MPR-53 53S Network Analyzer User Manual
The MPR-53 53S is a network analyzer that measures all electrical network parameters. It has 5 display screens that can show values for over 50 parameters at the same time.
The MPR-53 53S utilises the Modbus serial communication protocol. The device features two digital inputs for monitoring electrical contacts. These inputs can be used to remotely control data from a battery, thermostat, automatic fuse, or pump. They can also be used to control energy meters and select which one is measuring.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
NETWORK ANALYSER
MPR-53/53S
L3 PHASE MIN. APPARENT POWER TOTAL MIN. IMPORT ACTIVE POWER TOTAL MIN. EXPORT ACTIVE POWER
TOTAL MIN. IMPORT REACTIVE POWER TOTAL MIN. EXPORT REACTIVE POWER
L1 PHASE MAX. VOLTAGE L2 PHASE MAX. VOLTAGE L3 PHASE MAX. VOLTAGE
L1-L2 PHASE-PHASE MAX. VOLTAGE L2-L3 PHASE-PHASE MAX. VOLTAGE L3-L1 PHASE-PHASE MAX. VOLTAGE
L1 PHASE MAX. CURRENT L2 PHASE MAX. CURRENT L3 PHASE MAX. CURRENT
L1 PHASE MAX. ACTIVE POWER L2 PHASE MAX. ACTIVE POWER L3 PHASE MAX. ACTIVE POWER L1 PHASE MAX. REACTIVE POWER L2 PHASE MAX. REACTIVE POWER L3 PHASE MAX. REACTIVE POWER L1 PHASE MAX. APPARENT POWER L2 PHASE MAX. APPARENT POWER L3 PHASE MAX. APPARENT POWER
TOTAL MAX. IMPORT ACTIVE POWER TOTAL MAX. EXPORT ACTIVE POWER TOTAL MAX. IMPORT REACTIVE POWER TOTAL MAX. EXPORT REACTIVE POWER L1 PHASE MAX. CURRENT DEMAND L2 PHASE MAX. CURRENT DEMAND L3 PHASE MAX. CURRENT DEMAND
L1 PHASE IMPORT MAX. DEMAND ACTIVE POWER L1 PHASE EXPORT MAX. DEMAND ACTIVE POWER L2 PHASE IMPORT MAX. DEMAND ACTIVE POWER L2 PHASE EXPORT MAX. DEMAND ACTIVE POWER L3 PHASE IMPORT MAX. DEMAND ACTIVE POWER L3 PHASE EXPORT MAX. DEMAND ACTIVE POWER L1 PHASE IMPORT MAX. DEMAND REACTIVE POWER L1 PHASE EXPORT MAX. DEMAND REACTIVE POWER L2 PHASE IMPORT MAX. DEMAND REACTIVE POWER L2 PHASE EXPORT MAX. DEMAND REACTIVE POWER L3 PHASE IMPORT MAX. DEMAND REACTIVE POWER L3 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L1 PHASE MAX. DEMAND APPARENT POWER L2 PHASE MAX. DEMAND APPARENT POWER L3 PHASE MAX. DEMAND APPARENT POWER TOTAL IMPORT MAX. DEMAND ACTIVE POWER TOTAL EXPORT MAX. DEMAND ACTIVE POWER
TOTAL IMPORT MAX. DEMAND REACTIVE POWER TOTAL EXPORT MAX. DEMAND REACTIVE POWER int int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int unsigned int unsigned int unsigned int unsigned int int int int int int int int int int int int int unsigned int unsigned int unsigned int int int int int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
VA Watt Watt Var Var VA Volt Volt Volt Volt Volt Volt
Amper Amper Amper Watt Watt Watt
Var Var Var VA VA VA Watt Watt Var Var VA
Amper Amper Amper Watt Watt Watt Watt Watt Watt
Var Var Var Var Var Var VA VA VA Watt Watt Var Var VA
VOLTAGE TRANSFORMER RATIO CURRENT TRANSFORMER RATIO
DEMAND TIME PULSE RATIO
PULSE OUTPUT 1 PARAMETER SETTING PULSE OUTPUT 2 PARAMETER SETTING
ENERGY COUNTER 1 SELECTION ENERGY COUNTER 2 SELECTION short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int
0.1 1 - 1 - - - - - - - - - -
- - - - - - - - - - - -
BAUD RATE 1-6 : 1: 38400 bps 2: 19200 bps 3: 9600 bps 4: 4800 bps 5: 2400 bps PARITY 0-2 : 0: No 1: Odd 2: Even PASSWORD ENABLE 0-1 : 0: Disable 1: Enable
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0-3000)xUT (0-3000)xUT (0-3000)xUT (0-5000)xUT (0-5000)xUT (0-5000)xUT (0-6000)xCT (0-6000)xCT (0-6000)xCT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0-6000)xCT (0-6000)xCT (0-6000)xCT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
0-40000 0-2000
0-1 1-60 0-6 0-5 0-5 0-3 0-3
0 - 247 1 - 5 0 - 2 0-9999
ENERGY COUNTER 1 SELECTION 0-3 : 0 : On (EC -Energy counter- will count on all conditions) 1: EC will count when Digital Input1 is 1 (1=active) 2: EC will count when Digital Input2 is 1 (1=active) 3: Inverse Energy Counter 2 (It will count when EC2 is not counted) ENERGY COUNTER 2 SELECTION 0-3 : 0 : On (EC -Energy counter- will count on all conditions) 1: EC will count when Digital Input1 is 1 (1=active) 2: EC will count when Digital Input2 is 1 (1=active) 3: Inverse Energy Counter 1 (It will count when EC1 is not counted)
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
TGVA_MIN_M AGGIM_MIN_M AGGEX_MIN_M RGGIM_MIN_M RGGEX_MIN_M VAG_MIN_M RMAX_GER_M SMAX_GER_M TMAX_GER_M L1MAX_GER_M L2MAX_GER_M L3MAX_GER_M RMAX_AKIM_M SMAX_AKIM_M TMAX_AKIM_M RGAG_MAX_M SGAG_MAX_M TGAG_MAX_M RGRG_MAX_M SGRG_MAX_M TGRG_MAX_M RGVA_MAX_M SGVA_MAX_M TGVA_MAX_M AGGIM_MAX_M AGGEX_MAX_M RGGIM_MAX_M RGGEX_MAX_M VAG_MAX_M RDEM_AKIM_M SDEM_AKIM_M TDEM_AKIM_M
RGAG_IM_DEM_M RGAG_EX_DEM_M SGAG_IM_DEM_M SGAG_EX_DEM_M TGAG_IM_DEM_M TGAG_EX_DEM_M RGRG_IM_DEM_M RGRG_EX_DEM_M SGRG_IM_DEM_M SGRG_EX_DEM_M TGRG_IM_DEM_M TGRG_EX_DEM_M
RGVA_DEM_M SGVA_DEM_M TGVA_DEM_M AGGIM_DEM_M AGGEX_DEM_M RGGIM_DEM_M RGGEX_DEM_M VAG_DEM_M
0098 009A 009C 009E 00A0 00A2 00A4 00A6 00A8 00AA 00AC 00AE 00B0 00B2 00B4 00B6 00B8 00BA 00BC 00BE 00C0 00C2 00C4 00C6 00C8 00CA 00CC 00CE 00D0 00D2 00D4 00D6 00D8 00DA 00DC 00DE 00E0 00E2 00E4 00E6 00E8 00EA 00EC 00EE 00F0 00F2 00F4 00F6 00F8 00FA 00FC 00FE
152 154 156 158 160 162 164 166 168 170 172 174 176 178 180 182 184 186 188 190 192 194 196 198 200 202 204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 246 248 250 252 254
VT_RATIO_H CT_RATIO_H
CALCULATION_H DEMAND_TIME_H PULSE_RATE_H PULSE_OUT1_H PULSE_OUT2_H
ENG_CNT1_H ENG_CNT2_H
ADRESS_H BAUD_H PARITY_H
8000 8002 8004 8006 8008 800A 800C 800E 8010 8012 8014 8016 8018 801A
32768 32770 32772 32774 32776 32778 32780 32782 32784 32786 32788 32790 32792 32794
PULSE OUTPUT 1-2 PARAMETER SETTING 0-5 : 0: Active 1: Active Import 2: Active Export 3: Reactive 4: Reactive Import 5: Reactive Export
L1 PHASE VOLTAGE L2 PHASE VOLTAGE L3 PHASE VOLTAGE L1 PHASE CURRENT L2 PHASE CURRENT L3 PHASE CURRENT
L1-L2 PHASE-PHASE VOLTAGE L2-L3 PHASE-PHASE VOLTAGE L3-L1 PHASE-PHASE VOLTAGE
L1 PHASE ACTIVE POWER L2 PHASE ACTIVE POWER L3 PHASE ACTIVE POWER L1 PHASE REACTIVE POWER L2 PHASE REACTIVE POWER L3 PHASE REACTIVE POWER L1 PHASE APPARENT POWER L2 PHASE APPARENT POWER L3 PHASE APPARENT POWER
TOTAL IMPORT ACTIVE POWER TOTAL EXPORT ACTIVE POWER
TOTAL INDUCTIVE REACTIVE POWER TOTAL CAPACITIVE REACTIVE POWER
TOTAL APPARENT POWER AVERAGE INDUCTIVE COS
L1 PHASE VOLTAGE ANGLE L2 PHASE VOLTAGE ANGLE L3 PHASE VOLTAGE ANGLE L1 PHASE CURRENT ANGLE L2 PHASE CURRENT ANGLE L3 PHASE CURRENT ANGLE
L1 PHASE VOLTAGE THD L2 PHASE VOLTAGE THD L3 PHASE VOLTAGE THD L1 PHASE CURRENT THD L2 PHASE CURRENT THD L3 PHASE CURRENT THD DIGITAL INPUT STATUS IMPORT ACTIVE ENERGY-1 L1 PHASE MIN. VOLTAGE L2 PHASE MIN. VOLTAGE L3 PHASE MIN. VOLTAGE
L1-L2 PHASE-PHASE MIN. VOLTAGE L2-L3 PHASE-PHASE MIN. VOLTAGE L3-L1 PHASE-PHASE MIN. VOLTAGE
L1 PHASE MIN. CURRENT L2 PHASE MIN. CURRENT L3 PHASE MIN. CURRENT
