Allen-Bradley FLEX I/O Very High-speed Counter Module Installation Instructions
Allen-Bradley FLEX I/O Very High-speed Counter Module is an intelligent I/O module designed for high-speed counting in industrial applications. It interfaces with any Allen-Bradley programmable controller equipped with Ethernet capability. The module offers features like multiple input channels, configurable filters, and programmable outputs for versatile industrial control and monitoring.
PDF
Download
Document
Advertisement
Advertisement
Installation Instructions Original Instructions FLEX I/O Very High-speed Counter Module Catalog Number 1794-VHSC Topic Summary of Changes Overview Install the Module Wire the Module Interpret the Status Indicators Specifications Additional Resources Page 1 3 4 4 8 10 13 Summary of Changes This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes. Topic Updated Certifications Page 12 FLEX I/O Very High-speed Counter Module Installation Instructions O ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. 岤䠑㖈㸝鄳ծꂁ縨ծ乼⡲ㄤ絶䫡劥❡ㅷ霼ꢓ靀劥俒咓⟄⿺ Ⱖ➭餴彂 鿈ⴔⴀ涸剣Ⱒ霃㢊㸝鄳ծꂁ縨ㄤ乼⡲涸湱䎾俒咓կꤑ✫䨾剣鷓欽錞薴ծ岁䖒ㄤ叻ⲥ涸 湱Ⱒ銳宠⛓㢪欽䨪鵮䗳곢擿䜪㸝鄳ㄤ䱹絁霹僈կ 㸝鄳ծ靈侮ծ䫏鵘ծ⢪欽ծ絆鄳ծ䬒⽸ㄤ絶䫡瘝ぐ고乼⡲䗳곢歋絑鵂鷓䔲雲絅涸⚁⚌➃プ䭽撑鷓欽涸乼⡲錞薴㹊倶կ 㥵卓劢䭽撑ⵖ鸣㉁䭷㹁涸倰䒭⢪欽霪霃㢊ⴭ〳腊⠔䰀㹲霃㢊䲿⣘涸⥂䫡կ ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes. El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de práctica aplicable. Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada. ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis. É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o código de prática aplicável. Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada. ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы, перечисленные в разделе «Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования. Пользователи обязаны ознакомиться с инструкциями по установке и прокладке соединений, а также с требованиями всех применимых норм, законов и стандартов. Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться обученным персоналом в соответствии с применимыми нормами и правилами. Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена. : ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten, bevor Sie dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den Installations- und Verdrahtungsanweisungen vertraut machen. Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit den anwendbaren Ausführungsvorschriften vorgenommen werden. Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein. ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer, configurer, utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur. Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur. Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise. : , , , . , . , , , , , , . . ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”, riguardanti l’installazione, la configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici e standard applicabili. Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste. Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa. DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır. Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun şekilde yapılabilir. Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir. 岤䠑✲갪㖈㸞酤鏤㹁乽⡲䧴笞隌劥欴ㅷ锞⯓ꠗ隡姽俒⟝⟃⿻倴 չⰦ➮须彂պ畎眏⚥剤ꡠ㸞酤鏤㹁莅乽⡲姽鏤⪔涸俒⟝⢪欽罏䗳갭擿䜫㸞酤ㄤꂂ箁䭸 爚⚛痘ざ䨾剤岁鋊岁䖒ㄤ垦彋銴宠 ⺫䭍㸞酤锅侮❜➰⢪欽⢪欽穉酤䬓⽹ㄤ笞隌瘞⹛⡲鿪䗳갭❜歋䊺竤麕黠殹鎯箻涸➃㆞鹎遤⟃痘ざ黠欽涸㻜⡲岁鋊 㥶卓㼟鏤⪔欽倴ꬌ醢鸤㉂䭸㹁涸欽鸁儘〳腋剚鸤䧭鏤⪔䨾䲿⣘涸⥃隌⸆腋「䴦 POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigurace a provozu tohoto zařízení. Uživatelé se musejí vedle požadavků všech relevantních vyhlášek, zákonů a norem nutně seznámit také s pokyny pro instalaci a elektrické zapojení. Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy. Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje. UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi kodeksami, prawem i normami. Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z obowiązującym kodeksem postępowania. Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone. OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller utföra underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder. Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk. Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion. LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert, configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen. Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in overeenstemming met de geldende praktijkregels. Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt. 2 Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 FLEX I/O Very High-speed Counter Module Installation Instructions Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/ IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see: • Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements. • NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures. Prevent Electrostatic Discharge ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • Use a static-safe workstation, if available. • Store the equipment in appropriate static-safe packaging when not in use. ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. See Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more information. Overview The FLEX™ I/O very high-speed counter module performs high speed counting for industrial applications. The module is an intelligent I/O module that interfaces signals with any Allen-Bradley® programmable controller that has Ethernet capability. FLEX I/O Very High-speed Counter Module – 1794-VHSC 2 1 3 4 5 7 6 Component Identification 1 2 3 Description Flexbus connector Latching mechanism Keyswitch 4 5 Description Terminal base Terminal base alignment groove 6 7 Description Module alignment bar Module Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 3 FLEX I/O Very High-speed Counter Module Installation Instructions Install the Module Read this for information on how to install the FLEX I/O module, which mounts on a 1794-TB3G or 1794-TB3GS terminal base. ATTENTION: During mounting of all devices, be sure that all debris (metal chips, wire strands, and so on) are kept from falling into the module. Debris that falls into the module could cause damage on power-up. Mount on Terminal Base 1. 2. 3. 4. 5. Rotate the keyswitch (3) on the terminal base (4) clockwise to position 1 as required for this type of module. Make sure the Flexbus connector (1) is pushed all the way to the left to connect with the neighboring terminal base or adapter. You cannot install the module unless the connector is fully extended. Make sure that the pins on the bottom of the module are straight so that they align properly with the connector in the terminal base. Position the module (7) with its alignment bar (6) aligned with the groove (5) on the terminal base. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (2) is locked into the module. Wire the Module ATTENTION: To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies. Do not exceed a length of 3 m (9.8 ft) for DC power cabling. ATTENTION: Do not daisy chain power or ground from this terminal base unit to any AC or DC digital module terminal base units. ATTENTION: Do not wire more than two conductors on any single terminal. IMPORTANT We recommend that you use a twisted-pair, individually shielded cable with a maximum length of 300 m (1000 ft). To connect wiring for 1794-TB3G and 1794-TB3GS terminal bases, see Figure 1 and Table 1 to complete the following: Figure 1 - Wiring for 1794-TB3G and 1794-TB3GS 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 A A A B B Z Z O0 O1 A A B 24V Inputs 16 17 18 B Z Z O2 O3 28 29 30 24V Inputs 19 20 21 22 23 24 25 26 27 31 32 33 B Chassis ground A A B B Z Z R0 R1 A 5V Inputs 34 35 36 37 +24V DC COM NC +V A B B Z Z R2 Chassis R3 ground 5V Inputs 38 39 40 41 42 43 44 45 46 47 48 49 50 51 C -V +V -V NC +24V DC COM Chassis grounds for shields Chassis ground Where: 4 A, A = incremental encoder input A (+5V DC or +24V DC) B, B = incremental encoder input B (+5V DC or +24V DC) Z, Z = incremental encoder input Z (+5V DC or +24V DC) O = sourcing outputs