connections size
Suction Discharge
1”3/4 1”1/4
Suction
Pipe sizing
Discharge
1”1/8” 3/4”
Rotolock valve
Suction Discharge
V02 V04
ELECTRICAL CONNECTIONS AND WIRING
Single phase electrical characteristics
Nominal capacitor values and relays
* PSC: Permanent Split Capacitor
CSR: Capacitor Start Run
(1) Run capacitors: 440 volts
(2) Start capacitors: 330 Volts
Trickle circuit
PSC wiring
CSR wiring
Motor Code
Winding
MT/MTZ018
MT/MTZ022
MT/MTZ028
MT/MTZ032
MT/MTZ036
MT/MTZ040
MT/MTZ044
MT/MTZ050
MT/MTZ056
MT/MTZ064
50 Hz
Models
MT/MTZ018 JA-5
MT/MTZ022 JC-5
MT/MTZ028 JE-5
MT/MTZ032 JF-5
MT/MTZ036 JG-5
MT/MTZ050 HK-5
60 Hz
Models
MT/MTZ018 JA-1
MT/MTZ022 JC-1
MT/MTZ028 JE-1
MT/MTZ032 JF-1
MT/MTZ036 JG-1
MT/MTZ040 JH-1
MT/MTZ044 HJ-1
MT/MTZ050 HK-1
MT/MTZ056 HL-1
MT/MTZ064 HM-1
99
97
114
136
143
51
49.3
81
84
84
LRA - Locked Rotor
1
Current (A)
5
MCC - Maximum
Continuous Current (A)
1 5
-
-
92
-
-
40
41
51
70
60
13
17
25
26.5
30
34
31
36
42.5
46
(A) μF
20
20
20
25
25
30
PSC/CSR*
Run capacitors
(1)
(C) μF
10
10
10
10
10
15
PSC/CSR*
Run capacitors
(1)
(A) μF (C) μF
15
30
10
15
25
25
25
35
30
30
35
30
25
20
20
20
15
15
20
25
-
-
29
-
-
10
15
20
20
22
Winding resistance (Ω)
( ± 7 % at 20° C)
5 1 run start
1.36
4.82
1.25
2.49
0.74
1.85
0.64
2.85
0.64
2.85
0.53
2.00
0.45
1.90
0.37
1.79
0.32
1.61
0.32
2.10
run
1.80
1.78
1.16
0.90
0.89
-
-
0.52
-
start
4.70
4.74
3.24
4.30
4.35
-
-
2.65
-
-
CSR only
Start capacitors
(2)
Start relay
(B) μF
100
100
100
135
135
135
3ARR3J4A4
CSR only
Start capacitors
(2)
(B) μF
Start relay
100
100
135
100
100
100
135
135
200
235
3ARR3J4A4
The trickle circuit provides the facility of heating the compressor crankcase by feeding a small current to the auxiliary winding and the run capacitor
See the drawings page 14.
By using PSC or CSR starting systems, compressor models MT/MTZ018-022 can be operated without crankcase heaters as the heater function is provided by the trickle circuit. For the larger single phase compressor models MT/
MTZ028-064, the use of the PTC crankcase heater is recommended.
PSC wiring may be used for refrigerant circuits with capillary tubes or expansion valves with bleed ports. Pressure equalisation must be ensured before start-up because of the low starting torque characteristics of this system.
CSR wiring provides additional motor torque at start-up, by the use of a start capacitor in combination with the run capacitor. This system can be used for refrigerant circuits with capillary tubes or expansion valves. The start capacitor is only connected during the starting operation, a potential relay is used to disconnect it after the start sequence.
The single phase compressor motors are internally protected by a temperature/current sensing bimetallic protector, which senses the main and start winding currents, and also the winding temperature. Once the protector has tripped, it may take up to two to four hours to reset and restart the compressor.
Check that power supply corresponds to compressor characteristics (refer to compressor nameplate).
13
ELECTRICAL CONNECTIONS AND WIRING
Suggested wiring diagrams
Single phase
PSC wiring with trickle circuit
C Common
S Start winding (auxiliary)
R Run winding (main)
Single phase
CSR wiring with trickle circuit
C Common
S Start winding (auxiliary)
R Run winding (main)
Single phase
CSR wiring without trickle circuit
C Common
S Start winding (auxiliary)
R Run winding (main)
Capacitors A and C are replaced by a single capacitor of size A + C
14
ELECTRICAL CONNECTIONS AND WIRING
Three phase electrical characteristics
Motor Code
MT/MTZ018
MT/MTZ022
MT/MTZ028
MT/MTZ032
MT/MTZ036
MT/MTZ040
MT/MTZ044
MT/MTZ045
MT/MTZ050
MT/MTZ051
MT/MTZ056
MT/MTZ057
MT/MTZ064
MT/MTZ065
MT/MTZ072
MT/MTZ073
MT/MTZ080
MT/MTZ081
MT/MTZ100
MT/MTZ 125
MT/MTZ 144
MT/MTZ 160
Motor protection and suggested wiring diagrams
LRA - Locked Rotor
Current (A)
57
60
74
3
38
38
98
115
38
42
115 48.5
115 42
120 48.5
130 60
130
137
64
67
23
25
30
4
20
16
135
135
155
140
140
157
64
80
80
80
80
90
210 105 170
259 115 208
259 140 208
-
143
-
132
-
126
74
77
-
77
-
105
-
124
-
44
74
6
30
-
-
-
62
-
-
-
75
90
99
44
-
50
-
-
-
44
-
-
22
26
7
-
-
MCC - Maximum
Continuous Current (A)
-
100
-
102
-
110
150
165
165
78
-
72
-
78
-
-
72
9
-
3
9
22.5
11
32
35
35
16
18
17
22
22
17
10
9.5
9.5
25 12
22 11.5
26 12
24
29
12
15
4
5
6
6
7
8.5
7.5
11.5
8 13
9 17
19
-
23
18
16
-
-
25
36
36
43
28 14 -
30 15.5
27
32 17 -
54
64
70
18
19
22
27
30
36
29
-
35
43
51
51
Winding resistance (Ω)
( ± 7 % at 20° C)
-
-
17
-
-
-
22
25
29
-
5.5
7
7
-
-
9
-
6
3 4 6
2.49
10.24
3.38
2.49
10.24
3.38
7
-
-
9
-
6.58
8.5
1.37
7.11
2.30
9 1.27
6.15
1.27
-
8.90
4.80
4.20
9.5
1.16
5.57
1.16
8.60
4.10
-
8.5
-
-
-
0.95
4.56
0.95
-
13 0.74
3.80
1.13
5.83
1.68
0.69
3.22
-
10 13.5
0.72
3.80
1.39
5.83
1.68
0.69
3.60
-
11 15 0.57
2.41
0.76
3.86
-
0.55
2.39
-
17.5
0.57
2.41
0.76
-
-
1.64
-
-
-
0.55
2.39
0.48
0.48
1.90
1.90
-
18.5
0.55
1.90
0.56
-
22.5
0.48
1.90
0.56
-
-
-
-
-
-
1.32
-
1.30
-
26 0.50
1.85
0.67
3.10
1.26
30 0.38
1.57
0.43
2.51
0.84
40 0.27
1.19
0.37
2.00
0.72
46 0.27
1.10
0.37
1.76
1.10
The 3-phase compressors are protected by an internal motor protector, connected to the neutral point of the star connected stator windings, the protector cuts out all 3-phases simultaneously.
Note: once the overload protector has tripped it may take up to 3 hours to reset and restart the compressor.
For all 3-phase compressors, a PTC crankcase heater is required.
Wiring diagram with pump-down cycle
Control device
.............................................................................................
TH
Optional short cycle timer (3 min) 5 pts
........
180 s
Control relay
...................................................................................................
KA
Liquid Solenoid valve
.................................................................
LLSV
Compressor contactor
....................................................................
KM
Safety lock out relay
.............................................................................
KS
Pump-down control & L.P. switch
....................................