L1 PHASE MIN. ACTIVE POWER L2 PHASE MIN. ACTIVE POWER L3 PHASE MIN. ACTIVE POWER L1 PHASE MIN. REACTIVE POWER L2 PHASE MIN. REACTIVE POWER L3 PHASE MIN. REACTIVE POWER L1 PHASE MIN. APPARENT POWER L2 PHASE MIN. APPARENT POWER unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int
0.1 0.1 0.1 0.001 0.001 0.001
Volt Volt Volt
Amper Amper Amper unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int int int int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.01
1 1 1 1 1 1 0.1 0.1 0.1 0.1 0.1 0.1 - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.1 0.1 0.1 0.1 0.1 0.1
0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Volt Volt Volt Watt Watt Watt Var Var Var VA VA VA
- - -
Watt Watt Var Var VA
- - Hz
Degre Degre Degre Degre Degre Degre
% % % % % % - Wh Wh Wh Wh VArh VArh VArh VArh Wh Wh Wh Wh VArh VArh VArh VArh Volt Volt Volt Volt Volt Volt
Amper Amper Amper Watt Watt Watt
Var Var Var VA VA
(0-3000)xUT (0-3000)xUT (0-3000)xUT (0-6000)xCT (0-6000)xCT (0-6000)xCT
R R R R R R
0-360 0-360 0-360 0-360 0-360 0-360 0-999 0-999 0-999 0-999 0-999 0-999
(0-5000)xUT (0-5000)xUT (0-5000)xUT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 -18000)xCTxVT (0 -18000)xCTxVT (0 -18000)xCTxVT
(-1000 -1000) (-1000 -1000) (-1000 -1000)
(0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT
(-1000 -1000) (-1000 -1000) (4000 -7000)
0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF
(0-3000)xUT (0-3000)xUT (0-3000)xUT (0-3000)xUT (0-3000)xUT (0-3000)xUT (0-6000)xCT (0-6000)xCT (0-6000)xCT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT
R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
R_GER_M S_GER_M T_GER_M R_AKIM_M S_AKIM_M T_AKIM_M L1_GER_M L2_GER_M L3_GER_M RGAG_M SGAG_M TGAG_M RGRG_M SGRG_M TGRG_M RGVA_M SGVA_M TGVA_M RGCOS_M SGCOS_M TGCOS_M AGGIM_M AGGEX_M RGGIM_M RGGEX_M
VAG_M COSIM_M COSEX_M FREQ_M
RGERILIM_ACI_M SGERILIM_ACI_M TGERILIM_ACI_M
RAKIM_ACI_M SAKIM_ACI_M TAKIM_ACI_M RGGER_THD_M SGGER_THD_M TGGER_THD_M RGAK_THD_M SGAK_THD_M TGAK_THD_M
ACTIVE_IM_HM_1 ACTIVE_IM_LM_1 ACTIVE_EX_HM_1 ACTIVE_EX_LM_1
REACTIVE_IM_HM_1 REACTIVE_IM_LM_1 REACTIVE_EX_HM_1 REACTIVE_EX_LM_1
ACTIVE_IM_HM_2 ACTIVE_IM_LM_2 ACTIVE_EX_HM_2 ACTIVE_EX_LM_2
REACTIVE_IM_HM_2 REACTIVE_IM_LM_2 REACTIVE_EX_HM_2 REACTIVE_EX_LM_2
RMIN_GER_M SMIN_GER_M TMIN_GER_M L1MIN_GER_M L2MIN_GER_M L3MIN_GER_M RMIN_AKIM_M SMIN_AKIM_M TMIN_AKIM_M RGAG_MIN_M SGAG_MIN_M TGAG_MIN_M RGRG_MIN_M SGRG_MIN_M TGRG_MIN_M RGVA_MIN_M SGVA_MIN_M
0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0038 003A 003C 003E 0040 0042 0044 0046 0048 004A 004C 004E 0050 0052 0054 0056 0058 005A 005C 005E 0060 0062 0064 0066 0068 006A 006C 006E 0070 0072 0074 0076 0078 007A 007C 007E 0080 0082 0084 0086 0088 008A 008C 008E 0090 0092 0094 0096
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150
8
A3918/Rev.1
VERKKOANALYSAATTORI
MPR-53/53S
Yleistä
MPR-53/53A mittaa sähköverkon kaikki parametrit. Lukemia varten on
5 näyttöruutua, joissa voi näkyä yli 50 parametrin arvo samanaikaisesti.
MPR-53/53S käyttää Modbus-sarjaliikenneprotokollaa.
Vaiheiden näyttöruudut
Ylös
Alas
Maksimin LED
SET
Minimin LED
∑
W-,
∑
VA- ja HZ-
∑
VAr- ja Cos ϕ
- Takaisin Poistuminen
näytöt näytöt
MPR-53/53S:n käyttö
Parametrejä selataan vaiheiden ruuduissa pystysuuntaisilla nuolipainikkeilla
(VLN, VLL, A, W, VAr, VA, Cos ϕ
, kWh, kVArh, THD). Kokonaispätöteho
(∑
W), kokonaisnäennäisteho (
∑
VA) ja taajuus (Hz) valitaan -painikkeella.
Kokonaisloisteho (
∑
Var) ja cos ϕ
valitaan Esc-painikkeella.
Digitaaliset tulot
Laitteessa on 2 digitaalista tuloliitäntää, joita käytetään sähkökoskettimien tilan valvontaan. Digitaalisilla tuloilla on 2 toimintoa:
- Mahdollistaa digitaalisesta tuloliitännästä saadun datan kauko-ohjaus
(paristo, termostaatti, automaattisulake, pumpun tila)
- Ohjata energiamittareita ja määrätä kumpi niistä mittaa.
Mitattavat parametrit:
VLN (vaihejännite) VA (näennäisteho) THD (harm. kokonaissärö)
VLL (jänn. vaihe-vaihe) Cos ϕ Hz (taajuus)
A (vaihevirta) AI (kWh) (kulutettu pätöenergia) ∑ W (kokonaispätöteho)
W (pätöteho) AE (kWh) (tuotettu pätöenergia) ∑ VAr (kokonaisloisteho)
VAr (loisteho) rl (kVArh) (kututettu loisenergia) ∑ VA (kokonaisnäennäisteho)
rE (kVArh) (tuotettu loisenergia)
PAINIKKEIDEN TOIMINNOT
Valvontatilassa parametrien selaaminen (VLN, VLL, A, W, VAr,
VA, Cos
ϕ
, kWh, kVArh, THD). Ohjelmointitilassa arvon suuren-
taminen sekä siirtyminen eteenpäin.
Valvontatilassa parametrien selaaminen (VLN, VLL, A, W, VAr,
VA, Cos
ϕ
, kWh, kVArh, THD). Ohjelmointitilassa arvon pienen-
täminen sekä siirtyminen taaksepäin.
Valvontatilassa selaaminen: minimi-, maksimi-, keski- ja tosi-
aikaiset arvot. Ohjelmointitila avataan painamalla painiketta
3 sekuntia. Ohjelmointitilassa muutosten tallentaminen ja
siirtyminen alavalikkoon.
(Back) Valvontatilassa selaaminen:
∑
W,
∑
VA ja Hz.
Ohjelmointitilassa siirtyminen taaksepäin.
(ESC) Valvontatilassa selaaminen:
∑
VAr ja Cos
ϕ.
Ohjelmointitilassa paluu ylempään valikkoon tai ohjelmoinnin
lopetus tallentamatta mitään.
Jos salasana on käytössä ja SET-painiketta painetaan
3 sekuntia, on annettava salasana, ennen kuin valikko avautuu.
Virtamuuntajan muuntosuhteen asetus
Tässä kohdassa asetetaan virtamuuntajan muuntosuhde
väliltä 1 - 2000.
Energiapulssilähdöt
Laitteessa on 2 energiamittaria ja ensimmäinen niistä lähettää pulssilähtötietoa. Toinen ei tee sitä.
Pul1 (loisenergian pulssilähtö): Pulssi lähtee, kun mitattu energia kasvaa pulssiin tarvittavan määrän (1 VArh…1 MVArh).
Pul1 ottaa huomioon ainoastaan kulutetun loisenergian
.
Pul2 (pätöenergian pulssilähtö) Pulssi lähtee, kun mitattu energia kasvaa pulssiin tarvittavan määrän (1 wh...1 Mwh). Pul 2 ottaa huomioon sekä kulutetun että tuotetun pätöenergiaan. Pienin pulssiaika on 1,6 sekuntia.
Huom. Jos MPR-53/53S:n ja sähköjärjestelmän välillä ei
käytetä virtamuuntajaa, muuntosuhteeksi asetetaan 1.
Esimerkki: Jos käytössä on virtamuuntaja, jonka muunto-
suhde on 250/5 A, muuntosuhteeksi asetetaan 50 (250/5).
Paina SET-painiketta 3 sekuntia (näytössä näkyy trA Fo)
Paina SET-painiketta
Minimi-, maksimi- ja keskiarvojen näyttö:
Minimi- ja maksimiarvot ovat saatavissa parametreille VLN, VLL, A, W, VAr,
VA,
∑
W,
∑
VAr ja
∑
VA. Keskiarvot ovat saatavissa parametreille A, W, VAr, VA,
∑
W,
∑
VA,
∑
VAr. Jos mittausarvo on pienempi kuin aiemmin tallentunut minimiarvo, uusi arvo tallentuu minimiksi. Jos taas arvo ylittää aiemman maksimiarvon, se tallentuu uudeksi maksimiksi. Keskiarvo saadaan koontijakson (esim. 15 min) ajalta. Jos uusi keskiarvo ylittää edellisen, uusi tallentuu keskiarvoksi.
Kun SET-painiketta painetaan ja näytössä on jokin parametri, jota tämä toiminto koskee, ruudussa näkyy minimi-, maksimi- tai keskiarvo. Jos ruudussa on jokin muu parametri, tosiaikaisten arvojen näyttö jatkuu. Tällainen muu parametri on esim. tehokerroin. Sille ei ole minimi-, maksimi- ja keskiarvojen näyttöä.