Input power for Output O0 (A-6); Output O1 (A-7) - C-37 (+) and C-39 (-) Input power for Output O2 (A-14); Output O3 (A-14) - C-46 (+) and C-48 (-) R = returns for sourcing outputs Chassis ground +V = +5V or +24V DC isolated power externally supplied for outputs (1 A max) -V = negative isolated power connection (1 A max) +24V DC= 24V DC terminal base power for module COM = return for 24V DC terminal base power for module Chassis ground = chassis ground for input or output cable shields NC = No Connection Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 FLEX I/O Very High-speed Counter Module Installation Instructions Table 1 - Wiring Connections Encoder Inputs A A B B Z Z Outputs O0 O1 O2 O3 24V DC 24V COM 5V or 24V output power -V output power Chassis ground 24V Inputs A-0 A-1 A-2 A-3 A-4 A-5 Source Out A-6 A-7 A-14 A-15 Channel 0 5V Inputs 24V Inputs B-17 A-8 B-18 A-9 B-19 A-10 B-20 A-11 B-21 A-12 B-22 A-13 Return B-23 B-24 B-31 B-32 Terminals C-34 and C-50 Terminals C-35 and C-51 Terminals C-37 and C-46 Terminals C-39 and C-48 Terminals B-16, B-33, C-38, C-40…C-45, C-47 Channel 1 5V Inputs B-25 B-26 B-27 B-28 B-29 B-30 ATTENTION: Do not connect 24V signals to the +5V input terminals. It can result in permanent damage to the module. Block-transfer Read and Write The following block-transfer read and write word bit information is presented for experienced users only. Input Map (Read) Dec Oct Word 0 1 2 3 4 5 6 7 8 Where: 15 14 13 12 11 10 9 0 7 6 5 4 3 17 16 15 14 13 12 11 10 7 6 5 4 3 Channel 0 Current Count (least significant word) Channel 0 Current Count (most significant word) Channel 1 Current Count (least significant word) Channel 1 Current Count (most significant word) Channel 0 Stored/Accumulated Count (least significant word) Channel 0 Stored/Accumulated Count (most significant word) Channel 1 Stored/Accumulated Count (least significant word) Channel 1 Stored/Accumulated Count (most significant word) PE FP NR TF OS 3 OS 2 OS 1 OS 0 C1 C0 ZF ZS C1 PE = Programming error (error code in bits 11:0) FP = Field power (24V DC power lost) NR = Not ready (configuring field programmable array FPGA) TF = Test fail flag = 1 (indicating failure during power-up) red indicator on. Code in bits 2:0 indicate fail code (1 = RAM; 2 = ROM; 3 = EEPROM; 4 = FPGA) Test flag = 1 with red indicator blinking, upper byte of counter control word in nonzero – in production test mode. OS = Output status (current state of output) C1, C0 = Stored data count ZF = Zero frequency detected ZS = Z input status Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 2 2 1 1 0 0 C0 ZF ZS 5 FLEX I/O Very High-speed Counter Module Installation Instructions Output Map (Write) Dec Oct Word 0 1 2 3 Where: 15 14 13 12 11 10 9 0 7 6 5 4 17 16 15 14 13 12 11 10 7 6 5 4 Reserved for test 0 VR1 CP1 CR1 0 LC3 OE3 FO3 0 LC2 OE2 FO2 0 LC1 OE1 FO1 Channel 0 PWM Output Value (0…95.00%) Channel 1 PWM Output Value (0…95.00%) VR = Value reset of stored/accumulated count (channel) CP = Counter preset (channel) CR = Counter reset (channel) LC = Local control (channel) - Outputs remain under control when Flexbus is not powered - 1 = enabled OE = Output enable (channel) - Permitting output to be turned on from FO, compare match, or PWM - 1 = enabled FO = Forced output (channel) - 1 = on PWM = Pulse-width modulation (0…9,500 decimal) 3 3 0 0 2 2 VR0 LC0 1 1 CP0 OE0 0 0 CR0 FO0 Configuration Image When a configuration is sent to the module, it is checked for consistency before being applied. If an error is found, the PE bit is asserted and the module locally retains its previous configuration. Your user application program should monitor the PE bit. Configuration Map Dec Oct 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 15 14 13 12 11 10 17 16 15 14 13 12 Counter Configuration Filter Selection Time Base Value/PWM Period Channel 0 Gate Interval Channel 1 Gate Interval Reserved Channel 0 Rollover Value (least significant word) Channel 0 Rollover Value (most significant word) Channel 1 