EPR-04 04S Power Meter User Manual
The EPR-04 04S is a three-phase power meter that measures active and reactive power, energy, apparent power, and power factor. It also has a MODBUS serial interface for communication with other devices. This meter is designed for use in a variety of applications, including commercial and industrial buildings, data centers, and power distribution systems.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
POWERMETER
EPR-04/04S
L3 PHASE MIN. APPARENT POWER TOTAL MIN. IMPORT ACTIVE POWER TOTAL MIN. EXPORT ACTIVE POWER
TOTAL MIN. IMPORT REACTIVE POWER TOTAL MIN. EXPORT REACTIVE POWER int int int int
0.1 0.1 0.1 0.1 0.1 0.1
VA Watt Watt Var Var VA
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W
L1 PHASE MAX. ACTIVE POWER L2 PHASE MAX. ACTIVE POWER L3 PHASE MAX. ACTIVE POWER L1 PHASE MAX. REACTIVE POWER L2 PHASE MAX. REACTIVE POWER L3 PHASE MAX. REACTIVE POWER L1 PHASE MAX. APPARENT POWER L2 PHASE MAX. APPARENT POWER L3 PHASE MAX. APPARENT POWER
TOTAL MAX. IMPORT ACTIVE POWER TOTAL MAX. EXPORT ACTIVE POWER TOTAL MAX. IMPORT REACTIVE POWER TOTAL MAX. EXPORT REACTIVE POWER int int int int int int unsigned int unsigned int unsigned int int int int int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Watt Watt Watt Var Var Var VA VA VA Watt Watt Var Var VA
L1 PHASE IMPORT MAX. DEMAND ACTIVE POWER L1 PHASE EXPORT MAX. DEMAND ACTIVE POWER L2 PHASE IMPORT MAX. DEMAND ACTIVE POWER L2 PHASE EXPORT MAX. DEMAND ACTIVE POWER L3 PHASE IMPORT MAX. DEMAND ACTIVE POWER L3 PHASE EXPORT MAX. DEMAND ACTIVE POWER L1 PHASE IMPORT MAX. DEMAND REACTIVE POWER L1 PHASE EXPORT MAX. DEMAND REACTIVE POWER L2 PHASE IMPORT MAX. DEMAND REACTIVE POWER L2 PHASE EXPORT MAX. DEMAND REACTIVE POWER L3 PHASE IMPORT MAX. DEMAND REACTIVE POWER L3 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L1 PHASE MAX. DEMAND APPARENT POWER L2 PHASE MAX. DEMAND APPARENT POWER L3 PHASE MAX. DEMAND APPARENT POWER TOTAL IMPORT MAX. DEMAND ACTIVE POWER TOTAL EXPORT MAX. DEMAND ACTIVE POWER
TOTAL IMPORT MAX. DEMAND REACTIVE POWER TOTAL EXPORT MAX. DEMAND REACTIVE POWER int int int int int int int int int int int int unsigned int unsigned int unsigned int int int int int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Watt Watt Watt Watt Watt Watt Var Var Var Var Var Var VA VA VA Watt Watt Var Var VA
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
0098 009A 009C 009E 00A0 00A2 00A4 00A6 00A8 00AA 00AC 00AE 00B0 00B2 00B4 00B6 00B8 00BA 00BC 00BE 00C0 00C2 00C4 00C6 00C8 00CA 00CC 00CE 00D0 00D2 00D4 00D6 00D8 00DA 00DC 00DE 00E0 00E2 00E4 00E6 00E8 00EA 00EC 00EE 00F0 00F2 00F4 00F6 00F8 00FA 00FC 00FE
152 154 156 158 160 162 164 166 168 170 172 174 176 178 180 182 184 186 188 190 192 194 196 198 200 202 204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 246 248 250 252 254
L1 PHASE ACTIVE POWER L2 PHASE ACTIVE POWER L3 PHASE ACTIVE POWER L1 PHASE REACTIVE POWER L2 PHASE REACTIVE POWER L3 PHASE REACTIVE POWER L1 PHASE APPARENT POWER L2 PHASE APPARENT POWER L3 PHASE APPARENT POWER
TOTAL IMPORT ACTIVE POWER TOTAL EXPORT ACTIVE POWER
TOTAL INDUCTIVE REACTIVE POWER TOTAL CAPACITIVE REACTIVE POWER
TOTAL APPARENT POWER AVERAGE INDUCTIVE COS int int int int int int unsigned int unsigned int unsigned int int int int int int int int int int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.01
Watt Watt Watt Var Var Var VA VA VA
- - -
Watt Watt Var Var VA
- - Hz long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int
- 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
- Wh Wh Wh Wh
VArh VArh VArh VArh Wh Wh Wh Wh VArh VArh VArh VArh
L1 PHASE MIN. ACTIVE POWER L2 PHASE MIN. ACTIVE POWER L3 PHASE MIN. ACTIVE POWER L1 PHASE MIN. REACTIVE POWER L2 PHASE MIN. REACTIVE POWER L3 PHASE MIN. REACTIVE POWER L1 PHASE MIN. APPARENT POWER L2 PHASE MIN. APPARENT POWER int int int int int int unsigned int unsigned int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Watt Watt Watt Var Var Var VA VA
(-1000 -1000) (-1000 -1000) (-1000 -1000) (-1000 -1000) (-1000 -1000) (4000 -7000)
(0 -18000)xCTxVT (0 -18000)xCTxVT (0 -18000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R R R R R R R R R R R R R R R R R R R R
0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
(0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W R/W R/W
RGAG_M SGAG_M TGAG_M RGRG_M SGRG_M TGRG_M RGVA_M SGVA_M TGVA_M RGCOS_M SGCOS_M TGCOS_M AGGIM_M AGGEX_M RGGIM_M RGGEX_M VAG_M COSIM_M COSEX_M FREQ_M
RGAG_MIN_M SGAG_MIN_M TGAG_MIN_M RGRG_MIN_M SGRG_MIN_M TGRG_MIN_M RGVA_MIN_M SGVA_MIN_M
ACTIVE_IM_HM_1 ACTIVE_IM_LM_1 ACTIVE_EX_HM_1 ACTIVE_EX_LM_1
REACTIVE_IM_HM_1 REACTIVE_IM_LM_1 REACTIVE_EX_HM_1 REACTIVE_EX_LM_1
ACTIVE_IM_HM_2 ACTIVE_IM_LM_2 ACTIVE_EX_HM_2 ACTIVE_EX_LM_2
REACTIVE_IM_HM_2 REACTIVE_IM_LM_2 REACTIVE_EX_HM_2 REACTIVE_EX_LM_2
0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0038 003A 003C 003E 0040 0042 0044 0046 0048 004A 004C 004E 0050 0052 0054 0056 0058 005A 005C 005E 0060 0062 0064 0066 0068 006A 006C 006E 0070 0072 0074 0076 0078 007A 007C 007E 0080 0082 0084 0086 0088 008A 008C 008E 0090 0092 0094 0096
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150
A2871/Rev.3
TEHOMITTARI
EPR-04/04S
DIGITAALINEN TEHOMITTARI EPR-04/04S
EPR-04/04S mittaa kolmesta vaiheesta seuraavat teho- ja energiaparametrit:
- Pätöteho (W) - Pätöenergia (kWh)
- Loisteho (VAr) - Loisenergia (kVArh)
- Näennäisteho (VA) - Cos ϕ
Lukemia selataan SET-painikkeella. Kolmessa ensimmäisessä näyttöruudussa näkyvät vaiheiden L1, L2 ja L3 arvot. Neljännessä ruudussa taas näkyy valitun parametrin kokonaisarvo (W, Var, VA, kWh tai kVArh).
EPR-04/04S mittaa myös tehon maksimi-, minimi- ja keskiarvon sekä suurimman keskiarvon. Laitteessa on MODBUS-sarjaliitäntä.
Merkkivalot:
1. W : Pätöteho 2. VAr : Loisteho 3. VA : Näennäisteho
4. kWh : a) A-I : Kulutettu pätöenergia
b) A-E : Tuotettu pätöenergia
5. kVArh : a) r-L : Induktiivinen loisenergia
b) r-C : Kapasitiivinen loisenergia
6. Cos ϕ : sähköverkon cos ϕ
Toimintaperiaate:
EPR-04/04S kertoo tuloliittimistä lukemansa arvot jännitteen ja virran muuntosuhteilla. Siten näytön lukemat ovat järjestelmän todellisia arvoja.
Digitaaliset tulot
Laitteessa on 2 digitaalista tuloliitäntää, joita käytetään sähkökoskettimien tilan valvontaan. Digitaalisilla tuloilla on 2 toimintoa:
- Mahdollistaa digitaalisesta tuloliitännästä saadun datan kauko-ohjaus
(paristo, termostaatti, automaattisulake, pumpun tila)
- Ohjata energiamittareita ja määrätä kumpi niistä mittaa.
Energiapulssilähdöt
Laitteesa on kaksi energiapulssilähtöä: Pul1 ja Pul2.
Pul1 (loisenergian pulssilähtö): 400 ms kestävä pulssitieto lähtee, kun energialukema kasvaa 1 kVArh:n verran. Pul 1 koskee ainoastaan induktiivista loisenergiaa.
Pul2 (pätöenergian pulssilähtö): 400 ms kestävä pulssi lähtee, kun energialukema kasvaa 1 kWh:n verran. Pul2 koskee sekä kulutettua että tuotettua pätöenergiaa. Pienin pulssijakso on 1,6 sekuntia.
Minimi-, maksimi- ja keskiarvot
Minimi-, maksimi ja keskiarvot ovat saatavissa pätöteholle (W), loisteholle
(VAr), näennäisteholle (VA), kokonaispätöteholle (W), kokonaisloisteholle
(VAr) ja kokonaisnäennäisteholle (VA).
Jos mittausarvo on pienempi kuin aiemmin tallentunut minimiarvo, uusi arvo tallentuu minimiksi. Jos taas arvo ylittää aiemman maksimiarvon, se tallentuu uudeksi maksimiksi. Keskiarvo saadaan koontijakson (esim. 15 min) ajalta. Jos uusi arvo ylittää edellisen, se tallentuu uudeksi keskiarvoksi.
Kun nuolipainiketta painetaan ja näytössä on jokin parametri, jota tämä toiminto koskee, ruudussa näkyvät minimi-, maksimi- ja keskiarvot. Jos ruudussa on jokin muu parametri, tosiaikaisten arvojen näyttö jatkuu.
Tällainen muu parametri on esim. tehokerroin, jolle ei minimi-, maksimija keskiarvojen näyttöä ole saatavissa.