Harmonisen kokonaissärön näyttö
Kun VLN- ja THD-ledit palavat, ruudussa on jännitteen harmoninen kokonais-
.
särö. Virran harmoninen kokonaissärö näkyy silloin, kun A- ja THD-ledit palavat
H-, L- ja M-ledit
Nämä ledit tarkoittavat valittujen parametrien minimi-, maksimi- ja keskiarvoja:
H = maksimiarvo
L = minimiarvo
M = keskiarvo
Pätö- ja loistehojen laskenta
Jos äärimmäisenä vasemmalla oleva led vilkkuu, pätö- ja loistehojen suunta on negatiivinen. Pätö- ja loistehoille on kaksi laskentatapaa:
1) MPR-53/53S laskee kulutetut ja tuotetut arvot yhteen ja näyttää niiden summan.
2) Kulutetut ja tuotetut arvot näkyvät erikseen.
Huom.
1) Piste neljännessä näyttöruudussa äärimmäisenä oikealla olevan numeron kohdalla tarkoittaa, että lukema on tuotettu pätöteho.
Jos pistettä ei ole, lukema on kulutettu pätöteho.
2) Piste viidennessä näyttöruudussa äärimmäisenä oikealla olevan numeron kohdalla tarkoittaa, että lukema on kapasitiivinen loisteho.
Jos pistettä ei ole, loisteho on induktiivinen.
3) Jos parametri on ollut näytössä 20 sekuntia, kun virta katkeaa, sama parametri on näytössä edelleen, kun virta taas kytkeytyy.
1
(näytössä näkyy trA Fo Ctr)
Paina SET-painiketta (ensimmäinen numeropaikka vilkkuu)
Aseta ensimmäinen numero nuolipainikkeilla
Paina SET-painiketta
(toinen numeropaikka vilkkuu)
Aseta toinen numero nuolipainikkeilla
Paina SET-painiketta.
(kolmas numero-
paikka vilkkuu)
Aseta kolmas numero
nuolipainikkeilla
Paina SET-painiketta (viimeinen numeropaikka vilkkuu)
Aseta viimeinen numero nuolipainikkeilla
Paina SET-painiketta. Näytössä näkyy trA Fo Ctr
Asetus on tehty, mutta ei vielä tallennettu.
Tallennus tapahtuu seuraavasti:
Etsi ESC-painikkeella näyttö SAU E SEt yES
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihto-
ehdon
no, uusi asetus ei tallennu, vaan entinen jää voimaan.
VERKKOANALYSAATTORI
MPR-53/53S
2
Jännitemuuntajan muuntosuhde
Tässä kohdassa asetetaan jännitemuuntajan muuntosuhde.
Asetusalue on 0,1 - 4000,0.
Huom! Jos jännitemuuntaja ei ole käytössä, muuntosuhteeksi pitää asettaa 1.
Esimerkki: Jos jännitemuuntajan muuntosuhde on
34,5 kV/100 V, suhteeksi pitää asettaa 345 (34500/100).
Paina SET-painiketta 3 sekuntia
(näytössä näkyy trA Fo)
Paina SET-painiketta
(näytössä näkyy trA Fo Ctr)
Etsi nuolipainikkeilla näyttöön trA Fo Utr
Paina SET-painiketta
(ensimäinen numeropaikka vilkkuu)
Aseta ensimmäinen numero nuolipainikkeilla
Paina SET-painiketta.
(Toinen numeropaikka vilkkuu)
Aseta toinen numero nuolipainikkeilla
Paina SET-painiketta (kolmas numeropaikka vilkkuu)
Aseta kolmas numero nuolipainikkeilla
Paina SET-painiketta (neljäs numeropaikka vilkkuu)
Aseta neljäs numero nuolipainikkeilla
Paina SET-painiketta (viimeinen numeropaikka vilkkuu)
Aseta viimeinen numero nuolipainikkeilla
Paina SET-painiketta. Näytössä näkyy trA Fo Utr
Asetus on tehty mutta ei vielä tallennettu.
Tallennus tapahtuu seuraavasti:
Etsi ESC-painikkeella näyttö SAU E SEt yES.
Paina SET-painiketta
Jos painat ESC-painiketta tai valitset nuolipainikkeilla no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Loisenergian laskentamenetelmän asetus
Loisenergian laskentatapoja on kolme. Ne esitetään alla
olevassa taulukossa.
Taulukosta näkyvät myös arvot, jotka pitää asettaa
mekaanisille ja digitaalisille energiamittareille.
Mechanical Energymeter Digital Energymeter
0 1
Reactive Energy
(Q)
Jännitevektori kiervoltage ve c tor and multiply with current
2 3
4 5
¥
S V n
.I
n
.sin(j n
)
S 2 -P 2
Selitys
Suosituin loistehon laskentamenetelmä
Vn-arvot x In-arvot 19.:een harmoniseen yliaaltoon asti. Tätä laskentaa suositellaan verkkoanalysaattoreille.
Tehokolmiomenetelmä: Sen mukaan
S 2 -P
S = pätöteho, P = näennäisteho
Paina SET-painiketta 3 sekuntia
(näytössä näkyy trA Fo)
Paina SET-painiketta
(näytössä näkyy trA Fo Ctr)
Etsi nuolipainikkeilla näyttöön CAL CUL Ati
Paina SET-painiketta
Valitse energian laskentamenetelmä nuolipainikkeilla
Paina SET-painiketta
Etsi ESC-painikkeella näyttö SAU E SEt yES
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Koontijakson asetus
Tässä valikossa asetetaan koontijakson pituus väliltä
1 - 60 minuuttia.
Paina SET-painiketta 3 sekuntia
(näytössä näkyy trA Fo)
Etsi nuolipainikkeilla näyttö dE ti
Paina SET-painiketta
(ensimmäinen numeropaikka vilkkuu)
Aseta ensimmäinen numero nuolipainikkeilla
Paina SET-painiketta (toinen numeropaikka vilkkuu)
Aseta toinen numero nuolipainikkeilla
Paina SET-painiketta, näytössä näkyy dE ti.
(Asetus on tehty, mutta ei vielä tallennettu. Tallennus tapahtuu seuraavasti:)
Etsi ESC-painikkeella näyttö SAU E SEt yES).
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Minimi-, maksimi- ja energia-arvojen valvonta ja nollaus
Tässä kohdassa poistetaan minimi- ja maksimiarvot sekä energiamittareiden lukemat. Heti tämän jälkeen tosiaikaiset arvot tallentuvat minimi- ja maksimiarvoiksi. Katso minimi- ja maksimiarvojen käsittelyä varten lukua PAINIKKEIDEN
TOIMINNOT. Huom! Sähkökatko ei vaikuta laitteen muistiin tallennettuihin parametreihin.
Kun näytössä on rES Et ja suljet kaikki valikot ja vahvistat muutokset, kaikkien parametrien minimi- ja maksimiarvot sekä energiamittareiden lukemat nollautuvat samanaikaisesti.
2
+_
Max: 30 VDC
L1
L2
L3
1A
Gnd A B
RS-485
TR
Auxiliary
Supply
Voltage Measuring Input Current Measuring Input
L1 L2 L3 N
I
L1
I
L2
I
L3
N k
K L l k
K L l k
K
3 Phase without neutral l
L
PR-16 Box Connection Diagram Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
Voltage
Measuring Input
L1 L2
1 2
L3 N
3 4
L1
L2
L3
N
3 Phase neutral
Current
Measuring Input
I
L1
I
L2
I
L3
5 6 7 8 9 10 k
K L l k
K l
L k
K l
L
Auxiliary
Supply
1A
Un
13 14
Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
+_
Max: 30 VDC
(12-48V DC)
- + - +
Gnd A B
RS-485
TR
Auxiliary
Supply
Un
Voltage Measuring Input Current Measuring Input
L1 L2 L3 N
I
L1
I
L2
I
L3
1A
N
L1
L2 k
K
L3
3 Phase without neutral current input with
Aron wiring configuration
Max: 30 VDC l
L
+_ k
K l
L
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
Voltage
Measuring Input
L1 L2
1 2
L3 N
3 4
I L1 I L2 I L3
5 6 7 8 9 10
L1
L2
L3 k
K L l k
K L l
3 Phase without neutral current input with
Aron wiring configuration
Max: 30 VDC
+_
Auxiliary
Supply
Un
13 14
1A N
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
Voltage
Measuring Input
L1 L2
1 2
L3 N
3 4
Current
Measuring Input
I
L1
I
L2
I
L3
5 6 7 8 9 10
L1
L2
L3 k
K L l k
K l
L k
K l
L
3 Phase without neutral
*Available only for MPR-53S
1A
Auxiliary
Supply
Un
13 14
N
MPR-53S COMPUTER CONNECTION
31 DEVICES CAN BE CONNECTED AT THE SAME LINE
MAX. 1200 mt.
RS485/RS232
CONVERTER
B
A
GND
TR B A GND
...
MPR-53S-31
TR B A GND
MPR-53S-2
TR B A GND
MPR-53S-1
9 PIN CONNECTOR
PC
Voltage
Measuring Input
L1 L2
1 2
L3 N
3 4
Current
Measuring Input
I L1 I L2 I L3
5 6 7 8 9 10
L1
L2
L3 k
K L l k
K l
L
3 Phase without neutral current input with
Aron wiring configuration
Auxiliary
Supply
Un
13 14
1A N
M A X . 2 4 7 D E V I C E S C A N B E C O N N E C T E D AT S A M E L I N E B Y U S I N G R E P E AT E R .
MAX. 1200 mt.
MAX. 1200 mt.
RS485/RS232
CONVERTER
B
A
GND
PC
TRB A GND
MPR-53S-247
...
REPEATER MPR-53S-31
...
