Bard DC3000 DC3002, DC3003 lead/lag controller Installation instructions
Below you will find brief information for lead/lag controller DC3002, lead/lag controller DC3003. This manual describes steps for installing the lead/lag controller for two or three air conditioners. Controller provides total redundancy for the structure and equal wear on both units, also it has dehumidification control and standby generator disable operation. It is fully configurable and suitable for both 50 and 60 Hz operation.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
22
INSTALLATION INSTRUCTIONS & REPLACEMENT PARTS LIST DC3002 and DC3003 SOLID STATE LEAD/LAG CONTROLLER with DC FAN CONTROL Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. © Copyright 2007 Manual No.: Supersedes: File: Date: 2100-484A 2100-484 Vol. III Tab 19 03-07-08 Manual Page 2100-484A 1 of 22 CONTENTS Getting Other Information and Publications 3 DC3000 General Information Shipping Damage .................................................. 4 General .................................................................. 4 Theory of Operation ............................................... 4 Controller Certifications ......................................... 4 Specifications/Features for Basic Controller DC3000 Basic Controller ....................................... 5 Mounting the Controller Installation Instructions .......................................... 5 Temperature Sensors Remote Indoor Sensor ........................................... 5 Remote Outdoor Sensor ........................................ 5 Temperature Sensor Logic Using Multiple Sensors .......................................... 5 Controller Input/Output Specifications Main Controller Board ............................................ 6 Internal Alarm Board .............................................. 6 Low Voltage Field Wiring Circuitry in the DC3000 .......................................... 7 Controller Grounding Earth ground .......................................................... 7 Controller Power-Up Time Delay on Power-Up ....................................... 7 Fire Suppression Circuit Disabling the DC3000 ............................................ 7 Staging Delay Periods Stages 1 - 4 ............................................................ 7 Blower Operation Various Blower Options ......................................... 7 Security (Locking) Feature Locking and Unlocking the DC3000 ...................... 9 Generator Run Feature Standby Generator Disable Operation ................... 9 Backup DC Power Connection Input Connections Available .................................. 9 DC Fan Control Free Cooling & Emergency Ventilation ................ 10 Shelter Purge Control .......................................... 10 Controller Wiring Refer to Connection Diagram ...................... 10 & 11 Alarm Wiring Wiring Alarm Relays ............................................ 16 2nd Stage Cooling Alarm Alarm Output is Available ..................................... 16 Refrigerant Pressure Alarms Connecting the Alarm Circuit ............................... 16 Emergency Ventilation Sequence Using Economizers Two Operating Sequences .................................. 16 Programming Instructions ................................... 19 Figures Figure 1 DC3002 Controller Connections for 2 Air Conditioners with Economizer ................... 11 Figure 2 DC3002 Controller Connections for 2 Air Conditioners with No Economizer .............. 12 Figure 3 DC3003 Controller Connections for 3 Air Conditioners with 3 Economizers .............. 13 Figure 4 DC3003 Controller Connections for 3 Air Conditioners with Economizers (No Economizer A/C #3) ......................... 14 Advance (Swap) Lead/Lag Unit Feature Manual Switching of Units ..................................... 7 Figure 5 DC3003 Controller Connections for 3 Air Conditioners with No Economizers ............ 15 Accelerate Timer Feature Testing the Timer Function ..................................... 7 Figure 6 Alarm Board Connections for Normally Closed “NC” Open-On-Alarm Strategy ................... 17 Figure 7 Alarm Board Connections for Normally Open “NO” Close-On-Alarm Strategy ..... 18 (Label) DC3000 Series ....................................... 20 Sequence of Operation - Cooling (Air Conditioners) No Economizer ...................................................... 8 With Economizers .................................................. 8 Figure 8 Parts List Description ............................. 21 Sequence of Operation - Heating (Air Conditioners) With Electric Heat .................................................. 9 Table 1 Controller Connection Diagrams ............ 10 Table 2 Parts List ................................................ 22 Humidity Control Option Adding Optional Humidity Control .......................... 8 Manual 2100-484A Page 2 of 22 Tables Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. FOR MORE INFORMATION, CONTACT THESE PUBLISHERS: ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue, NW Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721 ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286 Standard for the Installation .............. ANSI/NFPA 90A of Air Conditioning and Ventilating Systems Standard for Warm Air Heating ........ ANSI/NFPA 90B and Air Conditioning Systems ASHRAE American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478 BARD Bard Manufacturing Company, Inc. 1914 Randolph Drive Bryan, OH 43506 Telephone: (419) 636-1194 Fax: (419) 636-2640 Manual Page 2100-484A 3 of 22 THEORY OF OPERATION ** IMPORTANT ** The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. Please read entire manual before proceeding. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. GENERAL NOTE: DC3000 is used throughout this Manual as a general reference to the controller system. There are two controller models, DC3002 for 2 HVAC units and DC3003 for 3 HVAC units, and these model numbers are referenced when specific features or characteristics apply only to either the DC3002 or the DC3003. Occasional reference is made to alarm board AB3002 or AB3003. AB3002 is the internal alarm board for the DC3002 controller, and AB3003 is the internal alarm board for the DC3003 controller. These instructions explain the operation, installation and troubleshooting of the DC3000 controller. All internal wiring is complete. Only attach low voltage field wiring to designated terminal strips. The DC3000 is for use with units with or without economizers, and has a dehumidification control feature if an optional humidity controller is connected. Each unit should be sized to handle the total load of the structure if 100% redundancy is required. It is recommended that a five (5) minute compressor time delay relay be installed in each unit. The DC3000 controllers are suitable for both 50 and 60 HZ operation, and are fully configurable such that they can be used in virtually any installation. See Controller Programmable Features and Default Settings. Manual 2100-484A Page 4 of 22 The DC3002 controller is used to control two wall mount air conditioners from one control system. It provides total redundancy for the structure and equal wear on both units. It can be used with units with or without economizers and it is recommended that both units be equipped alike. The DC3003 controller is designed to control 3 air conditioners, and can be used for 2 if it is anticipated the third unit may be installed later. NOTE: If this is done, see Note 1 on Alarm Board Connections (Figure 6 or 7) to prevent nuisance Power Loss Alarm indication for absent HVAC #3 When DC3003 is used for controlling three HVAC units, only units 1 or 2 operate in lead/lag sequence. HVAC #3 is always last to operate and functions only in the number 3 position. All three units are available to operate on-demand as required. Alarm capability is standard on both models. CONTROLLER CERTIFICATIONS The DC3000 main controller board, optional alarm boards, and remote sensors have undergone extensive testing for immunity and emissions. This system is FCC-compliant, in accordance with CE requirements, and meets the following standards: EN50082-2 Standard for Immunity EN55011 Standard for Emissions SPECIFICATIONS/FEATURES FOR BASIC CONTROLLER DC3000 Basic Controller •Input power: 18 to 32VAC, 60/50Hz, power is supplied from A/C #1 and/or A/C #2 •Isolation circuitry: no line or low voltage phasing required •Backup power: connection for -24VDC or -48VDC (-20 to -56V) maintains microprocessor operation, front panel indication, and alarm relay operation during commercial power outages. •Digital display: 4-character LCD •Temperature display: F or C •HVAC outputs: Form A (NO) relays (1A @ 24VAC) •Cooling control stages: 2 for each A/C unit •Heating Control stages: 1 for each A/C unit •Dehumidification circuit: requires optional humidity controller as input signal. •Operating temperature range: 0 to 120F (-18 to 49C) •Storage temperature range: -20 to 140F (-29 to 60C) •Temperature accuracy: +/- 1F from 60-85F (16-30C) +/- 1% outside 60-85F •Lead/lag changeover time: 0 to 30 days •Timing accuracy: +/- 1% •Inter-stage time delay: 10 seconds between stages •Inter-stage differential: 2F (1C) for all modes •On-Off differential: 2F (1C) is standard, 4F (3C) when “excessive cycling” mode is enabled. •Cooling set point range: 65 to 90F (18 to 32C) •Comfort setting-Cooling 72F (22C), Heating 68F(20C), for 1 hour. •Dead band (difference between cooling and heating set points): 2F to 20F (1C to 10C) •Fire/smoke interface: standard NC circuit jumper, remove for connection to building system control, shuts down both A/C units immediately. •Memory: EEPROM for set point and changeable parameters (maintains settings on power loss). •Temperature sensors: 1 local is standard, will accept up to 2 optional 25-foot remote sensors, Bard part number 8612-023. One can be used for remote indoor sensor and one is dedicated for outdoor sensor for DC Fan free cooling operation, if desired. •Controller Enclosure: 20-gauge pre-painted steel, 9.25"W x 13.50"H x 3.00"D, hinged cover, thirteen (13) .875" diameter electrical knockouts. •LEDs for basic controller: Lead unit, Cooling stages 1 through 4, Heating Stages 1 through 4, Dehumidification operation. DC3003 has cooling stage and alarm LED’s displayed internally for HVAC #3. •Six (6) Push-button controls: On/Off switch-Change lead unit-Increase and Decrease set points-Program/SaveComfort. MOUNTING THE CONTROLLER Included in the controller carton is the controller and installation instructions. The controller should be installed on a vertical wall approximately four (4) feet above the floor - away from drafts and outside doors or windows. Four (4) mounting holes are provided for mounting to the wall, and 7/8" holes for conduit connections are provided in both the base, sides and top of the controller. TEMPERATURE SENSORS The standard (local) temperature sensor has 12" leads and