H-, L- ja M-ledit
Nämä ledit tarkoittavat valittujen parametrien minimi-, maksimi- ja keskiarvoja:
H = maksimiarvo, L = minimiarvo, M = keskiarvo.
Pätö- ja loistehojen laskenta
Jos äärimmäisenä vasemmalla oleva led vilkkuu, pätö- ja loistehojen suunta on negatiivinen. Pätö- ja loistehoille on kaksi laskentatapaa:
1) Laite laskee kulutetut ja tuotetut arvot yhteen ja näyttää niiden summan.
2) Laite laskee kulutetut ja tuotetut arvot erikseen.
- Piste neljännessä näyttöruudussa äärimmäisenä oikealla olevan numeron kohdalla tarkoittaa, että lukema on tuotettu pätöteho. Jos pistettä ei ole, lukema on kulutettu pätöteho.
- Piste neljännessä näyttöruudussa äärimmäisenä oikealla olevan numeron kohdalla tarkoittaa, että lukema on kapasitiivinen loisteho. Jos pistettä ei ole, loisteho on induktiivinen.
- Jos parametri on ollut näytössä 20 sekuntia, kun virta katkeaa, sama
parametri on näytössä edelleen, kun virta taas kytkeytyy.
Vaiheiden merkkivalot
Vaiheiden näyttöruudut
Kilo-LED
Mega-LED
Kokonaisarvojen näyttö
S
Cosj
EPR- 04S
ESC
SET
Ylös
ESC
SET
Alas
1
TOIMINTOPAINIKKEET
SET
ESC
SET
SET
SET
W-ledin palaessa näyttää tosiaikaiset suurimmat tehoarvot ja suurimmat kokonaiskeskiarvot. Myös siirrytään valikoissa ylöspäin.
W-ledin palaessa näyttää tosiaikaiset pienimmät tehoarvot ja kokonaiskeskiarvot. Siirtyminen valikoissa alaspäin.
Selataan parametrejä W, VAr, VA, kWh, kVArh, cos ϕ . Painamalla
3 sekuntia avataan ohjelmointitila. Muutosten tallentaminen ja siirtyminen alavalikkoon.
Ohjelmoinnissa paluu ylempään valikkoon ja ohjelmointitilan sulkeminen tallentamatta mitään.
Virtamuuntajan muuntosuhteen asetus
Tässä kohdassa asetetaan virtamuuntajan muuntosuhde.
Huom!. Jos mittarin ja sähköjärjestelmän välillä ei käytetä virtamuuntajaa, muuntosuhteeksi asetetaan 1.
Esimerkki: Jos käytössä on virtamuuntaja, jonka muuntosuhde on
250/5 A, muuntosuhteeksi asetetaan 50 (250/5).
Paina SET-painiketta 3 sekuntia.
Näytössä näkyy trA Fo.
Paina SET-painiketta. Näytössä näkyy trA Fo Ctr ja toisen näyttöruudun viimeinen numeropaikka
L1 k
L1 L2 L3
Cosj vilkkuu.
Aseta neljäs numero nuolipainikkeilla.
Paina SET-painiketta.
Kolmannen ruudun ensimmäinen numeropaikka vilkkuu. Jos neljäs numero ei tullut oikein, paina
ESC-painiketta ja korjaa numero.
L2
L3
S k k k kWh kVArh
ESC
SET
SET
SET
ESC
Aseta kolmas numero nuolipainikkeilla.
Paina SET-painiketta. Kolmannen näyttöruudun keskimmäinen numeropaikka vilkkuu. Jos kolmas numero ei tullut oikein, paina
ESC-painiketta ja korjaa numero.
Aseta toinen numero nuolipainikkeilla.
Cosj k
L1
M
W VAr VA kWh kWArh k
L2
M
L3
M k
L1
L2
Esc
Paina SET-painiketta.
Kolmannen ruudun viimeik
S
M EPR-04S
POWERMETER
S e t nen numeropaikka vilkkuu. Jos toinen numero ei tullut oikein, paina
ESC-painiketta ja korjaa numero.
L3
Aseta viimeinen numero nuolipainikkeilla.
Paina SET-painiketta. Näytössä näkyy trA Fo Ctr. Asetus on tehty, mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti:
Etsi ESC-painikkeella näyttö SAU SEt yES.
SET
SET
SET
SET
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, asetus ei tallennu, vaan entinen jää voimaan.
Jännitemuuntajan muuntosuhteen asetus
Tässä kohdassa asetetaan jännitemuuntajan muuntosuhde.
Huom! Jos jännitemuuntajaa ei käytetä, muuntosuhteeksi pitää asettaa 1.
Esimerkki: Jos jännitemuuntajan muuntosuhde on 34,5 kV/100 V, suhteeksi pitää asettaa 345 (34500/100).
Paina SET-painiketta 3 sekuntia. Ruudussa näkyy trA Fo.
Paina SET-painiketta. Ruudussa näkyy trA Fo Ctr.
Etsi nuolinäppäimillä näyttöön rtA Fo Utr.
Paina SET-painiketta. Toisen näyttöruudun viimeinen numeropaikka vilkkuu.
TEHOMITTARI
EPR-04/04S
SET
Aseta numero nuolipainikkeilla.
Paina SET-painiketta. Kolmannen näyttöruudun ensimmäinen numeropaikka vilkkuu. Jos edellinen numero ei tullut oikein,
L1
L2 paina ESC ja korjaa numero.
Aseta numero nuolipainikkeilla.
L3 k k k
L1 L2 L3
Cosj kWh kVArh
SET
SET
SET
ESC
SET
Loisenergian laskentamenetelmän asetus
Mechanical Energymeter
0 1
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Loisenergian laskentatapoja on kolme. Ne esitetään alla olevassa taulukossa. Taulukosta näkyvät myös arvot, jotka pitää
asettaa mekaanisille ja digitaalisille energiamittareille.
Digital Energymeter
2 3
Reactive Energy
(Q)
90° rotation of voltage vector and
¥ n=1
Selitys
Suosituin loistehon laskentamenetelmä
Vn-arvot x In-arvot 19.:een harmoniseen yliaaltoon asti. Tätä laskentaa suositellaan verkkoanalysaattoreille.
Tehokolmiomenetelmä: Sen mukaan
Q = (Q = loisteho,
S = pätöteho, P = näennäisteho)
SET
SET
4 5 S 2 -P 2
Paina SET-painiketta 3 sekuntia. Näytössä näkyy trA Fo.
Paina SET-painiketta. Näytössä näkyy rtA Fo Ctr.
SET
SET
ESC
SET
Paina SET-painiketta. Kolmannen näyttöruudun keskimmäinen numeropaikka vilkkuu. Jos edellinen numero ei tullut oikein.
paina ESC ja korjaa numero.
Aseta numero nuolipainikkeilla.
S k ESC
SET
Paina SET-painiketta. Kolmannen näyttöruudun viimeinen numeropaikka vilkkuu. Jos edelliL1 L2 L3 k
L1
M k
L2
M k
L3
M nen numero ei tullut oikein, paina ESC ja korjaa numero.
Aseta viimeinen numero nuolipainikkeilla.
Cosj
M k
S
W VAr VA kWh kWArh
EPR-04S
POWERMETER
Paina SET-painiketta.
Näytössä näkyy trA Fo Utr. Asetus on tehty, mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti:
Etsi ESC-painikkeella näyttö SAU SEt yES.
S V n
.I
n
.sin(j n
)
Etsi nuolipainikkeilla näyttöön CAL CLt.
Paina SET-painiketta. Laskenta-arvo 1 vilkkuu.
Valitse energian laskentamenetelmä nuolipainikkeilla
Paina SET-painiketta. Näytössä näkyy CAL CLt. Asetus on tehty, mutta ei vielä otettu käyttöön. Käyttöönotto tapahtuu seuraavasti:
L1
Etsi ESC-painikkeella näyttöön SAUE SEt yES.
Cosj k
L1
M
W VAr VA kWh kWArh k
L2
M
L3
M k
L2
Esc
Paina SET-painiketta.
Jos painat ESC-painiketta k
S
M EPR-04S
POWERMETER tai valitset nuolipainikkeilla vaihtoehdon no, asetus ei tallennu vaan entinen jää voimaan.
S e t
Esc
S e t
L3
Koontijakson pituuden asetus
SET
SET
SET
SET
Tässä kohdassa asetetaan koontijakson pituus.
Paina SET-painiketta 3 sekuntia.
Ruudussa näkyy trA Fo.
Etsi nuolipainikkeilla näyttö dE ti.
Paina SET-painiketta. Kolman- nen näyttöruudun keskimmäinen numeropaikka vilkkuu.
Cosj
EPR- 04S
ESC
Aseta numero nuolipainikkeilla.
S
SET
Paina SET-painiketta. Kolmannen näyttöruudun viimeinen numeropaikka vilkkuu. Jos ensimmäinen numero ei tullut oikein, paina ESC-painiketta ja korjaa numero.
Aseta numero nuolipainikkeilla.
Cosj k
L1
M
W VAr VA kWh kWArh k
L2
M
L3
M k
L1 L2
Esc
Paina SET-painiketta.
Ruudussa näkyy dE ti.
k
S
M
Asetus on tehty mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti.
S e t
L3
ESC
SET
Etsi ESC-painikkeella näyttö SAU SEt yES.
Paina SET-painiketta
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Pulssivalikko
Pulssivalikossa voidaan sehdä seuraavat asetukset:
PUL SE rAt, PUL SE o-1 ja PUL SE o-2
PUL SE rAt io: Pulssisuhteeksi voidaan asettaa: 1, 10, 100
(W/Varh/VA); 1, 10, 100 (kWh/kVArh/kVA); 1 MWh/MVArh/MVA
PUL SE o-1: Jokainen lisäys lähdössä 1 lasketaan yhdeksi pulssiksi.
Lähdön 1 parametriksi voidaan valita: Act (tuotettu/kulutettu), A-I
(pätö kulutettu), A-E (pätö tuotettu), rEA (induktiivinen/kapasitiivinen), r-L (lois induktiivinen), r-C (lois-kapasitiivinen).
PUL SE o-2: Jokainen lisäys lähdössä 2 lasketaan yhdeksi pulssiksi.
Lähdön 2 parametriksi voidaan valita: Act (tuotettu/kulutettu), A-I
(pätö kulutettu), A-E (pätö tuotettu), rEA (induktiivinen/kapasitiivinen), r-L (lois induktiivinen), r-C (lois kapasitiivinen).
SET
Paina SET-painiketta 3 sekuntia. Ruudussa näkyy trA Fo.
SET
SET
SET
ESC
SET
Etsi nuolipainikkeilla näyttöön PULSE.