MPR-53S-2 MPR-53S-1
CONNECTOR (DB9)
PR 19 Box Connection Diagram
L1
L2
L3
N k
K L l k
K L l k
K
Max: 30 VDC
_
+
1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
6
L1
7
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
Pul 1 Pul 2
RS485
19 20 21 22
GND B A TR
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
L l
L1
N
3 Phase neutral
L1
L2
L3 k
K L l k
K L l k
K
Max: 30 VDC
_
+
1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
6
7
L1
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
Pul 1 Pul 2
RS485
19 20 21 22
GND B A TR
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
L l
L1
N
3 Phase without neutral
PK 26 Box Connection Diagram
Max: 30 VDC
+_
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
~ L1 L2 L3 N
I
L1
I
L2
I
L3
1A
L1
L2
L3
N
3 Phase neutral
*Available only for MPR-53S k
K l
L k
K L l k
K l
L
L1
L2
L3 k
K L l k
K L l
Max: 30 VDC
_
+
1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
6
L1
7
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
Pul 1 Pul 2
RS485
19 20 21 22
GND B A TR
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
3 Phase without neutral current input with
Aron wiring configuration
L1
N
L1
L2
L3 k
K L l k
K L l
Max: 30 VDC
_
+
1
I
L1
2 3 4 5
I
L2
Current Measuring Input
I
L3
6
7
L1
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
Pul 1 Pul 2
RS485
19 20 21 22
GND B A TR
Voltage Measuring Input
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
L1
N
3 Phase without neutral current input with
Aron wiring configuration
+_
Max: 30 VDC
Gnd A B
RS-485
TR
Auxiliary
Supply Voltage Measuring Input Current Measuring Input
~ L1 L2 L3 N
I
L1
I
L2
I
L3
1A N
L1
L2
L3 k
K
3 Phase without neutral current input with
Aron wiring configuration
L l k
K l
L
VERKKOANALYSAATTORI
MPR-53/53S
Minimi- maksimi arvojen sekä energialukemien nollaus
Menettele seuraavasti, kun laite on mittaustilassa:
Paina SET-painiketta 3 sekuntia
(näytössä näkyy trA Fo)
Etsi nuolipainikkeilla näyttöön rES Et.
Paina SET-painiketta
Näytössä näkyy rESEt HL
Valitse poistettava parametri nuolipainikkeilla
Paina SET-painiketta
Jos haluat poistaa mittausarvon, valitse nuolipainikkeilla yES, muussa tapauksessa valitse no.
Paina SET-painiketta (näytössä näkyy rESEt).
Etsi ESC-painekkeella näyttöön SAU E SEt yES
Paina SET-painiketta 3 sekuntia
(näytössä näkyy trA Fo)
Etsi nuolipainikkeilla näyttö Eng Cnt
Paina SET-painiketta
(näyttöön tulee Eng Cnt E-1)
Valitse nuolipainikkeilla
E-1 tai E-2.
Paina SET-painiketta
Valitse nuolipainikkeilla on, i-1, i-2 tai
E-1 / E-2.
Paina SET-painiketta
Etsi ESC-painikkeella näyttö SAU E SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, lukemat eivät nollaudu.
Pulssivalikko
Pulssivalikossa voidaan tehdä seuraavat asetukset:
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Salasanan asetus
PUL SE rAt io, PUL SE o-1 ja PUL SE o-2.
PUL SE rAt io : Pulssisuhteeksi voidaan asettaa: 1, 10, 100
(W/VArh/VA); 1, 10, 100 (kWh/kVArh/kVA); 1 MWh/MVArh/MVA
PUL SE o-1 : Tässä parametrissä jokainen lisäys lähdössä 1 lasketaan yhdeksi pulssiksi. Lähdön 1 parametriksi voidaan valita:
Salasanan muuttaminen
Act (tuotettu/kulutettu), A-I (pätö kulutettu), A-E (pätö tuotettu), rEA
(induktiivinen/kapasitiivinen), r-L (lois induktiivinen), r-C (lois-kapasitiivinen).
PUL SE o-2 : Tässä parametrissä jokainen lisäys lähdössä 2 lasketaan yhdeksi pulssiksi. Lähdön 2 parametriksi voidaan valita:
Act (tuotettu/kulutettu), A-I (pätö kulutettu), A-E (pätö tuotettu), rEA
(induktiivinen/kapasitiivinen), r-L (lois induktiivinen), r-C (lois-kapasitiivinen).
Paina SET-painiketta 3 sekuntia (näytössä näkyy trA Fo)
Tässä kohdassa asetetaan salasana ja aktivoidaan se.
Salasanassa on 4 numeroa. Se suojaa laitteen asetuksia.
Tässä kohdassa vaihdetaan salasana.
Huom! Tehtaan asetus salasanaksi on 0000.
Salasana muutetaan seuraavalla tavalla:
Paina SET-painiketta 3 kertaa
(näytössä näkyy trA Fo)
Etsi nuolinäppäimillä näyttöön PULSE
Paina SET-painiketta (näytössä näkyy PULSE rAt io)
Valitse nuolipainikkeilla PUL SE rAtio, PUL SE o-1 tai
PUL SE o-2
Etsi nuolipainikkeilla näyttöön Pin.
Paina SET-painiketta
(näytössä näkyy Pin ACt IUA tE)
Etsi nuolipainikkeilla näyttöön Pin CHA ngE
Anna vanha salasana käyttäen nuolipainikkeita
Paina SET-painiketta.
Valitse parametri nuolipainikkeilla.
Paina SET-painiketta ja SET-painiketta
Anna uusi salasana käyttäen nuolipainikkeita ja SET-painiketta
Anna uusi salasana uudelleen käyttäen nuolipainikkeita ja SET-painiketta
Etsi ESC-painikkeella näyttö SAU E SEt yES
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihto-
Paina SET-painiketta. Näytössä näkyy Pin CHA ngE.
Asetus on tehty, mutta ei vielä tallennettu. Menettele seuraavasti.
ehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Energianmittausvalikko
Laitteessa on kaksi energiamittaria: E-1 ja E-2.
Mittarille E-1 on 4 parametriä:
On : E-1 mittaa energiaa muista asetuksista riippumatta.
i-1 : E-1 mittaa, kun digitaalinen tulo 1 on toiminnassa (=1).
i-2 : E-1 mittaa, kun digitaalinen tulo 2 on toiminnassa (= 1).
E-2 : E-1 ei mittaa silloin, kun E-2 mittaa
E-2-mittarille on samat asetukset
Huom! Jos E-1:lle valitaan asetus E-2 ja jos E-2:lle valitaan E-1,
Etsi ESC-painikkeella näyttö SAU E SEt yES
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi salasana ei tallennu, vaan entinen jää voimaan.
silloin kumpikin mittari mittaa.
3
VERKKOANALYSAATTORI
MPR-53/53S
Salasanan käyttöönotto
Tässä kohdassa salasana otetaan käyttöön.
Kun salasana on käytössä, se pitää antaa aina päästäkseen valikoihin tosiaikaisten mittausarvojen katselusta.
Huom! Tehtaalla asetettu oletussalasana on 0000.
Salasana otetaan käyttöön seuraavalla tavalla, kun laite on valvontatilassa:
Paina SET-painiketta 3 sekuntia. Näytössä näkyy trA Fo.
Etsi nuolipainikkeilla näyttö Pin.
Paina SET-painiketta. Näytössä näkyy PinACt IUA tE.
Paina SET-painiketta.
Ensimmäinen numeropaikka vilkkuu.
Aseta ensimmäinen numero nuolipainikkeilla.
Paina SET-painiketta.
Toinen numeropaikka vilkkuu.
Aseta toinen numero nuolipainikkeilla.
Paina SET-painiketta. Kolmas numeropaikka vilkkuu.
Aseta kolmas numero nuolipainikkeilla.
Paina SET-painiketta.
Viimeinen numeropaikka vilkkuu.
Aseta viimeinen numero nuolipainikkeilla.
Paina SET-painiketta. Ruudussa näkyy Pin ACt oF.
Asetus on tehty mutta ei vielä tallennettu. Menettele seuraavasti:
Etsi ESC-painikkeella näyttö SAU E SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, salasana ei tule käyttöön.
Sarjamuotoinen tiedonsiirto (vain MPR-53S)
Laite käyttää MODBUS RTU -protokollaa. Tiedonsiirtoportti on optoeristetty.
Kaikki mittaustulokset voidaan siirtää tietokoneeseen. PC-ohjelmassa
voidaan asettaa muuntosuhteet ja tiedonsiirtoparametrit sekä nollata
tallennetut minimi-, maksimi- ja keskiarvot sekä energialukemat.
Tiedonsiirtoparametrien asetukset
Laitteen osoitteen asetus (vain MPR-53S)
Paina SET-painiketta 3 sekuntia.
Etsi nuolipainikkeilla näyttö rS-485
Paina SET-painiketta. Ruudussa näkyy rS-485 Adr ES
Paina SET-painiketta. Ensimmäinen numeropaikka vilkkuu.
Aseta ensimmäinen numero nuolipainikkeilla.
4
Paina SET-painiketta. (Toinen numeropaikka vilkkuu)
Aseta toinen numero nuolipainikkeilla.
Paina SET-painiketta. (Viimeinen numeropaikka vilkkuu)
Aseta viimeinen numero nuolipainikkeilla.
Paina SET-painiketta. (Näytössä näkyy rS-485 Adr ES)
Etsi ESC-painikkeella näyttö SAU E SEt yES
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Tiedonsiirtonopeuden asetus (vain MPR-53S)
Asetusvaihtoehdot ovat 2400, 4800, 9600, 19200 ja 38400 b/s
Paina SET-painiketta 3 sekuntia
Etsi nuolipainikkeilla näyttö rS-485.
Paina SET-painiketta. Näytössä näkyy rS-485 Adr ES
Etsi nuolipainikkeilla näyttö rS-485 bAU d.
Paina SET-painiketta. Baudiarvo vilkkuu.
Aseta baudiarvo nuolipainikkeilla.
Paina SET-painiketta. Asetus on nyt tehty, mutta ei vielä tallennettu. Menettele seuraavasti:
Etsi ESC-painikkeella näyttö SAU E SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
Pariteetin asetus (vain MPR-53S)
Asetusvaihtoehdot ovat no, odd ja even (= ei, pariton ja parillinen)
Paina SET-painiketta 3 sekuntia.
Etsi nuolipainikkeilla näyttö rS-485.
Paina SET-painiketta. Näytössä näkyy rS-485 Adr ES.
Etsi nuolipainikkeilla näyttö rS-485 PAr ity
Paina SET-painiketta jotta pääset asettamaan pariteetin.
Valitse nuolipainikkeilla pariteetiksi no, odd tai even
(= ei, pariton tai parillinen)
Paina SET-painiketta. Näytössä näkyy rS-485 PAr.
Etsi ESC-painikkeella näyttö SAU E SEt yES.
Paina SET-painiketta.
Jos painat ESC-painiketta tai valitset nuolipainikkeilla vaihtoehdon no, uusi asetus ei tallennu, vaan entinen jää voimaan.