comes installed from the factory. The controller is designed to accept 1 additional remote indoor sensor, and connects to “Rem 1”. The Bard part number for the optional sensor with 25-foot leads is 8612-023. This remote indoor sensor can be installed as required in the structure to address hot spots, barriers to airflow, etc. It can also be used as the local sensor Outdoor sensor, same 8612-023 with 25-foot leads, is required for non-economizer installations when DC fan is to be used for free cooling. This sensor connects to the “Out” terminals. It is recommended that the sensor lead wires be installed in conduit for protective purposes. The highest reading of any connected indoor sensor will be used for high temperature alarm and the lowest reading sensor will be used for low temperature alarm. NOTE: All sensors are polarity sensitive. The copper lead must connect to terminal CU, and the silver lead to AG. Sensors are solid state, not RTD. Use only sensors supplied by Bard. TEMPERATURE SENSOR LOGIC The standard local (Loc) sensor monitors the temperature at the controller location. If this is the only sensor connected, it will control the temperature read-out, the space (building) temperature, and also be used for Low and High Temperature alarm functions. If one REMOTE sensor is installed and connected (Rem 1), the temperature read-out will display and the building will be controlled to an average of connected sensors. If there is more than 10F difference from the highest to the lowest connected sensor, the actual control will be governed by the hottest sensor for cooling and the coldest sensor for heating. If two indoor temperature sensors are used, the average of the two sensors becomes the controller cooling and testing set point. Manual Page 2100-484A 5 of 22 CONTROLLER INPUT/OUTPUT SPECIFICATIONS DC3002/3003 CONTROLLER CONNECTIONS DC3002/3003 CONTROLLER CONNECTIONS Located on Main Controller Board Located on Internal Alarm Board AB3002 C – 24VAC common R – 24VAC hot G – fan (Form A, NO) Y1 – 1st-stage cool (Form A, NO) Y2 – 2nd-stage cool (Form A, NO) W – heat (Form A, NO) Unit #2 C – 24VAC common R – 24VAC hot G – fan (Form A, NO) Y1 – 1st-stage cool (Form A, NO) Y2 – 2nd-stage cool (Form A, NO) W – heat (Form A, NO) Unit #3 C – 24VAC common (DC3003 only R – 24VAC hot and located on G – fan (Form A, NO) Internal Alarm Y1 – 1st-stage cool (Form A, NO) Board) Y2 – 2nd-stage cool (Form A, NO) W – heat (Form A, NO) F1-F2 Fire/smoke interface Shipped with jumper installed (a) 48Vdc Back-up power input -24Vdc or –48Vdc -20V to –56V range Local Main sensor, 12-inch leads NOTE: CU – copper, AG – silver Polarity sensitive Sensors are Rem 1 Optional remote indoor sensor solid state, CU – copper, AG – silver not RTD. Polarity sensitive Use Bard Out Optional outdoor sensor (b) CU – copper, AG – silver sensors only. Polarity sensitive Gen Generator interface G1-G2 Shipped with jumper installed (a) H1-H2 Humidity controller input Requires optional controller Field installed (a) These connections require either jumper or Normally Closed (NC) relay contact at the Fire/Smoke and Generator interface for Controller to function. (b) Required connection if field installed DC Fan is to be used for free cooling and no economizers are installed in HVAC units. DC3002 Inputs Lockout 1 2,3 – input from HVAC #1 Lockout 2 2, 3 – input from HVAC #2 Y Unit 1 signals when comp. #1 is active Y Unit 2 signals when comp. #2 is active DC3002 Alarm Outputs Smoke/Fire Form C (SPDT) Lockout 1 Form C (SPDT) Refrigerant alarm HVAC #1 Lockout 2 Form C (SPDT) Refrigerant alarm HVAC #2 Power Loss 1 Form C (SPDT) Power loss HVAC #1 Power Loss 2 Form C (SPDT) Power loss HVAC #2 Low Temp Form C (SPDT) Low temperature alarm High Temp 1 Form C (SPDT) High temperature alarm #1 High Temp 2 Form C (SPDT) High temperature alarm #2 Controller Form C (SPDT) Controller failure alarm DC3002 Control Outputs Econ 1 E, F - Form A (NO) See note (c ) Econ 2 E, F - Form A (NO) See note (c ) DC Fan Form C (SPDT) Pilot relay for DC Fan control 2nd Stage Form C (SPDT) 2nd-stage cooling alarm (c ) Make these connections to terminals E & F in HVAC 1 and 2 respectively if desired to have economizers open for emergency ventilation at High Temp Alarm #2 setpoint condition. Unit #1 Note: All alarm/output relays are dry contacts rated 1A @ 24VAC, 120VAC or 150VDC. DC3003 Inputs Everything from DC3002 plus: Lockout 3 2,3 – input from HVAC #3 DC3003 Alarm Outputs (on AB3003 Internal Alarm Board) Everything from DC3002 plus: Lockout 3 Form C (SPDT) Refrigerant alarm HVAC # 3 Power Loss 3 Form C (SPDT) Power loss HVAC #3 DC3003 Control Outputs Econ 3 E, F - Form A (NO) See note (c ) Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy. Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized. When multiple alarms are grouped together and issued as a single alarm there will be no off-site indication of which specific problem may have occurred, only that one of the alarms in the group has been triggered. The individual alarm problem will be displayed on the LED display on face of the controller. Manual 2100-484A Page 6 of 22 LOW VOLTAGE FIELD WIRING STAGING DELAY PERIODS The DC3000 is powered from the air conditioners that it is controlling, 24VAC (18-32V) low voltage only. The following delays are built in for both cooling and heating: Circuitry in the DC3000 isolates the power supplies of all connected air conditioners so that no back feeds or phasing problems can occur. Additionally, if any air conditioner loses power, the DC3000 and the other air conditioner are unaffected and will continue to operate normally. Connect the low voltage field wiring from each unit per the low voltage field wiring diagrams in Section on “Controller Wiring”. CONTROLLER GROUNDING A reliable earth ground must be connected in addition to any grounding from conduit. CONTROLLER POWER-UP Whenever power is first applied to the controller, there is a twenty (20) second time-delay prior to any function (other than display) becoming active. This time-delay is in effect if the controller On/Off button is used when 24VAC from air conditioners is present, and also if controller is in “ON” position and 24VAC from all connected air conditioners is removed and then restored. FIRE SUPPRESSION CIRCUIT To disable the DC3000 and shut down both air conditioners, terminals F1 and F2 may be used. The F1 and F2 terminals must be jumpered together for normal operation. A normally closed (nc) set of dry contacts may be connected across the terminals and the factory jumper removed for use with a field-installed fire suppression system. The contacts must open if a fire is detected. See appropriate connection diagram - Figures 1, 2 or 3 for this connection. Contacts should be rated for pilot duty operation at 2 amp 24VAC minimum. Shielded wire (22-gauge minimum) must be used, and the shield must be grounded to the controller enclosure. IMPORTANT NOTE: Some Bard models employ an electronic blower control that has a 60-second blower off-delay. In order to have immediate shutdown of the blower motor, in addition to disabling the run function of the air conditioners will require a simple wiring modification at the blower control located in the electrical control panel of the air conditioners being controlled by the lead/lag controller. To eliminate the 60-second blower off-delay, disconnect and isolate the wire that is factory-connected to the “R” terminal on the electronic blower control, and then connect a jumper from the “G” terminal on the blower control to the “R” terminal on the blower control. The electronic blower control will now function as an on-off relay with no offdelay, and the blower motor will stop running immediately when the F1-F2 fire suppression circuit is activated (opened). Stage 1 – 0 seconds for blower (if not already on as continuous) 10 seconds for cooling or heating output Stage 2 – 10 seconds after Stage 1 for blower 10 additional seconds for cooling or heating output Stage 3 – 10 seconds after Stage 2 Stage 4 – 10 seconds after Stage 3 Note: For cooling Stages 1 and 2, the stage LED will blink for 10 seconds while the cooling output is delayed after that stage is called for. There is also a delay after the stage is satisfied, and after the LED stops blinking, the stage will turn off. There is a minimum 10-second delay between stages 2 & 3, and 3 & 4, but no delayed output when stage is turned on or off, and LED for those stages will not blink. BLOWER OPERATION The controller can be configured to have main HVAC blowers cycle on and off on demand; have all blowers run continuously (for DC3003, the blower is not “On” continuously for HVAC #3, but runs on demand only condition); or have the lead unit blower run continuously with the lag unit blower cycling on demand. Lead unit blower operating continuously is the default setting. There is also an option to have all blowers cycle on if one remote sensor is connected, and a temperature difference of more than 5F between any two sensors is observed. This helps to redistribute the heat load within the structure and should reduce compressor operating time. When any of the stages are satisfied, the stage LED will blink for ten (10) seconds before the stage is actually turned off. ADVANCE (SWAP) LEAD/LAG UNIT FEATURE Pressing the Advance button for one (1) second will cause the lead and lag units to change positions. This may be useful during service and maintenance procedures. Note: DC3003 always operates HVAC #3 in last position: only HVAC #1 and #2 operate in lead/lag sequence. ACCELERATE TIMER FEATURE Pressing the UP arrow button for five (5) seconds will activate an accelerate (speed-up) mode, causing the normal changeover time increments of days to be reduced to seconds. Example: 7 days becomes 7 seconds. When “ACC” displays, release button. Whichever LED is on, indicating lead unit will blink over for each second until the controller switches. This is a check for the timer functionality. Manual Page 2100-484A 7 of 22 HUMIDITY CONTROL OPTION The standard air conditioning system can be adapted to perform dehumidification control by addition of a simple humidity controller that closes-on-rise, and is connected to terminals H1 and H2 on the main controller board. Recommended Bard part number is 8403-038 (H600A 1014). See appropriate connection diagram Figures 1, 2 or 3 for this connection. The humidity control logic needs to be enabled in the program menu. Go to HuLE in the Programming Menu and change from No to Yes. This permits the following sequence of operation: 1. Temperature control always has priority over dehumidification. If there is any stage of cooling demand active, the dehumidification sequence is locked out. 2. If all stages of cooling are satisfied, and relative humidity is above the set point of humidity controller: a. The lag unit compressor and blower will operate until the set point of humidity controller is satisfied (or cancelled by a call for cooling). b. If the space