DAIKIN EWWQ 090G, 720L, EWLQ 090G, 720L, EWHQ 100G, 400G, EWAQ-G 075, 155, 080, 170, EWYQ-G 075, 160 chiller Operation manual

DAIKIN EWWQ 090G, 720L, EWLQ 090G, 720L, EWHQ 100G, 400G, EWAQ-G 075, 155, 080, 170, EWYQ-G 075, 160 chiller Operation manual

Below you will find brief product information for chiller EWWQ 090G, chiller EWWQ 720L, chiller EWLQ 090G, chiller EWLQ 720L, chiller EWHQ 100G, chiller EWHQ 400G, chiller EWAQ-G 075, chiller EWAQ-G 155, chiller EWAQ-G 080, chiller EWAQ-G 170, chiller EWYQ-G 075, chiller EWYQ-G 160. These chillers are designed to provide cooling and heating solutions for a variety of applications. The units feature a scroll compressor designed for quiet operation and energy efficiency. Both water-cooled and air-cooled units are available, providing options for different environmental and installation requirements.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

DAIKIN Air and Water cooled scroll chillers & heat pump Operation manual | Manualzz
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
OPERATION MANUAL
Air and Water cooled scroll chillers & heat pump
D-EOMHW00107-15EN
Water cooled ranges:
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
Air cooled ranges:
EWAQ-G 075155 SS - R410A - Air-cooled scroll chillers
EWAQ-G 080170 XS - R410A - Air-cooled scroll chillers
EWYQ-G 075160 XS - R410A - Air-cooled scroll heat pumps
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
1
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Table of Contents
1
SAFETY CONSIDERATIONS .................................................................................................. 6
1.1
General ............................................................................................................................. 6
1.2
Avoid electrocution ........................................................................................................... 6
1.3
Safety Devices .................................................................................................................. 7
1.3.1
General safety devices .............................................................................................. 7
1.3.2
Circuit safety devices ................................................................................................. 7
1.3.3
Component safety devices ......................................................................................... 7
1.4
Available sensors.............................................................................................................. 9
1.4.1
Pressure transducers ................................................................................................. 9
1.4.2
Temperature sensors ................................................................................................. 9
1.4.3
Thermistors................................................................................................................ 9
1.5
Available Controls ............................................................................................................. 9
1.5.1
Evaporator - Condenser pumps ................................................................................. 9
1.5.2
Compressors ............................................................................................................. 9
1.5.3
Expansion Valve ........................................................................................................ 9
1.5.4
Four Way Valve ......................................................................................................... 9
1.6
Abbreviations used ......................................................................................................... 10
1.7
Customer Terminal Block Connections ........................................................................... 10
1.7.1
2
3
Connections description and purpouse .................................................................... 10
GENERAL DESCRIPTION .................................................................................................... 13
2.1
Overview......................................................................................................................... 13
2.2
Controller Operating Limits ............................................................................................. 13
2.3
Controller Architecture .................................................................................................... 13
2.4
Communication Modules ................................................................................................ 14
2.4.1
Modbus Module installation ..................................................................................... 15
2.4.2
Bacnet Module installation ....................................................................................... 15
2.4.3
Lon Module installation ............................................................................................ 16
Using the Controller ............................................................................................................... 16
3.1
General Recommendation .............................................................................................. 17
3.2
Browsing ......................................................................................................................... 17
3.3
Passwords ...................................................................................................................... 18
Operation Manual
2
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
4
Air and Water cooled scroll chillers & heat pump
Operation
Manual
3.4
Editing ............................................................................................................................ 19
3.5
Basic Control System Diagnostic .................................................................................... 20
3.6
Controller maintenance ................................................................................................... 21
3.7
Software Update procedure ............................................................................................ 22
3.8
Optional Remote User Interface ...................................................................................... 24
3.9
Embedded Web Interface ............................................................................................... 26
Menu Structure ...................................................................................................................... 28
4.1
Main Menu ...................................................................................................................... 28
4.2
View/Set Unit .................................................................................................................. 29
4.2.1
Thermostat Ctrl ........................................................................................................ 29
4.2.2
Network Ctrl ............................................................................................................. 29
4.2.3
Unit Cond Ctrl (W/C only) ........................................................................................ 29
4.2.4
Pumps ..................................................................................................................... 30
4.2.5
Master/Slave ............................................................................................................ 30
4.2.6
Date/Time ................................................................................................................ 32
4.2.7
Power Conservation ................................................................................................ 32
4.2.8
Controller IP setup ................................................................................................... 32
4.3
View/Set Circuit .............................................................................................................. 33
4.3.1
Settings ................................................................................................................... 33
4.4
Tmp Setpoints................................................................................................................. 35
4.5
Temperatures ................................................................................................................. 35
4.6
Available Modes ............................................................................................................. 36
4.7
Timers ............................................................................................................................ 36
4.8
Alarms ............................................................................................................................ 36
4.9
Commission Unit............................................................................................................. 36
4.9.1
Configure Unit .......................................................................................................... 37
4.9.2
Alarm Limits ............................................................................................................. 37
4.9.3
Calibrate Unit Sensors ............................................................................................. 38
4.9.4
Calibrate Circuit Sensors ......................................................................................... 38
4.9.5
Unit Manual Control ................................................................................................. 39
4.9.6
Circuit 1 Manual Control .......................................................................................... 39
4.9.7
Scheduled Maintenance .......................................................................................... 40
4.10
Save and Restore ........................................................................................................... 40
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
3
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
4.11
5
Operation
Manual
About this Chiller............................................................................................................. 41
Working with this unit ............................................................................................................. 41
5.1
Unit Setup ....................................................................................................................... 41
5.1.1
Control Source ......................................................................................................... 41
5.1.2
Available Mode Setting ............................................................................................ 42
5.1.3
Temperature Setpoint Settings ................................................................................ 42
5.1.4
Thermostat Control Settings .................................................................................... 43
5.1.5
Alarm Settings ......................................................................................................... 45
5.1.6
Pumps ..................................................................................................................... 46
5.1.7
Power Conservation ................................................................................................ 46
5.2
Unit/Circuit Start-up ........................................................................................................ 49
5.2.1
Prepare the unit to start ........................................................................................... 49
5.2.2
Preparing circuits to start ......................................................................................... 51
5.3
Circuit Capacity Control .................................................................................................. 52
5.3.1
Low Evaporating Pressure ....................................................................................... 52
5.3.2
High Condensing Pressure ...................................................................................... 53
5.4
Mode Change-Over (H/P only) ........................................................................................ 53
5.5
Backup Heaters (A/C only).............................................................................................. 53
5.6
Condensation Control (W/C only).................................................................................... 54
5.6.1
Pressure (W/C only) ................................................................................................ 54
5.6.2
Cond In / Cond Out (W/C only) ................................................................................ 55
5.6.3
Fan Control (A/C only) ............................................................................................. 55
5.7
EXV Control .................................................................................................................... 55
5.8
Defrost (A/C only) ........................................................................................................... 56
5.9
Four Way Valve (H/P gas side reversal only) .................................................................. 57
5.10
Master/Slave ................................................................................................................... 57
5.10.1
Master Slave Overview ............................................................................................ 57
-
Plant 1 : Single Common Pump ...................................................................................... 58
-
Plant 2 : Single Chiller Pump .......................................................................................... 58
-
Plant 4. Chiller with sectioned evaporator ....................................................................... 58
5.10.2
Electrical Connection ............................................................................................... 59
5.10.3
Master Slave Operation ........................................................................................... 61
5.10.4
Master Slave Options............................................................................................... 63
Operation Manual
4
Air and Water cooled scroll chillers & heat pump
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
6
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Alarms ................................................................................................................................... 65
6.1.1
Unit Warning Alarms ................................................................................................ 65
6.1.2
Unit Pumpdown Stop Alarms ................................................................................... 67
6.1.3
Unit Rapid Stop Alarms............................................................................................ 69
6.1.4
Master Slave Alarm ................................................................................................. 72
6.1.5
Circuit Warning Alarms ............................................................................................ 74
6.1.6
Circuit Pumpdown Stop Alarms ............................................................................... 75
6.1.7
Circuit Rapid Stop Alarms ........................................................................................ 75
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
5
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
1 SAFETY CONSIDERATIONS
1.1 General
Installation, start-up and servicing of equipment can be hazardous if certain factors particular to the
installation are not considered: operating pressures, presence of electrical components and
voltages and the installation site (elevated plinths and built-up up structures). Only properly
qualified installation engineers and highly qualified installers and technicians, fully trained for the
product, are authorised to install and start-up the equipment safely.
During all servicing operations, all instructions and recommendations, which appear in the
installation and service instructions for the product, as well as on tags and labels fixed to the
equipment and components and accompanying parts supplied separately, must be read,
understood and followed.
Apply all standard safety codes and practices.
Wear safety glasses and gloves.
Use the proper tools to move heavy objects. Move units carefully and set them down gently.
1.2 Avoid electrocution
Only personnel qualified in accordance with IEC (International Electrotechnical Commission)
recommendations may be permitted access to electrical components. It is particularly
recommended that all sources of electricity to the unit be shut off before any work is begun. Shut
off main power supply at the main circuit breaker or isolator.
IMPORTANT: This equipment uses and emits electromagnetic signals. Tests have shown
that the equipment conforms to all applicable codes with respect to electromagnetic
compatibility.
RISK OF ELECTROCUTION: Even when the main circuit breaker or isolator is switched
off, certain circuits may still be energized, since they may be connected to a separate
power source.
RISK OF BURNS: Electrical currents cause components to get hot either temporarily or
permanently. Handle power cable, electrical cables and conduits, terminal box covers
and motor frames with great care.
ATTENTION: In accordance with the operating conditions the fans can be cleaned
periodically. A fan can start at any time, even if the unit has been shut down.
Operation Manual
6
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
1.3 Safety Devices
Each unit is equipped with safety devices of three different kinds:
1.3.1 General safety devices
Safeties of this level of severity will shut down all the circuits and stop the entire unit. When a
general safety device will occur a manual intervention on the unit will be required in order to reestablish the normal operability of the machine. There are exceptions to this general rule in case of
alarms linked to temporary abnormal conditions.

Emergency Stop
A push button is placed on a door of the unit electrical panel. The button is highlighted by a red
color in yellow background. A manual pressure of the emergency stop button stops all loads from
rotating, thus preventing any accident which may occur. An alarm is also generated by the Unit
Controller. Releasing the emergency stop button enables the unit, which may be restarted only
after the alarm has been cleared on the controller.
The emergency stop causes all motors to stop, but does not switch off power to the unit. Do not
service or operate on the unit without having switched off the main switch.
1.3.2 Circuit safety devices
Safety of this level of severity will shut down the circuit they protect. The remaining circuits will
keep running.
1.3.3 Component safety devices
Safety of this level of severity will shut down a component against abnormal running condition that
could create permanent damages to it. An overview of the protecting devices is listed below:

Overcurrent/Overload Protections
Overcurrent/overload devices protect electrical motors used on compressors, and pumps in
case of overload or short circuit. In case of inverter-driven motors, overload and overcurrent
protection is integrated in the electronic drives. A further protection from short circuit is
accomplished by fuses or circuit breakers installed upstream each load or group of loads.

Overtemperature Protections
Compressors are also protected from overheating by thermistors immersed into motor windings.
Should the winding temperature exceed a fixed threshold, the thermistors will trip and cause the
motor to stop.

Phase reversal, under/over voltage, ground fault protections
When one of those alarms occurs the unit is immediately stopped or even inhibited to start. The
alarms clear automatically once the problem is fixed. This auto clear logic allows the unit to
automatically recover in case of temporary conditions where the supply voltage reaches the
upper or lower limit set on the protection device. In the other two cases a manual intervention
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
7
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
on the unit will be required in order to solve the problem. In case of a phase reversal alarm two
phases requires to be inverted.
In the event of a power supply outage, the unit will restart automatically without the need for an
external command. However, any faults active when the supply is interrupted are saved and
may in certain cases prevent a circuit or unit from restarting.
Direct intervention on the power supply can cause electrocution, burns or even death. This action
must be performed only by trained persons.

Flowswitch
The unit must be protected by a flowswitch. The flowswitch will stop the unit when the water
flow becomes lower than the minimum allowed flow. When the water flow is restored the flow
protection resets automatically. Exception is when the flowswitch opens with at least one
compressor running, in this case the alarm shall be cleared manually.

Freezing protection
Antifreeze protection prevents the water to freeze in the evaporator. It is automatically activated
when the water temperature (entering or leaving) at the evaporator drops below the antifreeze
limit. In freeze condition if the unit is in standby the evaporator pump will be activated to prevent
freezing of the evaporator. If the freeze condition will activate when the unit is running all the
unit will shut down in alarm while the pump will keep running. Alarm will automatically clear
when the freeze condition will clear.

Low pressure protection
If the circuit operates with a suction pressure lower than an adjustable limit for a certain time the
circuit safety logic will shut down the circuit and generate an alarm. The alarm requires a
manual action on the Unit Controller to be reset. Reset will take effect only if the suction
pressure is no longer lower that the safety limit.

High Pressure Protection
If the discharge pressure becomes too high and exceeds a limit which is linked with the
operational envelop of the compressor the circuit safety logic will try to prevent the alarm or, if
the corrective actions have no effect, it will shut down the circuit before the Mechanical High
Pressure switch will open. This alarm required a manual action on the Unit Controller to be
reset.

Mechanical High Pressure Switch
Each circuit is equipped with at least one high pressure switch which tries to prevent the relief
safety valve to open. When the discharge pressure becomes too high the Mechanical High
Pressure switch will open and immediately stop the compressor cutting the power supply to the
auxiliary relay. The alarm can be cleared as soon as the discharge pressure becomes normal
Operation Manual
8
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
again. The alarm must be reset on the switch itself and on the Unit Controller. The triggering
pressure value cannot be changed.

Relief Safety Valve
If the pressure becomes too high in the refrigerant circuit, the relief valve will open to limit the
maximum pressure. If this happens switch off immediately the machine and contact your local
service organization.
1.4 Available sensors
1.4.1 Pressure transducers
Two electronic sensors are used to measure the evaporating and condensing pressure of each
circuit. The range of each sensor is clearly indicated on the sensor casing.
1.4.2 Temperature sensors
The evaporator and condenser water sensors are installed in the entering and leaving side.
Additionally each circuit installs a suction temperature sensor to monitor and control the
superheated refrigerant temperatures.
1.4.3 Thermistors
Each compressor is equipped with PTC thermistors which are immersed into motor windings for
motor protection. Thermistors trip to a high value in case the motor temperature reaches a
hazardous temperature.
1.5 Available Controls
In the following the different functions will be distinguished between Water Cooled (W/C) and Air
Cooled (A/C) units and Cooling Only (C/O) and Heat Pumps (H/P). If not specified one specific
function can apply to any W/C unit independently from being a C/O or H/P unit.
1.5.1 Evaporator - Condenser pumps
The controller can regulate one or two evaporator pumps and takes care of automatic change-over
between pumps. It’s also possible to prioritize the pumps and temporarily disable one of the twos.
The controller can also regulate an unique condenser water pump (W/C units only).
1.5.2 Compressors
The controller can regulate two or four compressors installed on one or two independent refrigerant
circuit. All the safeties of each compressor will be managed by the controller.
1.5.3 Expansion Valve
The controller can regulate an electronic expansion valve per each refrigerant circuit to guarantee
the best operation for the refrigerant circuit.
1.5.4 Four Way Valve
The controller can command a four way valve per each refrigerant circuit where required. The
valve is used to reverse the unit mode from Cool to Heat.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
9
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
1.6 Abbreviations used
In this manual, the refrigeration circuits are called circuit #1 and circuit #2.
The following abbreviations are used frequently:
UC
HMI
A/C
W/C
C/O
H/P
CL
CP
EP
CSRT
ESRT
ST
SSH
EXV
ELWT
EEWT
CLWT
CEWT
Unit controller
Human Machine Interface
Air Cooled
Water Cooled
Cooling Only
Heat Pump
Condenser Less
Condensing Pressure
Evaporating Pressure
Condensing Saturated Refrigerant Temperature
Evaporating Saturated Refrigerant Temperature
Suction Temperature
Suction SuperHeat
Electronic Expansion Valve
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
Condenser Leaving Water Temperature
Condenser Entering Water Temperature
1.7 Customer Terminal Block Connections
1.7.1 Connections description and purpouse
The contacts below are available at the user’s terminal block referred as MC24 or MC230 in the
wiring diagram. The following table summarizes the connections at the user’s terminal block.
Description
Evaporator Flow Switch (mandatory)
Terminals
724, 708
Condenser
Flow
Switch
(W/C 794, 793
mandatory)
Cooling/Heating Remote switch (H/P 743,744
units only)
Double setpoint
713,709
External Fault
884, 885
On-Off Remote
741, 742
General Alarm
Evaporator Pump #1 start
Evaporator Pump #2 start (A/C only)
Evaporator Pump #2 start (W/C only)
Operation Manual
525, 526
527,528
530, 531
893,894
10
Notes
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
For potential-free contacts
Sampling voltage / current DC 24 V / 8 mA
NO digital output (24…230 Vac ext supply)
NO digital output (24…230 Vac ext supply)
NO digital output (24…230 Vac ext supply)
NO digital output (24 Vdc - 25mA )
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Condenser Pump #1 start (W/C only)
Condenser Pump #2 start (W/C only)
Demand Limit
Setpoint Override
Condenser three way valve (W/C only)
Condenser tower fan speed (W/C only)
Master/Slave Water Temperature
Master/Slave Bus Connection
520,521
540,541
888, 889
886, 887
772, 773
772, 774
890, 896
900, 901
Operation
Manual
NO digital output (24…230 Vac ext supply)
NO digital output (24…230 Vac ext supply)
4-20 mA analog input
4-20 mA analog input
0-10V analog output
0-10V analog output
NTC10K / PT1000 temperature sensor
Serial communication
1.7.1.1 Flow Switch
Although the flow switch is offered as an optional, it is mandatory to install one and connect it to
the digital input terminals in order to enable chiller operation only when a minimum flow is sensed.
Operating the unit by-passing the flow switch input or without an appropriate flow switch may
damage the water heat exchanger due to freezing. Operation of the flow switch must be checked
prior to start up the unit.
1.7.1.2 Double setpoint
This contact can be used to switch between two different LWT setpoints and, depending on the
application, between different modes of operation.
Ice operation must be selected in case of ice storage application. In this case the UC will run the
chiller in on/off mode switching all the chiller off as soon as the setpoint is reached. In this case the
unit will run to full capacity and then will switch off applying an ice delay different chiller starts.
1.7.1.3 External Fault (optional)
This contact is available to report to the UC a fault or a warning from an external device. It could be
an alarm coming from an external pump to inform the UC of the fault. This input can be configured
as a fault (unit stop) or a warning (displayed on the HMI without any action on the chiller).
1.7.1.4 Remote On-Off
This unit can be started through a remote enable contact. The Q0 switch must be selected to
“Remote”.
1.7.1.5 General Alarm
In case of a unit alarm, this output is closed thus indicating a fault condition to an externally
connected BMS.
1.7.1.6 Evaporator Pump Start
Two digital outputs are enabled when the pumps (#1 or #2) are required to start. The output for the
pump #2 requires a relay with less than 20 mA excitation current.
1.7.1.7 Setpoint override (optional)
This input allows to apply an offset on the Active Setpoint to adjust the operating point of the
ELWT. This input can be used to maximize the comfort.
1.7.1.8 Demand Limit (optional)
This input allows to limit the maximum number of compressor in run state.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
11
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Operation Manual
12
Air and Water cooled scroll chillers & heat pump
Operation
Manual
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
2 GENERAL DESCRIPTION
2.1 Overview
The UC is a system for controlling single or dual-circuit W/C and A/C liquid chillers / heat-pump.
The UC controls compressor start-up necessary to maintain the desired heat exchanger leaving
water temperature.
On W/C units the UC can optionally controls a three way valve or a cooling tower to perform a
condensing control. One of the following three variables can be selected as condensing target:
-
Condenser leaving water temperature (W/C only)
Condenser entering water temperature (W/C only)
Condensing saturated refrigerant temperature
Safety devices are constantly monitored by the UC to ensure their safe operation. UC also gives
access to a Test routine covering all inputs and outputs. The controller can work in accordance
with three independent modes:



Local mode: the machine is controlled by commands from the user interface.
Remote mode: the machine is controlled by remote contacts (volt-free contacts).
Network mode: the machine is controlled by commands from a BAS system. In this case, a
data communication cable is used to connect the unit to the BAS.
When the UC operates autonomously (Local or Remote mode) it retains all of its own control
capabilities but does not offer any of the command features of the Network mode (monitoring only).
2.2 Controller Operating Limits
Operation (IEC 721-3-3):





Temperature -40...+70 °C
Restriction LCD -20… +60 °C
Restriction Process-Bus -25….+70 °C
Humidity < 90 % r.h (no condensation)
Air pressure min. 700 hPa, corresponding to max. 3,000 m above sea level
Transport (IEC 721-3-2):



Temperature -40...+70 °C
Humidity < 95 % r.h (no condensation)
Air pressure min. 260 hPa, corresponding to max. 10,000 m above sea level.
2.3 Controller Architecture
The overall controller architecture is the following:



A unit controller (UC)
I/O extensions as needed depending on the configuration of the unit
Communications interface(s) as selected
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
13
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps

Air and Water cooled scroll chillers & heat pump
Operation
Manual
Peripheral Bus is used to connect I/O extensions to the main controller.
Controller/
Extension Module
Main Controller
EEXV Module 1
EEXV Module 2
Option Module
Siemens Part Number
Address
Usage
POL638.00/MCQ
POL94E.00/MCQ
POL94E.00/MCQ
POL965.00/MCQ
n/a
3
5
18
Used on all configurations
Used on all configurations
Used when configured for 2 circuits
Used when options required
All boards are supplied from a common 24 Vac sourced directly from the unit. Extension boards
can be directly powered by the Unit Controller. All boards can be also supplied by a 24Vdc source.
These are the limits for the two different power supplies available:


AC: 24V  20% (frequency 45  65Hz)
DC: 24V  10%
Maintain the correct G-G0 polarity when connecting the power supply directly to the extension
boards. The peripheral bus communication will not operate and the boards may be damaged.
2.4 Communication Modules
Any of the following modules can be connected directly to the left side of the main controller to
allow a BAS or other remote interface to function. Up to three can be connected to the controller at
a time. To make the connection is required to remove the knockout covers on both UC and
communication module as shown in the following pictures.
Operation Manual
14
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
The controller should automatically detect and configure itself for new modules after booting up.
Removing modules from the unit will require manually changing of the configuration.
Module
BacNet/IP
Lon
Modbus
BACnet/MSTP
Siemens Part Number
POL908.00/MCQ
POL906.00/MCQ
POL902.00/MCQ
POL904.00/MCQ
Usage
Optional
Optional
Optional
Optional
Separate documents contains all the information about the different protocols supported and how
to setup a proper communication with a BMS.
2.4.1 Modbus Module installation
In case of Modbus connection with a BMS the corresponding module has to be installed on the
unit. It has to be connected to the Unit Controller as indicated in the previous section.
The module has two different ports available but only the top port is programmed and operational.
A dedicated menu allows to properly setup the communication parameters.
2.4.2 Bacnet Module installation
In case of Bacnet connection with a BMS, there are two different modules available depending on
the physical connection to the customer network. The two possible connections are IP or MSTP.
A dedicated menu allows to properly setup the communication parameters.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
15
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
2.4.3 Lon Module installation
In case of Lon connection with a BMS, there are two different modules available depending on the
physical connection to the customer network. The type of connection is FTT10.
A dedicated menu allows to properly setup the communication parameters.
3 Using the Controller
The control system consists of a unit controller (UC) equipped with a set of extension modules that
implement additional features. All boards communicate via an internal peripheral bus with the UC.
The UC continuously manages the information received from the various pressure and
temperature probes installed on the unit. The UC incorporates a program that controls the unit.
Two different types of UC HMI are available as standard HMI:
1. Inbuilt HMI (A/C units)
This HMI is provided of three buttons and one wheel button.
Alarm status (from any page it links with the page with alarm list, alarm log and alarm
snapshot if available)
INFO Back to Main Page
ESC Back to the previous level (it can be the Main Page)
Used to scroll between the different menu pages, settings and data available on the HMI
for the active password level. Rotating the wheel allows to navigate between lines on a
Wheel
screen (page) and to increase and decrease changeable values when editing. Pushing
Button
the wheel acts as an Enter Button and will jump from a link to the next set of parameters.
Operation Manual
16
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
2. External HMI (POL871.72) (W/C units)
1
4
2
5
1
3
6
1
This External HMI is provided of six buttons.
1
i
2

3
4
5
6
▲
▼

Back to Main Page
Alarm status (from any page it links with the page with alarm list, alarm log and
alarm snapshot if available)
Back to the previous level (it can be the Main Page)
Go above
Go below
Confirm
3.1 General Recommendation
Before switching on the unit read the following recommendations:

When all the operations and all the settings have been carried out, close all the switchbox
panels
The switchbox panels can only be opened by trained personnel
When the UC requires to be accessed frequently the installation of a remote interface is
strongly recommended
Compressor are protected from freezing by electrical heaters. These heaters are supplied
through unit main supply and temperature controlled by thermostat.
the LCD display of the unit controller may be damaged by extremely low temperatures. For
this reason, it is strongly recommended to never power off the unit during winter, especially
in cold climates.




3.2
Browsing
When power is applied to the control circuit, the HMI screen will be active and display the Home
screen.
An example of the HMI screens is shown in the following picture.
M a
E n T
U n I
O F
A c T
i
e
t
f
i
n
r
M
P
S t
:
U
v e
e
a
a
n
S
n
s
t
i
e
u
s w o r d
u s =
t
S W
t p t =
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
1 / 11

7 . 0 ° C
Operation Manual
17
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
In the inbuilt HMI a ringing bell in the top right corner will indicate an active alarm, If the bell
doesn’t move it means that the alarm has been acknowledged but not cleared because the alarm
condition hasn’t been removed.
Same alarm indication is performed by the LED of the button 2 of the external HMI.
M a
E n T
U n I
O F
A c T
i
e
t
f
i
n
r
M
P
S t
:
U
v e
e
a
a
n
S
n
s
t
i
e
1 / 

u
s w o r d
u s =
t
S W
t p t =
7 . 0 ° C
The active item is highlighted in contrast, in this example the item highlighted in Main Menu is a
link to another page. By pressing the button 6, the HMI will jump to a different page. In this case
the HMI will jump to the Enter Password page.
E n t e r
E n t e r
P a s s w o r d
2 / 2
P W
* * * *
3.3 Passwords
The HMI structure is based on access levels that means that each password will disclose all the
settings and parameters allowed to that password level. Basic information about the status
including the active alarm list, active setpoint and controlled water temperature can be accessed
without the need to enter the password.
The UC handles two level of passwords:
USER
5321
MAINTENANCE 2526
The following information will cover all data and settings accessible with the maintenance
password. User password will disclose a subset of the settings explained in chapter 4.
In the Enter Password screen, the line with the password field will be highlighted to indicate that
the field on the right can be changed. This represents a setpoint for the controller. Pressing the
wheel or button 6 the individual field will be highlighted to allow an easy introduction of the numeric
password. By changing all fields, the 4 digits password will be entered and, if correct, the additional
settings available with that password level will be disclosed.
E n t E r
E n t e R
P a s s w o r d
P W
Operation Manual
18
2 / 2
5 * * *
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
The password will time out after 10 minutes and is cancelled if a new password is entered or the
control powers down. Entering an invalid password has the same effect as continuing without a
password.
Once a valid password has been entered, the controller allows further changes and access without
requiring the user to enter a password until either the password timer expires or a different
password is entered. The default value for this password timer is 10 minutes.
3.4 Editing
Only line with highlighted value field can be edited, through the right buttons it is possible selected
and modify the value.
A parameter with an “R” is read only; it is giving a value or description of a condition. An “R/W
indicates a read and/or write opportunity; a value can be read or changed (providing the proper
password has been entered).
Example 1: Check Status, for example -is the unit being controlled locally or by an external
network? We are looking for the Unit Control Source since this a unit status parameter, start at
Main Menu and select View/Set Unit and press the wheel or button 6 to jump to the next set of
menus. There will be an arrow at the right side of the box, indicating that a jump to the next level is
required.
In the new page rotate the wheel or use button 4/5 to highlight the Network Ctrl and press the
wheel or the button 6 again to jump to the next menu where it is possible read the actual Control
Source.
Example 2: Change a Set point, the chilled water set point for example. This parameter is
designated as Cool LWT Set point 1 and is a unit set parameter. From the Main Menu select Active
Setpt. The arrow indicated that there is a link to a further menu.
Press the wheel or button 6 and jump to the temperature setpoint page. Select Cool LWT 1 and
press the wheel or button 6 to jump to the item change page. Rotate the wheel or use buttons 4 / 5
to adjust the set point to the desired value. When this is done press the wheel or button 6 again to
confirm the new value. With the button ESC or 3 it will be possible to jump back to the main menu
where the new value will be displayed.
Example 3: Clear an Alarm,. The presence of a new alarm is indicated with a Bell ringing on the
top right of the display. If the Bell is frozen one or more alarm had been acknowledged but are still
active. To view the Alarm menu from the Main Menu scroll down to the Alarms line. Note the arrow
indicating this line is a link. Press the button 6 to jump to the next menu Alarms. There are two
lines here; Alarm Active and Alarm Log. Alarms are cleared from the Active Alarm link. Press the
button 6 to jump to the next screen. When the Active Alarm list is entered scroll to the item AlmClr
which is set to off by default. Change this value to on to acknowledge the alarms. If the alarms can
be cleared then the alarm counter will display 0 otherwise it will display the number of alarm still
active. When the alarms are acknowledged the Bell on the top right of the display will stop to ring if
some of the alarms are still active or will disappear if all the alarms are cleared.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
19
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
3.5 Basic Control System Diagnostic
Unit controller, extension modules and communication modules are equipped with two status LED
(BSP and BUS) to indicate the operational status of the devices. The BUS LED indicates the status
of the communication with the controller. The meaning of the two status LED is indicated below.
UC BSP LED
BSP LED
Solid Green
Solid Yellow
Solid Red
Flashing Green
Flashing Yellow
Flashing Yellow/Red
Flashing Red
Flashing Red/Green
(*) Contact Service.
Mode
Application running
Application loaded but not running (*) or BSP Upgrade mode active
Hardware Error (*)
BSP startup phase. The controller needs time for starting.
Application not loaded (*)
Fail safe mode (in case that the BSP upgrade was interrupted)
BSP Error (software error*)
Application/BSP update or inizialization
Extension modules
BSP LED
BSP LED
Solid Green
Solid Red
Flashing Red
Flashing Red/Green
Mode
BSP running
Hardware Error (*)
BSP Error (*)
BSP upgrade mode
BUS LED
BUS LED
Solid Green
Solid Yellow
Solid Red
Mode
Communication running, I/O working
Communication running but parameter from the application wrong or missing, or uncorrect factory calibration
Communication down (*)
Communication modules
BSP LED (same for all modules)
BSP LED
Solid Green
Solid Yellow
Solid Red
Flashing Red
Flashing Red/Green
(*) Contact Service.
Mode
BPS running, communication with controller
BSP running, no communication with controller (*)
Hardware Error (*)
BSP Error (*)
Application/BSP update
LON module BUS LED
BUS LED
Solid Green
Solid Yellow
Solid Red
Flashing
Yellow
Mode
Ready for Communication. (All Parameter loaded, Neuron configured). Doesn't indicate a communication
with other devices.
Startup
No Communication to Neuron (internal error, could be solved by downloading a new LON application)
Communication not possible to the Neuron. The Neuron must be configured and set online over the LON
Tool.
Bacnet MSTP BUS LED
BUS LED
Solid Green
Solid Yellow
Solid Red
Operation Manual
20
Mode
Ready for Communication. The BACnet Server is started. It doesn't indicate a active communication
Startup
BACnet Server down. Automatically a restart after 3 seconds are initiated.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Bacnet IP BUS LED
BUS LED
Solid Green
Solid Yellow
Solid Red
Mode
Ready for Communication. The BACnet Server is started. It doesn't indicate a active communication
Startup. The LED stays yellow until the module receives a IP Address, therefore a link must be established.
BACnet Server down. Automatic restart after 3 seconds is initiated.
Modbus BUS LED
BUS LED
Solid
Green
Solid
Yellow
Solid Red
Mode
All Communication running
Startup, or one configured channel not communicating to the Master
All configured Communications down. Means no communication to the Master. The timeout can be configured.
In case that the timeout is zero the timeout is disabled.
3.6 Controller maintenance
The UC requires to maintain the installed battery. Battery model is: BR2032 and it is produced
by many different vendors.
On board real time clock settings are maintained thanks to a battery mounted on the controller.
Make sure that the battery is replaced regularly each 2 years.
Battery is only used to supply the onboard real time clock. All the other settings are retained in a
non volatile memory.
To replace the battery gently remove the plastic cover of the controller display using a screw
driver as shown in the following pictures:
Be careful to avoid damages to the plastic cover. The new battery shall be placed in the proper
battery holder which is highlighted in the following picture, respecting the polarities indicated
into the holder itself.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
21
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
3.7 Software Update procedure
UC can be updated by using an SD card and an appropriate pin.
Actual BSP and software version installed on UC can be checked in the About Chiller page.
SD card has to be FAT32 formatted before any update process can be started. Supported SD
types are:
- SD standard
- High speed SD
- SDHC
The following SD cards have also been tested and found operational:
- 1 GByte SD V1.0 (Inmac)
- 2 GByte SD V2.0 SpeedClass 2 (SanDisk),
- 4 GByte SDHC V2.0 SpeedClass 6 (Hama High Speed Pro),
- 4 GByte SDHC V2.0 SpeedClass 4 (SanDisk Ultra II),
- 8 GByte micro SDHC SpeedClass 4 (Kingston)
In case an update is received all the files included in the archive are to be saved in the SD card
with their original name. The standard software pack is composed with 6 files:
1.
2.
3.
4.
5.
6.
BSP file (operative system of the UC),
Code file,
HMI file,
OBH file (multilingual and protocol support),
HMI for Web (web interface),
Cloud file.
The software for this specific range of units cannot be used with the Large UCs (POL687.xx/MCQ)
used on other products. In case of doubts, please contact your Daikin Service reference.
Operation Manual
22
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Before proceeding is required to disable the unit using the Q0 switch and perform a normal
shutdown procedure.
To install the software, take care to make a copy of the controller settings on the SD card by using
the Save/Restore menu (see Save and Restore menu for details).
Remove power to the controller using the Q12 switch and insert the SD card in its slot as shown in
the picture with the contact strips looking toward you.
Once this is done, insert the pin in the reset hole, gently push the service microswitch and keep it
pressed until the update process is initiated.
Service microswitch is an electronic component. An excessive pressure on the service microswitch
can permanently damage the UC. Please take care of not exceed with your strength to avoid
damages to your unit.
With the service microswitch pressed, re-establish the power to the controller using the Q12
switch. After a short while the BSP led on the UC will start to blink between green and off. When
this happen release the service microswitch and wait for the update process to start. Update
process is indicated by the BSP led blinking between green and red.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
23
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
In case of BSP update the BSP led will stop in off. If this happen the update process has to be
repeated once more. If the BSP led will stop in yellow color the process is completed and the
controller restarted.
After the controller is restarted the BSP led will blink green during the boot up and then it will
remain solid green to indicate normal operations. It’s now possible to restore the previous settings
if available and restart the unit.
3.8 Optional Remote User Interface
As an option an external Remote HMI can be connected on the UC. The Remote HMI offers the
same features as the inbuilt display plus the alarm indication done with a light emitting diode
located below the bell button.


The Remote interface can be ordered with the unit and shipped loose as a field installed option. It
can also be ordered anytime after chiller shipment, mounted and wired on the job site as explained
in the following.
The remote panel is powered directly from the UC. No additional power supply is required.
All views, data and setpoint adjustments available on the UC HMIs are available on the remote
panel. Navigation is identical to the UC as described in this manual.
Operation Manual
24
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
The initial screen when the remote is turned on shows the units connected to it. Highlight the
desired unit and press the wheel to access it. The remote will automatically show the units
attached to it, no initial entry is required.
Long press of the ESC button will show the list of the connected controllers. Use the weel to select
the desired controller.
The Remote HMI can be extended up to 700m using the process bus connection available on the
UC. With a daisy-chain connection as below, a single HMI can be connected to up to 8 units. Refer
to the specific HMI manual for details.
The Remote interface can be also connected with an Ethernet cable (twisted pair). Maximum
length can change depending on the cable characteristic:
 Shielded cable: max length 50m,
 Non shielded cable: max length 3m.
Connection in this case has to be executed as shown in the following image.
EWWQ - EWLQ - EWHQ
Operation Manual
EWAQ - EWYQ
25
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
3.9 Embedded Web Interface
The unit controller an embedded web interface that can be used to monitor the unit when
connected to a local network. It is possible to configure the IP addressing of the controller as a
fixed IP of DHCP depending on the network configuration.
With a common web browser a PC can connect with the unit controller entering the IP address of
the controller or the host name, both visible in the “About Chiller” page accessible without entering
a password.
When connected it will be required to enter a user name and a password as shown in the picture
below:
Enter the following credential to get access to the web interface:
User Name: ADMIN
Password: SBTAdmin!
Operation Manual
26
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
The following page will be displayed:
The page is a copy of the onboard HMI and follows the same rules in terms of access levels and
structure.
In addition it allows to trend log a maximum of 5 different quantities. It’s required to click on the
value of the quantity to monitor and the following additional screen will become visible:
More than one page can be opened at the same time. This can allow to monitor more trends of
different tabs.
Depending on the web browser and its version the trend log feature may not be visible. It’s
required a web browser supporting HTML 5 like for example:



Microsoft Internet Explorer v.11,
Google Chrome v.37,
Mozilla Firefox v.32.
These software are only an example of the browser supported and the versions indicated have to
be intended as minimum versions.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
27
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
4 Menu Structure
All settings are divided in different menus. Each menu collects in a single page other sub-menus,
settings or data related to a specific function (for example Power Conservation or Setup) or entity
(for example Unit or Circuit). In any of the following pages a grey box will indicate changeable
values and the defaults.
4.1 Main Menu
Setpoint/Sub-Menu
Enter Password
View/Set Unit
View/Set Circuit
Unit Status=
Default
Range



Off: Unit Loc/Rem Sw
Active Setpt=
7.0°C 
Auto
Off:
Off:
Off:
Off:
Off:
Off:
Off:
Auto:
Auto:
Auto
Auto:
Auto:
Auto:
Auto:
Off:
-
Evap LWT=
-273.1°C 
-
Cond LWT=
-273.1°C
-
Ice Mode Tmr
All Cir Disabled
Unit Alarm
Keypad Disable
BAS Disable
Unit Loc/Rem Sw
Test Mode
Wait For Load
Evap Recirc (A/C only)
Water Recirc (W/C only)
Wait For Flow
Pumpdn
Max Pull Limited
Unit Cap Limit
Cfg Chg, Rst Ctrlr
Unit Capacity=
Chiller Enable=
0.0%
Enable
Enable-Disable
Unit Mode=
Cool 
-
Timers