Rollover Value (least significant word) Channel 1 Rollover Value (most significant word) Channel 0 Preset Value (least significant word) Channel 0 Preset Value (most significant word) Channel 1 Preset Value (least significant word) Channel 1 Preset Value (most significant word) Channel 0 Scaler Channel 1 Scaler 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 21 First Counter 1st ON Value (most significant word) 22 First Counter 1st OFF Value (least significant word) 23 First Counter 1st OFF Value (most significant word) 24 First Counter 2nd ON Value (least significant word) 25 First Counter 2nd ON Value (most significant word) 26 First Counter 2nd OFF Value (least significant word) 27 First Counter 2nd OFF Value (most significant word) 28 First Counter 3rd ON Value (least significant word) 29 First Counter 3rd ON Value (most significant word) 30 First Counter 3rd OFF Value (least significant word) 31 First Counter 3rd OFF Value (most significant word) 6 9 11 0 10 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 0 0 0 0 0 0 0 0 S4 S4 S4 S4 S3 S3 S3 S3 S2 S2 S2 S2 S1 S1 S1 S1 F4 F4 F4 F4 F3 F3 F3 F3 F2 F2 F2 F2 F1 F1 F1 F1 First Counter 1st ON Value (least significant word) Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 FLEX I/O Very High-speed Counter Module Installation Instructions Configuration Map (Continued) Dec Oct 32 15 17 14 16 13 15 12 14 11 13 10 12 33 First Counter 4th ON Value (most significant word) 34 First Counter 4th OFF Value (least significant word) 35 First Counter 4th OFF Value (most significant word) 36 Second Counter 1st ON Value (least significant word) 37 Second Counter 1st ON Value (most significant word) 38 Second Counter 1st OFF Value (least significant word) 39 Second Counter 1st OFF Value (most significant word) 40 Second Counter 2nd ON Value (least significant word) 41 Second Counter 2nd ON Value (most significant word) 42 Second Counter 2nd OFF Value (least significant word) 43 Second Counter 2nd OFF Value (most significant word) 44 Second Counter 3rd ON Value (least significant word) 45 Second Counter 3rd ON Value (most significant word) 46 Second Counter 3rd OFF Value (least significant word) 47 Second Counter 3rd OFF Value (most significant word) 48 Second Counter 4th ON Value (least significant word) 49 Second Counter 4th ON Value (most significant word) 50 Second Counter 4th OFF Value (least significant word) 51 52 53 54 55 Second Counter 4th OFF Value (most significant word) Counter Control Safe State Output Control Safe State Channel 0 PWM Safe State Channel 1 PWM Safe State 9 11 0 10 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 First Counter 4th ON Value (least significant word) Counter Configuration/Mode (Configuration Word 0) Bit Bit 7 15 Mode 6 14 0 0 0 0 1 110 and 111 0 1 5 13 0 0 1 1 0 4 12 0 1 0 1 0 3 2 11 10 Configuration 0 0 0 0 0 0 0 1 0 1 0 1 0 1 1 9 0 8 0 0 1 0 0 1 1 0 1 0 0 1 0 1 Counter 0 Counter 1 Description Counter Encoder X1 PWM Encoder X4 Period/Rate Continuous/Rate Rate Measurement Store Count Disabled Mode 1 – Store/Continue Mode 2 – Store; Reset/Resume Mode 3 – Store; Reset/Wait/Start Mode 4 – Store; Reset/Start Reserved Z input not inverted Z input inverted Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 7 FLEX I/O Very High-speed Counter Module Installation Instructions Filter Selection (Configuration Word 1) Bit Bit 7 15 0 6 14 ZF 5 13 BF 4 12 AF 3 11 Filter 0 0 0 0 1 2 10 1 9 0 8 0 0 0 1 0 0 0 1 0 0 0 1 0 0 0 Counter 0 Counter 1 Description No filter 50 kHz (10 µs + 0 µs/-1.6 µs) 5 kHz (100 µs + 0 µs/-13.2 µs) 500 Hz (1.0 ms + 0 ms/-125 µs) 50 Hz (10.0 ms + 0 ms/-1.25 ms) A input not filtered A input filtered B input not filtered B input filtered Z input not filtered Z input filtered 0 1 0 1 0 1 Interpret the Status Indicators This module has one red/green power/status indicator (OK), and one yellow indicator for each input and output. The I/O status indicators are multiplexed in 2 groups (A0, B0, Z0, O0, O1); and (A1, B1, Z1, O2, O3) at a frequency