Altronix AL400ULM Multi-Output Access Control Power Supply Charger Access Control Power Supply Installation Guide

Altronix AL400ULM Multi-Output Access Control Power Supply Charger Access Control Power Supply Installation Guide

Below you will find brief information for Access Control Power Supply AL400ULM Multi-Output Access Control Power Supply Charger. The AL400ULM Multi-Output Access Control Power Supply Charger is a high-performance power supply designed specifically for use with access control systems and accessories. It converts a 115 VAC / 60Hz input into five individually regulated 12VDC or 24VDC power limited outputs. Each output can be used to power a variety of access control hardware devices, including mag locks, electric strikes, magnetic door holders, etc. It also features a built-in charger for sealed lead acid or gel type batteries, which provides backup power in the event of a power outage. The AL400ULM Multi-Output Access Control Power Supply Charger is UL listed fire, burglar, and access control power supply, CSFM - California State Fire Marshal Approved, CSA Approved (Canada), MEA - NYC Department of Buildings Approved, NFPA 72 compliant, Class 2 rated.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

AL400ULM Multi-Output Access Control Power Supply Charger Installation Guide | Manualzz

Installation Guide for

AL400ULM

Multi-Output Access Control

Power Supply Charger

AL400ULM - Multi-Output Access Control

Power Supply/Charger

Rev. 072500

Overview:

The AL400ULM multi-output access control power supply/charger is specifically designed for use with access control systems and accessories. The AL400ULM converts a 115 VAC / 60Hz input into five individually regulated 12VDC or 24VDC power limited outputs (see specifications). Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both fail-safe and fail-secure modes. Controlled trigger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm

Control Panel). A form “C” dry output relay enables HVAC Shutdown, Elevator Recall or may be used to trigger auxiliary devices.

Specifications:

• UL listed fire, burglar and access control power supply (UL1481, UL603, UL294)

• CSFM - California State Fire Marshal Approved.

• CSA Approved (Canada).

• MEA - NYC Department of Buildings Approved.

• NFPA 72 compliant.

• Class 2 rated.

• Input 115VAC / 60Hz, 1.45 amps.

• Field selectable 12VDC or 24VDC output.

• 4 amps continuous supply current at 12VDC.

• 3 amps continuous supply current at 24VDC.

• Five (5) individual power limited outputs.

• Current limit is 2.5 amps @ 12VDC or 24VDC per output.

• Filtered and electronically regulated outputs.

• 51 mV p/p output ripple.

• Maximum charge current .7 amp.

• Built-in charger for sealed lead acid or gel type batteries.

• Automatic switch over to stand-by battery when AC fails.

• Zero voltage drop when switching over to battery backup.

• Thermal and short circuit protection with auto reset.

• Short circuit and overload protection.

• DC output LED indicator.

• LEDs indicate condition of power outputs.

• Power & input trigger LED’s.

• AC fail supervision (form "C" contact).

• Low battery supervision (form "C" contact).

• Fire Alarm Panel or Access Control System trigger inputs.

(N.O. or N.C. supervised trigger input and polarity reversal trigger input (4mA draw from FACP).

• Power fail supervision relay (form “C” contact rated 1amp @ 28VDC).

• Output relay energizes when unit is triggered (form “C” contact rated 1amp @ 28VDC).

• Power supply is complete with enclosure, cam lock, transformer and battery leads.

• Enclosure accommodates up to two (2) 12AH batteries.

Enclosure dimensions: 15.5"H x 12"W x 4.5"D

R

Voltage Output Settings:

Output

12VDC

24VDC

Switch Position

SW1 CLOSED

SW1 OPEN

2

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

Stand-by Specifications:

Output

12VDC / 40 AH Battery

24VDC / 12 AH Battery

4 hr. of Stand-by &

5 Minutes of Alarm

Stand-by = 4.0 amps

Alarm = 4.0 amps

24 hr. of Stand-by &

5 Minutes of Alarm

Stand-by = 1.0 amps

Alarm = 4.0 amps

Stand-by = 200mA

Alarm = 3.0 amps

Stand-by = 1.0 amps

Alarm = 3.0 amps

60 hr. of Stand-by &

5 Minutes of Alarm

Stand-by = 300mA

Alarm = 4.0 amps

24VDC / 40 AH Battery Stand-by = 3.0 amps

Alarm = 3.0 amps

Stand-by = 300mA

Alarm = 3.0 amps

Installation Instructions:

The AL400ULM should be installed in accordance with article 760 The National Electrical Code or NFPA 72 and all applicable Local Codes.