-
Alarms

-
Commission Unit

-

-
Save and Restore
About Chiller
Operation Manual
28
Description
Submenu to activate access levels
Submenu for unit data and settings
Submenu for circuit data and settings
Status of the Unit
Active setpoint and link to the
Setpoint page (see section 4.3.1.5 for
more details).
Evaporator
leaving
water
temperature and link to the
Temperatures page (see section 4.5
for more details).
Condenser
leaving
water
temperature and link to the
Temperatures page (W/C only).
Actual unit capacity.
Chiller
operation
enable/disable
setting.
Actual unit mode and link to unit
available mode selection page (see
section 4.6 for more details).
Submenu
compressors
and
thermoregulation safety timers (see
section 4.7 for more details).
Submenu for alarms; same function
as Bell Button (see section 0 for more
details)
Submenu for the chiller configuration
(see section 0 for more details).
Submenu to the Save and Restore
page (see section
Application Info submenu (see
section 0 for more details).
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
4.2 View/Set Unit
Setpoint/Sub-Menu
Thermostat Ctrl
Network Ctrl
Unit Cond Ctrl
Pumps
Master/Slave
Date/Time/Schedule
Power Conservation
Modbus Setup
Bacnet IP Setup
Bacnet MSTP Setup
LON Setup
Ctrlr IP Setup
Cloud Connection
Default













Range
-
Description
Submenu Thermoregulation control parameter
Submenu Network Control
Submenu Unit Condensing Control (W/C only)
Submenu Pumps control and data
Submenu Master Slave
Submenu Date, Time and Quiet Night mode schedule
Submenu Unit Limiting functions
Submenu Setup of Modbus communication
Submenu Setup of Bacnet IP communication
Submenu Setup of Bacnet MSTP communication
Submenu Setup of LON communication
Submenu IP settings for on-board web-server
Submenu Cloud Connection
4.2.1 Thermostat Ctrl
This page resumes all thermoregulation parameters. For more details about this parameters and
the thermoregulation logic see section 5.1.4.
Setpoint/Sub-Menu
Start Up DT=
Shut Dn DT=
Stage DT=
Max Pulldn=
Max PullUp=
Stg Up Delay=
Stg Dn Delay=
Strt Strt Dly=
Stop Strt Dly=
Ice Cycle Dly=
OAT En Bckp Htr=
Default
2.7°C
1.5°C
1.0°C
1.7°C/min
1.7°C/min
2min
30sec
10min
3min
12h
-3.0°C
Range
0.0…5.0°C
0.0…5.0°C
0.0…Start Up DT°C
0.1…2.7°C/min
0.1…2.7°C/min
0…8min
20…60sec
10…60min
3…20min
1…23h
-20.0…5°C
Description
Offset respect the active setpoint for unit start.
Offset respect the active setpoint for unit shutdown
Offset respect the active setpoint for unit stage up and down
Max pull down rate of controlled water temperature
Max pull up rate of controlled water temperature
Compressor start inter-stage delay
Compressor stop inter-stage delay
Compressor Start to Start delay
Compressor Stop to Start delay
Ice cycle delay
Outside Air Temperature to enable the backup heater logic (see section
5.4
4.2.2 Network Ctrl
This page resumes all settings (unit on/off, unit mode, temperature setpoint, capacity limit) set by
BMS when the unit is controlled from network.
Setpoint/SubMenu
Control Source=
Netwrk En SP=
Netwrk Mode SP=
Netwrk Cool SP=
Netwrk Heat SP=
Netwrk Cap Lim=
Netwrk Ice SP=
Default
Range
Local
-
Local, Network
-
Description
Determines whether on/off, cooling/heating/ice setpoint, operation mode,
capacity limit, should be commanded by local (HMI) settings or from BMS
Unit enable from BMS
Unit mode from BMS
Cooling setpoint from BMS
Heating setpoint from BMS
Capacity limitation from BMS
Ice setpoint from BMS
4.2.3 Unit Cond Ctrl (W/C only)
This page resumes all settings for the unit condensing control. For more details about this
parameters and the unit condensing control logic see section 5.6.2
Setpoint/Sub-Menu
Cnd SP Clg=
Cnd SP Htg=
Cnd Act Sp=
Cnd Ctrl Tmp=
Output=
Max Output=
Default
35°C
10°C
100%
Range
20…55°C
-10…20°C
50…100%
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Description
Condenser setpoint for cooling mode
Condenser setpoint for heating mode
Active condensing temperature setpoint
Condensing control temperature
Actual condensing control output
Maximum condensing control output
Operation Manual
29
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Min Output
0%
Air and Water cooled scroll chillers & heat pump
0…50%
Operation
Manual
Minimum condensing control output
4.2.4 Pumps
This page resumes all setting for the water pumps management. For more details about this
parameters and the pump control logic refer to section 0.
Setpoint/Sub-Menu
Evap Pmp Ctrl=
Default
#1 Only
Cond Pmp Ctrl=
#1 Only
Recirc Tm=
Evap Pmp 1 Hrs=
Evap Pmp 2 Hrs=
Cond Pmp 1 Hrs
Cond Pmp 2 Hrs=
30s
0h
0h
0h
0h
Range
#1 Only
#2 Only
Auto
#1 Primary
#2 Primary
#1 Only
#2 Only
Auto
#1 Primary
#2 Primary
15…300s
Description
Set number of evaporator pumps operational and their priority
Set number of condenser pumps operational and their priority (W/C only)
Recirculation water timer
Running Hours Evaporator Pump 1 (if present)
Running Hours Evaporator Pump 2 (if present)
Running Hours Condenser Pump 1 (if present W/C only)
Running Hours Condenser Pump 2 (if present W/C only)
4.2.5 Master/Slave
This page resumes all submenus for the configuration and monitoring of the Master Slave function.
For more details refer to section 5.10
Setpoint/Sub-Menu
Standby Chiller
Options
Thermostat Ctrl
Data
Timers
Disconnect Unit
Default





No
Range
No,Yes
Description
Submenu Standby Chiller
Submenu Options
Submenu Thermostat Ctrl
Submenu Data
Submenu Timers
Parameter to disconnect the unit by the Master Slave network.
When this parameter is set to Yes the unit follows all local settings.
4.2.5.1 Standby Chiller
Through this menu page is possible to define all settings for the Standby chiller. Refer to the
section 5.10.4.2 for more details.
Setpoint/SubMenu
Standby Chiller=
Default
No
Rotation Type=
Interval Time=
Switch Time=
Time
7 Days
00:00:00
Tmp Cmp=
Tmp Comp Time=
Range
No, Auto, Master, Slave 1, Slave
2, Slave 3
Time, Sequence
1…365
00:00:00…23:59:59
No
No,Yes
120 min
0…600
Standby Reset=
Off
Off, Reset
Description
Define the standby chiller
Define the rotation type of the standby chiller if the previous
parameter Standby Chiller is set as Auto
Define the interval time (expressed in day) for the rotation of the
standby chiller
Define the time within the day when will be performed the switch
of the standby chiller
Enabling of the Temperature Compensation function through the
standby chiller.
Time constant for the enabling of the standby chiller used for the
Temperature Compensation
Parameter to reset the counter of the standby chiller rotation
4.2.5.2 Options
Through this menu, available only in the unit configured as Master, is possible to define some
parameters for the global behavior of the Master Slave Network. Refer to the section 5.10.4 for
more details
Operation Manual
30
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Setpoint/SubMenu
Master Priority=
Default
Range
1
1…4
Slave 1 Priority=
1
1…4
Slave 2 Priority=
1
1…4
Slave 3 Priority=
1
1…4
Master Enable=
Enable
Operation
Manual
Description
Start Up / Shut Down priority of the chiller Master
Priority = 1  highest priority
Priority = 4  lowest priority
Start Up / Shut Down priority of the chiller Slave 1
Priority = 1  highest priority
Priority = 4  lowest priority
Start Up / Shut Down priority of the chiller Slave 2.
Priority = 1  highest priority
Priority = 4  lowest priority
This menu is visible only if the parameter M/S Num Of Unit has been configured at
least with value 3
Start Up / Shut Down priority of the chiller Slave 3.
Priority = 1  highest priority
Priority = 4  lowest priority
This menu is visible only if the parameter M/S Num Of Unit has been configured at
least with value 4
Parameter is used to disable the Master Chiller
Enable,
Disable
4.2.5.3 Thermostat control
The parameters changeable with this menu, available only in the unit configured as Master, are
related to the thermoregulation of all Master Slave system.
Setpoint/SubMenu
Start Up DT=
Start Up DT=
Threshold=
Stage Up Time=
Stage Dn Time=
Default
Range
Description
2.7°C
1.5°C
60%
0.0…5.0°C
0.0…5.0°C
30%...100%
5min
5min
0min…20min
0min…20min
Offset respect the active setpoint for the unit startup.
Offset respect the active setpoint for the unit shutdown.
Threshold of load that have to reach all units running before allow the startup of a
new chiller
Minimum time between the start of two chillers
Minim time between the stop of two chillers
4.2.5.4 Data
In this menu, available only in the unit configured as Master, are collected all main data related to
the Master Slave function.
Setpoint/SubMenu
Next On=
Default
-
Next Off=
-
Standby Chiller=
-
Switch Date/Time
-
Master State=
Slave 1=
Slave 2=
Slave 3=
Master Load=
Slave 1 Load=
Slave 2 Load=
Slave 3 Load=
Master ELWT=
Slave 1 EWLT=
Slave 2 EWLT=
Slave 3 EWLT=
-
Range
-,Master, Slave 1, Slave 2,
Slave 4
-,Master, Slave 1, Slave 2,
Slave 4
-,Master, Slave 1, Slave 2,
Slave 4
dd/mm/yyyy
hh:mm:ss
Off, On
Off, On
Off, On
Off, On
0%...100%
0%...100%
0%...100%
0%...100%
-
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Description
Display next chiller that will be starts
Display next chiller that will be stopped
Display the actual standby chiller
Display the day and the time in the day when will be performed the
rotation of the sandby chiller
Display the actual state of the Master
Display the actual state of the Slave 1
Display the actual state of the Slave 2
Display the actual state of the Slave 3
Display the actual load of the Master
Display the actual load of the Slave 1
Display the actual load of the Slave 2
Display the actual load of the Slave 3
Display the Master ELWT
Display the Slave1 ELWT
Display the Slave2 ELWT
Display the Slave3 ELWT
Operation Manual
31
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
4.2.5.5 Timers
In this menu are reported the countdowns for startup and shutdown of a new chiller
Setpoint/Sub-Menu
Stage Up Timer=
Stage Dn Timer=
Default
-
Range
-
Description
Current delay for new chiller stage up
Current delay for new chiller stage down
4.2.6 Date/Time
This page will allow to adjust the time and date in the UC. This time and date will be used in the
alarm log. Additionally it’s also possible to set the starting and ending date for the DayLight Saving
time (DLS) if used.
Setpoint/Sub-Menu
Actual Time=
Actual Date=
UTC Diff=
DLS Enable=
DLS Strt Month=
DLS Strt Week=
DLS End Month=
DLS End Week=
Default
12:00:00
01/01/2014
-60min
Yes
Mar
2ndWeek
Nov
1stWeek
Range
NA, Jan…Dec
1st…5th week
Description
Difference with UTC
No, Yes
DayLight Saving time start month
DayLight Saving time start week
DayLight Saving time end month
DayLight Saving time end week
On board real time clock settings are maintained thanks to a battery mounted on the controller.
Make sure that the battery is replaced regularly each 2 years (see section 3.6).
4.2.7 Power Conservation
This page resumes all the settings that allows chiller capacity limitations. For more details about
these parameters and the functions LWT Reset and Demand Limit refer to section 5.1.7.
Setpoint/Sub-Menu
Unit Capacity
Demand Limit=
Lwt reset Type=
Max Reset Dt=
Start Reset Dt=
Cooling
Max Reset OAT=
Start Reset OAT=
Heating
Max Reset OAT=
Start Reset OAT=
Default
None
Range
None
4-20mA
Return
OAT (A/C only)
0.0…10.0°C
0.0…10.0°C
Description
Displays current unit capacity
Displays current demand limit
Set leaving water temperature setpoint reset type
Refer to section
23.8°C
15.5°C
10.0…29.4°C
10.0…29.4°C
Refer to section (A/C only)
Refer to section (A/C only)
0.0°C
6.0°C
10.0…-10.0°C
10.0…-10.0°C
Refer to section (A/C-H/P only)
Refer to section (A/C-H/P only)
5°C
5°C
Refer to section
Refer to section
4.2.8 Controller IP setup
The UC has an embedded web server showing a replica of the onboard HMI screens. To access
this additional web HMI can be required to adjust the IP settings to match the settings of the local
network. This can be done in this page. Please contact your IT department for further information
on how to set the following setpoints.
To activate the new settings a reboot of the controller is required, this can be done with the “Apply
Changes” setpoint.
The controller also supports DHCP, in this case the name of the controller must be used.
Operation Manual
32
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Setpoint/Sub-Menu
Apply Changes=
DHCP=
Act IP=
Act Msk=
Act Gwy=
Gvn IP=
Gvn Msk=
Gvn Gwy=
Prim DNS=
Sec DNS=
Host Name=
MAC=
Default
No
Off
-
Air and Water cooled scroll chillers & heat pump
Range
No, Yes
Off,On
-
Operation
Manual
Description
Reboot of the controller to apply the changes made
Enable or disable the DHCP (Dynamic Host Configuration Protocol)
Actual IP address
Actual Subnet mask
Actual Gateway
Given IP address (it will become the active) if the DHCP = Off
Given Subnet mask
Given Gateway
Primary DNS
Secondary DNS
Name of the controller
MAC address of the controller
4.3 View/Set Circuit
In this section it is possible to select between the available circuits and access data available for
the circuit selected.
Setpoint/Sub-Menu
Circuit #1
Circuit #2
Default


Range
Description
Menu for Circuit #1
Menu for Circuit #2 (if present)
The submenus accessed for each circuit are identical but the content of each of them reflects the
status of the corresponding circuit. In the following the submenus will be explained only once. If
only one circuit is available the item Circuit #2 in the above table will be hidden and not accessible.
Setpoint/Sub-Menu
Settings
Circuit Status=
Default

Circuit Cap=
Circuit Mode=
0.0%
Enable
Evap Pressure=
Cond Pressure=
Evap Sat Temp=
Cond Sat Temp=
Suction Temp=
Suction SH=
Evap Approach=
Cond Approach=
EXV Position=
VFD Speed
0%
Range
Off:
Off:
Off:
Off:
Off:
Off:
Off:
Off:
Run:
Run:
Run:
Run:
Run:
Run:
Run:
Enable
Disable
0-100%
Ready
Cycle Timer
All Comp Disable
Keypad Disable
Circuit Switch
Alarm
Test Mode
Low Prs Pause (W/C units)
Preopen
Pumpdown
Normal
Evap Press Low
Cond Press High
High Amb Limit (A/C units)
Defrost (A/C units)
Description
Link to circuit settings
Status of the circuit.
Circuit Capacity
Circuit keypad enabling
Evaporating Pressure
Condensing Pressure
Evaporating saturated temperature
Condensing saturated temperature
Suction Temperature
Suction Superheat
Evaporator Approach
Condenser Approach
Expansion valve position
Fan Speed (A/C only)
4.3.1 Settings
This page resumes the status of the circuit.
Setpoint/Sub-Menu
Default
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Range
Description
Operation Manual
33
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Compressors
Circ X Cond Ctrl
Fan Control
EXV
Defrost
Air and Water cooled scroll chillers & heat pump





Operation
Manual
Link to the compressor page
Link to the circuit condensing control page (W/C only)
Link to the circuit fan control page (A/C only)
Link to the EXV page
Link to the defrost page (A/C only)
4.3.1.1 Compressors
This page resumes all the relevant information about compressors of the related circuit.
Note the following compressors enumeration:
1. Compressor 1 and compressor 3 belong to the Circuit #1
2. Compressor 2 and compressor 4 belong to the Circuit #2
Setpoint/Sub-Menu
Comp Enable
Compressor 1
State
Start=
Stop=
Run Hours=
No. Of Starts=
Compressor 3
State
Start=
Stop=
Run Hours=
No. Of Starts=
Default