1
DIN1 input 1 input 2
DIN2 U U
High Byte
U U U U U U U U U
Low Byte
U U
0
U
TECHNICAL DATA
Operating Voltage (Un)
Operating frequency (f)
IIn
: Please look behind the device.
: 50/60 Hz
Auxiliary supply Power Consumption: < 4 VA
Measuring Input Power Consumption: < 1VA
VIn : 10-300 V AC 50/60 Hz. (L-N)
: 10-500 V AC 50/60 Hz. (L-L)
: 0.05 - 5.5 A~
1-120 A~ (for CT-25)
Measuring Range
Class
Voltage Transformer Ratio (Vtr)
Current Transformer Ratio (Ctr)
Max. Ctr x Vtr
Demand Time
Serial Interface (for MPR-53S)
Baud Rate (for MPR-53S)
Address (for MPR-53S)
Parity (for MPR-53S)
Pulse Output
Switch Period
Operation Current
Operation Voltage
Input
Ambient Temperature
Display
Dimensions
Equipment Protection Class
Box Protection Class
Box Material
Installation
: 10V...200 kV AC
: 0...215 M (W,VAr,VA)
: 99999999999.9 Wh,VArh
: 1% ± 1 digit [(10%-110%) xFull Scale]
: 0,1 ... 4000,0
: 1 ... 2000
: 40.000
: 1-60 min. (programmable)
: MODBUS RTU (RS 485)
Optically Isolated, programmable
: 2400-38400 bps
: 1-247
: No , Odd, Even, 8 Data bits, 2 Stop Bits
: NPN Transistor
: Min. 100 msec pulse perriod
80 msec pulse width
: Max. 50 mA
: 5.....24 V DC, max. 30 VDC
: 12...48 V AC / DC
: -5°C; +50°C
: Red LED Display
: PR-19, PR-16, PK-26
: Double Insulation-Class II ( )
: IP 40 (front panel)
: Non-flammable
: Panel Mounted (PR-16, PR-19)
Rail Mounted (PK-26)
2 Wire Thickness (for terminal block) : 2.5 mm
Weight
Installation Category
: 0.45 kg (
: Class III
PR-19, PK-26), 0.8 kg (PR-16)
Factory Settings
Trafo :
Ctr (Current Transformer Ratio) : 0020
Utr (Voltage Transformer Ratio) : 0001.0
CAL (Calculation Method) : 1
Pin :
0000 (Not Activated)
RS-485 :
Adr (Address) : 1
Bau (Baud Rate) : 9600
PAr (Parity) : no
Dimensions
10.8
30.1
7.6
9.5
Eng Cnt :
E-1 (Energy Counter 1) : on
E-2 (Energy Counter 2) : on
PULSE :
rAt (Ratio) : 1 o-1 (Output 1) : A-I o-2 (Output 2) : r-L
dEtý
(Delay Time) : 15
18
60.6
106.0
26.5
21.5
53.0
58.0
10.0
Type PK 26
79.3mm
70mm
121
138.4
143
Type PR 16
34.5
58mm
Type PR 19
96mm
PRECAUTIONS FOR INSTALLATION AND SAFE USE
Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment..
- When the device is connected to the network, do not remove the front panel.
- Do not try to clean the device with solvent or the like.Only clean with dry cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
- Only for rack panel mounting.
NETWORK ANALYSER
MPR-53/53S
For activating the user password, In the monitoring mode :
4
VERKKOANALYSAATTORI
MPR-53/53S
MODBUS RTU -PROTOKOLLA (vain MPR-53S)
MODBUS RTU -vakioviesti on seuraava:
OSOITE TOIMINTO DATA
8 BIT 8 BIT NX8BIT
T on ajanjakso, jona dataa ei saa kulkea siirtoväylässä, jotta kytketyt laitteet tunnistaisivat viestin päättyneen ja toisen alkavan. Tämän ajan tulee olla vähintään 3,5 merkin pituinen valitulla siirtonopeudella.
Osoitealue (1-247) tarkoittaa kytkettyjen laitteiden osoitteita. Datakenttä sisältää datan, jonka päälaite lähettää alalaitteille tai päinvastoin. CRC on MODBU RTU:n virheidentarkastusmenetelmä ja se sisältää 2 tavua.
Saatavana on seuraavat Modbus-toiminnot:
03H READ HOLD REGISTERS
06H PRESET SINGLE REGISTER
10H PRESET MULTIPLE REGISTERS
Read Hold (03) -toimintoa käytetään mittaus- ja asetusarvojen lukemiseen.
Laite lähettää virheilmoituksen, jos pyydetään lukemaan jokin muu kuin rekisteriluettelossa esiintyvä rekisteri.
Esimerkki: luetaan vaiheen 1 jännite lähettämällä viesti laitteeseen.
01 03 00 00 00 02 XX XX
01 Laitteen osoite
03 Toiminto
00 MSB-osoite
XX CRC MSB
XX CRC LSB
Preset Single Register (06) -toimintoa käytetään kirjoittamaan asetusarvoja, nollaamaan energiamittareita sekä minimi-, maksimi- ja keskiarvoja. Virtamuuntajan muuntosuhteeksi voidaan asettaa 0-2000, jännitemuuntajan suhteeksi 1-40000. Minimi-, maksimi- ja keskiarvot voidaan ainoastaan nollata. Jos lähetetty arvo ei sisälly mainittuihin alueisiin, laite vastaa virheilmoituksella. Esim. virtamuuntajan suhteeksi asetetaan 100:
01 06 80 02 00 64 XX XX
80 MSB-osoite
02 LSB-osoite
XX CRC LSB
Preset Multiple Register (10H) -toimintoa käytetään asettamaan useampi kuin yksi rekisteri kerrallaan. Esim. virtamuuntajan suhteeksi asetetaan
100 ja jännitemuuntajan suhteeksi 20,0:
01 10 80 00 00 02 04 00 C8 00 64 XX XX
01 Laitteen osoite
10 Toiminto
80 MSB-osoite
00 LSB-osoite
00 Rekisterinumero MSB
02 Rekisterinumero LSB
04 Tavujen lukumäärä
00 Data MSB
C8 Data LSB
00 Data MSB
64 Data LDB
XX CRC MSB
XX CRC LSB
Digitaaliset tulot (vain MPR-53S)
:
tulo 2
44H
1
DIN1
U U U U U U U U U U U U U U
Korkea tavu Matala tavu
tulo 1 U = määrittelemätön
0
Digitaaliset tulot lähetetään 16 bitin heksadesimaalimuodossa kuten yllä on esitetty.
Jos tulossa 1 on tasajännite 12-48 V, tulorekisterin 15. bitti saa arvon 1.
Muussa tapauksessa sen arvoksi tulee 0.
Jos tulossa 2 on tasajännite 12-48 V, tulorekisterin 14. bitti saa arvon 1.
Muussa tapauksessa sen arvoksi tulee 0.
Parametrit lähtevät 32 bitin heksadesimaalimuodossa. Esim. jännite
230,0 V on 000008FCH. Cos ϕ
:n arvot jaetaan 1000:lla. Cos muodossa 000003D4H. Energia-arvoissa on 64 tavua.
1234567890123456789 Wh = AB 54 A9 8C EB 1F 0A 02 Wh
ϕ
0,980 on
Datakaapelin tiedot:
- 24 AWG tai paksumpi
- Alle 100 ohmia/km
- Nimellinen ominaisimpedanssi 10 kHz:llä on 100 ohmia
- Keskinäinen kapasitanssi parin kahden johtimen välillä: alle 60 pF/m
- Keskinäinen parikapasitanssi (kapasitanssi yhden johtimien ja kaikkien muiden maahan kytkettyjen johtimien välillä): alle 120 pF/m
- Parikierretty johto
VIRHEKOODIT (vain MPR-53 S)
Alalaite (MPR-53/53S) lähettää virheviestin, kun se saa tunnistamattoman kyselyn. Virhekoodit ovat seuraavat:
01 Epäkelpo toiminto: Viesti on muunlainen kuin mitä yllä on esitetty.
02 Epäkelpo rekisteri: On pyydetty lukemaan jokin muu kuin rekisteriluettelossa oleva rekisteri.
03 Epäkelpo data: Muuntajalle on asetettu epäkelpo arvo tai keskiarvoksi nollasta eroava arvo.
5
TEKNISET TIEDOT
Toimintajännite (Un) : Katso arvokilvestä laitteen takasivulta
Toimintataajuus (f) : 50 ja 60 Hz
Laitteen oma tehonkulutus : < 4 VA
Mittaustulon tehonkulutus : < 1 VA
VIn : 10-300 V AC 50/60 Hz (L-N)
: 10-500 V AC 50/60 Hz (L-L)
IIn : 0,05-5,5 A~ 1-120 A~ (CT-25:lle)
Mittausalue : 10 V...200 kV AC / 0...215 M (W, VAr, VA) /
99999999999,9 Wh, VArh
Luokka : 1 % +/- 1 numero [(10 %-110 %) x max-arvo]
Jännitemuuntajan suhde (Vtr) : 0,1...4000,0
Virtamuuntajan suhde (Ctr) : 1...2000
Maksimi Ctr x Vtr : 40.000
Koontijakson pituus : 1 - 60 minuuttia (ohjelmoitavissa)
Sarjaliitäntä (MPR-53S) : MODBUS RTU (RS 485), optisesti eristetty
Siirtonopeus (MPR-53S) : 2400 - 38400 b/s
Osoite (MPR-53S) : 1 - 247
Pariteetti (MPR-53S) : ei, pariton, parillinen, 8 databittiä, 2 stop-bittiä
Pulssilähtö : NPN-transistori
Kytkentäaika : Min 100 ms pulssin kesto, 80 ms pulssin leveys
Toimintavirta : Max 50 mA
Toimintajännite : 5...24 V DC, max 30 V DC
Tulot : 12...48 V AC / DC
Ympäristön lämpötila : -5 ... +50 o C
Näyttö : Punainen LED-näyttö
Mitat : PR 19, PR-16, PK-26
Suojausluokka : Kaksoiseristys, luokka II
Kotelointiluokka : IP 40 (etupaneeli)
Kotelon materiaali : Palamaton
Asennus : Paneeliin (PR-16, PR-19), kiskoon (PK-26)
Johtimen paksuus (liittimessä) : 2,5 mm
2
Paino : 0,45 kg (PR-19, PK-26), 0,8 kg (PR-16)
Asennusluokka : Luokka III
Tehtaan asetukset
Trafo : Eng Cnt :
Ctr (virtamuuntajan muuntosuhde : 0020 E-1 (energiamittari 1) : on
Utr (jännitemuuntajan muuntosuhde : 0001.0 E-2 (energiamittari 2) : on
CAL (laskentamenetelmä) : 1
Pin : 0000 (ei otettu käyttöön) rAt (suhde) : 1
o-1 (lähtö 1) : A-I
RS-485 : o-2 (lähtö 2) : r-L
Adr (osoite) : 1
Bau (baudit) : 9600
dEti (viive) : 15
PAr (pariteetti : no
Mitat
10.8
30.1
7.6
9.5
18
60.6
26.5
21.5
53.0
58.0
96mm
10.0
106.0
Type PK 26
79.3mm
70mm
TURVAOHJEITA
Type PR 19
121
138,4
143
Type PR 16
34.5
58mm
Näiden ohjeiden noudattamatta jättäminen saattaa aiheuttaa hengenvaaran.