temperature drops to 68F, the electric heater of the lead unit will cycle to maintain heating set point. c. If space temperature drops to 2nd stage heating condition (4F below 1st stage), the lag unit compressor operating for dehumidification mode will cycle off until 2nd stage call is satisfied by 1st stage heat and building load. The electric heater in lag unit is locked out in dehumidification mode. CAUTION Humidity controller set point should be in 50-60% relative humidity area: Setting controller to lower settings will result in excessive operating time and operating costs for the electric reheat, and in extreme cases could cause evaporator (indoor) coil freeze-up if there are periods of light internal equipment (heat) loading. SEQUENCE OF OPERATION – COOLING AIR CONDITIONERS – (NO ECONOMIZER) First stage cooling set point is the setting (SP) input into the controller. Factory default is 75F/24C. At Stage 1 cooling SP, the blower of the lead unit will come on (if not already operating because of continuous fan selection for lead unit). The DC fan will also operate at this time if controller is configured for free cooling using DC fan, and if outdoor temperature is 1F or more below (dFon) setting for DC fan operation 50, 55 or 60F (default is 55). DC fan is off at 1F above the (dFon) setting. At Stage 2 cooling call (SP + 2F), the compressor for lead unit comes on. At Stage 3 cooling call (SP + 4F), the blower for the lag unit comes on, followed 10 seconds later by the compressor for the lag unit. SEQUENCE OF OPERATION – COOLING AIR CONDITIONERS – (WITH ECONOMIZERS) First stage cooling set point is the setting (SP) input into the controller. Factory default is 75F/24C. On a call for 1st Stage cooling, the blower will come on immediately (if not already on - See Blower Operation), and the Stage 1 LED will blink for 10 seconds before going solid, at which time the cooling output turns on. If the outdoor temperature and humidity conditions are below the set point of the economizer enthalpy control, the economizer will operate instead of the compressor. If outdoor conditions are not acceptable for free cooling, the compressor will automatically operate instead of the economizer. Stage 2 cooling is 2F (1C) warmer than Stage 1. On a call for 2nd Stage cooling, the blower of the lag unit is turned on, and the Stage LED will blink for 10 seconds before going solid, at which time either the economizer or the compressor will turn on - based on enthalpy control setting and outdoor conditions. Stage 3 cooling is 2F (1C) warmer than Stage 2. On a call for Stage 3 cooling, a signal is input into the lead unit economizer to cancel economizer and force lead unit compressor on. Stage 3 LED comes on solid with no blinking. Stage 4 cooling is 2F (1C) warmer than Stage 3. If the lead unit compressor and lag unit economizer cooling capacity are not sufficient to hold the building temperature, and Stage 4 calls for cooling, a signal is input into the lag unit economizer to cancel economizer and force the lag unit compressor on. Stage 4 LED comes on solid with no blinking. When any of the four (4) Stages are satisfied, the stage LED will blink for 10 seconds before the stage is actually turned off. DC3003 only: Stage 5 cooling is 1F warmer than Stage 4. Stage 5 LED is located on the alarm board mounted inside the controller, and is marked Y1. There is also a Y2 LED, and Y1 and Y2 will cycle together. Manual 2100-484A Page 8 of 22 SEQUENCE OF OPERATION – HEATING (AIR CONDITIONERS W/ELECTRIC HEAT) First stage heating set point is the dead band setting below first stage cooling set point (the SP entered into the program). The dead band is adjustable from 2-20F (1-10C), and the factory default is 10F (5C). Second stage heating set point is 2F (1C) cooler than Stage 1. DC3003 only: Stage 3 heat is the electric heater in HVAC #3. SECURITY (LOCKING) FEATURE The DC3000 controller can be locked such that unauthorized persons cannot make any changes to temperature set points or any other selectable parameters of the controller system. The ON/OFF and Comfort buttons remain fully active for their normal intent. The Advance/Change/Save button remains active for the Advance feature only, which allows the position of the lead and lag air conditioners to be swapped (reversed). The Program button remains partially active - allowing the review of temperature sensor(s) actual reading of temperature, and the current settings/choices that have been chosen. However, no changes can be made when the controller is locked, and if the change button is pressed when in the Program mode, the display will come up showing “Locd” instead of flashing the selectable choices for that parameter. The default (DEF) reset capability is also disabled when the controller is in locked mode. GENERATOR RUN FEATURE If desired, the DC3000 controller can be signaled from a standby generator system to lockout (disable operation) of the lag air conditioning system. This is sometimes mandated if the generator size is not sufficient to handle the building load (amperage) and that of all air conditioning systems. A normally closed (NC) dry contact as part of generator controls is required. These contacts must open when the generator is started, and such action will signal the DC3000 controller to this condition and disable lag air conditioner run function. On DC3003 with 3 HVAC’s, only the “lag” A/C is locked out; the lead A/C and A/C #3 will still function. A wire jumper is factory-installed across