Off
Range
Off, On
Compressor State
Date and time of the last start
Date and time of the last stop
Running hours of compressor
Number of compressor starts
Off, On
Compressor State
Date and time of the last start
Date and time of the last stop
Running hours of compressor
Number of compressor starts
0h
0
Off
Description
Link to Compressor Enable page
0h
0
The compressors enable page allows to enable or disable each compressor of the unit.
Setpoint/Sub-Menu
Comp 1
Comp 2
Comp 3
Comp 4
Default
Auto
Auto
Auto
Auto
Range
Off, Auto
Off, Auto
Off, Auto
Off, Auto
Description
Enabling of the compressor
Enabling of the compressor (if available)
Enabling of the compressor
Enabling of the compressor (if available)
If a compressor is switched to off while it is in running, it does not shutdown immediately, but the
controller waits normal shutdown for thermoregulation or unit off and after the compressor disabled
will not started until it is enabled again.
4.3.1.2 Circ 1 Cond Ctrl
This page resumes all parameters for the condensing circuit control. For more details about this
parameters and the circuit condensing control logic refer to section 5.6.2.
Setpoint/Sub-Menu
Cnd Sat Tmp SP=
Cnd Sat Tmp=
Output=
Max Output=
Min Output
Default
35.0°C
100.0%
0.0%
Range
30.0…50°C
50…100%
0…50%
Description
Condensing saturated temperature setpoint
Actual condensing saturated temperature
Actual condensing control output
Maximum condensing control output
Minimum condensing control output
4.3.1.3 Fan Control (A/C only)
This page resumes all settings for the fan control. For more details about this parameters and the
fan control logic see section 5.6.3
Setpoint/Sub-Menu
Cond Target=
Evap Target=
Operation Manual
34
Default
38.0°C
2.0°C
Range
20…55°C
-5…10°C
Description
Condensation target for fan control
Evaporation target for fan control (A/C H/P only)
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Cond Sat Temp=
Evap Sat Temp=
VFD Speed=
Fan Max Speed=
Fan Min Speed=
Air and Water cooled scroll chillers & heat pump
100%
20%
0-100%
50…100%
20…50%
Operation
Manual
Condenser pressure
Evaporator pressure
Actual fan speed
Maximum fan speed
Minimum fan speed
4.3.1.4 EXV
This page resumes all the relevant information about the status of the EXV logic. For more details
about this parameters and the control logic of the EXV refer to section 5.7.
Setpoint/Sub-Menu
EXV State=
Suction SH=
Evap Pressure
Act Position=
Cool SSH Target=
Heat SSH Target=
Max Op Pressure=
Default
Closed
6.5dK
6.5dK
900.0 kPa
Range
4.4…30.0dK
2.5…30.0dK
890.0…1172.2kPa
Description
Closed, Pressure, Superheat
Suction Superheat
Evaporating pressure
Expansion valve opening
Cool Suction Superheat setpoint
Heat Suction Superheat setpoint (H/P only)
Maximum operating pressure
4.3.1.5 Defrost (A/C only)
This page resumes all the relevant settings for defrost management. For further information about
the defrost procedure refer to section 5.8
Setpoint/Sub-Menu
Man Defrost=
Defrost Cnt=
Defrost State=
Default
Off
0
W
Cond Pr Lim=
Time to Defrost=
Defrost Parameter=
Defrost Timeout=
Reset Cnt=
2960kPa
20s
10dK
600s
Off
Range
Off, On
W, Pr1, 4W1, Df,
Pr2, 4W2, WuH
2200…3100kPa
0…310s
4…15dK
240…1800s
Off, On
Description
Closed, Pressure, Superheat
Counter of defrost cycles
Defrost execution phase
Condensing pressure limit to finish the defrost
Delay before the defrost is started when the defrost request is active
Parameter do identify the need for a defrost
Maximum defrost duration
Defrost counter Reset
4.4 Tmp Setpoints
This page allows to set the water temperature setpoints in the several modes. For more details
refer to the section 0.
Setpoint/Sub-Menu
Cool LWT 1=
Default
7.0°C
Cool LWT 2=
7.0°C
Ice LWT=
Heat LWT 1=
Heat LWT 2=
4.0°C
45.0°C
45.0°C
Range
4.0…15.0°C
(cool
mode)
-8.0…15.0°C (cool w/
glycol mode)
4.0…15.0°C
(cool
mode)
-8.0…15.0°C (cool w/
glycol mode)
-10.0…4.0°C
25.0…55.0°C
25.0…55.0°C
Description
Primary cooling setpoint
Secondary cooling setpoint (see 3.6.3)
Ice setpoint (ice banking with on/off mode)
Primary heating setpoint (H/P only)
Secondary heating setpoint (H/P only)
4.5 Temperatures
This page shows all water temperatures, evaporator and condenser delta temperature between
inlet and outlet.
Setpoint/Sub-Menu
Evap LWT=
Evap EWT=
Cond LWT=
Cond EWT=
Default
-
Range
-
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Description
Evaporator leaving water temperature
Evaporator entering water temperature
Condenser leaving water temperature
Condenser entering water temperatue
Operation Manual
35
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Evap Delta T=
Cond Delta T=
Evap LWT Slope=
Cond LWT Slope=
-
Air and Water cooled scroll chillers & heat pump
-
Operation
Manual
Evaporator delta temperature
Condenser delta temperature
Evaporator leaving water temperature rate of change
Condenser leaving water temperature rate of change
4.6 Available Modes
This page allows to set the operating mode of the unit. For more details about these parameters
and the available modes of the unit refer to section 5.1.2.
Setpoint/Sub-Menu
Modes
Default
Cool
Range
Cool
Cool w/Glycol
Cool/Ice w/Glycol
Ice
Heat/Cool
Heat/Cool w/Glycol
Heat/Ice w/Glycol
Pursuit
Test
Description
Available modes for unit operations.
4.7 Timers
This page indicates the remaining cycle timers for each compressor. When the cycle timers are
active any new start of a compressor is inhibited.
Setpoint/Sub-Menu
Comp 1=
Comp 2=
Comp 3=
Comp 4=
Clear Cycle Tmrs
Stg Up Dly Rem=
Stg Dn Dly Rem=
Clr Stg Delays=
Ice Cycle Dly Rem
Clear Ice Dly=
Default
Range
Description
Off
0s
0s
0s
0s
Off,On
Clear Cycle Timers
Off
Off,On
Clear Stages Delays
Off
Off,On
Cleat Ice Delay
4.8 Alarms
This link jumps to the Alarm page. Each of the items represents a link to a page with different
information. The information shown depends on the abnormal operating condition that caused the
activation of unit, circuit or compressor safeties. A detailed description of the alarms and how to
handle will be discussed in the section Troubleshooting this chiller.
Setpoint/Sub-Menu
Alarm Active
Alarm Log
Event Log
Alarm Snapshot
Default




Description
List of the active alarms
History of all the alarms and acknowledges
List of the events
List of alarm snapshots with all the relevant data recorded at time the alarm occurred.
4.9 Commission Unit
Setpoint/Sub-Menu
Configure Unit
Alarm Limits
Calibrate Unit Sensors
Calibrate Circuit Sensors
Unit Manual Control
Circuit 1 Manual Control
Operation Manual
36
Default






Range
Description
See section 0
See Section 4.9.2
See section 4.9.3
See section 4.9.4
See section 0
See section 0
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump


Circuit 2 Manual Contorl
Scheduled Maintenance
Operation
Manual
See section 4.9.7
4.9.1 Configure Unit
This page resumes all the specific settings for this unit like unit type, number of circuits, type of
condensing control, etc.. Part of these settings cannot be adjusted and are supposed to be set
during the manufacturing or commissioning of this unit. The modification of each parameter in this
menu requires that the unit switch is set to 0.
Setpoint/SubMenu
Apply Changes=
Unit Type=
Default
Range
No
EWWD
None
Noise Class=
Number Of Cir=
Inversion Type
Cond Ctrl Var=
Std
1
No
No
Cond Ctrl Dev=
M/S Address
None
Standalone
M/S Nom Of Unit
M/S Sns Type
2
NTC10K
Unit Alm Behavior=
Blinking
Display Units=
HMI Language=
Enable Options
PVM/GFP=
External Alarm=
Metric
English
Disable
Disable
Demand Limit=
Lwt Reset=
Comm Module 1=
Disable
Disable
None
Comm Module 2=
None
Comm Module 3=
None
No, Yes
EWWD, EWLD
None,
Chiller,
HeatPump
Std, Low
1,2
No, Water, Gas
No,
Pressure,
Cond In, Cond
Out
None, Valve, VFD
Standalone,
Master, Slave 1 ,
Slave 2, Slave 3
2,3,4
NTC10K, PT1000
Blinking,
NotBlinking
Metric,English
English
Disable, Enable
Disable,
Event,
Alarm
Disable, Enable
Disable, Enable
None, IP, Lon,
MSTP, Modbus,
AWM
Modbus, Bacnet
IP, Bacnet MSTP,
Lon, AWM
Modbus, Bacnet
IP, Bacnet MSTP,
Lon, AWM
Description
Type yes after changes
Select the unit type, chiller (EWWD) or condenser less (EWLD) (W/C only)
Select the unit type basing on the model name.
Selects between the two noise class. (A/C C/O only)
Number of circuit of the chiller
Type of inversion in heat pump mode. (W/C only)
Enabling of the condensing control (W/C only)
Select device type used for condensing control (W/C only)
Define if the chiller works as standalone or belongs to Master Slave
network,
Indicate the number of chiller belonging to Master Slave network. This
parameter have to be set only in the chiller Master, in all Slave units it can
be let at default value as ignored.
Define the sensor type used to measure the common leaving water
temperature.
This parameter have to be set only in the chiller Master, in all Slave units it
can be let at default value as ignored.
Behavior of the unit alarm digital output
Measurement system
Enabling of the phase voltage monitor
Enabling of the Event or External Alarm input.
Enabling of the Demand Limit signal
Enabling of the Lwt Reset signal
Auto-configured when UC link with related module
Auto-configured when UC link with related module
Auto-configured when UC link with related module
Modification to any of these values will require to be acknowledged to the controller by setting
“Apply Changes = Yes”. This will cause a controller reboot! This action can only be performed with
the Q0 switch on the unit switchbox set to 0.
4.9.2 Alarm Limits
This page contains all alarm limits, including low pressure alarm prevention thresholds. In order to
ensure proper operation they have to be set manually according to the specific application.
Setpoint/Sub-Menu
Low Press Alm=
Defau
lt
200.0k
Range
200.0…630.0kPa
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Description
Low pressure alarm limit
Operation Manual
37
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Evap Water Frz=
Pa
670.0k
Pa
650.0
KPa
3850k
Pa
4000k
Pa
2.0°C
Cond water Frz=
2.0°C
Low Press Hold=
Low Press Unld =
Hi Press Unld=
Hi Press Stop=
Flw Proof=
Evp Rec Timeout=
Low OAT Strt Time
Min Delta Pres=
5s
3min
165se
c
400.0k
Pa
Air and Water cooled scroll chillers & heat pump
Operation
Manual
150.0…793.0kPa
Low pressure hold limit
150.0…793.0kPa
Low pressure unload limit
3800…3980kPa
High pressure unload limit
3900…4300kPa
High pressure alarm limit
2.0…5.6°C (without
Glycol)
-20.0…5.6°C (with
Glycol)
2.0…5.6°C (without
Glycol)
-20.0…5.6°C (with
Glycol
5…15s
1…10min
150…240s
Evaporator freeze protection limit
50…700kPa
Minimum pressure difference to trigger the Low Delta Pressure alarm
Condenser freeze protection limit (W/C only)
Flow proof delay
Recirculating timeout before the alarm is raised
Start time during which the low pressure alarm is ignored.
Once tripped, the software will get back to normal operation. However, the alarm will not be reset
until the high pressure switches are manually reset through the button included in the switch.
4.9.3 Calibrate Unit Sensors
This page allows a proper calibration of the unit sensors.
Setpoint/Sub-Menu
Evap LWT=
Evp LWT Offset=
Evap EWT=
Evp EWT Offset=
Cond LWT =
Cond Lwt Offset=
Cond EWT=
Cond EWT Offset=
OA Temp=
OA Temp Offset=
Default
7.0°C
0.0°C
12.0°C
0.0°C
35°C
0.0°C
30.0°C
0.0°C
30.0°C
0.0°C
Range
-5.0…5.0°C
-5.0…5.0°C
-5.0…5.0°C
-5.0…5.0°C
-5.0…5.0°C
Description
Evaporator LWT current reading (includes the offset)
Evaporator LWT calibration
Evaporator EWT current reading (includes the offset)
Evaporator EWT calibration
Condenser LWT current reading (includes the offset) (W/C only)
Condenser LWT calibration (W/C only)
Condenser EWT current reading (includes the offset) (W/C only)
Condenser EWT calibration (W/C only)
Oustide Air Temperature current reading (includes the offset) (A/C only)
Oustide Air Temperature calibration (A/C only)
4.9.4 Calibrate Circuit Sensors
This page allows a proper calibration of the circuit sensors
Setpoint/Sub-Menu
Evap Pressure=
Evp Pr Offset=
Cond Pressure=
Cnd Pr Offset=
Suction Temp=
Suction Offset=
Discharge Temp=
Discharge Offset=
Default
Range
0.0kPa
-100.0…100.0kPa
0.0kPa
-100.0…100.0kPa
0.0°C
-5.0…5.0°C
0.0°C
-5.0…5.0°C
Description
Evaporator Pressure current reading (includes the offset)
Evaporator Pressure offset
Condenser Pressure current reading (includes the offset)
Condenser Pressure offset
Suction Temperature current reading (includes the offset)
Suction Temperature offset
Discharge Temperature current reading (includes the offset) (A/C only)
Discharge Temperature offset (A/C only)
Calibrations of the Evaporator Pressure and Suction Temperature are mandatory for the
applications with negative water temperature setpoints. These calibrations have to be performed
with proper gauge and thermometer.
An improper calibration of the two instruments may generate limitation of the operations, alarms
and even damages to components.
Operation Manual
38
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
4.9.5 Unit Manual Control
This page contains all the test point, status of the digital inputs, status of the digital output and raw
value of the analog inputs associated to the Unit. To activate the test point it’s required to set the
Available Modes to Test (see section 4.6).
Setpoint/Sub-Menu
Test Unit Alarm=
Test Evap Pump 1=
Test Evap Pump 2=
Test Cond Pump 1=
Test Cond Pump 2=
Test Cond Valve Out=
Test VFD Out=
Input/Output Values
Unit Sw Inpt=
Dbl Sp Inpt=
Evap Flow Inpt=
Cond Flow Inpt=
HP Switch Inpt=
PVM/GFP Inpt=
Ext Alm Inpt=
Unit Alm Outpt=
Evp Pmp1 Outpt=
Evp Pmp2 Outpt=
Cnd Pmp1 Outpt=
Cnd Pmp2 Outpt=
Evap EWT Res=
Evap LWT Res=
Cond EWT Res=
Cond LWT Res=
Dem Lim Curr=
LWT Reset Curr=
Cond Valve Outpt=
VFD Outpt=
Defaul
t
Off
Off
Off
Off
Off
0.0%
0.0%
Range
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
0Ohm
0Ohm
0Ohm
0Ohm
0mA
0mA
0.0V
0.0V
Description
Off/On
Off/On
Off/On
Off/On
Off/On
0…100%
0…100%
Test of the General Alarm relay output
Test of the Evaporator Pump #1
Test of the Evaporator Pump #2
Test of the Condenser Pump #1
Test of the Condenser Pump #2
Test Valve output for condensing control
Test VFD output for condensing control
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Status of the Unit Switch
Status of the Double Setpoint
Status of the Evaporator Flow switch
Status of the Condenser Flow switch
Status of the Heat Pump switch
Status of Phase Voltage monitor, Under-Over voltage protection or Ground
Fault protection (check option installed)
Status of the External Alarm
Status of the General Alarm relay
Status of the Evaporator Pump #1 relay
Status of the Evaporator Pump #2 relay
Status of the Condenser Pump #1 relay
Status of the Condenser Pump #2 relay
Resistance of the Evap EWT sensor
Resistance of the Evap LWT sensor
Resistance of the Cond LWT sensor
Resistance of the Cond LWT sensor
Current input for the Demand Limit
Current input for the Setpoint Reset
Voltage output for the valve of the condensing control
Voltage output for the VFD of the condensing control
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
340-300kOhm
340-300kOhm
340-300kOhm
340-300kOhm
3-21mA
3-21mA
0.0-10.0V
0.0-10.0V
4.9.6 Circuit 1 Manual Control
This page contains all the test point, status of the digital inputs, status of the digital output and raw
value of the analog inputs associated to the Circuit #1 (or Circuit #2 if present and depending on
the link followed). To activate the test point it’s required to set the Available Modes to Test (see
section 4.6).
Setpoint/SubMenu
Test Comp 1=
Test Comp 3=
Test 4 Way Valve=
Test VFD=
Test EXV Pos=
Test Cond Valve
Out=
Test VFD Out=
Input/Output Values
Evap Pr Inpt=
Cond Pr Inpt=
Suct Temp Res=
Comp 1 Output=
Comp 3 Output
Cond Valve Outpt=
Default
Range
Description
Off
Off
Off
Off
0.0%
0.0%
Off,On
Off,On
Off,On
Off,On
0-100%
0-100%
Test of the compressor 1 (first compressor of the circuit number 1)
Test of the compressor 3 (second compressor of the circuit number 1)
Test of the 4 way valve
Test of the VFD enable.
Test of the Expansion Valve movements
Test Valve output for condensing control
0.0%
0-100%
Test VFD output for condensing control
0.4-4.6V
0.4-4.6V
340-300kOhm
Off/On
Off/On
0.0-10.0V
Input voltage for the Evap Pressure
Input voltage for the Cond Pressure
Resistance of the Suction Temp sensor
Status of the compressor 1 (first compressor of the circuit number 1)
Status of the compressor 3 (second compressor of the circuit number 1)
Voltage output for the valve of the condensing control
0.0V
0.0V
0Ohm
Off
Off
0.0V
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
39
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
VFD Outpt=
0.0V
Air and Water cooled scroll chillers & heat pump
0.0-10.0V
Operation
Manual
Voltage output for the VFD of the condensing control
4.9.7 Scheduled Maintenance
This page may contains the contact number of the Service organization taking care of this unit and
the next maintenance visit schedule.
Setpoint/Sub-Menu
Next Maint=
Support Reference=
Default
Jan 2015
999-999-999
Range
Description
Schedule date for next maintenance
Reference number or email of Service Org
4.10 Save and Restore
The controller has a feature to save and then restore on an SD card the actual unit settings. This
feature can be useful when a software upgrade is needed or to keep a copy of the actual settings
for future usages like a controller replacement.
In case of backup, part of the settings like number of starts and running hours may not be restored.
Backups may be done periodically to save a more recent status of the settings.
This page has all the setpoints to command a save and/or a restore of a previously saved
parameter file.
Setpoint/Sub-Menu
SD Card State=
Default
NoCard
Save to SD=
Save SD Rslt=
Rstr From SD=
Rstr SD Rslt=
No
Idle
No
Idle
Range
NoCard, ReadOnly,
ReadWrite
No, Yes
Fail, Pass, Idle
No, Yes
Fail, Pass, Idle
Description
Status of the SD card.
Setpoint to force a parameter file creation on an SD card
Result of the Save command
Setpoint to force a parameter restore from an SD card
Before proceeding be sure that the SD card is properly fitted in its slot as shown in the picture. A
status of the SD card is also displayed in the same page to check if it’s allowed to save the
parameters.
To save a copy of the settings the SD Card State must be ReadWrite (1). If the State is ReadOnly (2)
check the position of the card-lock.
Operation Manual
40
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Read/Write
Operation
Manual
Read Only
When the SD card is in and Write is allowed change Save to SD to Yes. The Save to SD Result
will temporarily change to Fail and if the process is successful it will then change to Pass. A file
named “PARAM.UCF” will be saved in the root folder of the SD Card.
The same procedure is used to restore the settings from a previously saved configuration file. The
file must be stored in the root folder of the SD Card.
After the parameters have been restored a reboot of the controller is required to let the new
settings operational.
4.11 About this Chiller
This page resumes all the information needed to identify the unit and the current software version
installed. These information may be required in case of alarms or unit failure
Setpoint/Sub-Menu
Model
G.O.
Unit S/N=
Enter Data
BSP Ver=
App Ver=
HMI GUID=
Default
Range
OBH GUID=
Description
Code name
This field could contain the unit order number (OVyy-zzzzz)
Unit serial number
This field should contain the unit serial number (CH-yyLxxxxx)
Firmware version
Software version
Unique Identification of the HMI software
HEX number for HMI GUID
Unique Identification of the OBH software
HEX number for OBH GUID
5 Working with this unit
This chapter contains a guide on how to deal with the everyday usage of the unit. The next
sections describe how to perform routine tasks on the unit and which type of controls are available
on the unit.
5.1 Unit Setup
Before starting up the unit, some basic settings need to be set by the customer according to the
application.
Control Source
Available Modes
Temperature Setpoints
Thermostat Control Settings
Alarm Settings
Pumps
Power Conservation
Date/Time/Schedules








See chapter 4.2.2
See chapter 5.1.2
See chapter 0
See chapter 5.1.4
See chapter 5.1.5
See chapter 0
See chapter 5.1.7
See chapter 4.2.5
5.1.1 Control Source
This function allows to select which source should be used for unit control. The following sources
are available:
Local
Unit is enabled by local switches placed into the switchbox.
Chiller mode (cool, cool w/glycol, ice, heat, pursuit), LWT setpoint and capacity limit are determined by local settings in the
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
41
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Network
Air and Water cooled scroll chillers & heat pump
Operation
Manual
HMI.
Unit is enable by a remote switch.
Chiller mode, LWT setpoint and capacity limit are determined by an external BMS. This function requires:

Remote enable connection to a BMS (unit on/off switch must be in remote)

Communication module and its connection to a BMS.
More parameters about network control can be found in 4.2.2.
5.1.2 Available Mode Setting
The following operating modes can be selected through the Available modes menu 4.6:
Cool
Set if chilled water temperature down to 4°C is required. No glycol is generally needed in the water circuit,
unless ambient temperature may reach low values.
Cool w/Glycol
Set if chilled water temperature below 4°C is required. This operation requires proper glycol/water mixture in the
evaporator water circuit.
Cool/Ice w/Glycol
Set in case a dual cool/ice mode is required. This setting implies an operation with double setpoint which is
activated through a customer supplied switch, according to the following logic:

Switch OFF: The chiller will work in cooling mode with the Cool LWT 1 as the Active Setpoint.