Paina SET-painiketta. Näytössä näkyy PUL SE rAt.
Valitse nuolipainikkeilla PUL SE rAt, PUL SE o-1 tai PUL SE o-2.
Paina SET-painiketta.
Aseta arvo nuolipainikkeilla.
Paina SET-painiketta.
Asetus on tehty, mutta
Cosj k
L1
M
S
M k
W VAr VA kWh kWArh k
L2
M
EPR-04S
POWERMETER k
L3
M
L1
L2
Esc
S e t
L3 ei vielä tallennettu.
Tallennus tapahtuu seuraavasti:
Etsi ESC-painikkeella näyttö SAU E SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
2
POWERMETER
EPR-04/04S
+_
Max: 30 VDC
L1
L2
L3
1A
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
L1 L2 L3 N
I
L1
I
L2
I
L3
N k
K L l k
K L l k
K
3 Phase without neutral l
L
PR-16 Box Connection Diagram Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
L1
L2
L3
N
Voltage
Measuring Input
L1 L2
1 2
L3 N
3 4 k
K
Current
Measuring Input
I
L1
I
L2
I
L3
5 6 7 8 9 10 l
L k
K l
L k
K L l
3 Phase neutral
Max: 30 VDC
+_
Auxiliary
Supply
Un
13 14
1A
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
Voltage
Measuring Input
L1 L2
1 2
L3
3 4
L1
L2
L3
3 Phase without neutral
*Available only for EPM-04S
Current
Measuring Input
I
L1
I
L2
I
L3
5 6 7 8 9 10
1A
Auxiliary
Supply
Un
13 14
+_
Max: 30 VDC
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
Un
L1 L2 L3 N
I
L1
I
L2
I
L3
1A
N
L1
L2 k
K
L3
3 Phase without neutral current input with
Aron wiring configuration
Max: 30 VDC
L l
+_ k
K L l
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
Voltage
Measuring Input
L1 L2
1 2
L3 N
3 4
Current
Measuring Input
I
L1
I
L2
I
L3
5 6 7 8 9 10
Auxiliary
Supply
Un
13 14
1A N
L1
L2
L3 k
K L l k
K L l
3 Phase without neutral current input with
Aron wiring configuration Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
7
Voltage
Measuring Input
L1 L2
1 2
L3 N
3 4
Current
Measuring Input
I
L1
I
L2
I
L3
5 6 7 8 9 10
L1
L2
L3 k
K L l k
K l
L
3 Phase without neutral current input with
Aron wiring configuration
Auxiliary
Supply
Un
13 14
1A N
L1
L2
L3
N
POWERMETER
EPR-04/04S
PR 19 Box Connection Diagram k
K L l k
K L l k
K
Max: 30 VDC
_
+
1
7
L1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
Pul 1 Pul 2
6
RS485
19 20 21 22
GND B A TR
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
L l
3 Phase neutral
L1
L2
L3 k
K L l k
K L l k
K
Max: 30 VDC
_
+
1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
6
Pul C
Pul 1
( 12-48V DC )
InC In1 In2
Pul 2
RS485
13 14 15 16 17 18 19 20 21 22
GND B A TR
7
L1
Voltage Measuring Input
8
L2
9
L3 N
10 11
Auxiliary
Supply
12
L l
L1
N
3 Phase without neutral
PK 26 Box Connection Diagram
Max: 30 VDC
+_
L1
N
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
L1 L2 L3 N
I
L1
I
L2
I
L3
1A
L1
L2
L3
N
3 Phase neutral
*Available only for EPM-04S k
K L l k
K l
L k
K l
L
L1
L2
L3 k
K L l k
K L l
Max: 30 VDC
_
+
1
7
L1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
6
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Voltage Measuring Input
8
L2 L3
9
N
10
Auxiliary
Supply
11 12
3 Phase without neutral current input with
Aron wiring configuration
L1
L2
L3 k
K L l k
K L l
Max: 30 VDC
_
+
1
I
L1
2 3
L2
4 5
I
Current Measuring Input
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
I
L3
6
7
L1
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
L1
N
L1
N
3 Phase without neutral current input with
Aron wiring configuration
+_
Max: 30 VDC
6
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
L1 L2 L3 N
I
L1
I
L2
I
L3
1A N
L1
L2
L3 k
K L l
3 Phase without neutral current input with
Aron wiring configuration k
K L l
TEHOMITTARI
EPR-04/04S
Energianmittausvalikko
Laitteessa on kaksi energiamittaria: E-1 ja E-2.
E-1:llä on 4 parametriä: on: E-1 mittaa energiaa muista asetuksista riippumatta i-1: E-1 mittaa kun digitaalinen tulo 1 on toiminnassa (eli 1) i-2: E-1 mittaa kun digitaalinen tulo 2 on toiminnassa (eli 1)
E-2: E-1 ei mittaa silloin, kun E-2 mittaa.
E-2-mittarille on samanlaiset asetukset.
Jos E-1:lle valitaan asetus E-2 ja jos E-2:lle valitaan E-1, kumpikin mittaa.
SET
SET
SET
SET
Paina SET-painiketta 3 sekuntia. Näytössä näkyy trA Fo.
Etsi nuolipainikkeilla näyttöön Eng Cnt.
Paina SET-painiketta.
Näytössä näkyy Eng Cnt E-1.
Valitse nuolipainikkeilla E-1 tai E-2.
k
L1
M
Paina SET-painiketta.
Valitse nuolipainikkeilla asetus ON, i-1
Cosj k
S
M
W VAr VA kWh kWArh k
L2
M tai i-2.
Paina SET-painiketta. Asetus on tehty, mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti:
EPR-04S
POWERMETER k
L3
M
L1 L2
Esc
S e t
L3
ESC
SET
Etsi ESC-painikkeella näyttö SAUE SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon NO, asetus ei tallennu, vaan entinen jää voimaan.
Minimi-, maksimi- ja energia-arvojen nollaus
SET
SET
SET
ESC
SET
Tässä kohdassa poistetaan minimi- ja maksimiarvot sekä energiamittareiden lukemat. Heti tämän jälkeen tosiaikaiset arvot tallentuvat minimi- ja maksimiarvoiksi. Katso minimi- ja maksimiarvojen käsittelyä varten lukua PAINIKKEIDEN TOIMINNOT.
Huom! Sähkökatko ei vaikuta laitteen muistiin tallennettuihin parametreihin. Kun näytössä on rES Et ja suljet kaikki valikot ja vahvistat muutokset, kaikkien parametrien minimi- ja maksimiarvot sekä energiamittareiden arvot nollautuvat samanaikaisesti.
Menettele seuraavasti, kun laite on mittaustilassa:
Paina SET-painiketta 3 sekuntia.
Näytössä näkyy trA Fo.
Etsi nuolipainikkeilla näyttöön rES Et.
Paina SET-painiketta. Näytössä näkyy rES Et HL.
Valitse nollattava parametri nuolipainikkeella ja valitse sen jälkeen yES. Jos et halua nollata, valitse
NO.
Paina SET-painiketta. Asetus on tehty, mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti:
Etsi ESC-painikkeella näyttö SAUE SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset vaihtoehdon NO, lukemat eivät nollaudu.
Tässä valikossa asetetaan salasana ja otetaan se käyttöön.
Salasanassa on 4 numeroa. Se suojaa laitteen asetuksia.
Pin-valikossa on kaksi alavalikkoa.
Salasanan muuttaminen
Tässä valikossa muutetaan salasana.
Tehtaan asetus salasanaksi on 0000.
Menettele seuraavasti, kun laite on mittaustilassa.
3
SET
Paina SET-painiketta 3 sekuntia. Näytössä näkyy trAFo.
Etsi nuolipainikkeilla näyttöön Pin.
L1 k
L2 k
L1 L2 L3
Cosj
SET
SET
SET
SET
Paina SET-painiketta. Näytössä näkyy Pin ACt iUA tE.
L3 k
Etsi nuolipainikkeilla näyttöön Pin CHA ngE.
Anna vanha salasana nuoli- ja SET-painikkeilla.
Anna uusi salasana nuoli- ja SET-
S k
Cosj k
L1
M
W painikkeilla.
Anna uusi salasana k
S
M uudelleen nuoli- ja SET-painikkeilla.
VAr VA kWh kWArh k
L2
M kWh kVArh
EPR-04S
POWERMETER
L3
M k
L1
ESC
SET
L2
Esc
S e t
L3
SET
ESC
SET
SET
SET
SET
SET
SET
SET
ESC
SET
Paina SET-painiketta. Näytössä näkyy Pin CHA ngE. Asetus on tehty mutta ei vielä tallennettu. Menettele seuraavasti:
Etsi ESC-painikkeella näyttö SAU SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset edelliseen vaihtoehdon no, poistut tekemättä muutoksia. Entinen salasana jää voimaan.
Salasanan käyttöönotto
SET
Tässä kohdassa otetaan salasana käyttöön. Kun salasana on käytössä, se pitää antaa päästäkseen valikoihin tosiaikaisten mittausarvojen katselusta painamalla SET-painiketta 3 sekuntia.
Väärä salasana ei avaa valikoita.
Huom! Tehtaalla asetettu oletussalasana on 0000.
Menettele seuraavasti, kun laite on mittaustilassa:
L1 L2 L3
Paina SET-painiketta
3 sekuntia. Näytössä näkyy trA Fo.
L1 k
Cosj
Etsi nuolipainikkeilla näyttöön Pin.
Paina SET-painiketta. Näytössä näkyy Pin ACt iUA.
L2
L3 k k kWh k
Paina SET-painiketta. Toisen näyttöruudun viimeinen
S numeropaikka vilkkuu.
Aseta nuolipainikkeilla salasanan neljäs numero.
kVArh
ESC
Paina SET-painiketta. Kolmannen näyttöruudun ensimmäinen numeropaikka vilkkuu. Jos edellinen numero ei tullut oikein, paina ESC-painiketta ja korjaa numero.
k
L1
M k
L2
M k
L3
M
L1
L2 L3
Aseta kolmas numero nuolipainikkeilla.
Paina SET-painiketta.
Kolmannen ruudun kes-
Cosj
M k
S
W VAr VA kWh kWArh
EPR-04S
POWERMETER
Esc
S e t kimmäinen numeropaikka vilkkuu. Jos edellinen numero ei tullut oikein, korjaa se nyt.
L1 L2 L3
POWERMETER
EPR- 04S
Aseta toinen numero nuolipainikkeilla
Paina SET-painiketta. Kolmannen ruudun viimeinen numeropaikka vilkkuu. Jos edellinen numero ei tullut oikein, korjaa se.