BP
H.P. switch
..........................................................................................................
HP
Fused disconnect
....................................................................................
Q1
Fuses
............................................................................................................................
F1
External overload protection
..................................................
F2
Compressor motor
...................................................................................
M
Motor safety thermostat
.......................................................... thM
Discharge gas thermostat
.....................................................
DGT
15
ELECTRICAL CONNECTIONS AND WIRING
Wiring diagram without pump-down cycle
Control device
.............................................................................................
TH
Optional short cycle timer (3 min) 5 pts
........
180 s
Control relay
...................................................................................................
KA
Compressor contactor
....................................................................
KM
Safety lock out relay
.............................................................................
KS
H.P. switch
..........................................................................................................
HP
Fused disconnect
....................................................................................
Q1
Fuses
............................................................................................................................
F1
External overload protection
..................................................
F2
Compressor motor
...................................................................................
M
Discharge gas thermostat
.....................................................
DGT
Soft starters
Voltage application range
Starting current of Maneurop® 3phase compressors can be reduced by using a soft starter. Two diff erent versions are available: CI-tronic
TM
soft starters type MCI (recommended) and soft start kits with statoric resistors type SCR. The starting current can be reduced by up to 50% depending on the compressor model and the type of soft starter. Also mechanical stresses that occur at starting are reduced
Motor Code
1
3
4
5
6
7
9
which increases the life of the internal components.
For details of the CI-tronic
TM
MCI soft starters, please refer to literature
DKACT.PD.C50.C1.02.
For details of the SCR soft start kits, please contact Danfoss.
The number of starts should be limited to 6 per hour. HP/LP pressure equalisation is required before starting.
Nominal voltage
208-230 V / 1 ph / 60 Hz
200-230 V / 3 ph / 60 Hz
400 V / 3 ph / 50 Hz
460 V / 3 ph / 60 Hz
230 V / 1 ph / 50 Hz
230 V / 3 ph / 50 Hz
500 V / 3 ph / 50 Hz
575 V / 3 ph / 60 Hz
380 V / 3 ph / 60 Hz
Voltage application range
187 - 253 V
180 - 253 V
360 - 440 V
414 - 506 V
207 - 253 V
207 - 253 V
450 - 550 V
517 - 632 V
342 - 418 V
IP rating
The compressor terminal boxes IP rating according to CEI 529 are shown on the outline drawings section.
The IP ratings are only valid when correctly sized cable glands of the same IP rating are applied.
16
REFRIGERANTS AND LUBRICANTS
General information
Refrigerant
R22
R407C
R134a
R404A
R507A
Transitional refrigerants,
R22 based
Hydrocarbons
Type
HCFC
HFC
HFC
HFC
HFC
When choosing a refrigerant, diff erent aspects must be taken into consideration:
• Legislation (now and in the future)
• Safety expected running conditions fi nal choice:
• Environmental considerations lubricants
• Refrigerant cost
• Refrigerant availability
The table below gives an overview of the diff erent refrigerant - lubricant - compressor combinations for
Maneurop®‚ MT & MTZ compressors.
mendations & guidelines
Additional points could infl uence the
Lubricant type
Mineral
Polyolester
Polyolester
Compressor type
MT
Danfoss lubricant
White oil, 160P
MTZ
MTZ
Polyolester oil 160PZ
Polyolester oil 160PZ
Application
Medium / High temperature
Medium / High temperature
Medium / High temperature
Polyolester
Polyolester
MTZ
MTZ
Polyolester oil 160PZ
Polyolester oil 160PZ
Medium temperature
Medium temperature
Alkylbenzene
(ABM)
MT
Alkylbenzene oil 160 ABM
Note: Initial mineral oil charge has to be replaced by 160 ABM oil.
Medium / High temperature
Danfoss does not authorise the use of hydrocarbons in Maneurop® MT/MTZ compressors
The Montreal protocol states that CFC refrigerants such as R12 and R502 may no longer be applied in new installations in the signatory members countries.
Therefore capacity and other data for these refrigerants are not published in this document. Maneurop® MT compressors however are suitable for use with these refrigerants and can still be used as replacements in existing installations.
R22
R407C
R22 is an HCFC refrigerant and is still a wide use today. It has a low ODP (Ozone Depletion Potential) and therefore it will be phased out in the future.
Check local legislation. Always use mineral white oil 160P.
The Maneurop® MT compressor is dedicated for R22 and is supplied with an initial mineral oil charge.
Refrigerant R407C is an HFC refrigerant with similar thermodynamic properties to those of R22.
R407C has zero ozone depletion potential (ODP=0). Many installers and OEMs consider R407C to be the standard alternative for R22. R407C is a zeotropic mixture and has a temperature glide of about 6 K. For more specifi c information about zeotropic refrigerants; refer to section «zeotropic refrigerant mixtures». R407C must be charged in the liquid phase.
Always use the Maneurop® MTZ compressors with Danfoss 160PZ polyolester oil, which is supplied with the MTZ compressor for R407C applications.
Maneurop® MT compressors should never be used with R407C, even when the mineral oil is replaced with polyolester oil.
17
REFRIGERANTS AND LUBRICANTS
R134a
Refrigerant R134a is an HFC refrigerant with thermodynamic properties comparable to those of the CFC refrigerant R12. R134a has zero ozone depletion potential (ODP = 0) and is commonly accepted as the best
R12 alternative. For applications with high evaporating and high condensing temperatures, R134a is the ideal choice. R134a is a pure refrigerant and has zero temperature glide. For R134a applications always use the Maneurop® MTZ compressor with Danfoss
160PZ polyolester oil which is supplied with the MTZ compressor.
Maneurop® MT compressors should never be used for R134a, even when the mineral oil is replaced by polyolester oil.
R404A
R507A
Refrigerant R404A is an HFC refrigerant with thermodynamic properties comparable to those of the CFC refrigerant
R502. R404A has zero ozone depletion potential (ODP = 0) and is commonly accepted as one of the best R502 alternatives. R404A is especially suitable for low evaporating temperature applications but it can also be applied to medium evaporating temperature applications. R404A is a mixture and has a very small temperature glide, and therefore must be charged in its liquid phase, but for most other aspects this small glide can be neglected. Because of the small glide, R404A is often called a near-azeotropic mixture. For more information refer to section «zeotropic refrigerant mixtures». For low evaporating temperature applications down to -45°C, Maneurop® NTZ compressors should be used. Refer to the NTZ selection and application guidelines.
For medium temperature R404A applications, always use the Maneurop®
MTZ compressor with 160PZ polyolester oil which is supplied with the MTZ compressor.
Maneurop® MT compressors should never be used for R404A, even with the mineral oil replaced by polyolester oil.
Refrigerant R507A is an HFC refrigerant with thermodynamic properties comparable to those of the CFC refrigerant R502 and virtually equal to those of R404A. R507A has no ozone depletion potential (ODP = 0) and is commonly accepted as one of the best R502 alternatives. As with R404A,
R507A is particularly suitable for low evaporating temperature applications but it can also be used for medium evaporating temperature applications.
R507A is an azeotropic mixture with no temperature glide. For low evaporating temperature applications down to -45°C, Maneurop® NTZ compressor should be used. Refer to the NTZ selection and application guidelines. For medium temperature R507A applications, always use the Maneurop® MTZ compressor and Maneurop® 160PZ polyolester oil which is supplied with the MTZ compressor.
Maneurop® MT compressors should never be used for R507A, even with the mineral oil replaced by polyolester oil.
R22 based transitional refrigerants
Hydrocarbons
A wide variety of R22 based transitional refrigerants exist (also called service refrigerants or drop-in blends). These were developed as temporary R12 or R502 alternatives. Some examples are R401A, R401B, R409A and R409B as R12 alternatives and R402A, R402B,
R403A and R403B as R502 alternatives.
Because of the R22 component, they all have a (low) ozone depletion potential. Maneurop® MT compressors can be applied with these transitional refrigerants. The initial mineral oil charge must be replaced by Maneurop®160 ABM alkylbenzene oil.