Switch ON: The chiller will work in ice mode with the Ice LWT as the Active Setpoint.
Ice
Set if ice storage is required. The application requires the compressors to operate at full load until the ice bank is
completed, and then to stop for at least 12 hours. In this mode the compressor(s) will not operate at part load,
but will work only in on/off mode.
The following three modes allow to switch the unit between heat mode and one of the previous cool mode (Cool, Cool w/Glycol, Ice)
Set heat mode if warmed water temperature up to 55°C is required (H/P only)
Heat/Cool
Set in case a dual cool/heat mode is required. This setting implies an operation with double functioning which is
activated through the Cool/Heat switch on the electric box

Switch COOL: The chiller will work in cooling mode with the Cool LWT 1 as the Active Setpoint.

Switch HEAT: The chiller will work in heat pump mode with the Heat LWT 1 as the Active Setpoint.
Heat/Cool w/Glycol
Set in case a dual cool/heat mode is required. This setting implies an operation with double functioning which is
activated through the Cool/Heat switch on the electric box

Switch COOL: The chiller will work in cooling mode with the Cool LWT 1 as the Active Setpoint.

Switch HEAT: The chiller will work in heat pump mode with the Heat LWT 1 as the Active Setpoint.
Heat/Ice w/Glycol
Set in case a dual cool/heat mode is required. This setting implies an operation with double functioning which is
activated through the Cool/Heat switch on the electric box

Switch ICE: The chiller will work in cooling mode with the Ice LWT as the Active Setpoint.

Switch HEAT: The chiller will work in heat pump mode with the Heat LWT 1 as the Active Setpoint.
Pursuit (W/C only)
Set in case of double water control cool and contemporary heat.
Evaporator leaving water temperature follows the Cool LWT 1 setpoint.
Condenser leaving water temperature follows the Heat LWT 1 setpoint.
Test
Enables the Manual Control of the unit. The manual test feature helps in debugging and checking the
operational status of sensors and acutators. This feature is accessible only with the maintenance password in
the main menu. To activate the test feature is required to disable the Unit from the Q0 switch and change the
available mode to Test.
When the Available Mode setpoint is changed to Test for a unit that has been configured for brine
application, water setpoint, freeze limit and low pressure safeties are set to the minimum value for
non-brine units and require to be restored to the previously adjusted values.
5.1.3 Temperature Setpoint Settings
Purpose of the chiller is to keep the evaporator leaving water temperature as close as possible to a
pre-set value, called Active Setpoint. The Active Setpoint is calculated by the unit controller based
on the following parameters and physical input





Base setpoint determined by the actual operating mode (Cool, Cool w/Glycol, Ice, Heat,
Pursuit)
Double Setpoint (Digital input)
Setpoint Reset (4-20mA analog input)
OAT Reset (A/C only)
Evaporator Delta T Reset (A/C only)
Operation Manual
42
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
LWT setpoint can also be set via network if the appropriate control source has been selected.
Setpoint range is limited according to the selected operating mode. The controller includes two
setpoint in cooling mode (either standard cool or cool w/glycol) and one setpoint in ice mode, which
are activated according to Operating mode and Dual Setpoint selection. All default setpoint with
their ranges are reported in the table below.
Actual Operating Mode
Cool
Cool w/ Glycol
Ice
Heat
Double Setpoint Input
OFF
ON
OFF
ON
N/A
OFF
ON
LWT Setpoint
Cool LWT 1
Cool LWT 2
Cool LWT 1
Cool LWT 2
Ice LWT
Heat LWT 1
Heat LWT 2
Default
7.0°C
7.0°C
7.0°C
7.0°C
-4.0°C
45.0°C
45.0°C
Range
4.0°C  15.0°C
4.0°C  15.0°C
-10.0°C  15.0°C
-10.0°C  15.0°C
-10.0°C  4.0°C
25.0°C  55.0°C
25.0°C  55.0°C
The LWT setpoint can be overridden in case the setpoint reset (for details see chapter 5.1.7.2).
Double Setpoint, Setpoint Reset features are not operational in Ice Mode.
5.1.4 Thermostat Control Settings
Thermostat control settings allow to set up the response to temperature variations and the
precision of the thermostat control. Default settings are valid for most applications, however site
specific conditions may require adjustments in order to have a smooth and precise temperature
control or a quicker response of the unit. The parameters mentioned below can be set from the
menu 4.2.1
The following explanation can be read for Chiller/Heat Pump modes.
Compressors start conditions. The control will start the first compressor if the controlled
temperature is higher/lower than the active setpoint of at least a Start Up DT value. The other
compressors will start, one at a time, if the controlled temperature is higher/lower than the active
setpoint of at least Stage Up DT value.
Compressors shutdown conditions. The control will shut down the compressors, one at a time,
if the controlled temperature is lower/higher than the active setpoint of at least Stage Down DT
value. Last compressor in run will shut down if the controlled water temperature is lower/higher
than the active setpoint of at least Shut down DT value.
Temperature Limitation. The start-up and shut-down of all compressors are inhibited if the
controlled water temperature decreases/increases faster than Pull Down Rate/Pull Up Rate limit
value.
Time Limitation. The start-up and shut-down of each compressor must respect the following time
constrains.
1. A compressor can start only if since the last start-up or shut-down of any other compressor
the Stage Up Delay has expired.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
43
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
2. A compressor can stop only if since the last start-up or shut-down of any other compressor
the Stage Dn Delay has expired.
3. A compressor can start only if since its previous start-up the Start to Start Delay has
expired
4. A compressor can start only if since its previous stop the Stop to Start Delay has expired
The unit capacity remains constant if the controlled temperature is within the interval:
[ Setpoint - Stage Up DT ÷ Setpoint + Stage Down DT ]
The following table summarize the conditions for compressors start and shut down explained
above.
First Compressor Start
Cool Mode
Controlled Temperature > Setpoint + Start Up DT
Heat Mode
Controlled Temperature < Setpoint - Start Up DT
Other Compressor Start
Controlled Temperature > Setpoint + Stage Up DT
Controlled Temperature < Setpoint - Stage Up DT
Last Compressor Off
Controlled Temperature < Setpoint - Shut Dn DT
Controlled Temperature > Setpoint - Shut Dn DT
Other Compressor Off
Controlled Temperature < Setpoint - Stage Dn DT
Controlled Temperature > Setpoint - Stage Dn DT
A qualitative example of compressors start-up sequence in cool mode operation is shown in the
graph below.
Operation Manual
44
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Compressors start-up sequence - Cool
mode
ELWT [°C]
SP+StartUpΔT
SP+StageUpΔT
S
P
# Compressors On
Time
First
Compressor
On
Compressor starting
inhibited for maximum
pull down rate
Other Compressors On
Dead band
zone
4
3
2
1
Time
Compressors are always started and stopped to guarantee the balancing of running hours and
number or starts in multiple circuits units. This strategy optimizes the lifetime of compressors,
inverters, capacitors and all the others circuit components.
5.1.5 Alarm Settings
Factory defaults are set for standard cooling mode, therefore they may not be properly tuned when
working at different conditions. Depending on the application, the following alarm limits need to be
adjusted:




Low Press Hold
Low Press Unload
Evap Water Frz
Cond Water Frz (W/C only)
Low Press Hold
Low Press Unload
Evap Water Frz
Cond Water Frz
(W/C only)
Set the minimum refrigerant pressure of the unit. It is generally recommended to set to a value whose saturated
temperature is 8 to 10°C below the minimum active setpoint. This will allow a safe operation and a proper control
of compressor suction superheat.
Set lower than the hold threshold enough to allow a suction pressure recovery from fast transients without
unloading the compressor. A 20 kPa differential is generally appropriate for most applications.
Stops the unit in case the evaporator leaving temperature falls below a given threshold. To allow a safe operation
of the chiller, this setting must be adequate to the minimum temperature allowed by the mixture water/glycol
present in the evaporator water circuit.
Stops the unit in case the condenser leaving temperature falls below a given threshold. To allow a safe operation
of the chiller, this setting must be adequate to the minimum temperature allowed by the mixture water/glycol
present in the condenser water circuit.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
45
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
5.1.6 Pumps
The UC can manages one or two water pumps either for the evaporator either for the condenser.
Number of pumps and their priority can be set from the menu 4.2.4.
Evap Pump Ctrl
Cond Pump Ctrl
Recirc Tm
Set number of active pumps and priority
Set number of active pumps and priority (W/C only)
This parameter indicates the minimum time for which the evaporator/condenser flow switches must be active
before to start the thermostat control
The following options are available for the pumps:
#1 Only
#2 Only
Auto
#1 Primary
#2 Primary
Set to this in case of single pump or twin pump with only #1 operational (f.e. in case of maintenance on #2)
Set to this in case of twin pump with only #2 operational (f.e. in case of maintenance on #1)
Set for automatic pump start management. At each chiller start, the pump with the least number of hours will be activated.
Set to this in case of twin pump with #1 running and #2 as a backup
Set to this in case of twin pump with #2 running and #1 as a backup
5.1.6.1 Pumps control for W/C units
The UC manages the pumps differently depending on the water circuit that they belong.
The pumps connected to the load water circuit (water circuit connected with the plant) are started
when the unit is set to Enabled and there are compressors available to run. The pumps connected
to the source water circuit (water circuit connected with the cooling tower, water well, etc.) are
started only when at least one of the compressor is started. When the unit is configured as Heat
Pump with water inversion the controller inverts the functioning of the pumps. This means that the
pump managed for the load water circuit in cooling mode is managed, instead, for the source water
circuit in heating mode and viceversa.
If the condensing control is set as Pressure mode (see section 5.4) the pumps connected to the
source water circuit are managed in a different way. Each pump is related to one of the two
refrigerant circuits and it is started automatically only when required to guarantee the condensing
target.
When the unit is configured as Heat Pump with water inversion the controller inverts the
functioning of the pumps. This means that the pump managed for the primary water circuit in
cooling mode is managed, instead, for the secondary water circuit in heating mode and viceversa.
5.1.6.1 Pumps control for A/C units
In this case the UC only manages the pumps connected to the load water circuit. Lead pump is
started when the unit is set to Enabled and there are compressors available to run.
Depending on the HMI setting pumps are managed differently.
In case of twin pumps in case of flow loss, the UC will try to change over between the lead and the
standby pump to avoid flow loss alarms.
When the unit is disabled the pump is kept running for additional Recirculate Timer delay.
5.1.7 Power Conservation
The unit controller provides two different functions that allow to limit the chiller capacity.
1. Demand Limit: limits the maximum unit capacity.
2. Lwt Reset: applies an offset to the base water temperature setpoint.
Both function must be enabled through the menu Configure Unit 0.
Operation Manual
46
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
5.1.7.1 Demand Limit
Demand limit function allows the unit to be limited to a specified maximum capacity. The capacity
limit is given through an external 4-20 mA signal. The table below reports the unit limitation based
on the 4-20mA signal:
Number of
compressors
2
4
Demand Limit Signal [mA]
Maximum unit capacity [%]
< 12 mA
> 12 mA
< 8 mA
8 mA< < 12 mA
12 mA< < 16 mA
16 mA< < 20 mA
100%
50%
100%
75%
50%
25%
Maximum number of
compressors On
2
1
4
3
2
1
In the Power Conservation 4.2.7 menu are reported the actual unit capacity and actual demand
limit.
Unit Capacity
Demand Limit
Displays current unit capacity
Displays active demand limit
5.1.7.2 LWT Reset
The LWT Reset function applies a variable offset to the base temperature setpoint selected
through the interface from the menu Temperature Setpoints 4.3.1.5.
If the unit works in Chiller mode the offset has a positive value, so the new setpoint will be greater
than the base setpoint.
If the unit works in Heat pump mode the offset has a negative value, so the new setpoint will be
lower than the base setpoint.
This offset can be calculated starting from:



External signal (4-20mA),
Evaporator or Condenser (W/C only) ΔT (Return),
OAT Reset (A/C only)
The following setpoints are available through the menu 4.2.7:
Lwt Rest Type
Max Reset
Start Reset DT
Set the Setpoint Reset mode (None, 4-20 mA, Return, OAT)
Max Setpoint Reset (valid for all active modes)
Used on Setpoint Reset by Evaporator DT
Setpoint Reset by External 4-20 mA Signal
The active setpoint is calculated applying a correction based on an external 4-20mA signal. 4 mA
corresponds to 0°C correction, while 20 mA corresponds to a correction of the active setpoint as
set in Max Reset (MR). The pictures below shows how is modified the setpoint respectively in
chiller and heat pump mode. The following abbreviations are used.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
47
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
AS
Air and Water cooled scroll chillers & heat pump
Cool Mode
AS
LWT SP + MR
Operation
Manual
Heat Mode
LWT SP
MR
MR
LWT SP - MR
LWT SP
Signal
4mA
MR
AS
LWT SP
Signal
Signal
20mA
4mA
20mA
Max Reset
Active Setpoint
LWT Setpoint
4-20 mA Analog input singal
Setpoint Reset by Evaporator Return Temperature
The active setpoint is calculated applying a correction that depends on the evaporator entering
(return) water temperature
If the unit works in heat pump mode with water inversion the correction depends on the condenser
entering (return) water temperature (W/C only).
When the evaporator/condenser ΔT becomes lower than the SRΔT value, an offset to the LWT
setpoint is increasingly applied, up to the MR value when the ΔT is equal to zero
MR
AS
SRT
LWT SP
Max Reset
Active Setpoint
Start Reset DT
LWT Target
AS
Cool Mode
AS
LWT SP + MR
Heat Mode
LWT SP
MR
MR
LWT SP
LWT SP - MR
Evap T
SRT
0
SRT
Evap T
Cond T
The Return Reset may affect negatively the chiller operation when operated with variable
flow.
0 Avoid to use this strategy in case of inverter water flow control.
Setpoint Reset by Outside Air Temperature (OAT) (A/C only)
The active setpoint is calculated applying a correction that depends on the outside air temperature.
Operation Manual
48
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
AS
Air and Water cooled scroll chillers & heat pump
Cool Mode
AS
LWT SP + MR
Heat Mode
LWT SP
MR
MR
LWT SP - MR
LWT SP
OAT
MROAT-C
MR
AS
LWT SP
MROAT-C
SROAT-C
MROAT-H
SROAT-H
Operation
Manual
SROAT-C
SROAT-H
MROAT-H
OAT
Max Reset
Active Setpoint
LWT Target
Max Reset OAT Cooling
Start Reset OAT Cooling
Max Reset OAT Heating
Start Reset OAT Heating
5.2 Unit/Circuit Start-up
In this section, starting and stopping sequence of the unit will be described. All HMI status will be
briefly described to allow a better understanding of what is going on into the chiller control.
5.2.1 Prepare the unit to start
In order to let the unit start all the enable signals has to be changed to enable. The list of enabling
signals are:



Local/Remote Enable signals = Enable
Keypad Chiller Enable = Enable
BMS Chiller Enable Setpoint = Enable
These items will be now discussed. Each unit is equipped with a Local/Remote selector. It is
installed on the unit switchbox and can be positioned on three different positions: Local, Disable,
Remote as shown in the following picture:
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
49
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
With the Q1 switch in the Stop position the unit is disabled. Pump will not
start in normal operational condition. Compressors are kept disabled
independently from the status of the individual enable switches.
With the Q1 switch in the Start position the unit is enabled. Pump will
start if all other enable signals are set to enable and at least one
compressors is available to run
With the Q1 switch in the Remote position the unit can be enabled using
the additional connections available on the connection terminals. A
closed loop will identify an enable signal, this can come from a remote
switch or a timer by example.
The Keypad enable signal cannot be modified with the user password level but it requires the
maintenance password.
The last enable signal is coming through the high level interface, that mean from a Building
Management System. From a BMS connected to the UC using a communication protocol the unit
can be disabled. To see if the enable signal is coming from a BMS in the View/Set Unit and then
Status/Settings check the Control Source, if it is set to Network than the Network En SP setpoint in
the same page will reflect the actual signal coming from the BMS. If the value is set to Disable then
the unit cannot start. In this case check with your BAS company how the chiller is operated.
The Unit Status will inform about the current unit status, possible status will be described in the
following table:
Overall Status
Off:
Status
Ice Mode Tmr
All Cir Disabled
Unit Alarm
Keypad Disable
Unit Loc/Rem Switch
BAS Disable
Test Mode
Cfg Chg, Rst Ctrlr
Auto
Auto:
Operation Manual
50
Wait For Load
Description
This status can be shown only if the unit can work in Ice Mode. The unit is off
because the Ice setpoint has been satisfied. Unit will remain off until the Ice
Timer has expired.
No circuit is available to run. All circuits can be disabled by a component safety
condition active or can be disabled by keypad or can be all in alarms. Check the
individual circuit status for further details.
A unit alarm is active. Check the alarm list to see what is the active alarm
inhibiting the unit to start and check if the alarm can be cleared. Refer to the
Troubleshooting section before proceeding.
The Unit has been disabled by keypad. Check with your local maintenance if it
can be enabled.
The Local/Remote enable switch is set to disable. Turn it to Local to enable the
unit to start its starting sequence.
Unit is disabled by BAS/BMS system. Check with the BAS company how to start
the unit.
Unit mode set to Test. This mode is activated to check operability of onboard
actuators and sensors. Check with the local maintenance if the Mode can be
reverted to the one compatible with unit application (View/Set Unit – Set-Up –
Available Modes).
The configuration of the unit is changed and the controller requires a reboot
Unit is in Auto control. The pump is running and at least one compressor is
running.
Unit is in standby because the thermostat control satisfied the active setpoint.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Evap Recirc
Operation
Manual
Unit is running the evaporator pump to equalize the water temperature in the
evaporator.
Unit pump is running but the flow signal still indicate a lack of flow through the
evaporator.
Unit is shutting down.
Unit thermostat control is limiting the unit capacity because the water
temperature is dropping at a rate that could exceed the active setpoint.
Demand limit has been hit. Unit capacity will not further increase.
Ambient temperature is higher than 46.6°C the unit capacity will be limited to
50% in case of single circuit units.
One circuit is performing a defrost procedure
Wait For Flow
Pumpdn
Max Pulldn
Unit Cap Limit
High Amb Limit
(A/C only)
Defrost
As soon as the unit status turns to Auto, the start sequence is initiated. The start sequence follows
the steps indicated in the simplified flowchart:
N
Is there any compressor available?
Start the Pump
N
Is Flow established?
Star Thermostat control
5.2.2 Preparing circuits to start
To allow a circuit start up is required to enable the circuit through the parameter Circuit Mode in the
menu 0
The status of the circuit is indicated in the View/Set Circuit – Circuit #x. The possible status will be
described in the following table.
Overall Status
Off:
Status
Ready
Cycle Timer
All Comp Disable
Keypad Disable
Alarm
Test Mode
Run:
Preopen
Pumpdown
Normal
Evap Press Low
Cond Press High
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Description
Circuit is off waiting for a stage up signal from thermostat control
Circuit is off waiting for the compressor cycle timer to expire
Circuit is off, as all compressors are disable
Circuit is off by the local or remote HMI. Check with your local maintenance if it
can be enabled.
A circuit alarm is active. Check the alarm list to see what is the active alarm
inhibiting the circuit to start and check if the alarm can be cleared. Refer to the
Troubleshooting section before proceeding.
Circuit mode set to Test. This mode is activated to check operability of onboard
circuit actuators and sensors. Check with the local maintenance if the Mode can
be reverted to Enable.
EXV prepositioning before compressor starts.
Circuit is shutting down because of thermostat control or pumpdown alarm or
because the enable switch has been turned to off.
Circuit is running within the expected operational conditions.
Circuit is running with low evaporator pressure. This could be due to a transitory
condition or a lack of refrigerant. Check with the local maintenance if corrective
actions are required. Circuit is protected by preventive logic.
Circuit is running with high condenser pressure. This could be due to a transitory
Operation Manual
51
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
High Amb Limit
Defrost
Operation
Manual
condition or high ambient temperature or problems with the condenser fans.
Check with the local maintenance if corrective actions are required. Circuit will be
protected by preventive logic.
Ambient temperature is higher than 46.6°C the unit capacity will be limited to
50% in case of single circuit units.
This circuit is performing a defrost procedure
If the circuit is allowed to start, the starting sequence is initiated. Starting sequence is described in
a simplified version with the following flowchart.
N
Is the circuit required to start?
Valve preopening
First Compressor start
Thermostat control
N
Shutdown signal for thermostat or alarm?
Pumpdown of circuit then switch compressor off
5.3 Circuit Capacity Control
Once a Circuit is started, capacity will be adjusted according to thermostat control requirements.
However, there are some limitations which override the capacity control in order to prevent the
chiller from abnormal running conditions. These preventions are summarized below:


Low Evaporating Pressure
High Condensing Pressure
5.3.1 Low Evaporating Pressure
When the circuit is running and the evaporating pressure drops below the safety limits (see section
4.9.2) the circuit control logic reacts at two different levels in order to recover the normal running
conditions.
If the evaporating pressure drops below the Low Pressure Hold limit, a new starting of the
compressor is inhibited. This condition is indicated on the controller display in the circuit status as
“Run: Evap Press Low”. The status is automatically cleared when the evaporating pressure rise
above the Low Pressure Hold limit by 20 kPa.
Operation Manual
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
52
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
If the evaporating pressure drops below the Low Pressure Unld limit and at least two compressor
in the same circuit are on, one compressor is shut down in order to recover the normal operating
conditions. This condition is indicated on the controller display in the circuit status as “Run: Evap
Press Low”. The status is automatically cleared when the evaporating pressure rise above the Low
Pressure Hold limit.
If the evaporating pressure drops below the Low Press Alm limit the related circuit is immediately
stopped and a Low Pressure Alarm is generated.
See section 6.1.7.2 to troubleshoot this problem.
5.3.2 High Condensing Pressure
When the circuit is running and the condensing pressure rises above the safety limits the circuit
control logic reacts at two different levels in order to recover the normal running conditions.
If the condensing pressure rises above the High Pressure Unload limit and at least two compressor
in the same circuit are on, one compressor is shut down in order to recover the normal operating
conditions. This condition is indicated on the controller display in the circuit status as “Run: Cond
Press High”. The status is automatically cleared when the condensing pressure falls below the
High Pressure Hold limit by 862 kPa.
If the condensing pressure rises above the Hi Press Stop limit the related circuit is immediately
stopped and an High Pressure Alarm is generated.
See section 6.1.7.3 to troubleshoot this problem.
5.4 Mode Change-Over (H/P only)
Mode change-over switch is only present on units with the heat pump option. It allows to switch
from heat mode to cool mode and vice-versa. Change over should be performed seasonally,
following the prescriptions required for this specific activity.
With the Q8 switch in the Cooling position the unit will operate in Cool
mode. Cool setpoints will be used. In case of 4 way valve, the
corresponding solenoid valve will be de-energized.
With the Q8 switch in the Heating position the unit will operate in Heat
mode. Heat setpoints will be used. In case of 4 way valve, the
corresponding solenoid valve will be energized.
With the Q8 switch in the Remote position the unit will be commanded by
a remote switch. If the switch will remain open the unit will operate in
Cool mode. If the switch will close the unit will operate in Heat mode.
When a mode change over will be commanded, the unit will be switched off in order to execute the
exchange of the 4 way valve if installed.
5.5 Backup Heaters (A/C only)
In predefined circumstances and if enabled, the UC may decide to enable the additional backup
heater contact.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
53
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
The heater contact has to be connected to an external backup heater inserted into the buffer tank
of the customer’s water system.
There are several conditions that can enable the heater contact:
 When the unit runs at low ambient temperature it may not be able to satisfy the Heat
Setpoint. In this case if all of the following are TRUE:
o the OAT is lower than the Backup Heater enable temperature,
o the unit is running at full capacity,
o the Leaving Water Temperature is lower than the Heat Setpoint – Stage Up dT,
 If unit is in defrost,
 If there is an alarm active AND the Leaving Water Temperature is lower than the Heat
Setpoint – Stage Up dT,
To activate the Backup Heater no Capacity Limitation must be active.
The Backup Heater is then deactivated if any of the following is TRUE:
 the Leaving Water Temperature rises above the Heat Setpoint,
 the Unit Mode is different from Heat,
 A Capacity Limitation become active.
5.6 Condensation Control (W/C only)
The UC provides the possibility to choose between three different types of condensing control:
1. Pressure
2. Cond In
3. Cond Out
Depending on the unit type (Chiller, Condenser less, Heat pump with water inversion, Heat pump
with gas inversion) only some of the previous condensing controls are available.
5.6.1 Pressure (W/C only)
Pressure control is available for the following unit type:
-
Chiller
Condenser-less
In this control mode the controller regulates the condensing saturated temperature (quantity
directly connected to the condensing pressure). From the menu Circ x Cond Control 4.3.1.2 is
possible set condensing saturated temperature setpoint and the maximum and minimum output of
the regulation signal.
When this condensing control mode is active the controller provides two 0-10V signals (one per
circuit) that can be used to control one/two remote condensers (in case of condenser-less unit) or
one/two water valves (in case of chiller).
The controller also provides two digital contact (one per circuit) that can be used to enable the
remote condensers or the condensing pumps.
Operation Manual
54
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
5.6.2 Cond In / Cond Out (W/C only)
These two control modes are available for the following unit type:
-
Chiller
Heat pump with gas inversion
In this modes the controller regulates the condenser entering (Cond In) or leaving (Cond Out)
water temperature. Through the menu Unit Cond Ctrl 0 it is possible to set the water setpoints in
cool and heat modes. When one of these condensing controls is chosen the logic checks if the
setpoint is compatible with the operating area (envelope) of the compressors that depending on the
actual evaporating leaving water temperature. If necessary the condensing setpoint set by HMI is
overwritten and displayed in the item Cnd Act SP.
When this control is active the controller provides a unique 0-10V signal for the control of one three
way valve or one cooling tower. This means that for the Double circuit unit (Dual) the common
entering/leaving condenser water temperature will be controlled.
5.6.3 Fan Control (A/C only)
Fan control is used to keep the condenser pressure at a level that guarantee the best operation at
any ambient condition both in cool and heat mode.
In cooling mode the fan speed is controlled with a PID regulator in order to maintain the condenser
pressure at a stable value. Depending on the ambient temperature fans may not be able to
maintain the condenser pressure at the setpoint even while running at the full speed. Maximum fan
speed can be lower than 100%, this may depend on the noise class of this unit. In case an high
pressure event will activate the maximum fan speed can be forced to full speed also for low noise
units in order to prevent high pressure trips.
In heating mode the fan speed is controlled with a PID regulator in order to maintain the evaporator
pressure at a stable value. When the ambient temperature is below 15.0°C the fans are forced to
run at full speed independently from the evaporator pressure to keep the circuit operation stable
and avoid as much as possible defrosts. In heat mode the fans can reach the full speed if needed,
no limitation is applied in this case also for low noise units.
5.7 EXV Control
As a standard, the unit is equipped with one electronic expansion valve (EXV) per circuit, moved
by a stepper motor. The EXV controls the suction superheat in order to optimize evaporator
efficiency and avoid at the same time suction of liquid to the compressor.
The controller integrates a PID algorithm which manages the dynamic response of the valve in
order to keep a satisfactory quick and stable response to system parameter variations. PID
parameters are embedded into the controller and cannot be changed. The EXV has the following
operating modes:



Pre-open
Start
Pressure
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
55
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps

Air and Water cooled scroll chillers & heat pump
Operation
Manual
Superheat
The parameters mentioned below in italics can be set from the menu 4.3.1.3.
When the circuit is required to start, the EXV will go into the Pre-open with a fixed opening Pre
Open % for a fixed time Pre Open Time.
After that, the EXV can change to Start phase, in which it works always with a fixed opening Start
% and for a fixed time Start Time. The compressor will start synchronously with this transition.
Ended the Start phase the EXV switches in Pressure control to maintain the evaporating pressure
close to pressure target Max Op Pressure.
When the EXV works in pressure mode the transitions to Superheat mode is possible if the
following conditions are met:


SSH < SSH Target + 1.5°C
or
Pressure control active for plus than 5 minutes
When the EXV works in Superheat mode the control maintains the superheat close to the Cool
SSH target or Heat SSH target depending on the actual operating mode.
The transition from Superheat Control to Pressure Control may happen only if the evaporating
pressure increases above the Maximum Operating Pressure (MOP) limit:

Evap Press > Max Op Press
Whenever the circuit is running, the EXV position is limited between 2% or 98% position.
Any time the circuit is in the Off or starts the shutdown procedure, the EXV shall be in the closed
position. In this case additional closing steps are commanded to guarantee a proper recovery of
the zero position.
5.8 Defrost (A/C only)
When the outside air become colder the circuit can start a defrost procedure. An algorithm is used
to determine the presence of ice on the air heat exchanger. The ice accumulation tends to degrade
the performances and for this reason a defrost may be needed to remove the ice layer.
Defrost is divided in phases. In each phase a specific status is forced to allow a proper execution
of the defrost. First of all the circuit is prepared for the 4 way valve change over to cool mode. To
do this smoothly one compressor is switched off and the exv prepared to manage the change over.
The 4 way valve is then changed to cool mode position and after a delay the other compressors
are also started. The defrost will finish when the discharge pressure reaches a pressure target that
has been determined to guarantee a complete deicing of all the coil surface.
Decreasing the Condensing Pressure limit may cause ice accumulation on the coils with
degradation of the unit performance. In case of need contact your local Daikin Service
reference.
Operation Manual
56
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
If the Condensing Pressure limit is not reached within the Defrost Timeout limit, the defrost is
finished and the circuit changed over back to heat mode.
If during the defrost the circuit cannot reach the final Condensing Pressure limit before the
timer expires consider to increase this time limit. In case of doubts contact your local
Daikin Service reference.
There are other protections that may stop the defrost before it reaches the Condensing Pressure
limit or the timer expires. In particular if the discharge temperature rises above a safety limit value
the defrost is finished and the circuit change over back to heat mode.
During the whole period of operation in cool mode the fans will never be started to let the
Condensing Pressure reach the limit.
The Defrost will be performed in a sequence of 7 steps:
Nr
1
2
3
4
5
6
7
Phase
W
Pr1
4W1
Df
Pr2
4W2
WuH
Description
Wait for the defrost interstage timer to expire
Preparation to 4 Way Valve change-over to Cool Mode
4 Way Valve change-over to Cool Mode execution
Defrost
Preparation to 4 Way Valve change-over to Heat Mode
4 Way Valve change-over to Heat Mode execution
Heating Warm-Up (back to normal operation)
5.9 Four Way Valve (H/P gas side reversal only)
The four way valve is managed by each circuit to follow the active unit mode. To guarantee a
proper handling of this device the four way valve can only be commanded with a minimum delta
pressure. This statement implies that the four way valve command can be given only when a
compressor is running.
5.10 Master/Slave
In this section will be described the Master Slave (MS) control logic and all scenarios where this
function can be applied. MS control consists in a common management of more chillers
interconnected between them through the serial communication Konnex, where a chiller defined
Master gets the control of all other chillers defined Slaves.
5.10.1 Master Slave Overview
Master Slave function allows to control multi-chiller plant with a maximum of 4 chillers, 1 Master +
3 Slaves, connected in parallel in the water circuit. Temperature control is always performed on
the base of the common leaving water temperature read by the Master chiller.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
57
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
BUILDING
T
MASTER
SLAVE 1
SLAVE 2
SLAVE 3
The MS function is able to manage individually several plants. The main difference that identifies
every plant type is mainly in the number and in the connection method of the water pumps. The
MS never can provide a speed modulation signal for one or more water pumps.
- Plant 1 : Single Common Pump
The simplest plant that Master Slave function can manage is composed by a single common
pump installed on the water manifold that provided the water flow for all chillers of the network. The
pump enable is obtained putting in parallel the enable contacts of the evaporator water pump of
each chiller. First chiller enabled to start by the Master will activate the common pump. With this
plant type all chillers are always crossed by the water flow even if they are still.
- Plant 2 : Single Chiller Pump
In the second plant type every chiller of the Master Slave network is equipped with a pump. The
pump can be installed directly on the unit or in the pipe of the single chiller and it avoids the water
flow in the evaporator if the chiller is in off state. Every pump will be commanded only by the
chiller to which is connected.
-
Plant 3 : Double Chiller Pump
Third plant type is an extension of the previous plant. As standard every chiller can control two
evaporator water pumps: primary and standby. This function is maintained also in Master Slave.
Every pair of pumps is connected to the related chiller that will manage them rotation according to
the local settings.
- Plant 4. Chiller with sectioned evaporator
In the last plant type every chiller has the evaporator sectioned by a two way valve that avoids the
water flowing if the chiller is not running. The number of pumps and valves has to be the same of
number of chillers, as every pump and every valve is associated to a specific chiller. Like in the
Single Chiller Pump plant every chiller will enable its valve and its pump. No standby pump can be
managed in this plant type.
In this case it is advisable to connect the evaporator water pump enable provided by the chiller to
the valve and consequently the feedback of total opening of the valve to the enable of the pump. In
this way should be avoided all problems of over-pressure due to a simultaneous starting of the
pump and of the valve.
Operation Manual
58
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
BUILDING
BUILDING
MASTER
MASTER
SLAVE 1
SLAVE 1
SLAVE 2
SLAVE 2
SLAVE 3
SLAVE 3
Single Common Pump
Single Chiller Pump
BUILDING
MASTER
SLAVE 1
BUILDING
MASTER
SLAVE 2
SLAVE 1
SLAVE 2
SLAVE 3
SLAVE 3
Double Chiller Pump
Chiller with sectioned evaporator
5.10.2 Electrical Connection
In the following section are reported all electrical connections necessary for the correct operation of
the Master Slave function.
All schemes present in this section provide only a principle diagram of the electrical
connection
5.10.2.1 Process Bus
The following diagram shows how have to be connected the chillers between them to establish the
Master Slave Network. Starting from first chiller connect in parallel all terminals PB [CE+ / CE-] of
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
59
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
each controllers, accessible on the customer terminal board. Refer to the table 1.7 for the
enumeration of the terminals.
MASTER
CE- CE+
SLAVE 2
SLAVE 1
CE- CE+
CE- CE+
SLAVE 3
CE- CE+
5.10.2.2 Common leaving water temperature sensor
Common leaving water temperature sensor has to be connected to the chiller Master through the
customer terminal block (Master/Slave Temperature Sensor). Refer to the table 1.7 for the
enumeration of the terminals.
5.10.2.3 Pumps Connection
Different types of pump connections are available depending on the plant type where the Master
Slave function is used.
1. Single Common Pump
In the plant type Single Common Pump, where a unique pump provides all water flow, all enable
pump contacts of each chiller have to be connected in parallel so that it is possible to provide a
unique enabling contact for the common pump. The pump contact of each chiller is available on
the customer terminal block (Evaporator Pump #1 start). Refer to the table 1.7 for the enumeration
of the terminals.
MASTER
SLAVE 1
SLAVE 2
SLAVE 3
Ev. Pump #1
Ev. Pump #1
Ev. Pump #1
Ev. Pump #1
PUMP
For the water cooled unit with water inversion, remember that in heat mode the user side
pump is not the evaporator pump but the condenser pump. For this reason will be
necessary use the terminal Condenser Pump #1 start to control the common pump
2. Single Chiller Pump
In the plant type Single Chiller Pump, every pump have to be connected to the related unit. The
enabling contact is available on the customer terminal block (Evaporator Pump #1 start). Refer to
the table 1.7 for the enumeration of the terminals.
Operation Manual
60
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
MASTER
SLAVE 1
SLAVE 2
SLAVE 3
Ev. Pump #1
Ev. Pump #1
Ev. Pump #1
Ev. Pump #1
PUMP
PUMP
PUMP
PUMP
3. Double Chiller Pump
In the plant type Double Chiller Pump, every pair of pump have to be connected to the related
chiller. The enabling contact are available in the customer terminal block (Evaporator Pump#1 start
/ Evaporator Pump#2 start). Refer to the table 1.7 for the enumeration of the terminals.
MASTER
Ev. Pump #1
PUMP 1
SLAVE 1
Ev. Pump #2
Ev. Pump #1
PUMP 2
PUMP 1
SLAVE 2
Ev. Pump #2
PUMP 2
Ev. Pump #1
PUMP 1
SLAVE 3
Ev. Pump #2
PUMP 2
Ev. Pump #1
PUMP 1
Ev. Pump #2
PUMP 2
4. Chiller with sectioned evaporator
In the plant where the evaporator is sectioned by a two way valve, connect the valve to the pump
enable provided by the chiller and the pump to the total opening feedback of the valve. The
enabling contact is available in the customer terminal block (Evaporator Pump#1 start). Refer to
the table 1.7 for the enumeration of the terminals.
MASTER
SLAVE 1
SLAVE 2
SLAVE 3
Ev. Pump #1
Ev. Pump #1
Ev. Pump #1
Ev. Pump #1
VALVE
VALVE
PUMP
PUMP
VALVE
PUMP
VALVE
PUMP
5.10.3 Master Slave Operation
5.10.3.1 Master Slave configuration
The basic configuration of the Master Slave function requires the set of three parameters available
in the unit configuration menu 4.9.1:
Setpoint/SubMenu
M/S Address
Default
Standalone
Range
Standalone
Master
Slave 1
Slave 2
Slave 3
Description
Define if the chiller works as standalone or if belongs to Master Slave
network.
Standalone: Current unit does not belong to the Master Slave network
Master: Current unit is defined Master
Slave 1: Current unit is defined Slave 1
Slave 2: Current unit is defined Slave 2. This address can be assigned only
if the parameter M/S Num Of Unit = 3 or 4
Slave 3: Current unit is defined Slave 3. This address can be assigned only
if the parameter M/S Num Of Unit = 4
Example:
If in a network there are 3 chillers then them have to be addressed like :
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
61
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Master - Slave 1 - Slave 2. Any other addressing will generate a
configuration alarm
M/S Num Of Unit
M/S Sns Type
2
NTC10K
2,3,4
NTC10K, PT1000
Indicate the number of chiller belonging to Master Slave network. This
parameter have to be set only in the chiller Master, in all Slave units it can
be let at default value as ignored.
Define the sensor type used to measure the common leaving water
temperature.
This parameter have to be set only in the chiller Master, in all Slave units it
can be let at default value as ignored.
5.10.3.2 System enable
The startup and shutdown of all system can be performed applying the normal enabling commands
(Local/Remote switch, HMI command, enable by Modbus/BACNet/Lon) to the master unit.
All other slaves unit maintain however their local enabling. When a slave is locally not enable, the
master will consider it as not ready unit and will not send it starting commands.
Since that the master loses his its local enabling (used as system enable), it is present in the menu
4.2.5.2 the parameter Master Enable that allows to disable the Master. Disable the Master unit
means that it will not use for the thermoregulation but it will continue to acquire the common
leaving water temperature and it will continue to send the activation command to the slave units.
5.10.3.3 System setpoint
Temperature control in the MS is performed on the base of the common evaporator leaving water
temperature respect the target value set in the Master chiller. This setpoint is global for all system
and it is sent by the Master to all Slaves through the serial communication.
Like in the single chiller, every function to modify the target value (LWT Reset, Double setpoint,
changes by Modbus/BACNet/Lon) can be applied to the Master to modify the global temperature
target.
On the Slave chillers the parameter Active Setpt (refer to section 4.1) always will display
the target received by the master except when the unit is in alarm communication or the
function Disconnect Mode 5.10.4.3 is active.
5.10.3.4 System Operating Mode: Cool/Heat/Ice
All units belonging to the Master Slave network always have to work with same operating mode.
Since that in all units the operating mode is local, master chiller does not send its operating mode,
it is very important verify that the changeover Cool, Heat, Ice always will be performed in all unit.
For the water cooled chiller remember that the Master Slave cannot manage the Pursuit
mode.
5.10.3.5 Operation with a communication alarm
All Slave units communicate through a serial communication with the Master unit. If during the
normal functioning occurs a communication failure between Master and Slave the system continue
to run with the followings behavior:
Operation Manual
62
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
-
The Slave unit that has lost the communication with the Master starts to operate as a
Standalone unit following all local settings
-
The Master unit detects that there is a communication error with a Slave and if present
enable the Standby Chiller
-
If the Master unit loses the communication with all units of the network then all chiller will
work in standalone mode
5.10.4 Master Slave Options
5.10.4.1 Chiller Priority
Startup and shutdown of each chiller is managed by the Master based on the conditions reported
in the table below
Conditions
1st
2nd
3rd
4th
5th
Next Chiller to start
Highest priority
Lowest number of starts
Lowest running hours
Lowest address
-
Next Chiller to stop
Lowest priority
Lowest load
Highest running hours
Highest number of starts
Lowest address
First condition is related to the priority defined for each chiller. The priority default values are all 1,
i.e. all unit have the same priority. A value of 1 indicates highest priority, a value of 4 indicates
lowest priority. The priority values can be modified on the Master chiller (refer to section 4.2.5.2)
5.10.4.2 Standby Chiller
Master Slave function allows to define one of the chillers belonging to the network as standby
chiller. The standby chiller is normally off and becomes operating only when one of the following
conditions occurs:
1.
2.
3.
4.
At least one chiller is in alarm state.
At least one of the Slave chillers is in communication alarm with the Master chiller.
At least one chiller is not enabled.
The function Temperature Compensation is enabled and the water temperature setpoint is
not reached with the system at full load.
In the following is explained step by step how to set all parameters changeable through the menu
4.2.5.1 to configure the standby chiller according to the local requirements.
Step 1 : Selection of the standby chiller.
Setpoint/SubMenu
Default
Range
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Description
Operation Manual
63
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Standby Chiller
No
Air and Water cooled scroll chillers & heat pump
Operation
Manual
No = There are not standby chiller in the Master Slave network
Auto = One of the chillers of the Master Slave network will be always assigned as standby
chiller. The rotation of the standby chiller will be performed according to the configuration set
through the parameters Rotation Type and Interval Time
Master = Master chiller is always set as standby chiller
Slave 1 = The Slave 1 chiller is always set as standby chiller
Slave 2 = The Slave 2 chiller is always set as standby chiller
Slave 3 = The Slave 3 chiller is always set as standby chiller
No
Auto
Master
Slave 1
Slave 2
Slave 3
Step 2 : Define rotation type of the standby chiller.
Define the rotation type of the standby chiller make sense only if the parameter Standby Chiller is
set as Auto
Setpoint/SubMenu
Rotation Type
Range
Description
Time = The next Standby chiller will be the chiller with most running hours at the moment of the
changeover
Sequence = The next standby chiller will be the next according to the following sequences:
network with one slave: Master  Slave 1  Master
Time,
Sequence
-
network with tow slaves: Master  Slave 1  Slave 2  Master
-
network with three slaves: Master  Slave 1  Slave 2  Slave 3  Master
Step 3 : Interval time for rotation of the Standby Chiller.
Define the interval time for rotation of the Standby Chiller make sense only if the parameter
Standby Chiller is set as Auto
Setpoint/SubMenu
Interval Time
Default
Switch Time
00:00:00
7 Days
Range
1…365
00:00:00…23:59:59
Description
Define the interval time (expressed in day) for the rotation of the standby
chiller.
Define the time within the day when will be performed the switch of the
standby chiller
Step 4 : Enable of Temperature Compensation function
Choose if enable the temperature compensation function
Setpoint/SubMenu
Tmp Cmp
Tmp Comp Time
Default
Range
No
No,Yes
120 min
0…600
Description
No = The standby chiller becomes operating only in the following case:
1. At least one chiller is in alarm state.
2. At least one of the Slave chillers is in communication alarm with the Master
chiller.
3. At least one chiller is not enabled.
Yes = The standby chiller becomes operating in all previous cases and also if the all
other chillers are running at the maximum capacity and the water temperature setpoint is
not reached for at least a specific time defined by the parameter Tmp Comp Time
Time constant in which the system has to be at maximum capacity and the setpoint not
reached before that the standby chiller will be enabled.
Step 5 : Reset
The reset command can be used to force the rotation of the standby chiller.
Setpoint/SubMenu
Default
Operation Manual
64
Range
Description
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Standby Reset
Off
Off, Reset
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Off = No Action
Reset = Force a rotation of the standby chiller and reset the timer for rotation
5.10.4.3 Disconnect Mode
For each unit belonging to the Master Slave is possible activate the function Disconnect Mode
through the menu 4.2.5. This function allows to disconnect temporary the unit from the network and
manage it like if this unit has been configured as Standalone.
-
If a slave unit is in Disconnect mode then the master considers this unit as not available.
If the master unit is in Disconnect mode then also all other slave units are forced to work in
Disconnect mode.
This function can be used to easily perform maintenance operation of one or more chillers of the
network.
6 Alarms
The UC protects the unit and the components from operating in abnormal conditions. Protections
can be divided in preventions and alarms. Alarms can then be divided in pump-down and rapid
stop alarms. Pump-down alarms are activated when the system or sub-system can perform a
normal shutdown in spite of the abnormal running conditions. Rapid stop alarms are activated
when the abnormal running conditions require an immediate stop of the whole system or subsystem to prevent potential damages.
The UC displays the active alarms in a dedicated page and keep an history of the last 50 entries
divided between alarms and acknowledges occurred. Time and date for each alarm event and of
each alarm acknowledge are stored.
The UC also stores alarm snapshot of each alarm occurred. Each item contains a snapshot of the
running conditions right before the alarm has occurred. Different sets of snapshots are
programmed corresponding to unit alarms and circuit alarms holding different information to help
the failure diagnosis.
6.1.1 Unit Warning Alarms
6.1.1.1 External Event
This alarm indicate that a device, whose operation is linked with this machine, is reporting a
problem. This alarm can occur only if the parameter External Alarm is set as Event (see section 0)
Symptom
Unit status is Run.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+External EventAlm
String in the alarm log:
External EventAlm
String in the alarm snapshot:
External Event Alm
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Cause
There is an external event that has
caused the opening, for at least 5
seconds, of the digital input on the
option module POL965 with address
18.
Solution
Check for reasons of external event
and if it can be a potential problem for
a correct chiller operation.
Operation Manual
65
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
6.1.1.2 Bad Lwt Reset Input Signal
This alarm can occurs only when the function Lwt Reset is enabled (see section 0). It indicates that
the Lwt Reset signal input is out of admissible range
Symptom
Unit status is Run.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+LwtResetAlm
String in the alarm log:
LwtResetAlm
String in the alarm snapshot:
LwtReset Alm
Cause
Lwt Reset input signal is out of the
admissible range that is [3 - 21] mA
Solution
Check the electrical connection of the
Lwt Reset signal.
Check the device that produces the
Lwt Reset signal.
6.1.1.3 Bad Demand Limit Input Signal
This alarm can occurs only when the function Demand Limit is enabled (see section 0). It indicates
that the Demand Limit signal input is out of admissible range
Symptom
Unit status is Run.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+DemandLimitAlm
String in the alarm log:
DemandLimitAlm
String in the alarm snapshot:
DemandLimit Alm
Cause
Demand Limit input signal is out of
the admissible range that is [3 - 21]
mA
Solution
Check the electrical connection of the
demand limit signal.
Check the device that produces the
demand limit signal
6.1.1.4 Heat Recovery Entering Water Temperature (HREWT) sensor fault (A/C only)
This alarm is generated any time the input resistance is out of an acceptable range.
Symptom
Unit status is Off.
All circuits are stopped with a normal
shutdown procedure.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitAlHREwtSen
String in the alarm log:
 UnitAlHREwtSen
String in the alarm snapshot:
UnitAlHREwtSen
Cause
Sensor is broken.
Solution
Check for sensor integrity.
Check correct sensors operation
according with information about
kOhm (k) range related to
temperature values.
Sensor is shorted.
Sensor is not properly connected
(open).
Check if sensor is shorted with a
resistance measurement.
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors on the UC.
Check for correct sensors wiring
according with wiring diagram.
6.1.1.5 Heat Recovery Leaving Water Temperature (HREWT) sensor fault (A/C only)
This alarm is generated any time the input resistance is out of an acceptable range.
Symptom
Operation Manual
66
Cause
Solution
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Unit status is Off.
All circuits are stopped with a normal
shutdown procedure.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitAlHRLwtSen
String in the alarm log:
 UnitAlHRLwtSen
String in the alarm snapshot:
UnitAlHRLwtSen
Sensor is broken.
Operation
Manual
Check for sensor integrity.
Check correct sensors operation
according with information about
kOhm (k) range related to
temperature values.
Sensor is shorted.
Sensor is not properly connected
(open).
Check if sensor is shorted with a
resistance measurement.
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors on the UC.
Check for correct sensors wiring
according with wiring diagram.
6.1.2 Unit Pumpdown Stop Alarms
The following alarms will stop the unit commanding a pumpdown on all running circuits. The unit
will not run again until the root-cause of the alarm is not fixed.
6.1.2.1 Evaporator Entering Water Temperature (EEWT) sensor fault
This alarm is generated any time the input resistance is out of an acceptable range.
Symptom
Unit status is Off.
All circuits are stopped with a normal
shutdown procedure.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff EvpEntWTempSen
String in the alarm log:
UnitOff EvpEntWTempSen
String in the alarm snapshot:
UnitOff EvapEntWTemp Sen
Cause
Sensor is broken.
Solution
Check for sensor integrity.
Check correct sensors operation
according with information about
kOhm (k) range related to
temperature values.
Sensor is shorted.
Sensor is not properly connected
(open).
Check if sensor is shorted with a
resistance measurement.
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors on the UC.
Check for correct sensors wiring
according with wiring diagram.
6.1.2.2 Evaporator Leaving Water Temperature (ELWT) sensor fault
This alarm is generated any time the input resistance is out of an acceptable range.
Symptom
Unit status is Off.
All circuits are stopped with a normal
shutdown procedure.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff EvpLvgWTempSen
String in the alarm log:
UnitOff EvpLvgWTempSen
String in the alarm snapshot:
UnitOff EvapLvgWTemp Sen
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Cause
Sensor is broken.
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k) range related to temperature
values.
Sensor is shorted.
Sensor is not properly connected
(open).
Check if sensor is shorted with a
resistance measurement.
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring
according with wiring diagram.
Operation Manual
67
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
6.1.2.3 Condenser Entering Water Temperature (CEWT) sensor fault (W/C only)
This alarm is generated any time the input resistance is out of an acceptable range.
Symptom
Unit status is Off.
All circuits are stopped with a normal
shutdown procedure.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff CndEntWTempSen
String in the alarm log:
UnitOff CndEntWTempSen
String in the alarm snapshot:
UnitOff CndEntWTemp Sen
Cause
Sensor is broken.
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
kOhm (k) range related to
temperature values.
Sensor is shorted.
Sensor is not properly connected
(open).
Check if sensor is shorted with a
resistance measurement.
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring
according with wiring diagram.
6.1.2.4 Condenser Leaving Water Temperature (CLWT) sensor fault (W/C only)
This alarm is generated any time the input resistance is out of an acceptable range.
Symptom
Unit status is Off.
All circuits are stopped with a normal
shutdown procedure.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff CndLvgWTempSen
String in the alarm log:
UnitOff CndLvgWTempSen
String in the alarm snapshot:
UnitOff CndLvgWTemp Sen
Cause
Sensor is broken.
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k) range related to temperature
values.
Sensor is shorted.
Sensor is not properly connected
(open).
Check if sensor is shorted with a
resistance measurement.
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring
according with wiring diagram.
6.1.2.5 Outside Air Temperature (OAT) sensor fault (A/C only)
This alarm is generated any time the input resistance is out of an acceptable range.
Symptom
Unit status is Off.
All circuits are stopped with a normal
shutdown procedure.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff AmbTempSen
String in the alarm log:
UnitOff AmbTempSen
String in the alarm snapshot:
UnitOff AmbTemp Sen
Operation Manual
68
Cause
Sensor is broken.
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k) range related to temperature
values.
Sensor is shorted.
Sensor is not properly connected
(open).
Check if sensor is shorted with a
resistance measurement.
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring
according with wiring diagram.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
6.1.3 Unit Rapid Stop Alarms
The unit is immediately stopped. All the running circuits will stop rapidly without performing the
normal shutdown procedure.
6.1.3.1 EXV drive circuit #1/#2 communication fail alarm (W/C only)
This alarm is generated in case of communication problems with the EXV driver of circuit #1 or
circuit #2 identified respectively with labels EEXV-1 and EEXV-2.
Symptom
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Unit Off Exv*CtrlCommFail
String in the alarm log:
Unit Off Exv*CtrlCommFail
String in the alarm snapshot:
Unit Off Exv*CtrlCommFail
Cause
Module has no power supply
Module address is not properly set
Module is broken
Solution
Check the power supply from the
connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is
tightly inserted in the module
Check if module’s address is correct
referring to the wiring diagram.
Check if LED are on and both green.
If BSP LED is solid red replace the
module
Check if power supply is ok but LEDs
are both off. In this case replace the
module
* refers to either driver #1 or driver #2
6.1.3.2 Options controller communication fail alarm
This alarm is generated in case of communication problems with the module for optional functions.
POL965 with address 18. This alarm can occurs only if the at least one of the optional functions is
enabled (PVM, External Alarm, Demand Limit, LWT Reset; see section 0)
Symptom
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Unit Off OptCtrlrComFail