Aseta viimeinen numero nuolipainikkeilla.
L1
L2
L3 k k k k
S
Paina SET-painiketta. Näytössä näkyy Pin ACt oF. Asetus on tehty, mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti:
Cosj kWh kVArh
ESC
SET
Etsi ESC-painikkeella näyttö SAU SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset vaihtoehdon NO, salasana ei tule käyttöön.
TEHOMITTARI
EPR-04/04S
Sarjamuotoinen tiedonsiirto
(vain EPM-04S)
Laite kayttää MODBUS RTU -protokollaa. Tiedonsiirtoportti on optoeristetty.
Kaikki mittaustulokset voidaan siirtää tietokoneeseen. PC-ohjelmassa voidaan asettaa muuntosuhteet ja tiedonsiirtoparametrit sekä nollata tallennetut minimi-, maksimi- ja keskiarvot sekä energialukemat.
Tiedonsiirtoparametrien asetukset
Laitteen osoitteen asetus (vain EPM-04S)
SET
SET
SET
SET
ESC
SET
Paina SET-painiketta 3 sekuntia. Näytössä näkyy trA Fo.
Etsi nuolipainikkeilla näyttöön rS-485.
Paina SET-painiketta. Näytössä näkyy rS-485 Adr ES.
Paina SET-painiketta. Ensimmäinen numeropaikka vilkkuu.
Aseta osoitenumero nuolipainikkeilla.
Paina SET-painiketta. Uusi osoite tallentuu.
Etsi ESC-painikkeella näyttö SAU SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset vaihtoehdon NO, uusi asetus ei tule tallennu, vaan entinen jää voimaan.
Tiedonsiirtonopeuden asetus
Asetusvaihtoehdot ovat 2400, 4800, 9600, 19200 ja 38400 bps
SET
SET
SET
SET
ESC
SET
Paina SET-painiketta 3 sekuntia. Näytössä näkyy trA Fo.
Etsi nuolipainikkeilla näyttö rS-485.
Paina SET-painiketta. Näytössä näkyy rS-485 Adr ES.
Etsi nuolipainikkeilla näyttö rS-485 bAU dE.
Pariteetin asetus (vain EPM-04S)
SET
SET
SET
SET
ESC
Paina SET-painiketta. Baudiarvo vilkkuu.
Valitse siirtonopeus nuolipainikkeilla.
Paina SET-painiketta. Asetus on nyt tehty, mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti:
Etsi ESC-painikkeella näyttö SAU SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset vaihtoehdon NO, uusi asetus ei tallennu, vaan entinen jää voimaan.
Asetusvaihtoehdot ovat no, odd ja even (= ei, pariton ja parillinen
)
Paina SET-painiketta 3 sekuntia. Näytössä näkyy trA Fo.
Etsi nuolipainikkeilla näyttö rS-485.
Paina SET-painiketta. Näytössä näkyy rS-485 Adr ES.
Etsi nuolipainikkeilla näyttö rS-485 PAr ity.
Paina SET-painiketta.
Valitse nuolipainikkeilla pariteetiksi NO, ODD tai EVEN
(ei, pariton tai parillinen).
Paina SET-painiketta. Asetus on nyt tehty, mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti:
Etsi ESC-painikkeella näyttö SAU SEt yES.
SET
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset vaihtoehdon NO, uusi asetus ei tallennu, vaan entinen jää voimaan.
4
HUOM! Tiedonsiirto ENTES-PC-ohjelmaan toimii vain, jos siirtonopeudeksi asetetaan 38400 bps ja pariteetiksi NO.
MODBUS RTU -PROTOKOLLA (vain EPM-04S)
MODBUS RTU -vakioviesti on seuraava:
OSOITE TOIMINTO DATA
8 BIT 8 BIT NX8BIT
T on ajanjakso, jona dataa ei saa kulkea siirtoväylässä, jotta kytketyt laitteet tunnistaisivat viestin päättyneen ja toisen alkavan. Tämän ajan tulee olla vähintään 3,5 merkin pituinen valitulla siirtonopeudella.
Osoitealue (1-247) tarkoittaa kytkettyjen laitteiden osoitteita. Datakenttä sisältää datan, jonka päälaite lähettää alalaitteille tai päinvastoin. CRC on MODBU RTU:n virheidentarkastusmenetelmä ja se sisältää 2 tavua.
Saatavana on seuraavat Modbus-toiminnot:
03H READ HOLD REGISTERS
06H PRESET SINGLE REGISTER
10H PRESET MULTIPLE REGISTERS
Read Hold (03) -toimintoa käytetään mittaus- ja asetusarvojen lukemiseen. Laite lähettää virheilmoituksen, jos pyydetään lukemaan jokin muu kuin rekisteriluettelossa esiintyvä rekisteri.
Esimerkki: luetaan vaiheen 1 jännite lähettämällä viesti laitteeseen.
01 03 00 00 00 02 XX XX
01 Laitteen osoite
03 Toiminto
00 MSB-osoite
00 Registerin numero MSB
02 Rrekisterin numero LSB
XX CRC LSB
Preset Single Register (06) -toimintoa käytetään kirjoittamaan asetusarvoja, nollaamaan energiamittareita sekä minimi-, maksimi- ja keskiarvoja. Virtamuuntajan muuntosuhteeksi voidaan asettaa 0-2000, jännitemuuntajan suhteeksi 1-40000. Minimi-, maksimi- ja keskiarvot voidaan ainoastaan nollata. Jos lähetetty arvo ei sisälly mainittuihin alueisiin, laite vastaa virheilmoituksella. Esim. virtamuuntajan suhteeksi asetetaan 100:
01 06 80 02 00 64 XX XX
01 Laitteen osoite
02 LSB-osoite
00 Data MSB
64 Data LSB
XX CRC MSB
XX CRC LSB
Preset Multiple Register (10H) -toimintoa käytetään asettamaan useampi kuin yksi rekisteri kerrallaan. Esim. virtamuuntajan suhteeksi asetetaan
100 ja jännitemuuntajan suhteeksi 20,0:
01 10 80 00 00 02 04 00 C8 00 64 XX XX
01 Laitteen osoite
10 Toiminto
80 MSB-osoite
00 LSB-osoite
00 Rekisterinumero MSB
02 Rekisterinumero LSB
04 Tavujen lukumäärä
00 Data MSB
C8 Data LSB
00 Data MSB
64 Data LDB
XX CRC MSB
XX CRC LSB
Datakaapelin tiedot: - Parikierretty johto
- 24 AWG tai paksumpi, alle 100 ohmia/km
- Nimellinen ominaisimpedanssi 10 kHz:llä on 100 ohmia
- Keskinäinen kapasitanssi parin kahden johtimen välillä: alle 60 pF/m
- Keskinäinen parikapasitanssi (kapasitanssi yhden johtimien ja kaikkien muiden maahan kytkettyjen johtimien välillä): alle 120 pF/m.
Digitaaliset tulot (vain EPR-04S)
44H
1
DIN1 tulo 2
Korkea tavu Matala tavu
tulo 1 U = määrittelemätön
0
Digitaaliset tulot lähetetään 16 bitin heksadesimaalimuodossa kuten yllä on esitetty.
Jos tulossa 1 on tasajännite 12-48 V, tulorekisterin 15. bitti saa arvon 1.
Muussa tapauksessa sen arvoksi tulee 0.
Jos tulossa 2 on tasajännite 12-48 V, tulorekisterin 14. bitti saa arvon 1.
Muussa tapauksessa sen arvoksi tulee 0.
Parametrit lähtevät 32 bitin heksadesimaalimuodossa. Esim. jännite
230,0 V on 000008FCH. Cos ϕ :n arvot jaetaan 1000:lla. Cos ϕ 0,980 on muodossa 000003D4H. Energia-arvoissa on 64 tavua.
1234567890123456789 Wh = AB 54 A9 8C EB 1F 0A 02 Wh
VIRHEKOODIT (vain EPR-04S)
Alalaite (MPR-53/53S) lähettää virheviestin, kun se saa tunnistamattoman kyselyn. Virhekoodit ovat seuraavat:
01 Epäkelpo toiminto: Viesti on muunlainen kuin mitä yllä on esitetty.
02 Epäkelpo rekisteri: On pyydetty lukemaan jokin muu kuin rekisteriuettelossa oleva rekisteri.
03 Epäkelpo data: Muuntajalle on asetettu epäkelpo arvo tai keskiarvoksi nollasta eroava arvo.
TECHNICAL DATA
Operating Voltage (Un) : Please look at the back labels on the device
Operating frequency (f) : 50/60 Hz
Auxiliary supply Power Consumption : < 4 VA
Measuring Input Power Consumption : < 1VA
VIn : 10-300VAC 50/60Hz. (L-N)
: 10-500VAC 50/60Hz. (L-L)
IIn
Measuring Range
Measuring Category
Class
Voltage Transformer Ratio
Current Transformer Ratio
Max. Ctr x Vtr
Demand Time
Serial Interface (for EPM-04S)
Baud Rate (for EPM-04S)
Address (for EPM-04S)
Parity (for EPM-04S)
Pulse Output
Switch Period
Operation Current
Operation Voltage
Input
Ambient Temprature
Display
Dimensions
Equipment Protection Class
Box Protection Class
Box Material
Installation
Wire Thickness(for terminal block)
Weight
Installation Category
:
: 0.05 - 5.5 A~
1-120 A ~ (for CT-25)
: 0...215 M(W,VAr,VA)
: 999999999.999 kWh,kVArh
: CAT III
: 1±1digit [(%10-%110) xFull Scale]
: 0.1 ... 4000.0
: 1 ... 2000
: 40.000
: 1-60 min. (programmable)
: MODBUS RTU (RS 485)
: Optically Isolated, programmable
: 2400-38400 bps
: 1-247
: No , odd, Even, 8 Data Bits, 2 Stop Bits
: NPN Transistor
Min. 100 msec pulse perriod
80 msec pulse width
: Max. 50 mA
: 5.....24 V DC, max. 30 VDC
: 12...48 V DC
: -5°C; +50°C
: Red LED Display
: PR-19,PR-16, PK-26
: Double Insulation-Class II ( )
: IP 40
: Non-flammable
: Panel Mounted (PR-16, PR-19)
Rail Mounted (PK-26)
: 2.5 mm
2
: 0.45 kg (PR-19, PK-26)
0.8 kg (PR-16)
: Class III
18
121
138.4
143
Type PR 16
34.5
58mm
79.3mm
70mm
10.8
30.1
7.6
9.5
26.5
21.5
53.0
58.0
10.0
60.6
106.0
Type PK-26
96mm
Type PR 19 (96x96)
31 DEVICE CAN BE CONNECTED AT SAME LINE
MAX. 1200 mt.