- Katkaise virta, ennen kuin suoritat laitteelle asennus- tai huoltotoimenpiteitä.
- Älä irrota etulevyä, kun laite on kytkettynä verkkoon.
- Puhdista laite kuivalla liinalla. Älä käytä liuottimia tai muuta vastaavaa.
- Tarkasta, että liittimet on kytketty oikein.
- Huollon saa suorittaa vain pätevä asiantuntija.
- Valmistaja ei vastaa mahd. seurauksista, jotka aiheutuvat laitteen käytöstä.
- Asennus vain paneeliin.
VERKKOANALYSAATTORI
MPR-53/53S
PR 19 -tyypin kytkentäkaavio
L1
L2
L3
N k
K L l k
K L l k
K L l
Max: 30 VDC
_
+
1
I
L1
2 3 4
I
L2
Virranmittaustulot
5
I
L3
6
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Jännitteenmittaustulot
L1
7
L2
8
L3
9
N
10
Virranmittaustulot
syöttö
11 12
L1
N
3 vaihetta ja nolla
L1
L2
L3 k
K L l k
K L l k
K
1
I
L1
2 3
I
L2
4
Virranmittaustulot
5
I
L3
6
Max: 30 VDC
_
+
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Jännitteenmittaustulot
7
L1
Voltage Measuring Input
L2
8
L3
9
N
10
Oma tehon-
syöttö
11 12
L l
L1
N
3 vaihetta, ei nollaa
PK 26 -tyypin kytkentäkaavio
+_
Max: 30 VDC
Gnd A B
RS-485
TR
L1
L2
L3
N
syöttö
~ L1
1A
L2 L3 N
3 vaihetta ja nolla
* Vain MPR-53S
I
L1
I
L2
I
L3 k
K l
L k
K L l k
K l
L
L1
L2
L3 k
K L l k
K L l
1
I
L1
2 3 4
I
L2
Virranmittaustulot
5
I
L3
6
Max: 30 VDC
_
+
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Jännitteenmittaustulot
L1
7
L2
8
L3
9
N
10
Auxiliary
syöttö
11 12
L1
N
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
L1
L2
L3 k
K L l k
K L l
1 2 3 4
I
L1
Virranmittaustulot
5
I
L2
Current Measuring Input
I
L3
6
Max: 30 VDC
_
+
Pul C
( 12-48V DC )
InC In1 In2
13 14 15 16 17 18
RS485
19 20 21 22
GND B A TR
Pul 1 Pul 2
Jännitteenmittaustulot
7
L1 L2
8
L3
9
N
10
Auxiliary
syöttö
11 12
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
L1
N
6
+_
Max: 30 VDC
L1
L2
L3
Gnd A B
RS-485
TR
Oma tehon-
syöttö
~
Jännitteenmittaustulot Virranmittaustulot
L1 L2 L3 N L1 L2
I
L3
1A N k
K L l k
K l
L
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
NETWORK ANALYSER
MPR-53/53S
For erasing the values of min. and max. or energy counter,
In the measurement mode :
Press SET button for 3 seconds
(trA Fo menu is displayed)
By using UP-DOWN buttons, find rES Et menu.
Press SET button.
(rESEt HL menu is displayed)
By using UP-DOWN buttons, select which parameter you want to reset.
Press SET button
By using UP-DOWN buttons, if you want to delete the parameter select yES option otherwise select no option.
Press SET button. (rES Et is displayed)
Press ESC button one by one until (SAU E SEt yES) is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press
ESC button or choose no option instead of yES option by using UP-
DOWN buttons, new data will be cancelled and previous value will be activated.
Pulse Menu
In this menu, three parameters can be selected : PUL SE rAt ýo, PUL
SE o-1, PUL SE o-2
PUL SE rAt ýo : Pulse ratio can be set as :
1, 10, 100 (wh/VArh/VA); 1, 10, 100 (kwh/kVArh/kVA); 1 Mwh/MVArh/MVA.
PUL SE o-1 : If this parameter is selected, in every increase in output 1, one pulse is counted. Output 1 parameter can be set as :
ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive
/ Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive).
PUL SE o-2 : If this parameter is selected, in every increase in output 2, one pulse is counted. Output 2 parameter can be set as :
ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive
/ Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive).
Press SET button for 3 seconds (trA Fo menu is displayed)
Press SET button for 3 seconds
(trA Fo menu is displayed)
By using UP-DOWN buttons, find Eng Cnt menu.
Press SET button
(Eng Cnt E-1 menu is displayed)
By using UP-DOWN buttons, select E-1 or E-2.
Press SET button.
By using UP-DOWN buttons, select on, ý-1,
ý-2 or E-1 / E-2.
Press SET button.
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press
ESC button or choose no option instead of yES option by using
UP-DOWN buttons, new data will be cancelled and previous value will be activated.
User password Setup:
Changing of User Password:
By using UP-DOWN buttons, find PULSE menu.
Press SET button (PUL SE rAt ýo menu is displayed)
By using UP-DOWN buttons, select PUL SE rAt ýo, PUL SE o-1 or
PUL SE o-2.
Press SET button.
By using UP-DOWN buttons, select required parameter.
Press SET button.
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press
ESC button or choose no option instead of yES option by using
UP-DOWN buttons, new data will be cancelled and previous value will be activated.
Energy Counter (Eng Cnt) Menu
MPR-53/53S has 2 energy counters : Energy counter 1 (E-1),
Energy counter 2 (E-2).
E-1 has 4 parameters : on : Activate E-1 for energy counting without depending on any parameter.
ý-1 : Activate E-1, when digital input 1 is on (=1).
ý-2 : Activate E-1, when digital input 2 is on (=1).
E-2: Do not count to E-1, when E-2 is active.
E-2 can be set in the same way...
Note: If E-1 is selected on E-2 and if E-2 is selected on E-1, then it counts to both energy counters.
Press SET button, Pýn CHA ngE is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps).
Press ESC button one by one until (SAU E SEt yES) is displayed.
Press SET button.
When SAU E SEt yES is displayed, if you press
ESC button or choose no option instead of yES option by using
UP-DOWN buttons, new data will be cancelled and previous value will be activated.
3
NETWORK ANALYSER
MPR-53/53S
Voltage Transformer Ratio Setup
In this menu, voltage transformer ratio is set between 0,1 - 4000,0.
Note: If the voltage transformer is not used between the system and
MPR-53/53S, voltage transformer ratio is entered as 1.
Example: If a voltage transformer which has a ratio of 34.5KV/100V is used between the system and MPR-53/53S; Voltage transformer ratio is entered as 345. (34500/100)
90° rotation of voltage vector and multiply with current
¥
S V n
.I
n
.sin(j n
)
S 2 -P 2
Power Triangle Methode : According to this methode;
Q = S 2 -P 2
(Q : Reactive power, S : Active power, P : Apparent power)
Monitoring and Erasing of minimum, maximum and energy values:
In this menu, values of min.,max. or energy counters are erased.
It saves the instantaneously measured min. and max. values of
MPR-53/53S into its memory. Please kindly look at to the section of
FUNCTIONS OF BUTTONS for min. and max. values.
Note : Measured electrical parameters which are saved to the memory are not affected from the electric interruptions.
In the rESEt menu; when you quit from all menus, if you confirm the changes,min. and max. values of all parameters or energy counter values are erased at the same time.
2
VERKKOANALYSAATTORI
MPR-53/53S
+_
Max: 30 VDC
Gnd A B
RS-485
TR
Oma tehon-
syöttö
Jännitteenmittaustulot Virranmittaustulot
L1 L2 L3 N
I
L1
I
L2
I
L3
1A
N
L1
L2
L3
3 vaihetta, ei nollaa k
K L l k
K L l k
K l
L
PR-16 -tyypin
Max 30 VDC
kytkentäkaavio
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
L1
L2
L3
N
Jännitteenmittaustulot Virranmittaustulot
L1 L2
1 2
L3 N
3 4
I L1 I L2 I L3
5 6 7 8 9 10
Oma tehon-
Un
13 14
1A k
K L l k
K l
L k
K l
L
3 vaihetta ja nolla
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
+_
Max: 30 VDC
(12-48V DC)
- + - +
Gnd A B
RS-485
TR
Oma tehon-
syöttö
L1 L2 L3 N
I
L1
I
L2
I
L3
1A
N
L1 k
K l
L
L2
L3 k
K l
L
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
Jännitteenmittaustulot Virranmittaustulot
L1 L2 L3 N I L1 I L2 I L3
Oma tehon-
syöttö
Un
1 2 3 4 5 6 7 8 9 10 13 14
1A N
L1
L2 k
K L l k
K L l
L3
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
Max: 30 VDC
+_
-
24 23 22 21 20 19 18 17 16 15
TR B A GND
RS-485
INC PUL2 PUL1 PULC
L1
L2
L3
Jännitteenmittaustulot Virranmittaustulot
L1 L2
1 2
L3 N
3 4
I
L1
I
L2
I
L3
5 6 7 8 9 10
Oma tehon-
syöttö
Un
13 14
1A N k
K L l k
K l
L k
K l
L
3 vaihetta, ei nollaa
* Vain MPR-53S
MPR-53S:N KYTKENTÄ TIETOKONEESEEN
MPR-53S COMPUTER CONNECTION
MAX 1200 m
RS485/RS232
CONVERTER
B
A
GND
PC
TR B A GND
MPR-53S-31
...