Hydrocarbons such as propane, isobutane etc. are extremely fl ammable.
Danfoss does not authorise the use of hydrocarbons with Maneurop® MT or MTZ compressors in any way, even with a reduced refrigerant charge.
18
SYSTEM DESIGN RECOMMENDATIONS
Piping desing
Oil in a refrigeration circuit is required to lubricate moving parts in the compressor. During normal system operation small oil quantities will continuously leave the compressor, with the discharge gas. With good system piping design this oil will return to the compressor. As long as the amount of oil circulating through the system is small it will contribute to good system operation and improved heat transfer of oil in the system will have a negative eff ect on condenser and evaporator tem, the amount of oil returning to the compressor is lower than the amount of oil leaving the compressor, the compressor will become starved of oil and the condenser, evaporator and/or refrigerant lines will become fi lled with oil. In such situations, additional oil charge will only correct the compressor oil level for a limited period of time and increase the amount of surplus oil in the rest of the system.
Only correct piping design can ensure a good oil balance in the system.
Suction lines
Horizontal suction line sections shall have a slope of 0.5% in the direction of refrigerant fl ow (5 mm per meter).
The cross-section of horizontal suction lines shall be such that the resulting gas velocity is at least 4 m/s. In vertical risers, a gas velocity of 8 to 12 m/s is required to ensure proper oil return. A
U-trap is required at the foot of each vertical riser. If the riser is higher than
4 m, additional U-traps are required for each additional 4 meters. The length of each U-trap must be as short as possible to avoid the accumulation of excessive quantities of oil (see fi gure below).
For compressors mounted in parallel, the common suction riser should be designed as a double riser. Also refer to the News bulletin "Mounting instructions for installation of Maneurop® compressors in parallel " and " Parallel application guidelines".
Gas velocities higher than 12 m/s will not contribute to signifi cantly better oil return. However they will cause higher noise levels and result in higher suction line pressure drops which will have a negative eff ect on the system capacity.
19
SYSTEM DESIGN RECOMMENDATIONS
Note that the suction rotolock valves, which can be ordered from Danfoss as accessories, are designed for average pipe sizes, selected for systems running at nominal conditions.
The pipe sizes selected for specifi c systems may diff er from these recommended sizes.
It is recommended that the suction lines are insulated to limit suction gas superheat.
Discharge line
When the condenser is mounted above the compressor, a loop above the condenser and a U-trap close to the compressor are required to prevent liquid draining from the condenser into the discharge line during standstill.
Oil charge and oil separator
Filter driers
In most installations the initial cominstallations with line runs exceeding
20 m, or with many oil traps or an oil separator, additional oil may be required. In installations with the risk of slow oil return such as in multiple evaporator or multiple condenser installations, an oil separator is recommended. Also refer to page 29.
For new installations with MTZ compressors Danfoss recommends using the Danfoss DML 100%-molecular sieve, solid core fi lter drier. Molecular sieve fi lter driers with loose beads from third party suppliers shall be avoided.
For servicing of existing installations where acid formation is present the
Danfoss DCL solid core fi lter driers containing activated alumina are recommended.
The drier is to be oversized rather than undersized. When selecting a drier, always take into account its capacity
(water content capacity), the system refrigerating capacity and the system refrigerant charge.
Operating limits
High Pressure
A high pressure safety switch is required to stop the compressor, should the discharge pressure exceed the values shown in the table below. The high pressure switch can be set to lower values depending on the application and ambient conditions. The HP switch must either be in a lockout circuit, or be a manual reset device to prevent compressor cycling around the high pressure limit. When a discharge valve is used, the HP switch must be connected to the service valve gauge port, which cannot be isolated.
20
SYSTEM DESIGN RECOMMENDATIONS
Low pressure
Test pressure low side
Working pressure range high side
Working pressure range low side
Relief valve opening pressure diff erence
Relief valve closing pressure diff erence
A low pressure safety switch is recommended to avoid compressor operabar (g)
MT
R22
25
MTZ
R407C
25 tion at too lower suction pressures.
MTZ
R134a
25
MTZ
R404A / R507A
25 bar (g) bar (g) bar (g) bar (g)
10.9 - 27.7
1.0 - 7.0
30
8
12.5 - 29.4
1.4 - 6.6
30
8
7.9 - 22.6
0.6 - 4.7
30
8
13.2 - 27.7
1.0 - 7.2
30
8
Low ambient temperature operation
At low ambient temperatures, the condensing temperature and condensing pressure in air cooled condensers will decrease.
to supply enough liquid refrigerant to the evaporator. As a result the evaporator temperature will strongly decrease with the risk of frosting. At compressor start-up, the compressor can pull a deep vacuum and it can be switched off by the low pressure protection. Depending on the low pressure switch setting and delay timer short cycling can occur. To avoid these problems, several solutions are possible, based on reducing condenser capacity:
• Indoor location of condensers
• Liquid fl ooding of condensers (note: this solution requires extra refrigerant charge, which can introduce other problems. A non-return valve in the discharge line is required and special care should be taken when designing the discharge line.)
• Reduce air fl ow to condensers.
Other problems can also occur when the compressor is operating at low ambient temperature. During shut down periods, liquid refrigerant can migrate to a cold compressor.
For such conditions a belt-type crankcase heater is strongly recommended.
Note that with 100% suction gas cooled motors, Maneurop® compressors can be externally insulated.
Refer to section «Liquid refrigerant migration & charge limits» for more details.
Operating voltage and cycle rate
Operating voltage range
Cycle rate limit
The operating voltage limits are shown in the table on page 4. The voltage applied to the motor terminals must always be within these table limits. The maximum allowable voltage unbalance for 3-phase compressors is 2%. Voltage unbalance causes high current draw on one or more phases, which in turn leads to overheating and possible motor damage.
Voltage unbalance is given by the formula:
% voltage unbalance:
|V avg
- V
1-2
|+|V avg
- V
1-3
|+|V avg
- V
2-3
|
Vavg = Mean voltage of phases 1, 2 and 3
V1-2 = Voltage between phases 1 and 2 x 100
2 xV avg
V1-3 = Voltage between phases 1 and 3
V2-3 = Voltage between phases 2 and 3.
There may be no more than 12 starts per hour (6 when a soft start accessory is used). A higher number reduces the service life of the motor-compressor unit. If necessary, use an anti-short-cycle timer in the control circuit.
A time-out of six minutes is recommended. The system must be designed in such a way to guarantee a minimum compressor running time in order to provide proper oil return and
Note that the oil return rate varies as a function of the system design.
21
SYSTEM DESIGN RECOMMENDATIONS
Liquid refrigerant control and charge limits
Refrigeration compressors are basically designed as gas compressors. Depending on the compressor design and operating conditions, most compressors can also handle a limited amount of liquid refrigerant. Maneurop® MT and MTZ compressors have a large internal volume and can therefore handle relatively large amounts of liquid refrigerant without major problems.
However even when a compressor can handle liquid refrigerant, this will not be favourable to its service life. Liquid refrigerant can dilute the oil, wash oil out of bearings and result in high oil carry over, resulting in loss of oil from the sump. Good system design can limit the amount of liquid refrigerant in the compressor, which will have a positive eff ect on the compressor service life.
Liquid refrigerant can enter a compressor in diff erent ways, with diff erent eff ects on the compressor.
Off -cycle migration
Liquid fl oodback during operation
During system standstill and after pressure equalisation, refrigerant will condense in the coldest part of the system. The compressor can easily be the coldest spot, for example when it is placed outside in low ambient temperatures. After a while, the full system refrigerant charge can condense in the compressor crankcase. A large amount will dissolve in the compressor oil until the oil is completely saturated with refrigerant. If other system components are located at a higher level, this process can be even faster because gravity will assist the liquid refrigerant to fl ow back to the compressor. When the compressor is started, the pressure in the crankcase decreases rapidly.