RS485/RS232
CONVERTER
B
A
GND
PC
TR B A GND
...
EPR-04S -31
TR B A GND TR B A GND
9 PIN CONNEKTOR
EPR-04S -2 EPR-04S -1
U P T O 2 4 7 D E V I C E C A N B E C O N N E C T E D AT S A M E L I N E
B Y U S I N G R E P E AT E R .
MAX. 1200 mt.
MAX. 1200 mt.
TRB A GND
...
EPR-04S-247 REPEATER
RS485/RS232
CONVERTER
B
A
GND
PC
EPR-04S-31
...
CONNECTOR (DB9)
EPR-04S-1 EPR-04S-2
POWERMETER
EPR-04/04S
EPR-04/04S has MODBUS RTU communication protocol which is optical isolated.
All measured parameters can be transfer to the computer.Transformer ratios and parameters of communication can be set. Saved demand and energy values can erase
SET
SET
SET
SET
SET
SET
SET
SET
ESC
SET
Press SET button. (rS-485 Adr ES is displayed.
Press SET button again. (first digit of third number blinks).
By using UP-DOWN buttons set the desired value.
Press SET button for saving the new value.
ESC Press ESC button one by one until (SAU SEt yES) appears
SET
Press SET button when (SAU SEt yES) appears at the display. (When SAU SEt yES appears at the display,If you Press ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings.
Adjustment of Baud Rate (Available only for EPM-04S)
Baud Rate can be chosen as a value of 2400,4800,9600,19200, 38400 bps
SET
Press SET button 3 sec. (trA Fo menu is displayed)
By using UP-DOWN buttons find rS- 485.
Press SET button. (rS-485 Adr ES is displayed)
By using UP-DOWN buttons find rS- 485 bAU dE menu.
Press SET button (Baud value blinks).
By using UP-DOWN buttons select the desired value.
ESC Press ESC button one by one until (SAU SEt yES) appears
SET
Press SET button when (SAU SEt yES) appears at the display.
(When SAU SEt yES appears at the display,If you Press ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings.
Adjustment of Parity (Available only for EPM-04S) :
Parity can be adjust as no, odd or EVEn.
SET Press SET button 3 sec. (trA Fo menu is displayed).
SET
By using UP-DOWN buttons find rS- 485 bulunuz
Press SET button. (rS-485 Adr ES is displayed)
By using UP-DOWN buttons find rS- 485 PAr ýty menu.
Press SET button to set parity value.
By using UP-DOWN buttons, select parity value as no, odd or EVEn.
Press SET button for saving the new value. (Data is entered but is not activated yet. For activating the new data please follow the below steps)
Press ESC button one by one until (SAU SEt yES) appears
Press SET button when (SAU SEt yES) appears at the display.
(When SAU SEt yES appears at the display,If you Press ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings.
4
IMPORTANT NOTE: In order communicate with ENTES software Baudrate has to be 38400 bps and parity has to be no
MODBUS RTU PROTOCOL (Available only for EPM-04S)
Standart MODBUS RTU message is shown below.
T ADDRESS
8 BIT
FUNCTION
8 BIT
DATA
NX8BIT CRCH
CRCL T
The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247 ) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave.
CRC is a error check method by using MODBUS RTU protocol and consists of
2 bytes.
Available Modbus Function:
03H READ HOLD REGISTERS
06H PRESET SINGLE REGISTER
10H PRESET MULTIPLE REGISTERS
Read Hold (03) function is used for reading measured values and set value. If any request of reading of a register, excepted mentioned in register table, device will send an error message. For example to read phase1 Active power by sending a message to the device.
01 03 00 00 00 02 XX XX
01 Device address
03 Function
00 MSB address
14 LSB address
00 Register number MSB
02 Register number LSB
XX CRC MSB
XX CRC LSB
Preset Single Register (06) function is used for writting the setting values, erasing the energy counter or resetting the min., max., demand values.
Current transformers ratio can be set 0-2000, voltage transformer ratio can be set
1-40000. Min., Max. and Demand values can be only clear. If sent value is outside of this range device responds with an error message.
i.e. Setting CT as 100;
01 06 80 02 00 64 XX XX
01 Device address
06 Function
80 MSB address
02 LSB address
00 Data MSB
64 Data LSB
XX CRC MSB
XX CRC LSB
Preset Multiple Register(10H) is used to set more then one register at same time.
i.e. Setting CT as 100, Ut as 20.0;
01 10 80 00 00 02 04 00 C8 00 64 XX XX
01 Device Address
10 Function
80 MSB address
00 LSB address
00 Register number MSB
02 Register number LSB
04 Byte count
00 Data MSB
C8 Data LSB
00 Data MSB
64 Data LSB
XX CRC MSB
XX CRC LSB
Specifications for data cable ;
- 24 AWG or thicker
- Less than 100 ohm/ km
- Nominal characteristic impedance at 100 kHz of 100 ohms
- Less than 60 pF/m mutual capacitance (between two wires in a pair)
- Less than 120 pF/m mutual pair capacitance ( the capacitance between one wire and all others connected to earth).
- Twisted Pair
Digital Inputs (Available only for EPM-04S)
Digital input are sent in 16 bit hexadecimal format as below:
44H
1
DIN1 DIN2 input 2
U U U U U U U U U U U U U
0
U
High Byte Low Byte
If 12-48 V DC is applied to ln1 (Input 1), 15th bit of DIN register is set as 1.
Otherwise, 15th bit is set as 0.
If 12-48 V DC is applied to ln2 (Input 2), 14th bit of DIN register is set as 1.
Otherwise, 14th bit is set as 0.
The Parameters are sent in 32bit Hexadecimal format. For Example, 230.0V voltage will be sent as 000008FCH. Cosj values shall be divided to 1000.
0.980 Cosj will be sent as 000003D4H. Energy values are sent in 64 bytes.
1234567890123456789 Wh = AB 54 A9 8C EB 1F 0A 02 Wh
ERROR CODES
(Available only for EPM-04S)
Slave device (EPR-04/04S) sends error message when receive any missing query.
Error codes are given below.
01 Invalid Function: If any message except given above is used, then 01 error messages will be sent.
02 Invalid Register: Error 02 will be send when a reading of a register is requested, except the registers which mentioned in table.
03 Invalid data: If any different value is been set for dedicated Transformer values and nonzero for demand value, then error message 03 will be sent.
TEHOMITTARI
EPR-04/04S
TEKNISET TIEDOT
Toimintajännite (Un) : Katso laitteen arvokilvestä
Toimintajännitteen taajuus : 50 tai 60 Hz
Laitteen oma tehonkulutus : < 4 VA
Mittaustulon tehonkulutus : < 1 VA
VIn : 10 - 300 V AC 59/60 Hz (L-N)
: 10 - 500 V AC 50/60 Hz (L-L)
IIn : 0,05 - 5,5 A~
: 1 - 120 A~ (CT-25:lle)
Mittausalue : 0...215 M(W, VAr, VA)
: 999999999,999 kWh, kVArh
Mittausluokka : CAT III
Tarkkuus : 1 +/- 1 numero [(10% -119 %) x max-arvo]
Jännitemuuntajan suhde : 0,1...4000,0
Virtamuuntajan suhde : 1...2000
Maksimi Ctr x Vtr : 40.000
Koontijakson pituus : 1 - 60 min (ohjelmoitavissa)
Sarjaliitäntä (EPR-04S) : MODBUS RTU (RS 485)
optoeristetty, ohjelmoitavissa
Siirtonopeus (EPR-04S) : 2400 - 38400 bps
Osoitteita (EPR-04S) : 1 - 247
Pariteetti (EPR-04S) : Ei, pariton, parillinen, 8 databittiä, 2 stop-bittiä
Pulssilähtö : NPN-transistori
Kytkentäaika : Pulssin pituus min 100 ms
: Pulssin leveys 80 ms
Toimintavirta : Max 50 mA
Toimintajännite : 5...24 V DC, max 30 V Dc
Tulot : 12...47 V DC
Ympäristön lämpötila : -5...+50 o C
Näyttö : Punainen LED-näyttö
Mitat : PR-19, PR-16 ja PK-26
Suojausluokka : Kaksoiseristys, luokka II
Kotelointiluokka : IP 40
Kotelon materiaali : Palamaton
Asennus : Paneeliin (PR-16 ja PR-19)
kiskoon (PK-26)
Johtimien paksuus (liittimissä) : 2,5 mm 2
Paino : 0,45 kg (PR-19 ja PK-26)
0,8 kg (PR-16)
Asennusluokka : Luokka III
MITAT
121
138.4
143
96mm
Type PR 16
Type PR 19 (96x96)
18
34.5
58mm
79.3mm
70mm
10.8
EPR-04S:N KYTKENTÄ TIETOKONEESEEN
SAMAAN LINJAAN VOIDAAN KYTKEÄ 31 LAITETTA
MAX. 1200 mt.
KATSO MANUAALI:
26.5
30.1
60.6
106.0
Type PK-26
ENTES MITTAUSJÄRJESTELMÄN
KYTKENTÄKAAVIOT
21.5
53.0
58.0
7.6
9.5
10.0
TURVAOHJEITA
Näiden ohjeiden noudattamatta jättäminen saattaa aiheuttaa hengenvaaran.
- Katkaise virta, ennen kuin suoritat laitteelle asennus- tai huoltotoimenpiteitä.
- Älä irrota etulevyä, kun laite on kytkettynä verkkoon.
- Puhdista laite kuivalla liinalla. Älä käytä liuottimia tai muuta vastaavaa.
- Tarkasta, että liittimet on kytketty oikein.
- Huollon saa suorittaa vain pätevä asiantuntija.
- Valmistaja ei vastaa mahdollisista seurauksista, jotka aiheutuvat laitteen käytöstä.
- Asennus vain paneeliin.