1. Mount the AL400ULM in desired location. It is recommended to first review the following tables for screw terminals, switch selection and LED status indications. This will greatly facilitate installation hook-up.

Carefully review:

Voltage Output Settings (pg. 2) Terminal Identification Table (pg. 5)

(pgs. 6-7) Stand-by Specifications (pg. 3)

LED Diagnostics (pgs. 4-5)

Typical Application Diagrams

2. Set AL400ULM to the desired DC output voltage by setting SW1 to the appropriate positions

(refer to voltage output settings).

Door

CAUTION: De-energize unit prior to servicing.

For continued protection against fire hazard replace fuse with the same type and rating 3.5A, 250V.

Replace fuse cover before energizing.

AL400ULXB

RL1

Switch Position:

24VDC = SW1 OPEN

12VDC = SW1 CLOSED

DC

PTC3

Fuse

RL2

BAT AC

RL3

24V - OPEN

12V - CLOSED

SW1

ALTRONIX CORP.

BKLYN, N.Y. 11220

MADE IN USA

Wire Strap

(from Enclosure to Door)

L G N

115 power mains (nonpower limited)

Green

Lead

BAT FAIL NO C NC NO C NC AC FAIL

Battery and AC

Supervision Circuit

(power limited)

NEG1 NEG2 NEG3 NEG4 NEG5 - DC INPUT+

DC Output to devices

(power limited)

MOM5_S

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

1 2 3 4

POS (+) DC OUTPUT (ALARM)

5

Fire

Alarm

Interface

6 7 8 9 10

POS (+) DC OUTPUT (STANDBY)

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

Battery connection (non power limited)

Battery 1 Battery 2

Fig. 1

3

IIAL400ULM-Rev. 072500

Note: It is good operating practice to measure and verify output voltage before connecting devices to ensure proper operation of equipment.

3. Connect AC power (115VAC 50/60Hz to terminals marked [L, G, N] (Fig. 1, pg. 3). Use 18 AWG or larger for all power connections (Battery, DC output, AC input).

Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).

Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery

Wires). Minimum .25” spacing must be provided.

4. Connect fail-secure type locking hardware (e.g. door strikes and electronic dead bolts) positive leads to terminals marked [1 thru 5 POS (+) DC OUTPUT (ALARM)] (Fig. 1 , pg. 3) and the negative leads to terminals marked [NEG 1 thru NEG 5] (Fig. 1 , pg. 3).

5. Connect fail-safe type locking hardware (e.g. mag locks, door strikes and door holders) positive leads to terminals marked [6 thru 10 POS (+) DC OUTPUT (STAND-BY)](Fig. A, pg. 3) and negative leads to terminals marked [NEG 1 thru NEG 5] (Fig. 1 , pg. 3).

6. To trigger the AL400ULM from a FACP connect signaling circuit of FACP to inputs marked [NEG (-)] and [POS (+)] input (Fig. 1 , pg. 3). Polarity is shown in alarm condition.

For latching fire alarm interface (Fig. 5, 6, 7, pg. 7).

Note: A 2.2K EOL must be installed across terminals marked [TRIGGER] or MOM5 will remain in an alarm condition.

7. To trigger the AL400ULM using a supervised dry contact connect the 2.2K resistor in series for a N.C. trigger input and in parallel for N.O. trigger input (Fig. 2, pg. 6).

8. Connect auxiliary devices triggered by the AL400ULM to the terminals marked [DRY OUTPUT N.O.

& C] for normally open output or terminals marked [DRY OUTPUT N.C. & C] for normally closed output (Fig. 1 , pg. 3).

Note: This relay will energize when the AL400ULM is triggered.

9. For Access Control applications batteries are optional. When batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type if used. Connect one (1) 12VDC battery to terminals marked [+ BAT --] (Fig. 1 , pg. 3) for 12VDC operation. Use two (2) 12VDC batteries connected in series for 24VDC operation. (Battery leads included).

10. Connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] (Fig. 1 , pg. 3) and [Power Fail] (Fig. 1 , pg. 3) supervisory relay outputs marked [N.C., C, N.O.]. Use 22 AWG to 18 AWG for AC Fail & Low Battery reporting. AC Failure will report in 5 minutes.

Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used to provide a visual indication of AC power on.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level

(see power supply output specifications table).

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [+ BAT --] to insure that there is no break in the battery connection wires.

Note: Maximum charge current under discharge is .7 amps.

Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if necessary.

LED Diagnostics:

AL400ULXB - Power Supply

LED

AC (Green)

BAT (Red)

DC (Red)

ON

Normal operation.

Battery connected.

Normal operation.

OFF

No AC input.

Battery disconnected.

No DC output.

4

MOM5 - Output Module

LED ON

Power (Green)

Trigger (Green)

Outputs (Red)

Normal operation.

Input is triggered (alarm condition).

Output tripped due to a short circuit or overload condition.

OFF

Power failure.

No input trigger (non-alarm condition).

Normal operation.

Terminal Identification:

AL400ULXB - Power Supply

Terminal Legend

L, G, N

+ DC -

AC FAIL

N.C., C, N.O.

BAT FAIL

N.O., N.C., C

+ BAT --

Function/Description

115VAC 50/60Hz input.

12VDC @ 4 amps total continuous output (supplies power to MOM5).

24VDC @ 3 amps total continuous output (supplies power to MOM5).

Used to report loss of AC (e.g. connect to audible device or alarm panel).

Relay normally energized when AC power is present.

Contact rating 1 amp @ 30VDC.

Used to report low battery condition, no battery presence, (e.g. connect to alarm panel). Relay normally energized when battery power is present.

Contact rating 1 amp @ 30VDC.

Stand-by battery connections. Maximum charge rate is .7 amps.

MOM5 - Output Module

Terminal Legend Function/Description

--- DC INPUT +

TRIGGER

--- INPUT +

12 or 24VDC from power supply.

Dry normally open (N.O.) or normally closed (N.C.) supervised (2.2K EOL resistor) input trigger. A short or open circuit will transfer power from terminals marked

[POS. (+) DC OUTPUT (STAND-BY)] to terminals marked

[POS (+) DC OUTPUT (ALARM)].

Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity shown will transfer power from terminals marked [POS. (+) DC OUTPUT (STAND-BY)] to terminals marked [POS (+) DC OUTPUT (ALARM)] (e.g. fire alarm control panel indications cicrcuit)..

NEG 1 THRU NEG 5 Supplies constant negative (-) voltage.

POS (+) DC OUTPUT Supplies positive (+) voltage when dry trigger input or fire

(ALARM) 1-5 alarm wet trigger input is applied.

POS (+) DC OUTPUT Supplies positive (+) voltage in normal condition.

(STAND-BY) 6-10 Power is removed when dry trigger input or fire alarm wet trigger input is applied.

N.C., C., N.O.

DRY OUTPUT

When the MOM5 is triggered the C and N.O. terminals will close and the

C and N.C. terminals will open. This output is used to trigger auxiliary devices.

(e.g. HVAC Shutdown, Elevator Recall etc.) Contact rating 1 amp @ 30VDC.

N.C., C, N.O.

POWER FAIL

Form “C” contacts used for reporting no voltage is present at [-- DC input +] terminals. Under normal conditions, terminals N.O. and C are open, N.C. and C are closed. A loss of power causes N.O. and C to close and N.C. and C to open.

Contact rating 1 amp @ 30VDC.