At lower pressures the oil holds less refrigerant, and as a result part of the refrigerant will violently evaporate from the oil, causing the oil to foam.
This process is often called “boiling”.
The negative eff ects from migration on the compressor are:
• oil dilution by liquid refrigerant
• oil foam, transported by refrigerant gas and discharged into the system, causing loss of oil and in extreme situations risk for oil slugging
• in extreme situations with high system refrigerant charge, liquid slugging could occur (liquid entering the compressor cylinders).
During normal and stable system operation, refrigerant will leave the evaporator in a superheated condition and enter the compressor as a superheated vapour.
Normal superheat values at compressor suction are 5 to 30 K. However the refrigerant leaving the evaporator can contain an amount of liquid refrigerant due to diff erent reasons:
• wrong dimensioning, wrong setting or malfunction of expansion device
• evaporator fan failure or blocked air fi lters.
In these situations, liquid refrigerant will continuously enter the compressor.
The negative eff ects from continuous liquid fl oodback are:
• permanent oil dilution
• in extreme situations with high system refrigerant charge and large amounts of fl oodback, liquid slugging could occur.
Liquid fl oodback at change over cycles in reversible heat pumps
Liquid fl oodback and zeotropic refrigerants
I n heat pumps, change over from cooling to heating cycles, defrost and low load short cycles may lead to liquid refrigerant fl oodback or saturated refrigerant return conditions.
The negative eff ects are:
• oil dilution
• in extreme situations with high system refrigerant charge and large amounts of fl oodback, liquid slugging could appear.
Liquid fl oodback in systems working with a zeotropic refrigerant such as
R407C introduces additional negative eff ects. A part of the refrigerant leaves the evaporator in liquid phase and this liquid has a diff erent composition than the vapour.
This new refrigerant composition may result in diff erent compressor operating pressures and temperatures.
22
SYSTEM DESIGN RECOMMENDATIONS
Crankcase heater
A crankcase heater protects against the off -cycle migration of refrigerant and proves eff ective if oil temperature is maintained 10 K above the saturated LP temperature of the refrigerant.
Tests must thereby be conducted to ensure that the appropriate oil temperature is maintained under all ambient conditions. A PTC crankcase heater is recommended on all stand-alone compressors and split systems. PTC crankcase heaters are self-regulating.
Under extreme conditions such as very low ambient temperature a belt type crankcase heater could be used in addition to the PTC heater, although this is not a preferred solution for 1 and 2 cylinder compressors. The belt crankcase heater must be positioned on the compressor shell as close as possible to the oil sump to ensure good heat transfer to the oil.
Belt crankcase heaters are not self-regulating. Control must be applied to energise the belt heater once the compressor has been stopped and then to de-energise it while the compressor is running. The belt heater must be energised 12 hours before restarting the compressor following an extended down period.
If the crankcase heater is not able to maintain the oil temperature at 10 K above the saturated LP temperature of the refrigerant during off cycles or if repetitive fl oodback is present a the
Liquid Line Solenoid Valve (LLSV) + pump-down cycle is required, eventually in conjunction with a suction accumulator.
Liquid line solenoid valve
& pump-down
In refrigeration applications, the Liquid Line Solenoid Valve (LLSV) is highly recommended. During the off -cycle, the LLSV isolates the liquid charge in the condenser side, thus preventing against refrigerant transfer or excessive migration of refrigerant into the compressor. Furthermore, when using a LLSV in conjunction with a pumpdown cycle, the quantity of refrigerant in the low-pressure side of the system will be reduced.
A pump-down cycle design is required when evaporators are fi tted with electric defrost heaters.
Suction accumulator
A suction accumulator off ers considerable protection against refrigerant fl oodback at start-up, during operation or after the defrost operation. This device also helps to protect against off -cycle migration by means of providing additional internal free volume to the low pressure side of the system.
The suction accumulator must be selected in accordance with the accumulator manufacturer recommendations.
As a general rule, Danfoss recommends to size the accumulator for at least 50% of the total system charge.
Tests however must be conducted to determine the optimal size.
A suction accumulator shall not be used in systems with zeotropic refrigerant mixtures.
23
SOUND AND VIBRATION MANAGEMENT
Sound
Sound power level for MTZ with R404A, motor code 4
Te = -10°C,
TC = 45°C
* Sound data with hood are valid for the Danfoss acoustic hood accessory.
Running compressors cause sound and vibration. Both phenomena are closely related.
Sound produced by a compressor is transmitted in every direction by the ambient air, the mounting feet, the pipework and the refrigerant in the pipework.
The easiest way to reduce the sound transmitted through ambient air is to fi t a Danfoss acoustic hood accessory.
Because Maneurop® compressors are
100% suction gas cooled, and require no body cooling, they can be insulated. Values for the sound reduction achieved with acoustic hoods are shown also in the table on the right.
For inside mounted compressors, sound insulation of the plantroom is an alternative to sound insulation of the compressor.
Sound transmitted by mounting feet, pipework and refrigerant should be treated the same way as for vibration.
Please refer to the next section.
MTZ051
MTZ056
MTZ057
MTZ064
MTZ065
MTZ072
MTZ073
MTZ080
MTZ081
MTZ100
MTZ125
MTZ144
MTZ160
MTZ018
MTZ022
MTZ028
MTZ032
MTZ036
MTZ040
MTZ044
MTZ045
MTZ050
Model
MT/MTZ018 - 040
MT/MTZ044 - 081
MT/MTZ100 - 160
Sound power level at 50 Hz dB(A) without hood with hood*
85
84
83
83
79
79
79
79
83
81
81
80
80
73
74
71
71
70
70
80
80
83
79
78
77
77
72
72
73
73
76
74
74
74
74
65
68
64
64
64
65
74
74
76
Acoustic hood accessory
Acoustic hood for 1 cyl compressors
Acoustic hood for 2 cyl compressors
Acoustic hood for 4 cyl compressors
Sound power level at 60 Hz dB(A) without hood with hood*
87
86
86
86
82
82
84
84
84
81
81
84
84
73
77
73
73
76
72
82
82
84
81
80
80
80
75
75
78
78
78
74
74
78
78
66
71
66
66
69
67
76
76
78
code no.
7755001
7755002
7755003
24
SOUND AND VIBRATION MANAGEMENT
Vibration
The mounting grommets delivered with the compressor should always be used. They reduce the vibration transmitted by the compressor mounting feet to the base frame.
The base on which the compressor is
Care must be taken to avoid tubing having resonant frequencies close to those of the compressor frequency.
Vibration is also transmitted by the refrigerant gas. Maneurop®‚ compresthis vibration.
To further reduce vibration an extra and of adequate mass to ensure the full eff ectiveness of the mounting grommets.
The compressor should never be directly mounted to the base frame without the grommets, otherwise high vibration transmission would occur and the compressor service life reduced. Suction and discharge lines must have adequate fl exibility in 3 planes.
Eventually vibration absorbers may be required.
Note: Maneurop® MT & MTZ compressors have been designed and qualifi ed for stationary equipment used in A/C and Refrigeration applications.
Danfoss doesn’t warrant these compressors for use in mobile applications, such as trucks, railways, subways, etc...
25
INSTALLATION AND SERVICE
System cleanliness
System contamination is one of the main factors aff ecting equipment reliability and compressor service life.
Therefore it is important to ensure system cleanliness when manufacturing a refrigeration system. During the manufacturing process, system contamination can be caused by:
• Brazing and welding oxides
• Filings and particles from removing burrs from pipe-work
• Brazing fl ux
• Moisture and air.
Only use clean and dehydrated refrigeration grade copper tubes and silver alloy brazing material. Clean all parts before brazing and always purge nitrogen or CO
2
through the pipes during brazing to prevent oxidation. If fl ux is used, take every precaution to prevent leakage into the piping. Do not drill holes (e.g. for schräder valves) in parts of the installation that are already completed, when fi lings and burrs can not be removed. Carefully follow the instructions below regarding brazing, mounting, leak detection, pressure test and moisture removal. All installation and service work shall only be done by qualifi ed personnel respecting all procedures and using tools (charging systems, tubes, vacuum pump, etc.) dedicated for the refrigerant that will be used.