the G1 and G2 terminals on main controller board. To utilize the generator run feature, remove the jumper from G1 and G2, and connect the generator normally closed (NC, open-on-run) to the G1 and G2 terminals. BACKUP DC POWER CONNECTION There are input connections available for -24VDC or -48VDC (-20 to -56V) backup power connection. Making this connection will maintain microprocessor operation, front panel display, LED signaling, and alarm relay operation during periods of commercial power outages and when no standby generator is available. This circuit is protected by a replaceable .5A (500mA) 250V fuse. Locking and Unlocking the DC3000 Controller: 1. Locking the controller requires using 3 buttons while the controller is in the normal operating (run) mode. 2. Press and hold the Advance/Change/Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display shows “Locd”. 3. To unlock the controller, press and hold the Advance/Change/Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display shows “uLoc”. IMPORTANT The shelter DC battery power must be connected to the controller and wired as shown in controller wiring diagrams in order to control the DC Fan ventilation package during periods when AC power is not available. The backup DC power connection is polarity sensitive. If polarity is reversed, the controller will not function on backup power, no display and no alarm functions will be evident. Manual Page 2100-484A 9 of 22 DC FAN CONTROL The primary reason the DC30002 or DC3003 controller system would be used is for additionally controlling a DC Fan ventilation system installed in the shelter in addition to controlling either 2 or 3 HVAC units. The DC Fan package and intake system is independent of the HVAC systems, and is supplied by others. A DC Fan pilot-duty control relay, Form C (SPDT) rated at 1A is incorporated into both DC3002 and DC3003 alarm boards for this purpose. DC Fan package must include the load control relay, or be otherwise fieldsupplied. For Emergency Ventilation using the DC Fan package, either “Emergency Ventilation Only” or “Both” must be selected in the Program menu. This means that if the shelter temperature rises to 1F above the High Temperature #2 set-point, the DC Fan control relay will be energized. The High Temperature #2 alarm relay also is energized at the same time. Default setting for High Temperature #2 is 90F. NOTE: If economizers are installed, they can also be used for emergency ventilation. See Emergency Ventilation Sequence Using Economizers on page 16. DC FAN PURGE OPTION The DC Fan control can be configured to be used as follows: 1. For emergency ventilation only 2. For both free cooling and emergency ventilation 3. For free cooling only The controller default setting is “Both” When economizers are used in HVAC units 1 and 2 and Free Cooling is selected, the economizer controls make the decision when the DC Fan can be active as free cooling or not. The logic is as follows: 1. As long as at least one of the HVAC economizers is operating the DC Fan can operate 2. When outdoor conditions are not acceptable for free cooling using the economizers or when indoor load conditions as such that both economizers are forced off, the DC Fan is turned off. This is monitored by the Unit 1 and Unit 2 “Y” signals feeding from the HVAC 1 and 2 units to the DC3002 or DC3003 internal alarm boards. If both Unit 1 and 2 Y signals are present the DC Fan will not operate in Free Cooling mode. When economizers are not used, and Free Cooling with the DC Fan is desired, and optional remote sensor Bard Part Number 8412-023 must be used.: 1. Sensor is connected to main controller board OUT terminals CU (copper wire) and AG (silver colored wire). The sensor is polarity sensitive and will not work correctly if connected in reverse. 2. The sensor must be located outside the shelter and should be in a junction box for physical protection. 3. It should be on the north side of the shelter if possible to keep from being influenced by the effects of the sun. 4. In the Program menu under “dFon” there are 3 choices for the DC Fan decision for free cooling or not: 50-55-60F. Factory default is 55F. 5. If set-point is 55F, the outdoor temperature must be 54F or colder for DC Fan to operate. Above 56F the DC Fan would be inhibited for Free Cooling. Manual 2100-484A Page 10 of 22 The DC Fan can also be used for intermittent purge cycle if desired for purpose of controlling out-gassing from storage batteries or for any other reasons. DC Fan purge duration is defined in minutes: 1. Shown as “Purg” in Programming Menu 2. Choices are No, 1, 2, 3, 4, 5, 6, 7, 8, 9 or 10-minutes 3. Default is set to No DC Fan purge interval is defined in hours: 1. Shown as “Pint” in Programming Menu 2. Choices are 1, 2, 3, 4, 5, 6, 7, 8 up to 24-hours 3. Default is 1-hour 4. The “Pint” display is suppressed if Purg is set to No NOTE: The purge interval starts at the end of the selected purge duration. CONTROLLER WIRING The DC3002 can be used for controlling two (2) air conditioners with or without economizers. The DC3003 can be used for controlling three (3) air conditioners with or without economizers. Units with economizers will connect differently than units without economizers; therefore, it is important to use the correct connection diagram. See Table 1 for correct connection diagrams. TABLE 1 Economiz er Installed Connection Controller No. of Diagram Model HVAC Figure 1 D C 3002 2 HVAC #1 HVAC #2 HVAC #3 Yes Yes --- Figure 2 D C 3002 2 