TR B A GND
MPR-53S-2
TR B A GND
9 PIN CONNECTOR
TRB A GND
MPR-53S-247
...
MAX. 1200 mt.
MPR-53S-1
7
L1 L2
1 2
L3 N
3 4
I L1 I L2 I L3
5 6 7 8 9 10
syöttö
Un
13 14
1A N
L1
L2 k
K L l
L3 k
K l
L
3 vaihetta, ei nollaa, virtatuloille Aron-kytkentä
REPEATER
MAX. 1200 mt.
RS485/RS232
CONVERTER
B
A
GND
PC
MPR-53S-31
...
MPR-53S-2 MPR-53S-1
CONNECTOR (DB9)
VERKKOANALYSAATTORI
MPR-53/53S
L3 PHASE MIN. APPARENT POWER TOTAL MIN. IMPORT ACTIVE POWER TOTAL MIN. EXPORT ACTIVE POWER
TOTAL MIN. IMPORT REACTIVE POWER TOTAL MIN. EXPORT REACTIVE POWER
L1 PHASE MAX. VOLTAGE L2 PHASE MAX. VOLTAGE L3 PHASE MAX. VOLTAGE
L1-L2 PHASE-PHASE MAX. VOLTAGE L2-L3 PHASE-PHASE MAX. VOLTAGE L3-L1 PHASE-PHASE MAX. VOLTAGE
L1 PHASE MAX. CURRENT L2 PHASE MAX. CURRENT L3 PHASE MAX. CURRENT
L1 PHASE MAX. ACTIVE POWER L2 PHASE MAX. ACTIVE POWER L3 PHASE MAX. ACTIVE POWER L1 PHASE MAX. REACTIVE POWER L2 PHASE MAX. REACTIVE POWER L3 PHASE MAX. REACTIVE POWER L1 PHASE MAX. APPARENT POWER L2 PHASE MAX. APPARENT POWER L3 PHASE MAX. APPARENT POWER
TOTAL MAX. IMPORT ACTIVE POWER TOTAL MAX. EXPORT ACTIVE POWER TOTAL MAX. IMPORT REACTIVE POWER TOTAL MAX. EXPORT REACTIVE POWER L1 PHASE MAX. CURRENT DEMAND L2 PHASE MAX. CURRENT DEMAND L3 PHASE MAX. CURRENT DEMAND
L1 PHASE IMPORT MAX. DEMAND ACTIVE POWER L1 PHASE EXPORT MAX. DEMAND ACTIVE POWER L2 PHASE IMPORT MAX. DEMAND ACTIVE POWER L2 PHASE EXPORT MAX. DEMAND ACTIVE POWER L3 PHASE IMPORT MAX. DEMAND ACTIVE POWER L3 PHASE EXPORT MAX. DEMAND ACTIVE POWER L1 PHASE IMPORT MAX. DEMAND REACTIVE POWER L1 PHASE EXPORT MAX. DEMAND REACTIVE POWER L2 PHASE IMPORT MAX. DEMAND REACTIVE POWER L2 PHASE EXPORT MAX. DEMAND REACTIVE POWER L3 PHASE IMPORT MAX. DEMAND REACTIVE POWER L3 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L1 PHASE MAX. DEMAND APPARENT POWER L2 PHASE MAX. DEMAND APPARENT POWER L3 PHASE MAX. DEMAND APPARENT POWER TOTAL IMPORT MAX. DEMAND ACTIVE POWER TOTAL EXPORT MAX. DEMAND ACTIVE POWER
TOTAL IMPORT MAX. DEMAND REACTIVE POWER TOTAL EXPORT MAX. DEMAND REACTIVE POWER int int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int unsigned int unsigned int unsigned int unsigned int int int int int int int int int int int int int unsigned int unsigned int unsigned int int int int int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
VA Watt Watt Var Var VA Volt Volt Volt Volt Volt Volt
Amper Amper Amper Watt Watt Watt
Var Var Var VA VA VA Watt Watt Var Var VA
Amper Amper Amper Watt Watt Watt Watt Watt Watt
Var Var Var Var Var Var VA VA VA Watt Watt Var Var VA
VOLTAGE TRANSFORMER RATIO CURRENT TRANSFORMER RATIO
DEMAND TIME PULSE RATIO
PULSE OUTPUT 1 PARAMETER SETTING PULSE OUTPUT 2 PARAMETER SETTING
ENERGY COUNTER 1 SELECTION ENERGY COUNTER 2 SELECTION short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int
0.1 1 - 1 - - - - - - - - - -
- - - - - - - - - - - -
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0-3000)xUT (0-3000)xUT (0-3000)xUT (0-5000)xUT (0-5000)xUT (0-5000)xUT (0-6000)xCT (0-6000)xCT (0-6000)xCT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0-6000)xCT (0-6000)xCT (0-6000)xCT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT (0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
0-40000 0-2000
0-1 1-60 0-6 0-5 0-5 0-3 0-3
0 - 247 1 - 5 0 - 2 0-9999
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
TGVA_MIN_M AGGIM_MIN_M AGGEX_MIN_M RGGIM_MIN_M RGGEX_MIN_M VAG_MIN_M RMAX_GER_M SMAX_GER_M TMAX_GER_M L1MAX_GER_M L2MAX_GER_M L3MAX_GER_M RMAX_AKIM_M SMAX_AKIM_M TMAX_AKIM_M RGAG_MAX_M SGAG_MAX_M TGAG_MAX_M RGRG_MAX_M SGRG_MAX_M TGRG_MAX_M RGVA_MAX_M SGVA_MAX_M TGVA_MAX_M AGGIM_MAX_M AGGEX_MAX_M RGGIM_MAX_M RGGEX_MAX_M VAG_MAX_M RDEM_AKIM_M SDEM_AKIM_M TDEM_AKIM_M
RGAG_IM_DEM_M RGAG_EX_DEM_M SGAG_IM_DEM_M SGAG_EX_DEM_M TGAG_IM_DEM_M TGAG_EX_DEM_M RGRG_IM_DEM_M RGRG_EX_DEM_M SGRG_IM_DEM_M SGRG_EX_DEM_M TGRG_IM_DEM_M TGRG_EX_DEM_M
RGVA_DEM_M SGVA_DEM_M TGVA_DEM_M AGGIM_DEM_M AGGEX_DEM_M RGGIM_DEM_M RGGEX_DEM_M VAG_DEM_M
0098 009A 009C 009E 00A0 00A2 00A4 00A6 00A8 00AA 00AC 00AE 00B0 00B2 00B4 00B6 00B8 00BA 00BC 00BE 00C0 00C2 00C4 00C6 00C8 00CA 00CC 00CE 00D0 00D2 00D4 00D6 00D8 00DA 00DC 00DE 00E0 00E2 00E4 00E6 00E8 00EA 00EC 00EE 00F0 00F2 00F4 00F6 00F8 00FA 00FC 00FE
152 154 156 158 160 162 164 166 168 170 172 174 176 178 180 182 184 186 188 190 192 194 196 198 200 202 204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 246 248 250 252 254
VT_RATIO_H CT_RATIO_H
CALCULATION_H DEMAND_TIME_H PULSE_RATE_H PULSE_OUT1_H PULSE_OUT2_H
ENG_CNT1_H ENG_CNT2_H
ADRESS_H BAUD_H PARITY_H
8000 8002 8004 8006 8008 800A 800C 800E 8010 8012 8014 8016 8018 801A
32768 32770 32772 32774 32776 32778 32780 32782 32784 32786 32788 32790 32792 32794
L1 PHASE VOLTAGE L2 PHASE VOLTAGE L3 PHASE VOLTAGE L1 PHASE CURRENT L2 PHASE CURRENT L3 PHASE CURRENT
L1-L2 PHASE-PHASE VOLTAGE L2-L3 PHASE-PHASE VOLTAGE L3-L1 PHASE-PHASE VOLTAGE
L1 PHASE ACTIVE POWER L2 PHASE ACTIVE POWER L3 PHASE ACTIVE POWER L1 PHASE REACTIVE POWER L2 PHASE REACTIVE POWER L3 PHASE REACTIVE POWER L1 PHASE APPARENT POWER L2 PHASE APPARENT POWER L3 PHASE APPARENT POWER
TOTAL IMPORT ACTIVE POWER TOTAL EXPORT ACTIVE POWER
TOTAL INDUCTIVE REACTIVE POWER TOTAL CAPACITIVE REACTIVE POWER
TOTAL APPARENT POWER AVERAGE INDUCTIVE COS
L1 PHASE VOLTAGE ANGLE L2 PHASE VOLTAGE ANGLE L3 PHASE VOLTAGE ANGLE L1 PHASE CURRENT ANGLE L2 PHASE CURRENT ANGLE L3 PHASE CURRENT ANGLE
L1 PHASE VOLTAGE THD L2 PHASE VOLTAGE THD L3 PHASE VOLTAGE THD L1 PHASE CURRENT THD L2 PHASE CURRENT THD L3 PHASE CURRENT THD DIGITAL INPUT STATUS IMPORT ACTIVE ENERGY-1 L1 PHASE MIN. VOLTAGE L2 PHASE MIN. VOLTAGE L3 PHASE MIN. VOLTAGE
L1-L2 PHASE-PHASE MIN. VOLTAGE L2-L3 PHASE-PHASE MIN. VOLTAGE L3-L1 PHASE-PHASE MIN. VOLTAGE
L1 PHASE MIN. CURRENT L2 PHASE MIN. CURRENT L3 PHASE MIN. CURRENT
L1 PHASE MIN. ACTIVE POWER L2 PHASE MIN. ACTIVE POWER L3 PHASE MIN. ACTIVE POWER L1 PHASE MIN. REACTIVE POWER L2 PHASE MIN. REACTIVE POWER L3 PHASE MIN. REACTIVE POWER L1 PHASE MIN. APPARENT POWER L2 PHASE MIN. APPARENT POWER unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int
0.1 0.1 0.1 0.001 0.001 0.001
Volt Volt Volt
Amper Amper Amper unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int int int int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.01
1 1 1 1 1 1 0.1 0.1 0.1 0.1 0.1 0.1 - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.1 0.1 0.1 0.1 0.1 0.1
0.001 0.001 0.001 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Volt Volt Volt Watt Watt Watt Var Var Var VA VA VA
- - -
Watt Watt Var Var VA
- - Hz
Degre Degre Degre Degre Degre Degre
% % % % % % - Wh Wh Wh Wh VArh VArh VArh VArh Wh Wh Wh Wh VArh VArh VArh VArh Volt Volt Volt Volt Volt Volt
Amper Amper Amper Watt Watt Watt
Var Var Var VA VA
(0-3000)xUT (0-3000)xUT (0-3000)xUT (0-6000)xCT (0-6000)xCT (0-6000)xCT
R R R R R R
0-360 0-360 0-360 0-360 0-360 0-360 0-999 0-999 0-999 0-999 0-999 0-999
(0-5000)xUT (0-5000)xUT (0-5000)xUT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 -18000)xCTxVT (0 -18000)xCTxVT (0 -18000)xCTxVT
(-1000 -1000) (-1000 -1000) (-1000 -1000)
(0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT (0 -54000)xCTxVT
(-1000 -1000) (-1000 -1000) (4000 -7000)
0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF 0-FFFFFFFFFFFFFFFF
(0-3000)xUT (0-3000)xUT (0-3000)xUT (0-3000)xUT (0-3000)xUT (0-3000)xUT (0-6000)xCT (0-6000)xCT (0-6000)xCT
(-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT (-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT (0 - 18000)xCTxVT
R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
R_GER_M S_GER_M T_GER_M R_AKIM_M S_AKIM_M T_AKIM_M L1_GER_M L2_GER_M L3_GER_M RGAG_M SGAG_M TGAG_M RGRG_M SGRG_M TGRG_M RGVA_M SGVA_M TGVA_M RGCOS_M SGCOS_M TGCOS_M AGGIM_M AGGEX_M RGGIM_M RGGEX_M
VAG_M COSIM_M COSEX_M FREQ_M
RGERILIM_ACI_M SGERILIM_ACI_M TGERILIM_ACI_M
RAKIM_ACI_M SAKIM_ACI_M TAKIM_ACI_M RGGER_THD_M SGGER_THD_M TGGER_THD_M RGAK_THD_M SGAK_THD_M TGAK_THD_M