Compressor handling, mounting and connection to the system
Compressor handling
Maneurop® MT and MTZ compressors are provided with a lifting lug. This lug should always be used to lift the compressor. Once the compressor is installed, the compressor lifting lug should never be used to lift the complete installation.
Keep the compressor in an upright position during handling.
Compressor mounting
Mount the compressor on a horizontal plane with a maximum slope of 3 degrees. All compressors are supplied with three or four rubber mounting grommets, each complete with metal sleeves and nuts and bolts. Refer to the outline drawings on page 18 to 21.
These grommets largely attenuate the compressor vibration transmitted to the base frame. The compressor must always be mounted with these grommets. Refer to the table below for torque values.
Designation
Cable screw of T connector in electrical box
Rotolock valves and solder sleeves
Mounting grommet bolts
Oil sight glass
Oil equalisation connection screw 10/32 - UNF x 3
1"
1"1/4
1"3/4
1 - 2 - 4 cylinder
-
1 - 2 - 4 cylinder
Recommended torque
(Nm)
3
80
90
110
15
50
30
Compressor connection to the system
New compressors have a protective nitrogen holding charge. The suction and discharge caps should only be removed just before connecting the compressor to the installation to avoid air and moisture entering the compressor.
Whenever possible the compressor must be the last component to be integrated in the system. It is advisable to braze the solder sleeves or service valves to the pipework before the compressor is mounted. When all brazing is fi nished and when the total
26
INSTALLATION AND SERVICE
system is ready, the compressor caps can be removed and the compressor can be connected to the system with a minimum exposure to ambient air.
If this procedure is not possible, the sleeves or valves may be brazed to the pipes when mounted on the compressor.
In this situation nitrogen or CO
2
must be purged through the compressor via the schräder valve to prevent air and moisture ingress. Purging must start when the caps are removed and proceeded during the brazing process.
When rotolock valves are used on the compressor, they shall be closed immediately after mounting, thus keeping the compressor isolated from atmosphere or from a not yet dehydrated system.
Note: When the compressor is built into a ”pack” or “rack” confi guration which is not installed immediately on its fi nal location, a vacuum pull-down and moisture removal must be performed to this pack (rack) as if it were a complete system (see below). The pack must be charged with nitrogen or CO
2 and open tubes must be blocked with caps or plugs.
System pressure test
Leak detection
It is recommended that an inert gas such as nitrogen be used for pressure testing. Dry air may also be used but care should be taken since it can form an infl ammable mixture with the compressor oil. When performing a system
Maximum compressor test pressure, low side
Maximum compressor test pressure, high side pressure test, the maximum allowed pressure for the diff erent components should not be exceeded.
For MT/MTZ compressors the maximum test pressures are shown in the table below.
1-2-4 cylinder compressors
25 bar(g)
30 bar(g)
Do not exceed 30 bar pressure diff erence between high pressure side and low pressure side of the compressor because this will open the internal compressor relief valve.
Whenever possible (if valves are present) the compressor must be kept isolated from the system. Perform a leak detection using the fi nal refrigerant.
Pressurise with nitrogen or another neutral gas and use a leak detector for the applied refrigerant. Any spectrometric detection system using helium can also be applied.
Eventual leaks shall be repaired respecting the instructions written above. It is not recommended to use other gasses such as oxygen, dry air or acetylene as these gasses can form an
27
INSTALLATION AND SERVICE
Vacuum pull-down moisture removal
Start-up
Refrigerant charging
infl ammable mixture. Never use CFC or HCFC refrigerants for leak detection of HFC systems.
Note 1: Leak detection with refrigerant may not be allowed in some countries.
Check local regulations.
Note 2: Leak detecting additives shall not be used as they may aff ect the lubricant properties.
Warranty may be voided if leak detecting additives have been used.
Moisture obstructs the proper functioning of the compressor and the refrigeration system.
Air and moisture reduce service life and increase condensing pressure, and cause excessively high discharge temperatures, which can destroy the lubricating properties of the oil. Air and moisture also increase the risk of acid formation, giving rise to copper platting. All these phenomena can cause mechanical and electrical compressor failure.
To eliminate these factors, a vacuum pull-down according to the procedure below is recommended:
1. Whenever possible (if valves are present) the compressor must be kept isolated from the system.
2. After the leak detection, the system must be pulled-down under a vacuum of 500 microns (0.67 mbar). A two stage vacuum pump shall be used with a capacity appropriate to the system volume. It is recommended to use connection lines with a large diameter and to connect these to the service valves and not to the schrader connection to avoid too high pressure losses.
3. When the vacuum level of 500 micron is reached, the system must be isolated from the vacuum pump. Wait
30 minutes during which the system pressure should not rise. When the pressure rapidly increases, the system is not leak tight.
A new leak detection must be performed and the vacuum pull-down procedure should be restarted from step 1. When the pressure slowly increases, this indicates the presence of moisture. In this case step 2 and 3 should be repeated.
4. Connect the compressor to the system by opening the valves. Repeat step 2 and 3.
5. Break the vacuum with nitrogen or the fi nal refrigerant.
6. Repeat step 2 and 3 on the total system.
At commissioning, system moisture content may be up to 100 ppm. During operation the fi lter drier must reduce this to a level < 20 ppm.
Warning :
Do not use a megohmmeter or apply power to the compressor while it is under vacuum, as this may cause motor winding damage.
Never run the compressor under vacuum as it may cause compressor motor burn-out.
Before initial start-up or after a prolonged shut down period, energise the crankcase heater (if fi tted) 12 hours prior to start-up, or turn on power for single phase compressors with trickle circuit.
Zeotropic and «near-azeotropic» refrigerant mixtures such as R407C and
R404A must always be charged in the liquid phase. For the initial charge, the compressor must not run and service valves must be closed. Charge refrigerant as close as possible to the nominal system charge before starting the compressor. Then slowly add refrigerant in the liquid phase, on the low pressure side as far away as possible from the running compressor.
The refrigerant charge quantity must be suitable for both winter and summer operation. Refer also to section
«Protection against fl ooded starts and liquid fl oodback» for information about refrigerant charge limits.
Warning: when a liquid line solenoid valve is used, the vacuum in the low pressure side must be broken before applying power to the system.
28
INSTALLATION AND SERVICE
Oil charge and oil level
The oil charge must be checked before commissioning (1/4 to 3/4 of the oil sight glass). Check the oil level again after a minimum of 2 hours operation at nominal conditions. In most installations the initial compressor oil charinto account oil contained in accessories such as oil separators or oil traps).
If this amount has already been added and the oil level in the compressor keeps decreasing, the oil return in the with line runs exceeding 20 m or with many oil traps or an oil separator, additional oil may be required. Normally the quantity of oil added should be no more than 2% of the total refrigerant charge (this percentage does not take section "Piping design".
In installations where slow oil return is likely such as in multiple evaporator or multiple condenser installations, an oil separator is recommended. Refer to the table on page 17 to select the correct oil.
Suction gas superheat
The optimum suction gas superheat is
8 K. A lower superheat value will contribute to better system performance (hiof evaporator surface). Low super heat values however increase the risk of unwanted liquid fl oodback to the compressor.
For very low superheat values an electronically controlled expansion valve is recommended.
The maximum allowable superheat is about 30 K. Higher values can be accepted but in these cases, tests have to be performed to check that the maximum discharge temperature of
130°C will not be exceeded. Note that high superheat values decrease the compressor application envelope and system performance.
29
ACCESSORIES AND SPAREPARTS
The below tables show an extract of the available accessories and spareparts for Maneurop® reciprocating compres-
Rotolock accessories
Type Code no.