String in the alarm log:
Unit Off OptCtrlrComFail
String in the alarm snapshot:
Unit Off OptCtrlrComFail
Cause
Module has no power supply
Module address is not properly set
Module is broken
Solution
Check the power supply from the
connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is
tightly inserted in the module
Check if module’s address is correct
referring to the wiring diagram.
Check if LED are on and both green.
If BSP LED is solid red replace the
module
Check if power supply is ok but LEDs
are both off. In this case replace the
module
6.1.3.3 Phase Voltage Monitor alarm
Resolution of this fault requires a direct intervention on the power supply of this unit.
Direct intervention on the power supply can cause electrocution, burns or even death. This action
must be performed only by trained persons. In case of doubts contact your maintenance company.
This alarm is generated in case of problems with the power supply to the chiller. This alarm can
occur only if the PVM is enabled (see section 4.9.1)
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
69
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Symptom
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff PvmGfpAlm
String in the alarm log:
 UnitOff PvmGfpAlm
String in the alarm snapshot:
UnitOff PvmGfp Alm
Cause
Loss of one phase.
Not correct sequence connection of
L1,L2,L3.
Voltage level on the unit’s panel is not
in the allowed range (±10%).
There is a short-circuit on the unit.
Operation
Manual
Solution
Check voltage level on each of the
phases.
Check sequence of L1, L2, L3
connections according indication on
chiller’s electrical scheme.
Check that voltage level on each
phases is into the allowed range that
is indicated on the chiller label.
It is important to check the voltage
level on each phases not only with
chiller not running, but mainly with
chiller running from minimum capacity
up to full load capacity. That's
because voltage drop can occur from
a certain unit cooling capacity level,
or because of certain working
condition (i.e. high values of OAT);
In these cases the issue can be
related with the sizing of power
cables.
Check for correct electrical isolation
condition of each unit’s circuit with a
Megger tester.
6.1.3.4 Evaporator Flow Loss alarm
This alarm is generated in case of flow loss on the evaporator. This alarm protect the evaporator
against:
-
Freezing: when unit works as chiller or as heat pump with water inversion
High Pressure: when unit works as heat pump with gas inversion
Symptom
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff EvpFlwAlm
String in the alarm log:
 UnitOff EvpFlwAlm
String in the alarm snapshot:
UnitOff EvpFlw Alm
Cause
No evaporator water flow sensed or
water flow too low.
Solution
Check the evaporator water pump
filler and the water circuit for
obstructions.
Check the evaporator flow switch
calibration and adapt to minimum
water flow.
Check if evaporator pump impeller
can rotate freely and it has no
damages.
Check evaporator pumps protection
devices (circuit breakers, fuses,
inverters, etc.)
Check
evaporator
flow
switch
connections.
6.1.3.5 Condenser Flow Loss alarm (W/C only)
This alarm is generated in case of water flow loss to the condenser. This alarm protect the
condenser against:
-
Freezing: when unit works as heat pump with gas inversion
High Pressure: when unit works as chiller or as heat pump with water inversion
Symptom
Operation Manual
70
Cause
Solution
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+UnitOff CndFlwAlm
String in the alarm log:
 UnitOff CndFlwAlm
String in the alarm snapshot:
UnitOff CndFlw Alm
No condenser water flow sensed
continuously or water flow too low.
Operation
Manual
Check the condenser water pump
filler and the water circuit for
obstructions.
Check the condenser flow switch
calibration and adapt to minimum
water flow.
Check if condenser pump impeller
can rotate freely and it has no
damages.
Check condenser pumps protection
devices (circuit breakers, fuses,
inverters, etc.)
Check
condenser
flow
switch
connections.
6.1.3.6 Evaporator Water Freeze Protect alarm
This alarm is generated to indicate that the evaporator (entering or leaving) water temperature has
dropped below a safety limit.
Symptom
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
String in the alarm list:
+UnitOff EvpFreezeAlm
String in the alarm log:
UnitOff EvpFreezeAlm
String in the alarm snapshot:
UnitOff EvpFreeze Alm
Cause
Water flow too low.
Solution
Increase the water flow.
Inlet temperature to the evaporator is
too low.
Flow switch is not working or no water
flow.
Increase the inlet water temperature.
Refrigerant temperature become too
low (< -0.6°C).
Check the water flow and filter. No
good heat exchange conditions into
the evaporator.
Check the water temperatures with a
proper instrument and adjust the
sensor offsets
Sensors
temperature
readings
(entering or leaving) are not properly
calibrated
Check the flow switch and the water
pump.
6.1.3.7 Condenser Water Freeze Protect alarm
This alarm is generated to indicate that the condenser (entering or leaving) water temperature has
dropped below a safety limit.
Symptom
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
String in the alarm list:
+UnitOff CondFreezeAlm
String in the alarm log:
UnitOff CondFreezeAlm
String in the alarm snapshot:
UnitOff CondFreeze Alm
Cause
Water flow too low.
Solution
Increase the water flow.
Inlet temperature to the condenser is
too low.
Flow switch is not working or no water
flow.
Increase the inlet water temperature.
Refrigerant temperature become too
low (< -0.6°C).
Check the water flow and filter. No
good heat exchange condition into the
evaporator.
Check the water temperatures with a
proper instrument and adjust the
sensor offsets
Sensors
temperature
readings
(entering or leaving) are not properly
calibrated
Check the flow switch and the water
pump.
6.1.3.8 External alarm
This alarm is generated to indicate that an external device whose operation is linked with this unit
operation. This alarm can occur only if the parameter External Alarm is set to Alarm (see section 0)
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
71
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Symptom
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
UnitOff ExternalAlm
String in the alarm log:
 UnitOff ExternalAlm
String in the alarm snapshot:
UnitOff External Alm
Cause
There is an external alarm that has
caused the opening, for at least 5
seconds, of the port on the option
module POL965 with address 18.
Operation
Manual
Solution
Check causes of the external alarm.
Check electrical wiring from unit
controller to the external equipment in
case of any external events or alarms
have been occurred.
6.1.4 Master Slave Alarm
The following alarms are related to the function Master Slave.
6.1.4.1 Common Evaporator Leaving Water Temperature sensor fault
This alarm can occurs when the sensor used to measure the common leaving water temperature is
broken or not connected to the chiller defined master.
Symptom
Every unit in the Master Slave
Network works in local mode.
Bell icon is moving on master
controller’s display.
Led on the button 2 of the master
External HMI is blinking
String in the alarm list:
+Common LWTSen
String in the alarm log:
Common LWTSen
String in the alarm snapshot:
Common LWTSen
Cause
Sensor is broken.
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k) range related to temperature
values.
Sensor is shorted.
Sensor is not properly connected
(open).
Check if sensor is shorted with a
resistance measurement.
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring
according with wiring diagram.
6.1.4.2 Slave X Communication Alarm
This alarm displayed only on the Master unit and occurs every time that there is communication
error between Master and Slave.
Symptom
The Slave unit works in local mode.
Bell icon is moving on master
controller’s display.
Led on the button 2 of the master
External HMI is blinking
String in the alarm list:
+Slave X CommAlm
String in the alarm log:
 Slave X CommAlm
String in the alarm snapshot:
Slave X CommAlm
Operation Manual
72
Cause
Cable broken
Solution
Connection wrong
Check the polarity +/- of the
connection cable between Master
and Slave
Check for cable integrity
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
6.1.4.3 Master Communication Alarm
This alarm, dual to the previous, displayed only on the Slave unit occurs every time that there is
communication error between Master and Slave.
Symptom
The Slave unit works in local mode.
Bell icon is moving on Slave
controller’s display.
Led on the button 2 of the Slave
External HMI is blinking
String in the alarm list:
+Master CommAlm
String in the alarm log:
 Master CommAlm
String in the alarm snapshot:
Master CommAlm
Cause
Cable broken
Solution
Connection wrong
Check the polarity +/- of the
connection cable between Master
and Slave
Check for cable integrity
6.1.4.4 Slave X Missing
This alarm displayed on the Master unit occurs when there is a configuration error in the function
Master Slave
Symptom
All system Master Slave cannot start
Bell icon is moving on Master
controller’s display.
Led on the button 2 of the Master
External HMI is blinking
String in the alarm list:
+Slave X Missing
String in the alarm log:
 Slave X Missing
String in the alarm snapshot:
Slave X Missing
Cause
There is more than one unit
configured with the same address and
consequently the address in alarm is
not configured
The parameter “M/S Num of Unit” is
set incorrectly
Solution
Check all address assigned to each
unit of the master slave network
Verify that the number of unit set in
this parameter is the same of the
number of unit that really belong to
the Master Slave network
6.1.4.5 Master Missing
This alarm displayed on the Slave unit occurs when there is a configuration error in the function
Master Slave
Symptom
All system Master Slave cannot start
Bell icon is moving on Slave
controller’s display.
Led on the button 2 of the Slave
External HMI is blinking
String in the alarm list:
+Slave X Missing
String in the alarm log:
 Slave X Missing
String in the alarm snapshot:
Slave X Missing
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Cause
There is more than one unit
configured with the same address and
consequently the address in alarm is
not configured
The parameter “M/S Num of Unit” is
set incorrectly
Solution
Check all address assigned to each
unit of the master slave network
Verify that the number of unit set in
this parameter is the same of the
number of unit that really belong to
the Master Slave network
Operation Manual
73
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
6.1.5 Circuit Warning Alarms
The following alarms will stop the circuit immediately but will allow the circuit to restart when the
anti-recycle timers are expired.
6.1.5.1 Low Outside Ambient Temperature At Start Alarm
This alarm can occurs only if the condenser less unit type is configured or if the unit is A/C (see
section 0). It indicates that the circuit is starting with low outside ambient temperature.
Symptom
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Cx LowOatStartAlm
String in the alarm log:
 Cx LowOatStartAlm
String in the alarm snapshot:
Cx LowOatStart Alm
Cause
Low outside ambient temperature
Solution
Check the operating condition of the
condenser-less unit.
Refrigerant charge low.
Check sight glass on liquid line to see
if there is flash gas.
Measure sub-cooling to see if the
refrigerant charge is correct.
6.1.5.2 Failed Pumpdown
This alarm is generated to indicate that the circuit hadn’t been able to remove all the refrigerant
from the evaporator.
Symptom
Circuit status is Off.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Cx FailedPumpdownAlm
String in the alarm log:
 Cx FailedPumpdownAlm
String in the alarm snapshot:
Cx FailedPumpdown Alm
Cause
EEXV is not closing completely,
therefore there’s “short-circuit”
between high pressure side with low
pressure side of the circuit.
Solution
Check for proper operation and full
closing position of EEXV. Sight glass
should not show refrigerant flow after
the valve is closed.
Evaporating pressure sensor is not
working properly.
Check that the C-LED on the EXV
driver is solid green. If both LEDs on
the EXV driver are blinking alternately
the valve motor is not properly
connected.
Check for proper operation of
evaporating pressure sensor.
Compressor on circuit is internally
damaged with a mechanical problems
for example on internal check-valve,
or on internal spirals or vanes.
Check compressors on circuits.
6.1.5.3 Failed Pumpdown in High Pressure (A/C only)
This alarm is generated to indicate that the circuit hadn’t been able to remove all the refrigerant
from the evaporator before getting too close to the High Pressure alarm limit. In this case the
pumpdown is finished before the pumpdown pressure target is reached.
Symptom
Circuit status is Off.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Cx FailedPumpdownHiPr
String in the alarm log:
Operation Manual
74
Cause
Excessive refrigerant charge
Solution
Verify the refrigerant
checking the subcooling
charge
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
by
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
 Cx FailedPumpdownHiPr
String in the alarm snapshot:
Cx FailedPumpdownHiPr
6.1.6 Circuit Pumpdown Stop Alarms
The circuit is stopped with the normal pumpdown procedure. It will not be allowed to start again
until the root-cause of the alarm is fixed.
6.1.6.1 Suction Temperature Sensor fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Circuit status is Off.
The circuit is switched off with the
normal shutdown procedure.
Bell icon is moving on controller’s
display.
String in the alarm list:
+CxOff SuctTempSen
String in the alarm log:
 CxOff SuctTempSen
String in the alarm snapshot:
CxOff SuctTemp Sen
Cause
Sensor is shorted.
Sensor is broken.
Sensor is not good connected (open).
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k) range related to temperature
values.
Check if sensor is shorted with a
resistance measurement.
Check for correct installation of the
sensor on refrigerant circuit pipe.
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according with electrical scheme.
6.1.6.2 Discharge Temperature Sensor fault (A/C only)
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Circuit status is Off.
The circuit is switched off with the
normal shutdown procedure.
Bell icon is moving on controller’s
display.
String in the alarm list:
+CxOff DischTempSen
String in the alarm log:
 CxOff DischTempSen
String in the alarm snapshot:
CxOff DischTemp Sen
Cause
Sensor is shorted.
Sensor is broken.
Sensor is not good connected (open).
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k) range related to temperature
values.
Check if sensor is shorted with a
resistance measurement.
Check for correct installation of the
sensor on refrigerant circuit pipe.
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according with electrical scheme.
6.1.7 Circuit Rapid Stop Alarms
The circuit is immediately stopped to prevent damages to the components. The circuit will not be
allowed to run again until the root-cause of the alarm is fixed.
6.1.7.1 EXV drive circuit #1/#2 communication fail alarm (A/C only)
This alarm is generated in case of communication problems with the EXV driver of circuit #1 or
circuit #2 identified respectively with labels EEXV-1 and EEXV-2.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
75
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Symptom
Unit status is Auto.
The circuit is stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+C*Off EXVCtrlrComFail
String in the alarm log:
 C*Off EXVCtrlrComFail
String in the alarm snapshot:
C*Off EXVCtrlrComFail
Cause
Module has no power supply
Module address is not properly set
Module is broken
Operation
Manual
Solution
Check the power supply from the
connector on the side of the module.
Check if LEDs are both green.
Check if the connector on the side is
tightly inserted in the module
Check if module’s address is correct
referring to the wiring diagram.
Check if LED are on and both green.
If BSP LED is solid red replace the
module
Check if power supply is ok but LEDs
are both off. In this case replace the
module
* refers to either driver #1 or driver #2
6.1.7.2 Low Pressure alarm
This alarm is generated if the evaporating pressure drops below the Low Pressure Unload and the
control is not able to compensate this condition.
Symptom
Circuit status is Off.
The compressor does not load
anymore or even unload, circuit is
stopped immediately.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Cx Off EvapPressLo
String in the alarm log:
 Cx Off EvapPressLo
String in the alarm snapshot:
Cx Off EvapPress Lo
Cause
Refrigerant charge is low.
Protection limit not set to fit customer
application.
High Evaporator Approach.
Water flow into water heat exchanger
is too low (W/C only).
Evaporating pressure transducer is
not working properly.
EEXV is not working correctly.
It’s not opening enough or it’s moving
in the opposite direction.
Water temperature is low
Default alarm limit not valid for the
specific plant
Fans do not operate properly (A/C
H/P only)
Operation Manual
76
Solution
Check sight glass on liquid line to see
if there is flash gas.
Measure sub-cooling to see if the
refrigerant charge is correct.
Check the evaporator approach and
the corresponding water temperature
setpoint to evaluate the low pressure
hold limit.
Clean the evaporator
Check the quality of the fluid that
flows into heat exchanger.
Check the glycol percentage and type
(ethilenic or propilenic)
Increase the water flow. Check the
minimum water flow for this unit.
Check the sensor for proper operation
and calibrate the readings with a
gauge.
Check if pump-down can be finished
for pressure limit reached.
Check valve movements.
Check connection to the valve driver
on the wiring diagram.
Measure the resistance of each
winding, it has to be different from 0
Ohm.
Increase inlet water temperature.
Adjust the low pressure alarm
settings.
Check Fans operation. Check that all
the fans can run freely and at the
proper speed.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Check the phase cut device.
6.1.7.3 High Pressure alarm
This alarm is generated if the condensing pressure rise above the Hi Press Stop limit.
Symptom
Circuit status is Off.
The compressor does not load
anymore or even unload,
circuit is stopped.
Bell icon is moving on
controller’s display.
Led on the button 2 of External
HMI is blinking
String in the alarm list:
+Cx Off CndPressHi
String in the alarm log:
 Cx Off CndPressHi
String in the alarm snapshot:
Cx Off CndPress Hi
Cause
The condenser pump does
not operate properly. (W/C
only)
Condenser water flow too
low (W/C or H/P only)
Inlet water temperature of
the condenser is too high.
(W/C only)
Excessive charge of
refrigerant into the unit.
Condensing
pressure
transducer
could
not
operate properly.
Fans do not operate
properly (A/C only)
Solution
Check if condenser pump protections have been
activated.
Check the minimum water flow admitted
The water temperature measured at the inlet of the
condenser may not exceed the limit indicated in the
operational range (working envelope) of the chiller.
Check liquid sub-cooling and suction super-heat to
control indirectly the correct charge of refrigerant.
If necessary recover all the refrigerant to weight the
entire charge and to control if the value is in line with kg
indication on unit label.
Check for proper operation of the high pressure sensor.
Check Fans operation. Check that all the fans can run
freely and at the proper speed.
Check the phase cut device.
6.1.7.4 Low Delta Pressure Alarm (A/C only)
This alarm is generated if the pressure difference between condensing and evaporating pressure is
below a minimum Delta Pressure limit for more than 10 minutes.
Symptom
Circuit status is Off.
The compressor does not load
anymore or even unload, circuit is
stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI
is blinking
String in the alarm list:
+CxOff DeltaPressLo
String in the alarm log:
 CxOff DeltaPressLo
String in the alarm snapshot:
CxOff CxOff DeltaPressLo
Cause
Compressors are not running
Solution
Check the
compressors.
starter
signals
to
Condenser Pressure Transducer is
not working properly
Check if the Thermal protection of
compressors is properly connected to
the UC (see section 6.1.7.5).
Check if the Mechanical High
Pressure
Switch
is
properly
connected to the UC (see section
6.1.7.5).
Refer to section 6.1.7.10 for further
details.
Evaporator Pressure Transducer is
not working properly
Refer to section 6.1.7.9 for further
details.
6.1.7.5 Circuit X Alarm
This alarm is generated when the digital input DI1 on the EXV driver of the related circuit is open.
This digital input collects a series of alarm signals coming from different protection devices:
1.
2.
3.
4.
Mechanical High Pressure Switch
Compressor 1 Circuit X Thermal Protection/Soft Starter Failure
Compressor 2 Circuit X Thermal Protection/Soft Starter Failure
Phase cut device failure (A/C only)
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
77
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
This means that this alarm is generated if at least one of the previous digital contact is open. When
this happens an immediate shutdown of the compressors and all the other actuators in this circuit
is commanded.
Symptom
Circuit status is Off.
The compressor does not load
anymore or even unload, circuit is
stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+CxOff CircAlm
String in the alarm log:
 CxOff CircAlm
String in the alarm snapshot:
CxOff Circ Alm
Cause
Mechanical High Pressure Switch
(MHPS) open
Solution
Perform same check of the High
Pressure Alarm 6.1.7.3
MHPS damaged or not calibrated.
Check for correct plug-in of the
electrical connectors.
Check for proper operation of the high
pressure switch.
Compressor 1/2 Thermal Protection
open
Compressor 1/2 Soft Starter Failure
Excessive charge of refrigerant.
Check liquid sub-cooling and suction
super-heat to control indirectly the
correct charge of refrigerant
Check the correct operation of the
electronic expansion valve. Blocked
valve can to impede the correct
refrigerant flow.
Check Alarm code on the Soft Starter
and
refer
to
the
related
documentation to fix the alarm.
Check the size of the Soft Starter
compared with
the
associated
compressor maximum current.
6.1.7.6 Start Fail Alarm
This alarm can occurs only if the condenser less unit type is configured (see section 0). This alarm
is generated just the UC recognizes a low evaporating pressure and a low saturated condensing
temperature at the starting of the circuit. This alarm is auto-reset just occurs, as the unit tries
automatically to restart the circuit. At the third occurrence of this failure a Restart Fault Alarm is
generated (see alarm 6.1.7.7).
Symptom
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Cx StartFailAlm
String in the alarm log:
 Cx StartFailAlm
String in the alarm snapshot:
Cx StartFail Alm
Cause
Low outside ambient temperature
Solution
Check the operating condition of the
condenser-less unit
Refrigerant charge low.
Check sight glass on liquid line to see
if there is flash gas.
Measure sub-cooling to see if the
refrigerant charge is correct.
Condensing Setpoint not correct for
the application
Dry cooler not correctly installed
Evaporator or condensing sensor
pressure broken or not correctly
installed
Operation Manual
78
Check if necessary to increase the
condensing saturated temperature
setpoint
Check that the dry cooler is safe from
strong wind
Check the proper operation of the
pressure transducers.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
6.1.7.7 Restart Fault Alarm
This alarm can occurs only if the condenser less unit type is configured. This alarm is generated if
for three times the UC recognizes a low evaporating pressure and a low saturated condensing
temperature at the starting of the circuit.
Symptom
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Cx Off RestrtsFaultAlm
String in the alarm log:
 Cx Off RestrtsFaultAlm
String in the alarm snapshot:
Cx Off RestrtsFault Alm
Cause
Low outside ambient temperature
Solution
Check the operating condition of the
condenser-less unit
Refrigerant charge low.
Check sight glass on liquid line to see
if there is flash gas.
Measure sub-cooling to see if the
refrigerant charge is correct.
Condensing Setpoint not correct for
the application (W/C only)
Dry cooler not correctly installed (W/C
only)
Evaporator or condensing sensor
pressure broken or not correctly
installed
Check if necessary to increase the
condensing saturated temperature
setpoint
Check that the dry cooler is safe from
strong wind
Check the proper operation of the
pressure transducers.
6.1.7.8 No Pressure Change At Start alarm
This alarm indicates that the compressor is not able to start or it is not able to create a minimum
variation of the evaporating or condensing pressures after start.
Symptom
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+Cx Off NoPressChgStartAlm
String in the alarm log:
 Cx Off NoPressChgStartAlm
String in the alarm snapshot:
Cx Off NoPressChgStart Alm
Cause
Compressor cannot start
Compressor
direction.
is
turning
Solution
Check if the start signal is properly
connected to the compressor.
in
wrong
Refrigerant circuit is empty of
refrigerant.
Not proper operation of evaporating
or condensing pressure transducers.
Check correct phases sequence to
the compressor (L1, L2, L3) according
to the electrical scheme.
Check circuit pressure and presence
of refrigerant.
Check
proper
operation
of
evaporating or condensing pressure
transducers.
6.1.7.9 Evaporating Pressure sensor fault
This alarm indicates that the evaporating pressure transducer is not operating properly.
Symptom
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+CxOff EvapPressSen
String in the alarm log:
 CxOff EvapPressSen
String in the alarm snapshot:
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Cause
Sensor is broken.
Sensor is shorted.
Sensor is not properly connected
(open).
Solution
Check for sensor integrity.
Check correct sensors operation
according information about mVolt
(mV) range related to pressure values
in kPa..
Check if sensor is shorted with a
resistance measurement.
Check for correct installation of the
sensor on refrigerant circuit pipe. The
transducer must be able to sense the
pressure through the valve’s needle.
Operation Manual
79
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Cx Off EvapPress Sen
Operation
Manual
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according electrical scheme.
6.1.7.10 Condensing Pressure sensor fault
This alarm indicates that the condensing pressure transducer is not operating properly.
Symptom
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
Led on the button 2 of External HMI is
blinking
String in the alarm list:
+CxOff CndPressSen
String in the alarm log:
 CxOff CndPressSen
String in the alarm snapshot:
Cx Off CondPress Sen
Operation Manual
80
Cause
Sensor is broken.
Sensor is shorted.
Sensor is not properly connected
(open).
Solution
Check for sensor integrity.
Check correct sensors operation
according information about mVolt
(mV) range related to pressure values
in kPa.
Check if sensor is shorted with a
resistance measurement.
Check for correct installation of the
sensor on refrigerant circuit pipe. The
transducer must be able to sense the
pressure through the valve’s needle.
Check for absence of water or
humidity on sensor electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according electrical scheme.
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
This page has been left intentionally free
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
Operation Manual
81
EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ- R410A - Air-cooled scroll chillers
EWYQ- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A..
Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is
given for the completeness, accuracy, reliability or fitness for particular purpose of its content, and the products and services presented
therein. Specification are subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied
Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use
and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A..
DAIKIN APPLIED EUROPE S.p.A.
Via Piani di Santa Maria, 72 - 00040 Ariccia (Roma) - Italia
Tel: (+39) 06 93 73 11 - Fax: (+39) 06 93 74 014
http://www.daikinapplied.eu
Operation Manual
82
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN

advertisement

Key Features

  • Water-cooled and Air-cooled options
  • Scroll compressor for quiet operation
  • Energy efficiency
  • Multiple model sizes
  • Integrated safety features
  • Remote control capabilities
  • Network connectivity

Frequently Answers and Questions

What types of chillers are available?
Both water-cooled and air-cooled chillers are available.
What type of compressor is used in these chillers?
These chillers use a scroll compressor.
How can these chillers be controlled?
The chillers can be controlled locally, remotely, or through a network connection.
What are the safety features of these chillers?
The chillers have multiple safety features, including overcurrent/overload protection, overtemperature protection, and phase reversal protection.

Related manuals

Download PDF

advertisement