advertisement
WhisperKOOL
1738 E. Alpine Ave. Stockton, CA 95205
1(800) 343-9463 www.whisperkool.com
3. Mounting the pump: the tank has two slots provided to mount the unit.
The slots are located on the ends of the tank (Figure 5). The unit should be mounted either on the side of the air conditioner unit or nearby wall.
Pump must be level and the inlet must be below the coil drain. Conduit fittings are not compatible with the plastic pump housing.
4. The pump should not be installed in a manner that will subject it to splashing or spraying.
5. This pump is not intended for use inside air plenums.
INTRODUCTION
The condensate pump kit is designed as an automatic condensate removal pump for water dripping off an air conditioner evaporative coil. The pump is controlled by a float/switch mechanism that turns the pump on when approximately 2-1/4” of water collects in the tank, and automatically switches off when the tank drains to approximately 1-1/4”.
The pumps are carefully packaged, inspected and tested to insure safe operation and delivery. When you receive your pump, examine it carefully to determine that there are no broken or damaged parts that may have occurred during shipment. If damage has occurred, make notation and notify WhisperKool. They will assist you in replacement or repair, if required.
READ INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE
OR SERVICE THE LITTLE GIANT PUMP. KNOW THE PUMP APPLICATION, LIMITA-
TIONS AND POTENTIAL HAZARDS. PROTECT YOURSELF AND OTHERS BY OB-
SERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS
COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE! RETAIN
INSTRUCTIONS FOR FUTURE REFERENCE. INSTALLATION AND CONNECTIONS
ARE TO BE MADE BY A QUALIFIED PERSON.
!
WARNING !
SAFETY GUIDELINE
DO NOT USE TO PUMP FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASO-
LINE, FUEL OIL, KEROSENE, ETC. DO NOT USE IN EXPLOSIVE ATMOSPHERES.
PUMP SHOULD BE USED WITH LIQUIDS COMPATIBLE WITH PUMP COMPONENT
MATERIALS.
DO NOT HANDLE PUMP WITH WET HANDS OR WHEN STANDING ON A WET OR
DAMP SURFACE, OR IN WATER. THIS PUMP IS SUPPLIED WITH A GROUNDING
CONDUCTOR AND/OR GROUNDING TYPE ATTACHMENT PLUG. TO REDUCE THE
RISK OF ELECTRICAL SHOCK, BE CERTAIN THAT IT IS CONNECTED TO A PROP-
ERLY GROUNDED GROUNDING TYPE RECEPTACLE.
IN ANY INSTALLATIONS WHERE PROPERTY DAMAGE AND/OR PERSONAL
INJURY MIGHT RESULT FROM AN INOPERATIVE OR
LEAKING PUMP DUE TO POWER OUTAGES, DISCHARGE LINE
BLOCKAGE, OR ANY OTHER REASON, A BACKUP SYSTEM(S) AND/OR ALARM
SHOULD BE USED.
SUPPORT PUMP AND PIPING WHEN ASSEMBLING AND WHEN INSTALLED. FAIL-
URE TO DO SO MAY CAUSE PIPING TO BREAK, PUMP TO FAIL, MOTOR BEARING
FAILURES, ETC.
ELECTRICAL CONNECTIONS
!
WARNING !
1. Shut off electrical power at fuse box before making any connections. All wiring must comply with local codes.
2. Line voltage: Connect power cord to line voltage specified on motor and nameplate. Power cord must be connected to a constant source of power
(not a fan or other device that runs intermittently). If power cord does not have a plug, wiring is as follows: green (or green/yellow)—ground. Black
(or brown)— line. White (or blue)—neutral.
Connect here to turn alarm on.
Connect here to turn thermostat off.
NOTE: All wiring to be done by qualified service technician. Refer to local codes in your area.
3. Safety switch: The safety overflow switch should be connected to a class II low voltage circuit. To control a thermostatic circuit the COM and NO connections from the safety switch are to be wired in series with the low voltage thermostat circuit to shut
Safety Switch
(Low Voltage ClassII) down the heating/AC circuit. The COM and
NC switch contacts may be used to actuate a low voltage alarm circuit (connected in series) if the heating/cooling system can not be disrupted. The safety switch comes from the factory with leads connected to the COM and NO switch terminals. Typical hook-up of “NC” circuits would be (Figures 2 & 3).
4. If fused plug is used on 230V units, a 1.0 amp fuse is recommended.
Remove cardboard insert.
PIPING
1. Run flexible tubing or pipe from evaporator drain into one of the three pump inlets. Be sure inlet piping is sloped downward to allow gravity flow (Figure 4). Extend the inlet piping into the tank from 1 to 3 inches to ensure that it will not interfere with proper float operation. Be sure that the inlet piping is cut at an angle where it enters the tank.
INSTALLATION
1. Before installing pump, allow air conditioner to cycle several times, collecting condensate in a separate container to help flush any residual oils that may remain in the system.
2. Carefully unpack the pump. Remove the cardboard packing from the motor cover air slots. Carefully slide the packing away from the pump. This packing is used to prevent switch movement during shipment (Figure 1).
Discharge Line Installation
Inverted “U” Trap
Slope down from highest point
Drop to bottom of pump or below if possible
2. The outlet piping should be flexible tubing secured with a hose clamp (not provided) or pipe (3/8 inch I.D. maximum to prevent excessive flow back to unit).
From condensate unit, extend discharge piping straight up as high as necessary. Do not extend this line above the head/GPH of the particular model being installed. From this high point, slope discharge line down slightly to a point
Mounting Slots
Check Value
above drain area; then turn down and extend to a point below or approximately level with the bottom of the condensate unit. This will give a siphoning effect which will improve efficiency of the condensate unit and will, in most cases, eliminate the need for a check valve (Figure 5). If it is not possible to slope discharge line down, make an inverted “U” trap directly above the pump at the highest point.
SERVICE INSTRUCTIONS
!
WARNING !
1. Make certain that the unit is disconnected from the power source before attempting to service or remove any component!
2. Be sure the floats move freely. Clean as necessary (Figure 6).
3. Clean the tank with warm water and mild soap.
4. Check the inlet and outlet piping. Clean as necessary. Be sure there are no kinks in the line that would inhibit flow.
TESTING
Safety switch float
Extreme is for Example Only
Motor switch float
1. Turn on power.
2. Remove motor/tank cover assembly and hold level.
3. Test motor switch by raising motor switch float with finger (Figure 6). Motor should turn on just before float contacts cover.
4. Test safety switch by raising safety switch float with finger. Safety switch should activate before float contacts cover.
5. Replace motor/tank cover assembly on tank. This pump is suitable for gas furnace condensate applications. Caution must be taken to ensure acidity of condensate does not increase below the average pH of 3.4 (to prevent localized pocket of acid that acts like a battery causing pitting) by routinely cleaning or flushing tank with fresh water.
Drain Line
Cooling System
Pump Mounted to Wall
Drain Line
To: Garden
Sink
Sewer
Potted Plant
advertisement