Description
G01
G01
G09
G09
G07
G07
V06-V01 7703004
Valve set, V06 (1"~1/2"), V01 (1"~3/8")
V09-V06 7703005
Valve set, V09 (1-1/4"~5/8"), V06 (1"~1/2")
V07-V04 7703006
Valve set, V07 (1-3/4"~7/8"), V04 (1-1/4"~3/4")
V02-V04 7703009
Valve set, V02 (1-3/4"~1-1/8"), V04 (1-1/4"~3/4")
C06-C01 7703011
Angle adapter set, C06 (1"~1/2"), C01 (1"~3/8")
C09-C06 7703012
Angle adapter set, C09 (1-1/4"~5/8"), C06 (1"~1/2")
C07-C04 7703013
Angle adapter set, C07 (1-3/4"~7/8"), C04 (1-1/4"~3/4")
C02-C04 7703014
Angle adapter set, C02 (1-3/4"~1-1/8"), C04 (1-1/4"~3/4")
8156130
7956001
8156131
7956002
8156132
7956003
8156009
Gasket, 1"
Gasket, 1"
Gasket, 1-1/4"
Gasket, 1-1/4"
Gasket, 1-3/4"
Gasket, 1-3/4"
Gasket set, 1", 1-1/4", 1-3/4", Oil sight glass gaskets black & white sors. For an exhaustive list please refer to Accessories & Spareparts catalogue, ref. FRCC.EK.002.A1.02
Application Packaging Pack size
MT/MTZ018-028 (exept 028 code 1)
MT/MTZ032-040 (& 028 code 1)
MT/MTZ044-072
MT/MTZ080-160
MT/MTZ018-028 (exept 028 code 1)
MT/MTZ032-040 (& 028 code 1)
MT/MTZ044-072
MT/MTZ080-160
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Models with 1" rotolock connection
Models with 1" rotolock connection
Multipack
Industry pack
Models with 1-1/4" rotolock connection Multipack
Models with 1-1/4" rotolock connection Industry pack
Models with 1-3/4" rotolock connection Multipack
Models with 1-3/4" rotolock connection Industry pack
10
50
10
50
10
50
6
6
4
4
6
6
4
4
All 1-2-4 cylinder models Multipack 10
Crankcase heaters
Type Code no.
Description
PTC35W 7773001
PTC crankcase heater, 35 W, incl. heat transfer paste
PTC35W 7973009
PTC crankcase heater, 35 W, incl. heat transfer paste
PTC35W 7773125
PTC crankcase heater, 35 W, mounting without paste
PTC35W 7973011
PTC crankcase heater, 35 W, mounting without paste
7773106
Belt type crankcase heater, 55 W, 230 V, CE mark, UL
7773002
Belt type crankcase heater, 54 W, 240 V, UL
7773013
Belt type crankcase heater, 54 W, 400 V, UL
7773111
Belt type crankcase heater, 54 W, 460 V, UL
7773109
Belt type crankcase heater, 65 W, 110 V, CE mark, UL
7973001
Belt type crankcase heater, 65 W, 110 V, CE mark, UL
7773107
Belt type crankcase heater, 65 W, 230 V, CE mark, UL
7973002
Belt type crankcase heater, 65 W, 230 V, CE mark, UL
7773117
Belt type crankcase heater, 65 W, 400 V, CE mark, UL
7773010
Belt type crankcase heater, 50 W, 110 V, UL
7773003
Belt type crankcase heater, 50 W, 240 V, UL
7773009
Belt type crankcase heater, 50 W, 400 V, UL
7773006
Belt type crankcase heater, 50 W, 460 V, UL
7773119
Belt type crankcase heater, 75 W, 575 V, UL
7773110
Belt type crankcase heater, 75 W, 110 V, CE mark, UL
7773108
Belt type crankcase heater, 75 W, 230 V, CE mark, UL
7973005
Belt type crankcase heater, 75 W, 230 V, CE mark, UL
7773118
Belt type crankcase heater, 75 W, 400 V, CE mark, UL
7773004
Belt type crankcase heater, 75 W, 240 V, UL
7773014
Belt type crankcase heater, 75 W, 400 V, UL
7773008
Belt type crankcase heater, 75 W, 460 V, UL
7773105
Belt type crankcase heater, 75 W, 575 V, UL
Application
All models
All models
All models
All models
MT/MTZ018-040
MT/MTZ018-040
MT/MTZ018-040
MT/MTZ018-040
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ044-081
MT/MTZ100-160
MT/MTZ100-160
MT/MTZ100-160
MT/MTZ100-160
MT/MTZ100-160
MT/MTZ100-160
MT/MTZ100-160
MT/MTZ100-160
Packaging Pack size
Multipack
Industry pack
Multipack
Industry pack
Multipack
Multipack
Multipack
Multipack
Multipack
Industry pack
Multipack
Industry pack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Industry pack
Multipack
Multipack
Multipack
Multipack
Multipack
6
6
6
6
6
50
6
50
4
4
4
4
10
50
10
50
50
6
6
6
6
6
6
6
6
6
Acoustic hoods
Type Code no.
Description
7755001
Acoustic hood for 1 cylinder compressor
7755002
Acoustic hood for 2 cylinder compressor
7755003
Acoustic hood for 4 cylinder compressor
Application
MT/MTZ018-040
MT/MTZ044-081
MT/MTZ100-160
Packaging Pack size
Single pack
Single pack
Single pack
1
1
1
30
ACCESSORIES AND SPAREPARTS
3-phase soft start equipment
Type Code no.
Description Application
SCR01
SCR03
7702003
Soft start kit with statoric resistors, prewired box, SCR01 MT/MTZ044-081
7705001
Soft start kit with statoric resistors, prewired box, SCR03 MT/MTZ100-160
MCI 15 C 7705006
Electronic soft start kit, MCI 15C
MCI 25 C 7705007
Electronic soft start kit, MCI 25C
MT/MTZ018-081
MT/MTZ100-160
Packaging Pack size
Single pack
Single pack
Single pack
Single pack
1
1
1
1
Single phase PSC starting kits
Type
PSC
PSC
PSC
PSC
PSC
PSC
PSC
PSC
PSC
Code no.
Description
7701026
PSC starting kit, 20 μF, 10 μF
7701024
PSC starting kit, 25 μF, 10 μF
7701025
PSC starting kit, 15 μF, 10 μF
7701035
PSC starting kit, 30 μF, 15 μF
7701151
PSC starting kit, 25 μF, 25 μF
7701152
PSC starting kit, 25 μF, 20 μF
7701153
PSC starting kit, 35 μF, 20 μF
7701036
PSC starting kit, 30 μF, 20 μF
7701037
PSC starting kit, 30 μF, 25 μF
Application
MT/MTZ018-028 code 5
MT/MTZ032-036 code 5
MT/MTZ018 code 1
MT/MTZ022 & 044-050 code 1 & 050-5
MT/MTZ028 code 1
MT/MTZ032-036 code 1
MT/MTZ040 code 1
MT/MTZ056 code 1
MT/MTZ064 code 1
Packaging Pack size
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
4
6
4
4
6
4
4
4
4
Single phase CSR starting kits & starting kits in prewired box
Type
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
CSR
Code no.