No No --- Figure 3 D C 3003 2 or 3 Yes Yes Yes Figure 4 D C 3003 2 or 3 Yes Yes No Figure 5 D C 3003 2 or 3 No No No FIGURE 1 DC3002 CONNECTION DIAGRAM 2 UNITS WITH ECONOMIZERS Manual Page 2100-484A 11 of 22 FIGURE 2 DC3002 CONNECTION DIAGRAM 2 UNITS NO ECONOMIZERS Manual 2100-484A Page 12 of 22 FIGURE 3 DC3003 CONNECTION DIAGRAMS 3 UNITS WITH ECONOMIZERS Manual Page 2100-484A 13 of 22 FIGURE 4 DC3003 CONNECTION DIAGRAMS 3 UNITS WITH ECONOMIZERS (NO ECONOMIZER A/C #3) Manual 2100-484A Page 14 of 22 FIGURE 5 DC3003 CONNECTION DIAGRAMS 3 UNITS WITH NO ECONOMIZERS Manual Page 2100-484A 15 of 22 ALARM WIRING 2ND STAGE COOLING ALARM Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy. This alarm output is available for use if desired. It is important to note that in some installations, due to A/C system sizing and internal heat load, that the secondary (lag) air conditioning unit may be called upon to assist the lead air conditioner some of the time. If this is the case, or possibly when additional heat load is added, using the 2nd stage cooling alarm will cause nuisance alarm conditions. Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized. When multiple alarms are grouped together and issued as a single alarm, there will no off-site indication of which specific problem may have occurred, only that one of the alarms in the group has been triggered. The individual alarm problem will be shown on the LED display on the face of the controller. Note: All alarm/output relays are Form C (SPDT) dry contacts rated 1A @ 24VAC. The Power Loss and Controller Alarm relays are all “reverse actuated”, which means they are continuously energized (the NO contact is closed) and switched to NC position upon alarm condition. Therefore, it is important to closely follow the alarm board connection diagrams that follow. Any alarm feature that is not desired can simply be ignored (not connected). NOTE: The alarm LED display board is shipped uninstalled to protect it from possible damage during installation of the wiring to main controller board and/or the alarm board. It is polarity sensitive and is keyed so it can only be installed in correct position. NOTE: The LED display board can be replaced if needed independently of the alarm board. Bard part number is 8612-022. ALARM LED DISPLAY BOARD For installations where it is known that there is 100% redundancy (one air conditioning unit can handle 100% of the load 100% of the time) use of the 2nd Stage Cooling Alarm is a method to issue an alarm signal that the lead air conditioner is down (or not delivering full capacity) and that the lag air conditioner is now operating. REFRIGERANT PRESSURE ALARMS Air conditioners with “J” control module are equipped with an alarm relay that is activated upon high or low refrigerant pressure lockout conditions. Connecting terminals 2 and 3 from the air conditioner 24V terminal block to the matching terminals 2 and 3 on the alarm board will allow these alarms to function. EMERGENCY VENTILATION SEQUENCE USING ECONOMIZERS For units with economizers, there are two (2) emergency ventilation sequences designed into the controller. Both require the connection of terminals E and F from the air conditioner 24V terminal block to the matching terminals on the alarm board. Sequence one requires a refrigerant pressure alarm, coupled with high temperature alarm condition No. 1 (HAL 1 set point). If both of these conditions occur, the economizer in the air conditioner that issued the refrigerant alarm will drive open to ventilate the building. Sequence two (HAL 2 set point) is activated by high temperature alarm No. 2, and will initiate even without a refrigerant pressure alarm signal. Both economizers will be activated to provide emergency ventilation. This strategy help protect against building overheating if air conditioner(s) are inoperative for non-pressure related reasons (bad compressor, contactor, run capacitor, etc.). NOTE: The LED display board is polarized and will only fit in one direction as shown. It must be fully inserted in order for the controller to function properly. MIS-2042 Manual 2100-484A Page 16 of 22 FIGURE 6 ALARM BOARD CONNECTIONS FOR NORMALLY CLOSED "NC" OPEN-ON-ALARM STRATEGY Manual Page 2100-484A 17 of 22 FIGURE 7 ALARM BOARD CONNECTIONS FOR NORMALLY OPEN "NO" CLOSE-ON-ALARM STRATEGY Manual 2100-484A Page 18 of 22 PROGRAMMING INSTRUCTIONS To swap lead and lag unit positions, press the ADVANCE button. To enter the Program mode, press the PROGRAM button and release it when the message PROG appears on the display. When in Program mode, the DOWN and UP arrows are used to scroll through the programming steps. NOTE: When using the UP and DOWN arrows, push for approximately 1 second until the alternating display goes blank, then release and display will alternate between the step function and setting. To change the setting of any step, press the CHANGE button and the display will stop flashing, allowing change to the setting by using the DOWN or UP arrows. When desired setting is reached, press the SAVE button, and proceed as desired. When done with programming changes, press the PROGRAM button until display stops flashing and room temperature display is shown. If no buttons are pushed within thirty (30) seconds, the controller will automatically revert back to “RUN” mode. To reset all controller settings to the factory default values, press the PROGRAM button for 10 seconds until display reads dEF. A FLASHING display means that the function or choice is “SET”, and the display will alternate between the step function and setting. NOTE: When the controller has the security locking feature enabled, no changes to any selectable features can be made, and the default reset feature is also locked out. All of the programmable features/settings can be reviewed using the Program button and Up or Down arrows, but any attempt to change settings using the Change button will result is display showing “Locd” indicating controller is locked. See section on Security (Locking) Feature. See next page for Programmable Features, Default Settings and DC3000 front panel label layout. Manual Page 2100-484A 19 of 22 1st Stage 2nd Stage 3rd Stage 4th Stage 1st Stage 2nd Stage 3rd Stage 4th Stage Alarms Note: On the DC3003 version the Lead/Lag Controller alarm light will "Flash" if Unit #3 has Power Loss or Refrig. Alarm. Open cover to observe Fault light that is on the alarm board located inside. Cooling Heating Digital Display Lead Unit Unit #1 Dehumid. Operation Unit #2 Power Loss Sys. 1 Refrig. Alarm Sys. 1 On Off Fire/Smoke Alarm Low Temp. Alarm To swap lead and lag unit positions press the ADVANCE button. To enter the Program mode, press the PROGRAM button and release it when the message PROG, appears on the display. When in Program mode the DOWN and UP arrows are used to scroll through the programming steps. A FLASHING display means that the function or choice is “SET”, and the display will alternate between the step function and setting. To change the setting of any step press the CHANGE button and the display will stop flashing, allowing change to the setting by using the DOWN or UP arrows. When desired setting is reached press the SAVE button, and proceed as desired. When done with programming changes press the PROGRAM button until display stops flashing and room temperature display is shown. If no buttons are pushed within 30-seconds the controller will automatically revert back to "RUN" mode. Power Loss Sys. 2 Refrig. Alarm Sys. 2 Programming Instructions Program High Temp. Alarm 1 High Temp. Alarm 2 Lead/Lag Controller Failure Alarm Advance Change Save Comfort Programming Display Menu Refer to Installation Instructions for complete details. Cooling setpoint temperature SP (65 to 90 deg. F or 18 to 32 deg. C, Default is 75F/24C) Loc Temperature at local (main) Sensor r I Temperature at Remote 1 sensor location* Out Temperature at Outdoor sensor location* time (1 to 30 days LLOC Lead-lag-change-over or 0 for disabled, Default is 7) blower operation cFAn Continuous (None, Lead, Both, Default is lead) temperature alarm setpoint (28 to 65 deg. F LoAL Low or -2 to 18 deg. C, Default is 50F/10C) temperature alarm level 1 setpoint (70 to 120 deg. F HALI High or 21 to 49 deg. C, Default is 85F/24C) temperature alarm level 2 setpoint (70 to 120 deg. F HAL2 High or 21 to 49 deg. C, Default is 90F/32C) dFAn DC Fan Operation (Edcf "emergency vent only", Free "cooling", Both. Default is Both) * If installed. If sensors are not installed, no display is shown. See label inside cover for sensor logic. temperature setpoint for DC Fan dFon Outdoor operation. Requires Outdoor Sensor (50-55-60F, Default is 55) Deadband between cooling and heating setpoint (2 to 20 deg. F or 1 to 11 deg. C, Default is 10F/5C) dE9 Degrees shown in F or C (F or C, Default is F) Dehumidification Logic Enabled (Yes or No, HuLE Default is No) System 1 & 2 blowers run if delta T > 5F CbdS between sensors (Yes or No, Default is Yes) min. lead unit & 4 min. lag unit off-delay OFdE3enabled (Yes or No, Default is No) 3 minute compressor run time crun Minimum enabled (Yes or No, Default is No) compressor Turn On/Turn Off differential with CHYS Increase excessive compressor cycling (Yes or No, Default is Yes) Purg DC fan Purge duration in minutes (No,1,2,3,4,5,6,7,8,9,10 Default is No) Pint Interval between DC Fan Purge cycles in Hours (1,2,3,4,5,6,7,8,9,10 up to 24 Default is 1, Pint display is suppressed if Purg is No) db 7961-665C Manual 2100-484A Page 20 of 22 Comfort Mode Press COMFORT button once to reset to 72°F/22°C Cooling and 68°F/20°C Heating for 1-hour. Display will flash 72 (or 22) during override period. Press 2nd time to cancel during override if desired, or will automatically revert after 1-hour. is locked and no changes can be made. Locd Controller Consult building authority. FIGURE 8 PARTS LIST DESCRIPTION DIAGRAM 1 10 8 6 11 3 2 4 5 7 9 SEXP-445 B Manual Page 2100-484A 21 of 22 TABLE 2 Parts List Manual 2100-484A Page 22 of 22 D w g. N o. Part No. Description D C 3002 D C 3003 1 127-343-4 Control Box X X 2 8612-024 Controller Board X X 3 8612-025 Alarm Board AB3002 X 3 8612-026 Alarm Board AB3003 X 4 8612-022 Alarm Display X 5 113-340-4 Support Bracket X X 6 152-385-4 Control Box Door X X 7 8611-099 LTF Fitting X X 8 5400-002 Hinge X X 9 8612-023 Sensor X X 10 7961-663 Label/Keypad X X
advertisement
Key Features
- Lead/lag control
- DC Fan control
- Economizer control
- Dehumidification control
- Backup power
- Alarm functions
- Security locking feature
- Generator run feature
- Emergency ventilation
- Programmable features
Frequently Answers and Questions
How do I set the temperature set point?
Use the UP and DOWN arrow buttons to increase or decrease the set point.
How do I lock the controller?
Press and hold the ADVANCE/CHANGE/SAVE button and the UP and DOWN arrow buttons simultaneously for 20 seconds until the display shows "Locd".
How do I change the lead/lag unit positions?
Press the ADVANCE button for one second.