5

Fig. 2 AL400ULM module shown with wet and/or dry normally closed trigger inputs

(Non-Latching):

Typical Application Diagrams:

AL400ULM module shown with wet and/or dry normally open trigger inputs (Non-Latching):

(+)

(-)

DC VOLTAGE INPUT

FROM FACP

SIGNALING

OUTPUT OR ACCESS

CONTROL DEVICE

EOL 2.2K

(+)

(-)

DC VOLTAGE INPUT

FROM FACP

SIGNALING

OUTPUT OR ACCESS

CONTROL DEVICE

N.C. INPUT FROM

FACP OR ACCESS

CONTROL DEVICE N.O. INPUT FROM

FACP OR ACCESS

CONTROL DEVICE

Fig. 3 - Two (2) or more AL400ULM modules shown with wet and/or dry normally closed trigger inputs (Non-Latching):

- DC INPUT+

- DC INPUT+

MOM5_S

(+)

(--)

DC VOLTAGE INPUT

FROM FACP

SIGNALING

OUTPUT OR ACCESS

CONTROL DEVICE

MOM5_S

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

EOL 2.2K

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

EOL 2.2K

N.C. INPUT FROM

FACP OR ACCESS

CONTROL DEVICE

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

MOM5

MULTI-OUTPUT

MODULE

POWER

ON LED

TO TRIGGER INPUT

OF NEXT MOM5

Fig. 4 - Two (2) or more AL400ULM modules shown with wet and/or dry normally open trigger inputs (Non-Latching):

- DC INPUT+

- DC INPUT+

MOM5_S

(+)

(--)

DC VOLTAGE INPUT

FROM FACP

SIGNALING

OUTPUT OR ACCESS

CONTROL DEVICE

MOM5_S

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

EOL 2.2K

N.O. INPUT FROM

FACP OR ACCESS

CONTROL DEVICE

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

TO TRIGGER INPUT

OF NEXT MOM5

6

Fig. 5

Typical Application Diagrams:

AL400ULM module shown with with wet and/or dry normally closed fire alarm trigger inputs (Latching with Manual Reset):

AL400ULM module shown with with wet and/or dry normally open fire alarm trigger inputs

(Latching with Manual Reset):

(+)

(-)

DC VOLTAGE INPUT

FROM FACP

SIGNALING OUTPUT

(+)

(-)

DC VOLTAGE INPUT

FROM FACP

SIGNALING OUTPUT

EOL 2.2K

EOL 2.2K

N.C. INPUT

FROM FACP

SIGNALING

OUTPUT

N.O. INPUT

FROM FACP

SIGNALING

OUTPUT

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

N.C.

RESET

N.O. RESET

Fig. 6 - Two (2) AL400ULM modules shown with wet and/or dry normally closed fire alarm trigger inputs

(Latching with Manual Reset):

- DC INPUT+ (+) (-) DC VOLTAGE INPUT

FROM FACP

SIGNALING

OUTPUT OR ACCESS

CONTROL DEVICE

- DC INPUT+

MOM5_S

MOM5_S

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

EOL 2.2K

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

EOL 2.2K

N.C. INPUT

FROM FACP

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

N.O. RESET

Fig. 7 - Two (2) AL400ULM modules shown with wet and/or dry normally open fire alarm trigger inputs

(Latching with Manual Reset):

- DC INPUT+ (+) (-) DC VOLTAGE INPUT

FROM FACP

SIGNALING

OUTPUT OR ACCESS

CONTROL DEVICE

- DC INPUT+

(+)

(-) MOM5_S

MOM5_S

EOL 2.2K

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

ALTRONIX CORP.

BROOKLYN, NY 11220

MADE IN USA

EOL 2.2K

N.O. INPUT

FROM FACP

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

TRIGGER

LED

NC C NO

DRY OUTPUT

NC C NO

POWER FAIL

POWER

ON LED

N.C. RESET

7

Enclosure Dimensions:

15.5”H x 12”W x 4.5”D

2.25" 3.68"

12"

4.56"

2"

1.22"

4.5"

1"

.875" 9.97"

1.22"

1.3"

1"

1.22"

2"

8"

13.25"

13.53"

3.25"

2.2"

1.25"

15.5"

1.22"

2.25" 3.68" 4.56"

MEMBER

8

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.

1"

advertisement

Key Features

  • UL listed fire, burglar and access control power supply
  • Field selectable 12VDC or 24VDC output
  • Five (5) individual power limited outputs
  • Built-in charger for sealed lead acid or gel type batteries
  • Automatic switch over to stand-by battery when AC fails
  • Thermal and short circuit protection with auto reset

Frequently Answers and Questions

What type of battery does this power supply use?
The AL400ULM is designed to work with sealed lead acid or gel type batteries.
What is the maximum charge current?
The maximum charge current for this power supply is 0.7 amps.