Description
7701022
CSR starting kit, 20 μF, 10 μF, 98 μF
7701030
CSR starting kit, 25 μF, 10 μF, 98 μF
7701021
CSR starting kit, 15 μF, 10 μF, 98 μF
7701038
CSR starting kit, 15 μF, 30 μF, 98 μF
7701154
CSR starting kit, 25 μF, 25 μF, 140 μF
7701155
CSR starting kit, 25 μF, 20 μF, 98 μF
7701156
CSR starting kit, 35 μF, 20 μF, 98 μF
7701042
CSR starting kit, 30 μF, 15 μF, 140 μF
7701043
CSR starting kit, 30 μF, 20 μF, 98 μF + 98 μF
7701044
CSR starting kit, 30 μF, 25 μF, 98 μF + 140 μF
7701028
CSR starting kit, prewired box, 20 μF, 10 μF, 98 μF
7701054
CSR starting kit, prewired box, 25 μF, 10 μF, 98 μF
7701147
CSR starting kit, prewired box, 15 μF, 30 μF, 98 μF
7701148
CSR starting kit, prewired box, 25 μF, 25 μF, 140 μF
7701149
CSR starting kit, prewired box, 25 μF, 20 μF, 98 μF
7701150
CSR starting kit, prewired box, 35 μF, 20 μF, 98 μF
7701049
CSR starting kit, prewired box, 30 μF, 15 μF, 140 μF
Application
MT/MTZ018-028 code 5
MT/MTZ032-036 code 5
MT/MTZ018 code 1
MT/MTZ022 code 1
MT/MTZ028 code 1
MT/MTZ032-036 code 1
MT/MTZ040 code 1
MT/MTZ044-051 code 1
MT/MTZ056 code 1
MT/MTZ064 code 1
MT/MTZ018-028 code 5
MT/MTZ032-036 code 5
MT/MTZ022 code 1
MT/MTZ028 code 1
MT/MTZ032-036 code 1
MT/MTZ040 code 1
MT/MTZ044-050 code 1
Packaging Pack size
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Multipack
Single pack
Single pack
Single pack
Single pack
Single pack
Single pack
Single pack
1
1
1
1
1
1
1
6
6
4
6
4
4
4
4
4
4
Kickstart kits
Type Code no.
Description
7701060
Kickstart kit; relay + start capacitor 227 μF
7701059
Kickstart kit; relay + start capacitor 280 μF
Lubricants
Type Code no.
Description
160PZ
160PZ
160P
160P
7754019
7754020
7754001
7754002
POE lubricant, 160PZ, 1 litre can
POE lubricant, 160PZ, 2 litre can
Mineral oil, 160P, 2 litre can
Mineral oil, 160P, 5 litre can
160ABM 7754009
Alkylbenzene oil 160ABM, 2 litre can
Application
MT/MTZ018 code 1 & 5
MT/MTZ022-064 code 1 & 5 excl 050-5
Packaging Pack size
Single pack
Single pack
1
1
Application
MTZ with R404A, R507A, R134a, R407C
MTZ with R404A, R507A, R134a, R407C
MT or LT with R22 or R502
MT or LT with R22 or R502
MT or LT with transitional refrigerants
Packaging Pack size
Multipack
Multipack
Multipack
Multipack
Multipack
12
8
8
4
8
31
ORDERING INFORMATION AND PACKAGING
Ordering information
Maneurop® MT & MTZ reciprocating compressors can be ordered from
Danfoss Commercial Compressors in either industrial packs (also called multiple packaging) or in single packs
(also called individual packaging).
The code numbers ending on "M" in below tables represent the compressors in industrial packs. For ordering single packs, please replace the last letter "M" by letter "I".
R22
MT compressors in industrial pack (multiple packaging)
Compressor model
Design 1 )
1
208-230/1/60
3
200-230/3/60
MT018
MT022
MT028
MT032
MT036
MT040
MT044
MT045
MT050
MT051
MT056
MT057
MT064
MT065
MT072
MT073
MT080
MT081
MT100
MT125
MT144
MT160
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
Sv
VE
Sv
VE
S
VE
S
VE
Sv
VE
Sv
VE
-
MT18-1VM
MT22-1M
MT22-1VM
MT28-1M
MT28-1VM
-
MT32-1VM
-
MT36-1VM
MT40-1M
MT40-1VM
MT44-1M
MT44-1VM
-
-
-
MT50-1VM
-
-
-
MT56-1VM
-
-
-
MT64-1VM
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
) S = Single compressor, no oil sight glass, no oil equalisation connection
Sv = Single compressor, brazed oil sight glass, no oil equalisation connection
VE = Single compressor, threaded oil sight glass, 3/8" oil equalisation connection
MT50-3M
MT50-3VM
MT51-3M
MT51-3VM
MT56-3M
MT56-3VM
-
MT57-3VM
MT64-3M
MT64-3VM
MT65-3M
MT65-3VM
MT72-3M
MT72-3VM
MT73-3M
MT73-3VM
MT18-3M
MT18-3VM
MT22-3M
MT22-3VM
MT28-3M
MT28-3VM
MT32-3M
MT32-3VM
MT36-3M
MT36-3VM
MT40-3M
MT40-3VM
MT44-3M
MT44-3VM
-
MT45-3VM
-
MT80-3VM
-
MT81-3VM
MT100-3M
MT100-3VM
MT125-3M
MT125-3VM
MT144-3M
MT144-3VM
MT160-3M
MT160-3VM
4
460/3/60
400/3/50
MT50-4M
MT50-4VM
MT51-4M
MT51-4VM
MT56-4M
MT56-4VM
MT57-4M
MT57-4VM
MT64-4M
MT64-4VM
MT65-4M
MT65-4VM
MT72-4M
MT72-4VM
MT73-4M
MT73-4VM
MT18-4M
MT18-4VM
MT22-4M
MT22-4VM
MT28-4M
MT28-4VM
MT32-4M
MT32-4VM
MT36-4M
MT36-4VM
MT40-4M
MT40-4VM
MT44-4M
MT44-4VM
MT45-4M
MT45-4VM
MT80-4M
MT80-4VM
MT81-4M
MT81-4VM
MT100-4M
MT100-4VM
MT125-4M
MT125-4VM
MT144-4M
MT144-4VM
MT160-4M
MT160-4VM
Code no.
5
230/1/50
-
-
-
-
-
-
-
-
-
MT50-5VM
-
-
-
-
-
-
MT18-5M
MT18-5VM
MT22-5M
MT22-5VM
MT28-5M
MT28-5VM
MT32-5M
MT32-5VM
MT36-5M
MT36-5VM
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
575/3/60
500/3/50
-
-
-
-
-
-
-
-
-
MT50-7VM
-
-
MT56-7M
MT56-7VM
-
-
-
-
-
-
-
MT44-7VM
-
-
-
-
-
-
-
-
-
-
-
-
-
-
MT100-7M
MT100-7VM
MT125-7M
MT125-7VM
-
MT144-7VM
-
MT160-7VM
6
230/3/50
-
MT50-6VM
-
-
-
MT56-6VM
-
-
-
MT64-6VM
-
-
-
MT72-6VM
-
-
-
-
-
MT22-6VM
MT28-6M
MT28-6VM
MT32-6M
MT32-6VM
MT36-6M
MT36-6VM
MT40-6M
MT40-6VM
-
MT44-6VM
-
-
-
MT80-6VM
-
-
MT100-6M
MT100-6VM
MT125-6M
MT125-6VM
-
MT144-6VM
MT160-6M
MT160-6VM
9
380/3/60
MT50-9M
MT50-9VM
-
-
MT56-9M
MT56-9VM
-
-
MT64-9M
MT64-9VM
-
-
MT72-9M
MT72-9VM
-
-
-
-
-
MT22-9VM
-
MT28-9VM
-
-
-
MT36-9VM
-
-
MT44-9M
MT44-9VM
-
-
MT80-9M
MT80-9VM
-
-
MT100-9M
MT100-9VM
-
-
MT144-9M
MT144-9VM
MT160-9M
MT160-9VM
32
ORDERING INFORMATION AND PACKAGING
MTZ compressors in industrial pack
(multiple packaging)
R404A / R507A / R134a / R407C
Code no.