5
L1
L2
L3
N
TEHOMITTARI
EPR-04/04S
PR 19 -tyypin kytkentäkaavio
k
K L l k
K L l k
K
Max: 30 VDC
_
+
1
I
L1
2 3
I
L2
4 5
Current Measuring Input
I
L3
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
Pul 1 Pul 2
6
RS485
19 20 21 22
GND B A TR
Jännitteenmittaustulot
7
L1
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
L l
3 vaihetta ja nolla
L1
L2
L3 k
K L l k
K L l k
K
1
I
L1
2 3
I
L2
4 5
Current Measuring Input
I
L3
6
Max: 30 VDC
_
+
Pul C
Pul 1
( 12-48V DC )
InC In1 In2
Pul 2
RS485
13 14 15 16 17 18 19 20 21 22
GND B A TR
Jännitteenmittaustulot
7
L1
8
L2
9
L3 N
10 11
Auxiliary
Supply
12
L l
L1
N
3 vaihetta, ei nollaa
PK 26 -tyypin kytkentäkaavio
Max: 30 VDC
+_
Gnd A B
RS-485
TR
Auxiliary
Supply
~
Jännitteenmittaustulot Virranmittaustulot
L1 L2 L3 N
I
L1
I
L2
I
L3
1A
L1
L2
L3
N
3 vaihetta ja nolla
* Vain EPR-04S
*Available only for EPM-04S k
K L l k
K l
L k
K l
L
L1
N
L1
L2
L3
L1
L2
L3 k
K L l k
K L l
1
I
L1
2 3
I
L2
4 5
I
L3
6
Max: 30 VDC
_
+
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Jännitteenmittaustulot
7
L1
Voltage Measuring Input
8
L2 L3
9
N
10
Auxiliary
syöttö
11 12
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä k
K L l k
K L l
L1
N
Max: 30 VDC
_
+
1
I
L1
2 3
I
L2
4 5
Current Measuring Input
I
L3
6
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Jännitteenmittaustulot
7
L1
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
syöttö
11 12
L1
N
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
+_
Max: 30 VDC
6
Gnd A B
RS-485
TR
Auxiliary
Supply
~
Jännitteenmittaustulot Virranmittaustulot
L1 L2 L3 N
I
L1
I
L2
I
L3
1A N
L1
L2 k
K L l k
K
L3
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
L l
POWERMETER
EPR-04/04S
SET
SET
By using UP-DOWN buttons, select E-1 or E-2.
Press SET button.
k
L1
M k
L2
M
By using UP-DOWN buttons, select on, ý-1,
ý-2 or E-1 / E-2.
Cosj W VAr VA kWh kWArh k
S
M EPR-04S
POWERMETER
Press SET button, (Data is entered but is not activated yet.
For activating the new data please follow the below steps).
k
L3
M
L1 L2 L3
Esc
S e t
ESC
Press ESC button one by one until SAUE SEt yES is displayed.
SET
Press SET button. When SAUE SEt yES is displayed, if you press
ESC button or choose no option instead of yES option by using
UP-DOWN buttons, new data will be cancelled and previous value will be activated.
Monitoring and Erasing of minimum and maximum values:
In this menu, values of min., max., demand or energymeters are erased.
It saves the instantaneously measured min. and max. values of
EPR-04/04S into its memory. Please kindly look at to the section of
FUNCTIONS OF BUTTONS for min. and max. values.
Note: Informations which are saved to the memory are not affected from the electric interruptions.
In the rES Et dE E-1 or E-2 menu; when you choose and quit from all menus, if you confirm the changes,min. and max. values of all parameters or values of energymeters are erased at the same time. For erasing
the values of min., max., E-1 and E-2; In the measurement position.
SET
Press SET button 3 seconds
(trA Fo menu is displayed)
By using the UP-DOWN buttons find the rES Et menu.
SET
SET
Press SET button.(rES Et HL menu is displayed)
By using the UP-DOWN buttons, other parameters can be selected.
If you want to delete the value, choose yEs, if not choose no.
Press SET button, (Data is entered but is not activated yet.
For activating the new data please follow the below steps).
ESC
Press ESC button one by one until SAUE SEt yES is displayed.
SET
Press SET button. When SAUE SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
User password Setup:
In this menu user password is defined and activated.
You must define and activate a 4 digit user password for preventing device settings from the illegal usage.
There are 2 sub menu under the Pýn menu.
Changing of User Password:
This menu is used for changing the user password .
Note: Factory default value for user password is 0000
For changing the user password;In the measurement mode,
L1 L2 L3
Energy Counter (Eng Cnt) Menu
EPR-04/04S has 2 energy counters : Energy counter 1 (E-1),
Energy counter 2 (E-2).
E-1 has 4 parameters : on : Activate E-1 for energy counting without depending on any parameter.
ý-1 : Activate E-1, when digital input 1 is on (=1).
ý-2 : Activate E-1, when digital input 2 is on (=1).
E-2: Do not count to E-1, when E-2 is active.
E-2 can be set in the same way...
Note: If E-1 is selected on E-2 and if E-2 is selected on E-1, then it counts to both energy counters.
SET
Press SET button for 3 seconds
(trA Fo menu is displayed)
By using UP-DOWN buttons, find Eng Cnt menu.
SET
Press SET button
(Eng Cnt E-1 menu is displayed)
3
SET
SET
Press SET button 3 seconds
(trA Fo menu is displayed)
Bu using UP-DOWN buttons find Pýn menu.
L1 k
L2 k
Press SET button (Pýn ACt ýUA tE menu is displayed.)
L3 k
By using the UP-DOWN buttons find Pýn CHA ngE menu.
S k
Cosj kWh kVArh
ESC
SET
SET
By using UP-DOWN-SET button enter the old password
L1 L2 L3
SET
By using UP-DOWN-SET button enter the new password k
L1
M
Cosj W VAr VA kWh kWArh k
L2
M
L3
M k
Esc k
S
M EPR-04S
POWERMETER
S e t
SET
By using UP-DOWN-SET button reenter the new password.
SET
Press SET button, Pýn CHA ngE is displayed. Data is entered but is not activated yet. For activating the new data please follow the below steps).
ESC
Press ESC button one by one until (SAU SEt yES) appears at the display.
SET
Press SET button when (SAU SEt yES) appears at the display. (When
SAU SEt yES appears at the display,If you Press ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings.
Activating the user password:
This menu is used for activating the user password.
After the user password is activated for entering to the menus;
while the instant values are observed,user password is required if the button is Pressed for 3 sn. If the user password is entered wrong device does not latch
Note: Factory default value of user password is 0000
For activating the user password; In the measurement mode,
SET
SET
SET
SET
SET
SET
SET
ESC
SET
L1 L2 L3
Press SET button 3 sn.
(trA Fo menu is displayed)
L1 k
Cosj
By using UP-DOWN buttons find Pýn menu.
L2 k
Press SET button (Pýn ACt ýUA tE menu is displayed.)
L3 k
Press SET button (The number which is the last digit of second display blinks)
S k kWh kVArh
ESC
SET
By using UP-DOWN buttons enter to the fourth digit of desired value.
Press SET button (First number of the third display blinks). If you did not enter the fourth digit correct, you can reentry by pressing
L1 the ESC button
By using UP-DOWN buttons, enter to the third
Cosj k
L1
M
W VAr VA kWh kWArh k
L2
M k
L3
M
L2
Esc
L3 digit of desired value.
Press SET button
(The number which is in the middle of the third
M k
S
EPR-04S
POWERMETER display blinks. If you did not enter the third digit correct, you can reentry by pressing the ESC button)
By using UP-DOWN buttons, enter to the second digit of desired value
Press SET button (The number which is the last digit of third display blinks).
If you did not enter the second digit correct, you can reentry by pressing the ESC button)
By using UP-DOWN buttons, enter to the last digit of desired value.
L1
L2
L3
S k k k k
L1 L2 L3
Cosj kWh kVArh
EPR- 04S
S e t
POWERMETER
ESC
Press SET button, Pýn ACt oF is displayed (Data is entered but
SET is not activated yet. For activating the new data please follow the below steps)
Press ESC button one by one until (SAU SEt yES) appears at the display..
Press SET button when (SAU SEt yES) appears at the display. (When
SAU SEt yES appears at the display,If you Press ESC button or choose
no option instead of yES option, new data will be cancelled and previous value will be activated.
POWERMETER
EPR-04/04S
SET
SET
By using UP-DOWN buttons enter to the fourth digit of desired value.
L1 L2 L3
Press SET button (First number of the third display blinks). If you did not enter the fourth digit correct, you can reentry by pressing the
ESC button.
By using UP-DOWN buttons, enter to the third digit of desired value.
L1 k
L2 k
L3 k
Cosj kWh kVArh
Press SET button (The number which is in the middle of the third display blinks. If you did not enter the third digit correct, you can reentry by pressing the ESC button.
S k ESC
SET
By using UP-DOWN buttons, enter to the second digit of desired value
SET
SET
ESC
Press SET button (The number which is the last digit of third display blinks). If you did not enter the second digit correct, you can reentry by pressing the ESC button
L1 L2 k
L1
M k
L2
M k
L3
M
L3
By using UP-DOWN buttons, enter to the last digit of desired value.
Cosj W VAr VA kWh kWArh
Esc
M k
S
EPR-04S
POWERMETER
Press SET button, trA Fo Utr is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps.
S e t
Press ESC button one by one until (SAU SEt yES) appears at the display.
SET
Press SET button whenl (SAU SEt yES) appears at the display. (When
SAU SEt yES appears at the display,If you Press ESC button or choose no option instead of yES option, new data will be cancelled and previous value will be activated.
Reactive Energy Calculation Method Setting
Three different methods exist for reactive energy calculation in EPR-04/04S. Brief informations about these methods are explained in below table.
Related values which must be entered in the menu are also indicated in the table in order to select reactive power calculation method for mechanical and digital energymeters.
0
2
4
1
3
5
Description
90° rotation of voltage vector and multiply with current
It is the most preferred reactive power calculation methode.
S V n
.I
n
.sin(j n
)
S 2 -P 2 to 19 th harmonics. This calculation methode is mostly preferred for network analysers.
Power Triangle Methode : According to this methode;
Q = S 2 -P 2
(Q : Reactive power, S : Active power, P : Apparent power)
Demand Time Setup:
In this menu,demand time is adjusted .
L1 L2 L3
SET
Press SET button 3 seconds
(trA Fo menu is displayed)
L1 k
POWERMETER
EPR- 04S
Cosj
SET
By using UP-DOWN buttons find the dt menu.
Press SET button (The number which is in the middle of the third display blinks.)
L2 k
L3 k
By using UP-DOWN buttons, enter to the second digit of desired value
S k kWh kVArh
ESC
SET
SET
SET
Press SET button (The number which is the last digit of third display blinks). If you did not enter the second digit correct, you can reentry by pressing the ESC button.
L1 L2 L3
By using UP-DOWN buttons, enter to the last digit of desired value.
Cosj k
L1
M
W VAr VA kWh kWArh k
L2
M
L3
M k
Esc
Press set button, de tý is displayed. (Data is entered k
S
M but is not activated yet.
For activating the new data please follow the below steps).
S e t
ESC
Press ESC button one by one until (SAU SEt yES) appears at the display.
SET
Press SET button when (SAU SEt yES) appears at the display.