ACTIVE_IM_HM_1 ACTIVE_IM_LM_1 ACTIVE_EX_HM_1 ACTIVE_EX_LM_1
REACTIVE_IM_HM_1 REACTIVE_IM_LM_1 REACTIVE_EX_HM_1 REACTIVE_EX_LM_1
ACTIVE_IM_HM_2 ACTIVE_IM_LM_2 ACTIVE_EX_HM_2 ACTIVE_EX_LM_2
REACTIVE_IM_HM_2 REACTIVE_IM_LM_2 REACTIVE_EX_HM_2 REACTIVE_EX_LM_2
RMIN_GER_M SMIN_GER_M TMIN_GER_M L1MIN_GER_M L2MIN_GER_M L3MIN_GER_M RMIN_AKIM_M SMIN_AKIM_M TMIN_AKIM_M RGAG_MIN_M SGAG_MIN_M TGAG_MIN_M RGRG_MIN_M SGRG_MIN_M TGRG_MIN_M RGVA_MIN_M SGVA_MIN_M
0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0038 003A 003C 003E 0040 0042 0044 0046 0048 004A 004C 004E 0050 0052 0054 0056 0058 005A 005C 005E 0060 0062 0064 0066 0068 006A 006C 006E 0070 0072 0074 0076 0078 007A 007C 007E 0080 0082 0084 0086 0088 008A 008C 008E 0090 0092 0094 0096
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150
8
NETWORK ANALYSER
MPR-53/53S
General
MPR-53/53S is developed for measuring all the electrical parameters on the network.
Measured parameters are shown in 5 separate displays.This allows to monitor more than 50 parameters at the same time. MPR-53/53S has also MODBUS serial interface feature.
Phase Displays
UP
DOWN
Max. LED
SET
Minimum LED
Demand LED
SW, SVA and Hz
Display
SVAr ve Cosj
Display
Using of MPR-53/53S:
Back ESC
Parameters are shown in L1, L2, L3 displays (V
LN
; V
LL
; A; W; VAr; VA; Cosj; kWh, kVarh, THD) by using up-down buttons. Total Active (SW), Total Apparent Power
(SVA) and Frequency (Hz) are selected by back button.
Total Reactive Power (SVAr) and Cosj are selected by Esc button.
Digital Inputs
MPR-53/53S has 2 digital inputs which are used to monitor the status of electrical contacts. Digital input has 2 functions :
- Enabling remote control of the data received through the digital input terminal
(battery, thermostat, circuit breaker, pumps status)
- Controlling energy counters and determining which energy counter will be active.
Energy Pulse Outputs
There are 2 energy counters in MPR-53/53S and just 1 counter (1st counter) out of 2 counters is sending pulse output data. 2nd counter does not send pulse output data.
Pul1 (Reactive Energy Pulse Output) : A pulse output is given, if measured energymeter value increases in each pulse rate (1 VArh...1 MVArh).
Pul1 is used for only - (reactive import) energy value.
Pul2 (Active Energy Pulse Output) : A pulse output is given, if measured energy meter value increases in each pulse rate (1 wh...1 Mwh).
Pul2 is used for both - (Active Import) and - (Active Export) energy values.
Min. pulse period is 1.6 seconds.
Monitoring Min.- Max. and Demand Values:
Min. and Max. values are defined for VLN, VLL, A, W, VAr, VA, SW, SVAr, SVA.
Demand values are defined for A, W, VAr, VA, SW, SVA, SVAr.
If the measured instantaneous value is less than previous recorded min.
value, then the new value is recorded as min value, if exceeds the previous max.
value recorded as max. value. Demand value is the average of measured values for demand time (e.g.15 min) If average value for demand time exceeds the previous demand value, the new value is recorded as demand value.
If one of defined parameters is displayed when deman button is pressed , min.,max or demand values are displayed. When an undefined parameter is displayed if demand button is pressed, instant values are continued to display.
For example when power factor is displayed instant values are continued to display because min., max. and demand values are undefined.
Monitoring THD Values
When VLN and THD leds light on, voltage THD is monitored and also if A and
THD leds light on, current THD is monitored.
H-L-M LEDs
H-L-M LEDs are dedicated to displaying the min., max. and demand values according to selected parameters.
H: Maximum Value
L: Minimum Value
M: Demand Value
Calculation Methods for Active / Reactive Power Values
If the led on the most left side blinks it represents that active powers / reactive powers direction is negative.
There are two methods for calculating total active and total reactive powers :
1) Active / Reactive power can be calculated by summing import and export values and displaying as a single value.
2) Active / Reactive power can be calculated according to direction as import / export.
Note :
1) The dot at the most right digit of the fourth display represents that displayed value is export active power value. Vice versa, displayed value is import active power value.
2) The dot at the most right digit of the fourth display represents that displayed value is capacitive reactive power value. Vice versa, displayed value is inductive reactive power value.
3) The displayed parameter does not change if power is off after 20 seconds of stand-by.
Measured Parameters:
V
LN
(Phase Voltage ) VA (Apparent Power)
V
LL
(Phase to Phase Voltage) Cosj
A (Phase Current)
W (Active Power)
VAr (Reactive Power)
AI ( kWh) (Import Active Energy I)
AE (kWh) (Export Active Energy) rI (kVArh) (Import Reactive Energy) rE(kVArh) (Export Reactive Energy)
THD (Total Harmonic Distortion)
Hz. (Frequency)
S W (Total Active Power)
S VAr (Total Reactive Power)
S VA (Total Apparent Power)
FUNCTIONS OF BUTTONS
In the monitoring mode, it is used to pass between
(V
LN
, V
LL
, A, W, VAr, VA, Cosj, kWh, kVarh, THD) parameters.
At the programming mode, it provides to increase value of desired parameter and pass to the next menu.
In the monitoring mode, it is used to pass between
(V
LN
, V
LL
, A, W, VAr, VA, Cosj, kWh, kVarh, THD) parameters.
At the programming mode, it provides to decrease value of desired parameter and pass to the prevides menu.
(SET) In the monitoring mode, it is used to pass between min., max., demand and instant values. When it is pressed for 3 seconds, programming mode it is entered.
In the programming mode, it is used for saving parameters and moving to the sub menu.
(Back) In the monitoring mode, it is used to pass between SW, SVA and Hz parameters. It provides to pass to the previous menu.
(ESC) In the monitoring mode, it provides to pass between SVAr and
Cosj values. In the programming mode, it is used to enter to the upper menu or it is used to quit from the programming mode without saving values.
If user password is activated and set button is pressed for 3 seconds, a pin code is required in order to enter to the menu.
Current Transformer Ratio Setup
In this menu, current transformer ratio is set between 1 - 2000.
Note: If the current transformer is not used between the system and
MPR-53/53S, current transformer ratio is entered as 1.
Example: If a current transformer which has a ratio of 250/5A is used between the system and MPR-53/53S; Current transformer ratio is entered as 50 (250/5).
Press SET button for 3 seconds
(trA Fo menu is displayed)
Press SET button
(trA Fo Ctr menu is displayed)
Press SET button
(The number in first digit blinks)
By using UP-DOWN buttons, enter the value to the first digit.
Press SET button
(Second digit blinks).
By using UP-DOWN buttons, enter the value to the second digit.
Press SET button
(Third digit blinks)
By using UP-DOWN buttons, enter the value to the third digit.
Press SET button (Last digit blinks)
By using UP-DOWN buttons, enter the value to the last digit.
Press Set button, trA Fo Ctr is displayed.
(Data is entered but is not activated yet.
For activating the new data, please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press
ESC button or choose no option instead of yES option by using
UP-DOWN buttons, new data will be cancelled and previous value will be activated.
1
advertisement
Key Features
- Measures all electrical network parameters
- 5 display screens showing values for over 50 parameters
- Uses Modbus serial communication protocol
- Features two digital inputs for monitoring electrical contacts
- Remotely control data from a battery, thermostat, automatic fuse, or pump
- Control energy meters and select which one is measuring