5
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
Sv
VE
Sv
VE
S
VE
S
VE
Sv
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
Sv
VE
Compressor model
MTZ018
MTZ022
MTZ028
MTZ032
MTZ036
MTZ040
MTZ044
MTZ045
MTZ050
MTZ051
MTZ056
MTZ057
MTZ064
MTZ065
MTZ072
MTZ073
MTZ080
MTZ081
MTZ100
MTZ125
MTZ144
MTZ160
Design 1 )
-
MTZ50-1VM
-
-
-
MTZ56-1VM
-
-
-
MTZ64-1VM
-
-
-
-
-
-
MTZ18-1M
MTZ18-1VM
MTZ22-1M
MTZ22-1VM
MTZ28-1M
MTZ28-1VM
MTZ32-1M
MTZ32-1VM
MTZ36-1M
MTZ36-1VM
MTZ40-1M
MTZ40-1VM
-
MTZ44-1VM
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
208-230/1/60
3
200-230/3/60
4
460/3/60
400/3/50
MTZ50-3M
MTZ50-3VM
-
MTZ51-3VM
MTZ56-3M
MTZ56-3VM
-
MTZ57-3VM
MTZ64-3M
MTZ64-3VM
-
MTZ65-3VM
MTZ72-3M
MTZ72-3VM
-
MTZ73-3VM
MTZ18-3M
MTZ18-3VM
MTZ22-3M
MTZ22-3VM
MTZ28-3M
MTZ28-3VM
MTZ32-3M
MTZ32-3VM
MTZ36-3M
MTZ36-3VM
MTZ40-3M
MTZ40-3VM
MTZ44-3M
MTZ44-3VM
-
MTZ45-3VM
-
MTZ80-3VM
-
MTZ81-3VM
MTZ80-4M
MTZ80-4VM
MTZ81-4M
MTZ81-4VM
MTZ100-3M MTZ100-4M
MTZ100-3VM MTZ100-4VM
MTZ125-3M MTZ125-4M
MTZ125-3VM MTZ125-4VM
MTZ144-3M MTZ144-4M
MTZ144-3VM MTZ144-4VM
MTZ160-3M MTZ160-4M
MTZ160-3VM MTZ160-4VM
MTZ50-4M
MTZ50-4VM
MTZ51-4M
MTZ51-4VM
MTZ56-4M
MTZ56-4VM
MTZ57-4M
MTZ57-4VM
MTZ64-4M
MTZ64-4VM
MTZ65-4M
MTZ65-4VM
MTZ72-4M
MTZ72-4VM
MTZ73-4M
MTZ73-4VM
MTZ18-4M
MTZ18-4VM
MTZ22-4M
MTZ22-4VM
MTZ28-4M
MTZ28-4VM
MTZ32-4M
MTZ32-4VM
MTZ36-4M
MTZ36-4VM
MTZ40-4M
MTZ40-4VM
MTZ44-4M
MTZ44-4VM
MTZ45-4M
MTZ45-4VM
1
) S = Single compressor, no oil sight glass, no oil equalisation connection
Sv = Single compressor, brazed oil sight glass, no oil equalisation connection
VE = Single compressor, threaded oil sight glass, 3/8" oil equalisation connection
230/1/50
-
-
-
-
-
-
-
-
-
MTZ50-5VM
-
-
-
-
-
-
MTZ18-5M
MTZ18-5VM
MTZ22-5M
MTZ22-5VM
MTZ28-5M
MTZ28-5VM
MTZ32-5M
MTZ32-5VM
MTZ36-5M
MTZ36-5VM
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
6
230/3/50
7
575/3/60
500/3/50
9
380/3/60
-
MTZ50-6VM
-
-
-
MTZ56-6VM
-
-
-
MTZ64-6VM
-
-
MTZ72-6M
MTZ72-6VM
-
-
-
MTZ18-6VM
MTZ22-6M
MTZ22-6VM
MTZ28-6M
MTZ28-6VM
MTZ32-6M
MTZ32-6VM
MTZ36-6M
MTZ36-6VM
MTZ40-6M
MTZ40-6VM
-
MTZ44-6VM
-
-
-
MTZ80-6VM
-
-
-
-
-
-
MTZ80-9M
MTZ80-9VM
-
-
MTZ100-6M MTZ100-7M MTZ100-9M
MTZ100-6VM MTZ100-7VM MTZ100-9VM
MTZ125-6M MTZ125-7M MTZ125-9M
MTZ125-6VM MTZ125-7VM MTZ125-9VM
MTZ144-6M MTZ144-7M MTZ144-9M
MTZ144-6VM MTZ144-7VM MTZ144-9VM
MTZ160-6M MTZ160-9M
MTZ160-6VM MTZ160-7VM MTZ160-9VM
-
-
-
-
-
-
-
-
MTZ50-7M
MTZ50-7VM
-
-
MTZ56-7M
MTZ56-7VM
-
-
-
-
-
-
-
-
MTZ32-7M
MTZ32-7VM
-
MTZ36-7VM
-
-
MTZ44-7M
MTZ44-7VM
-
-
MTZ50-9M
MTZ50-9VM
-
-
MTZ56-9M
MTZ56-9VM
-
-
MTZ64-9M
MTZ64-9VM
-
-
MTZ72-9M
MTZ72-9VM
-
-
-
-
-
MTZ22-9VM
-
MTZ28-9VM
-
MTZ32-9VM
-
MTZ36-9VM
-
-
MTZ44-9M
MTZ44-9VM
-
-
33
ORDERING INFORMATION AND PACKAGING
Packaging
Model
Single pack
Dimensions
(mm)
Net weight
(kg)
Nbr
Dimensions
(mm)
Multipack
Gross weight
(kg)
Static stacking
Nbr
Industrial pack
Dimensions
(mm)
Gross weight
(kg)
Static stacking
1 cylinder
MT/MTZ018
MT/MTZ022
MT/MTZ028
MT/MTZ032
MT/MTZ036
MT/MTZ040
2 cylinders
MT/MTZ044-050
MT/MTZ045-051
MT/MTZ056-064
MT/MTZ057-065
MT/MTZ072-080
MT/MTZ073-081
4 cylinders
MT/MTZ100
MT/MTZ125
MT/MTZ144
MT/MTZ160
Single pack:
Multipack:
Industrial pack:
Nbr: l: 330 w: 295 h: 385 l: 395 w: 365 h: 455 39
40
41
35
37
37
21
21
23
24
25
26
6
6 l: 1000 w: 600 h: 510 l: 1150 w: 800 h: 560 254
257
262
227
239
239
142
142
151
158
164
168
4
4
12
6 l: 1200 w: 800 h: 500 l: 1200 w: 800 h: 550 333
342
347
294
306
306
279
279
295
305
322
329
4
4 l: 485 w: 395 h: 600
60
64
67
69
6 l: 1200 w: 1000 h: 730
398
414
430
444
4 6 l: 1200 w: 800 h: 650
388
404
420
434
4
One compressor in a cardboard box.
In some publications this packaging may be indicated as ‘individual packaging.
A full pallet of compressors, each individually packed in a cardboard box. Mainly dedicated to wholesalers and Danfoss distribution centers.
A full pallet of unpacked compressors. Mainly dedicated to OEM customers.
In some publications this packaging may be indicated as ‘Multiple packaging.
Number of compressor in a pack
34
The Danfoss product range for the refrigeration and air conditioning industry
Danfoss Refrigeration & Air Conditioning is a worldwide manufacturer with a leading position in industrial, commercial and supermarket refrigeration as well as air conditioning and climate solutions.
We focus on our core business of making quality products, components and systems that enhance performance and reduce total life cycle costs – the key to major savings.
Controls for
Commercial Refrigeration
Controls for
Industrial Refrigeration
Electronic Controls &
Sensors
Industrial Automation
Household Compressors Commercial Compressors Sub-Assemblies
Thermostats
We are off ering a single source for one of the widest ranges of innovative refrigeration and air conditioning components and systems in the world. And, we back technical solutions with business solution to help your company reduce costs, streamline processes and achieve your business goals.
Danfoss A/S • www.danfoss.com
FRCC.PC.004.A3.02 - Replace FRCC.PC.004.A2.02 - May 2006 electronic version only Produced by Danfoss CC- DSS - 09/2006
advertisement
Key Features
- Hermetic reciprocating type
- Medium and high evaporating temperature applications
- 100% suction gas cooled
- High efficiency circular valve design
- High torque motors
- Large internal free volume
- Available in 26 different models
- Seven different motor voltage ranges