(When SAU SEt yES appears at the display,If you Press ESC button or choose no option instead of yES option, you quit from adjustment menu without saving new settings and device continues to work with previous settings.
Pulse Menu
In this menu, three parameters can be selected : PUL SE rAt, PUL SE o-1, PUL SE o-2
PUL SE rAt ýo : Pulse ratio can be set as :
1, 10, 100 (wh/VArh/VA); 1, 10, 100 (kwh/kVArh/kVA); 1 Mwh/MVArh/MVA.
PUL SE o-1 : If this parameter is selected, in every increase in output 1, one pulse is counted. Output 1 parameter can be set as :
ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive
/ Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive).
PUL SE o-2 : If this parameter is selected, in every increase in output 2, one pulse is counted. Output 2 parameter can be set as :
ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive
/ Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive).
SET Press SET button for 3 seconds (trA Fo menu is displayed)
SET
SET
Press SET button for 3 seconds (trA Fo menu is displayed)
Press SET button (trAFo Ctr menu is displayed)
SET
By using UP-DOWN buttons, find CAL CLt menu.
Press SET button (Calculation value 1 blinks)
SET
SET
By using UP-DOWN buttons, select energy calculation method.
SET
ESC
SET
Press set button, CAL CLt is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps.
L1 L2 L3 k
L1
M k
L2
M
L3
M k
Press ESC button one by one until SAUE SEt yES is displayed.
Cosj W VAr VA kWh kWArh k
S
M EPR-04S
POWERMETER
Esc
S e t
Press SET button. When SAUE SEt yES is displayed, if you press
ESC button or choose no option instead of yES option by using
UP-DOWN buttons, new data will be cancelled and previous value will be activated.
2
SET
ESC
SET
By using UP-DOWN buttons, find PULSE menu.
Press SET button (PUL SE rAt menu is displayed)
By using UP-DOWN buttons, select PUL SE rAt, PUL SE o-1 or
PUL SE o-2.
Press SET button.
L1
By using UP-DOWN buttons, type the required value for selected parameter.
Cosj k
L1
M
W VAr VA kWh kWArh k
L2
M
Press SET button,
(Data is entered
S
M k
EPR-04S
POWERMETER but is not activated yet.
For activating the new data please follow the below steps).
k
L3
M
Press ESC button one by one until SAU E SEt yES is displayed.
L2
Esc
S e t
Press SET button. When SAU E SEt yES is displayed, if you press
ESC button or choose no option instead of yES option by using
UP-DOWN buttons, new data will be cancelled and previous value will be activated.
L3
POWERMETER
EPR-04/04S
+_
Max: 30 VDC
L1
L2
L3
Gnd A B
RS-485
TR
1A
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
~ L1 L2 L3 N
I
L1
I
L2
I
L3
N k
K L l k
K L l k
K l
L
Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
L1
L2
L3
N
Voltage
Measuring Input
Current
Measuring Input
L1 L2
1 2
L3 N
3 4
I
L1
I
L2
I
L3
5 6 7 8 9 10 k
K l
L k
K l
L k
K L l
Auxiliary
Supply
Un
1A
13 14
Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
L1
L2
L3
L1
Voltage
Measuring Input
L2 L3 N
Current
Measuring Input
I
L1
I
L2
I
L3
1 2 3 4 5 6 7 8 9 10 k
K L l k
K l
L k
K l
L
1A
Auxiliary
Supply
Un
13 14
N
+_
Max: 30 VDC
L1
L2
L3
Gnd A B
RS-485
TR
1A
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
~ L1 L2 L3 N
I
L1
I
L2
I
L3
N k
K L l k
K L l
Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
Voltage
Measuring Input
L1 L2
1 2
L3 N
3 4
Current
Measuring Input
I
L1
I
L2
I
L3
5 6 7 8 9 10
Auxiliary
Supply
L1
L2 k
K L l k
K L l
L3
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
3 Phase without neutral current input with
Aron wiring configuration Max: 30 VDC
1A
13 14
N
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
7
Voltage
Measuring Input
Current
Measuring Input
L1 L2
1 2
L3 N
3 4
I
L1
I
L2
I
L3
5 6 7 8 9 10
Auxiliary
Supply
1A
L1
L2
L3 k
K L l k
K l
L
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
Aron wiring configuration
13 14
N
TEHOMITTARI
EPR-04/04S
L3 PHASE MIN. APPARENT POWER TOTAL MIN. IMPORT ACTIVE POWER TOTAL MIN. EXPORT ACTIVE POWER
TOTAL MIN. IMPORT REACTIVE POWER TOTAL MIN. EXPORT REACTIVE POWER int int int int
0.1 0.1 0.1 0.1 0.1 0.1
VA Watt Watt Var Var VA
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W
L1 PHASE MAX. ACTIVE POWER L2 PHASE MAX. ACTIVE POWER L3 PHASE MAX. ACTIVE POWER L1 PHASE MAX. REACTIVE POWER L2 PHASE MAX. REACTIVE POWER L3 PHASE MAX. REACTIVE POWER L1 PHASE MAX. APPARENT POWER L2 PHASE MAX. APPARENT POWER L3 PHASE MAX. APPARENT POWER
TOTAL MAX. IMPORT ACTIVE POWER TOTAL MAX. EXPORT ACTIVE POWER TOTAL MAX. IMPORT REACTIVE POWER TOTAL MAX. EXPORT REACTIVE POWER
VOLTAGE TRANSFORMER RATIO CURRENT TRANSFORMER RATIO
DEMAND TIME PULSE RATIO
PULSE OUTPUT 1 PARAMETER SETTING PULSE OUTPUT 2 PARAMETER SETTING
ENERGY COUNTER 1 SELECTION ENERGY COUNTER 2 SELECTION int int int int int int unsigned int unsigned int unsigned int int int int int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Watt Watt Watt Var Var Var VA VA VA Watt Watt Var Var VA
L1 PHASE IMPORT MAX. DEMAND ACTIVE POWER L1 PHASE EXPORT MAX. DEMAND ACTIVE POWER L2 PHASE IMPORT MAX. DEMAND ACTIVE POWER L2 PHASE EXPORT MAX. DEMAND ACTIVE POWER L3 PHASE IMPORT MAX. DEMAND ACTIVE POWER L3 PHASE EXPORT MAX. DEMAND ACTIVE POWER L1 PHASE IMPORT MAX. DEMAND REACTIVE POWER L1 PHASE EXPORT MAX. DEMAND REACTIVE POWER L2 PHASE IMPORT MAX. DEMAND REACTIVE POWER L2 PHASE EXPORT MAX. DEMAND REACTIVE POWER L3 PHASE IMPORT MAX. DEMAND REACTIVE POWER L3 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L1 PHASE MAX. DEMAND APPARENT POWER L2 PHASE MAX. DEMAND APPARENT POWER L3 PHASE MAX. DEMAND APPARENT POWER TOTAL IMPORT MAX. DEMAND ACTIVE POWER TOTAL EXPORT MAX. DEMAND ACTIVE POWER
TOTAL IMPORT MAX. DEMAND REACTIVE POWER TOTAL EXPORT MAX. DEMAND REACTIVE POWER int int int int int int int int int int int int unsigned int unsigned int unsigned int int int int int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Watt Watt Watt Watt Watt Watt Var Var Var Var Var Var VA VA VA Watt Watt Var Var VA short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int
0.1 1 - 1 - - - - - - - - - -
- - - - - - - - - - - -
BAUD RATE 1-6 : 1: 38400 bps 2: 19200 bps 3: 9600 bps 4: 4800 bps 5: 2400 bps PARITY 0-2 : 0: No 1: Odd 2: Even PASSWORD ENABLE 0-1 : 0: Disable 1: Enable
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
0-40000 0-2000
0-1 1-60 0-6 0-5 0-5 0-3 0-3
0 - 247 1 - 5 0 - 2 0-9999 ENERGY COUNTER 1 SELECTION 0-3 : 0 : On (EC -Energy counter- will count on all conditions) 1: EC will count when Digital Input1 is 1 (1=active) 2: EC will count when Digital Input2 is 1 (1=active) 3: Inverse Energy Counter 2 (It will count when EC2 is not counted) ENERGY COUNTER 2 SELECTION 0-3 : 0 : On (EC -Energy counter- will count on all conditions) 1: EC will count when Digital Input1 is 1 (1=active) 2: EC will count when Digital Input2 is 1 (1=active) 3: Inverse Energy Counter 1 (It will count when EC1 is not counted)
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
TGVA_MIN_M AGGIM_MIN_M AGGEX_MIN_M RGGIM_MIN_M RGGEX_MIN_M VAG_MIN_M RGAG_MAX_M SGAG_MAX_M TGAG_MAX_M RGRG_MAX_M SGRG_MAX_M TGRG_MAX_M RGVA_MAX_M SGVA_MAX_M TGVA_MAX_M AGGIM_MAX_M AGGEX_MAX_M RGGIM_MAX_M RGGEX_MAX_M VAG_MAX_M
RGAG_IM_DEM_M RGAG_EX_DEM_M SGAG_IM_DEM_M SGAG_EX_DEM_M TGAG_IM_DEM_M TGAG_EX_DEM_M RGRG_IM_DEM_M RGRG_EX_DEM_M SGRG_IM_DEM_M SGRG_EX_DEM_M TGRG_IM_DEM_M TGRG_EX_DEM_M
RGVA_DEM_M SGVA_DEM_M TGVA_DEM_M AGGIM_DEM_M AGGEX_DEM_M RGGIM_DEM_M RGGEX_DEM_M VAG_DEM_M
0098 009A 009C 009E 00A0 00A2 00A4 00A6 00A8 00AA 00AC 00AE 00B0 00B2 00B4 00B6 00B8 00BA 00BC 00BE 00C0 00C2 00C4 00C6 00C8 00CA 00CC 00CE 00D0 00D2 00D4 00D6 00D8 00DA 00DC 00DE 00E0 00E2 00E4 00E6 00E8 00EA 00EC 00EE 00F0 00F2 00F4 00F6 00F8 00FA 00FC 00FE
152 154 156 158 160 162 164 166 168 170 172 174 176 178 180 182 184 186 188 190 192 194 196 198 200 202 204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 246 248 250 252 254
VT_RATIO_H CT_RATIO_H
CALCULATION_H DEMAND_TIME_H PULSE_RATE_H PULSE_OUT1_H PULSE_OUT2_H
ENG_CNT1_H ENG_CNT2_H
ADRESS_H BAUD_H PARITY_H
8000 8002 8004 8006 8008 800A 800C 800E 8010 8012 8014 8016 8018 801A
32768 32770 32772 32774 32776 32778 32780 32782 32784 32786 32788 32790 32792 32794
PULSE OUTPUT 1-2 PARAMETER SETTING 0-5 : 0: Active 1: Active Import 2: Active Export 3: Reactive 4: Reactive Import 5: Reactive Export
L1 PHASE ACTIVE POWER L2 PHASE ACTIVE POWER L3 PHASE ACTIVE POWER L1 PHASE REACTIVE POWER L2 PHASE REACTIVE POWER L3 PHASE REACTIVE POWER L1 PHASE APPARENT POWER L2 PHASE APPARENT POWER L3 PHASE APPARENT POWER
TOTAL IMPORT ACTIVE POWER TOTAL EXPORT ACTIVE POWER
TOTAL INDUCTIVE REACTIVE POWER TOTAL CAPACITIVE REACTIVE POWER
TOTAL APPARENT POWER AVERAGE INDUCTIVE COS int int int int int int unsigned int unsigned int unsigned int int int int int int int int int int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.01
Watt Watt Watt Var Var Var VA VA VA
- - -
Watt Watt Var Var VA
- - Hz long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int
- 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
- Wh Wh Wh Wh
VArh VArh VArh VArh Wh Wh Wh Wh VArh VArh VArh VArh
L1 PHASE MIN. ACTIVE POWER L2 PHASE MIN. ACTIVE POWER L3 PHASE MIN. ACTIVE POWER L1 PHASE MIN. REACTIVE POWER L2 PHASE MIN. REACTIVE POWER L3 PHASE MIN. REACTIVE POWER L1 PHASE MIN. APPARENT POWER L2 PHASE MIN. APPARENT POWER int int int int int int unsigned int unsigned int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Watt Watt Watt Var Var Var VA VA
(-1000 -1000) (-1000 -1000) (-1000 -1000) (-1000 -1000) (-1000 -1000) (4000 -7000)
(0 -18000)xCTxVT (0 -18000)xCTxVT (0 -18000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R R R R R R R R R R R R R R R R R R R R
0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
(0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W R/W R/W
RGAG_M SGAG_M TGAG_M RGRG_M SGRG_M TGRG_M RGVA_M SGVA_M TGVA_M RGCOS_M SGCOS_M TGCOS_M AGGIM_M AGGEX_M RGGIM_M RGGEX_M VAG_M COSIM_M COSEX_M FREQ_M
RGAG_MIN_M SGAG_MIN_M TGAG_MIN_M RGRG_MIN_M SGRG_MIN_M TGRG_MIN_M RGVA_MIN_M SGVA_MIN_M
ACTIVE_IM_HM_1 ACTIVE_IM_LM_1 ACTIVE_EX_HM_1 ACTIVE_EX_LM_1
REACTIVE_IM_HM_1 REACTIVE_IM_LM_1 REACTIVE_EX_HM_1 REACTIVE_EX_LM_1
ACTIVE_IM_HM_2 ACTIVE_IM_LM_2 ACTIVE_EX_HM_2 ACTIVE_EX_LM_2
REACTIVE_IM_HM_2 REACTIVE_IM_LM_2 REACTIVE_EX_HM_2 REACTIVE_EX_LM_2
0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0038 003A 003C 003E 0040 0042 0044 0046 0048 004A 004C 004E 0050 0052 0054 0056 0058 005A 005C 005E 0060 0062 0064 0066 0068 006A 006C 006E 0070 0072 0074 0076 0078 007A 007C 007E 0080 0082 0084 0086 0088 008A 008C 008E 0090 0092 0094 0096
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150
8
POWERMETER
EPR-04/04S
EPR-04/04S DIGITAL POWERMETER
EPR-04/04S is a 3-phase digital powermeter and energymeter which measures:
-Active Power (W)
-Reactive Power (VAr)
-Apparent Power (VA)
-Active Energy (kWh)
-Reactive Energy (kVArh)
-Cosj
These values are scrolled between by the set button ( ) First 3 displays show
L1, L2 and L3 phase values and the 4th display show total value of each selected measured value (W, VAr,VA,kWh or kVArh).
EPR-04/04S also measures Maximum Demand, Demand, maximum and minimum values of power. EPR-04/04S has MODBUS serial interface.
When :
1. W led lights: Active Power
2. VAr led lights: Reactive Power
3. VA led lights: Apparent Power
4. kWh led lights:
a-) A-I :Imported Active Energy
b-) A-E : Exported Active Energy
5. KVArh led lights:
a-) r-L :Reactive-Inducitive Energy
b-) r-C :Reactive-Capacitive Energy
6. Cosj led lights :Cosj of the network
is measured.
Operating Principle:
EPR-04/04S displays the energy and power values by multiplying voltage and current ratios by values read from input. So, the displayed values are the real values of system.
Digital Inputs
EPR-04/04S has 2 digital inputs which are used to monitor the status of electrical contacts. Digital input has 2 functions :
- Enabling remote control of the data received through the digital input terminal
(battery, thermostat, circuit breaker, pumps status)
- Controling energy counters and determining which energy counter will be active.
Energy Pulse Outputs
EPR-04/04S has 2 Energy Pulse Outputs; Pul1, Pul2.
Pul1 (Reactive Energy Pulse Output): A 400msec. pulse output is given, if measured energymeter value increases 1 KVArh. Pul1 is used for Reactive Inductive energy values.
Pul2 (Active Energy Pulse Output): A 400msec. pulse output is given, if measured energy meter value increases 1KWh. Pul2 is used for both (Active Import) and
(Active Export) energy values. Min. pulse period is 1.6 sec.
Demand and Maximum Demand
Demand is average of power for the demand time. Demand time can be changed between 1-60 minutes.
Maximum demand is the max. value of the average power values measured during demand time. If the new average value exceeds the maximum demand value, the new demand value is recorded as maximum demand.
Monitoring of Min.,Max. and Demand Values:
Min., Max. and demand values are defined for Active Power (W),reactive power
(VAr), apparent power (VA), total active power(W), total reactive power (VAr) and total apparent power(VA).
If measured instant value is smaller than min. value which was stored before, it is stored as new min. value. If measured instant value is greater than max. value which was stored before, it is stored as new max. value.
Demand value is the average value of the measured values in demand time. If the smallest value of the measured values (for example 15 minute) in demand time is greater than the demand value which was stored before, it is stored as new demand value.
If one of defined parameters is displayed when deman button is pressed , min.,max or demand values are displayed. When an undefined parameter is displayed if demand button is pressed, instant value is continued to display.
For example when power factor is displayed instant values are continued to display because min., max. and demand values are undefined.
H-L-M LEDs
H-L-M LEDs are dedicated to displaying the min., max. and demand values according to selected parameters.
H: Maximum Value, L: Minimum Value, M: Demand Value
Calculation Methods for Active / Reactive Power Values
If the led on the most left side blinks it represents that active powers / reactive powers direction is negative.
There are two methods for calculating total active and total reactive powers :
1) Active / Reactive power can be calculated by summing import and export values and displaying as a single value.
2) Active / Reactive power can be calculated according to direction as import / export.
Note :
1) The dot at the most right digit of the fourth display represents that displayed value is export active power value. Vice versa, displayed value is import active power value.
2) The dot at the most right digit of the fourth display represents that displayed value is capacitive reactive power value. Vice versa, displayed value is inductive reactive power value.
3) The displayed parameter does not change if power is off after 20 seconds of stand-by.
Phase Monitoring LEDs
L1 L2 L3
Phase
Monitoring
Display
Kilo LED
L1 k
Mega LED L2 k
L3 k
Cosj
POWERMETER
EPR- 04S kWh kVArh Up
Esc
Total (S)
Monitoring
Display
S k ESC
SET
Set
Down
1
FUNCTIONS OF BUTTONS
When W led lights,it shows max.power values which are measured instantaneously and it shows total max demand values. Also it is used for moving upwards in the menu.
When W led lights,it shows min.power values which are measured instantaneously and it shows total demand values. Also it is used for moving downwards in the menu.
SET
ESC
It is used for passing between parameters such as W, Var, VA, KWh,
KVArh, cosj. When it is pressed for 3 second, adjustment mode is entered. In the adjustment mode it is used for saving parameters and moving to the sub menu.
In the adjustment mode, it is used for entering to the upper menu or it is used for quiting from the adjustment mode without saving the values.
Current Transformer Ratio Setup
In this menu, current transformer ratio is adjusted.
Note: If the current transformer is not used between the system and
EPR-04/04S, current transformer ratio is entered as 1.
Example: If a current transformer which has a ratio of 250/5A is used between the system and EPR-04/04S; Current transformer ratio is entered as = 250/5
= 50.
SET
SET
Press SET button 3 seconds
(trA Fo menu is displayed)
Press SET button (trA Fo Ctr is displayed, the number which is the last digit of second display blinks)
By using UP-DOWN buttons enter to the fourth digit of desired value.
L1 k
L2 k
L3 k
L1 L2 L3
Cosj kWh kVArh
SET
SET
SET
Press SET button (First number of the third display blinks). If you did not
enter the fourth digit correct, you can reentry by pressing the ESC button.
S k
ESC
SET
By using UP-DOWN buttons, enter to the third digit of desired value.
Press SET button (The number which is in the middle of the third display blinks. If you did not enter the third digit correct, you can reentry by pressing the ESC button.
L1
By using UP-DOWN buttons, enter to the second digit of k
L1
M k
L2
M
L3
M k
L2 L3 desired value
Cosj W VAr VA kWh kWArh
Esc
Press SET button (The number which is the last digit of third k
S
M EPR-04S
POWERMETER
S e t display blinks). If you did not enter the second digit correct,you can reentry by pressing the ESC button
By using UP-DOWN buttons, enter to the last digit of desired value.
SET
Press SET button, trA Fo Ctr is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps).
ESC
SET
Press ESC button one by one until (SAU SEt yES) appears at the display.
Press SET button when (SAU SEt yES) appears at the display. (When
SAU SEt yES appears at the display,If you Press ESC button or choose
no option instead of yES option, new data will be cancelled and previous value will be activated.
Voltage Transformer Ratio Setup
SET
SET
SET
In this menu, voltage transformer ratio is adjusted.
Note: If the voltage transformer is not used between the system and EPR-
04/04S, voltage transformer ratio is entered as 1.
Example: If a voltage transformer which has a ratio of 34.5KV/100V is used between the system and EPR-04/04S; Voltage transformer ratio is entered as
= 345
= 34500/100
Press SET button 3 seconds (trA Fo menu is displayed)
Press SET button (trA Fo Ctr menu is displayed)
By using UP-DOWN buttons find the trA Fo Utr menu.
Press SET button (The number which is the last digit of second display blinks)