of 488 Hz. If inputs or outputs change at or near that frequency, the indicators vary in brightness. Allen-Bradley 1794-VHSC VERY HIGH SPEED COUNTER MODULE 0 B A A Z 0 OUT 1 A 1 B Z OUT 2 3 A = Status indicators B = Power indicator B Input and Output Status Indicators Indicator A (status of input A) B (status of input B) Z (status of input Z) Out 0, 1, 2, 3 Status Yellow Off Yellow Off Yellow Off Yellow Off Description The input A is active. The input A is not active. The input B is active. The input B is not active. The input Z is active. The input Z is not active. The output is On. Individual output is Off. When an active indicator (yellow) is lighted, a valid signal (active high or active low) is present at the input terminals. The module power/status indicator (OK) shows that power is applied to the module, and the status of the module. 8 Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 FLEX I/O Very High-speed Counter Module Installation Instructions Module Status Indicators Indicator Status Description • Hardware diagnostic error, TF set to 1 and module/channel status contains error code. • Hardware runtime failure (that is, watchdog timeout), module communication ceases. • The module is configuring hardware, NR is set to 1. • The module is in test mode (bits 8…15 of counter control word are nonzero), TF set to 1. Steady red Flashing red Flashing red with occasional flashing green Steady green OK • The module 24V power is below minimum rating. • The module is active and behaving normally. • The module is not configured. • Programming error, PE is set to 1 and the error code is supplied in bits 0…11 of the module/channel status word. • Field power fault, FP set to 1. • Adapter powered down, and module local power still active. • The ControlNet® cable is disconnected. • PLC in PROG mode. Flashing green Diagnostic Codes Returned by the Module If an incomplete, incorrect, or conflicting set of configuration parameters is sent to the module, the PE bit is asserted, the green module status indicator flashes, and an error code is displayed in bits 0…11 of the module/channel status word. The codes are identified in Table 2. Use a CIO instruction to access this information. Table 2 - Diagnostics Reported by Input Data Word 8 Read Word Bit 00 01 02 03 04 Word 8 05 06 07 08 09 10 11 Description A reserved configuration or mode was programmed. ZF/BF/AF were selected and no filter was programmed, or multiple filters were selected. A time base was entered that was not a multiple of 10, or the time base is out of range (>3000, that is 3 s). A configuration that requires a time base was selected and no gate interval was set, or the gate interval is out of range (>3 s) or the product of time base and gate interval is greater than 3 s. A rollover of zero was programmed through PWM was not selected; a rollover was programmed and PWM was selected; or the rollover is out of range (1 < rollover < 16,777,216). The preset (1 < preset < 16,777,216) is out of range. A configuration was selected that requires a scalar, and no scalar was programmed or multiple scalars were selected. A tie has been connected to an unprogrammed window. Counter 0 window ON and OFF values are equal and not zero or counter 0 window ON and OFF value greater than 16,777,215. Counter 1 window ON and OFF values are equal and not zero or counter 1 window ON and OFF value greater than 16,777,215. Reserved During hardware self-tests, when either Flexbus power or terminal base power is first applied and a fatal error occurs, the TF bit is asserted and the red module/power status indicator comes on. An error code is placed in the lower byte of the module/channel status word to indicate the failed resource. Use a CIO instruction to access this information. When using the CIO instruction, this would be word 10. Word 9 Bit Description Read Word Bit Word 9 00…07 02 01 00 Dec. 0 0 1 1 0 1 0 2 0 1 1 3 1 0 0 4 All other combinations are not used. Definition RAM test failed. ROM checksum test failed. EEPROM test failed. Programmable Gate Array loading failed. Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 9 FLEX I/O Very High-speed Counter Module Installation Instructions Specifications Input Specifications Attribute Number of input channels Number of inputs per counter Input voltage, determined by the terminal base terminations Input current Voltage, input, off-state Current, input, off-state Voltage, input, on-state Current, input, on-state Voltage, on-state, max Input frequency, max Input filter selections Value 2 2 groups of A/A, B/B, and Z/Z pairs with 5V DC or 15…24V DC terminations 5V DC or 15…24V DC 5V DC terminations: 19.1 mA @ 5V DC 25.7 mA @ 6V DC 15…24V DC terminations: 6.1 mA @ 15V DC 10.2 mA @ 24V DC 5V DC terminations: ≤1.25V DC 15…24V DC terminations: ≤1.8V DC ≤0.25 mA 5V DC terminations: ≥2.6V DC 15…24V DC terminations: ≥12.5V DC ≥5 mA 5V DC terminations: ±6V 15…24V DC terminations. See Derating Curve on page 12. 1.0 MHz counter and encoder X1 (no filters) 500 kHz encoder X2 (no filters) 250 kHz encoder X4 (no filters) Off, 10 µs, 100 µs, 1.0 ms, 10.0 ms per A/B/Z group Output Specifications Attribute Number of outputs Output control Voltage range, output supply Leakage current, off-state Voltage drop, on-state Current, on-state, max Current per output pair, max Short circuit current Surge current Delay time, Off to On Delay time, On to Off 10 Value 2 isolated groups of 2: (0.5 A @ 5V DC, max; 1.0 A @ 12…24V DC, max) Outputs can be tied to 8 compare windows 5…7V DC 10…31V DC Less than 300 µA 5V DC terminations: 0.9V DC @ 0.5 A 12…24V DC terminations: 0.9V DC @ 1.0 A 5V DC terminations: 0.5 A 12…24V DC terminations: 1.0 A 5V DC terminations: 0.5 A 12…24V DC terminations: 1.0 A 5V DC terminations: 0.9 A 12…24V DC terminations: 4.0 A The outputs are short-circuit protected and turned off until power is cycled. 2 A for 50 ms, repeatable every 2 s 25 µs (load dependent) 150 µs (load dependent) Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 FLEX I/O Very High-speed Counter Module Installation Instructions General Specifications Attribute Module location External DC power supply voltage range, nom External DC power supply voltage External DC power supply current Dimensions, H x W x D, with module installed on terminal base, approx. Value 1794-TB3G and 1794-TB3GS 24V DC 19.2…31.2V DC (includes 5% AC ripple) 100 mA @ 24V DC 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in.) 50V (continuous), Basic Insulation Type, between six isolated areas including: Flexbus Module 24V DC power A0/B0/Z0 inputs Isolation voltage A1/B1/Z1 inputs 00/01 and output power supply 1 02/03 and output power supply 2 Tested @ 850V DC for 1 s Flexbus current 75 mA @ 5V DC (with terminal base power off) Power dissipation, max 5.0 W @ 31.2V DC Thermal dissipation, max 17.1 BTU/hr @ 31.2V DC indicator – 1 green/red Indicators (field side driven, logic side Power/status Input status indicators – logic side – 6 yellow indication) Output status indicators – logic side – 4 yellow Keyswitch position 1 Enclosure type rating None (open-style) Wire size Determined by the installed terminal base 2 – on signal ports Wiring category(1) 2 – on power ports Terminal base screw torque Determined by the installed terminal base (1) Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Environmental Specifications Attribute Temperature, operating Temperature, nonoperating Surrounding air temperature, max Relative humidity Vibration Shock, operating Shock, nonoperating Conducted emission ESD immunity Radiated RF immunity Value IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…55 °C (32…131 °F) IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…+85 °C (-40…+185 °F) 55 °C (131 °F) IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95% noncondensing IEC60068-2-6 (Test Fc, Operating): 5 g @ 10...500 Hz IEC60068-2-27 (Test Ea, Unpackaged shock): 30 g IEC60068-2-27 (Test Ea, Unpackaged shock): 50 g IEC 61000-6-4: 0.15…30 MHz on power ports. IEC 61000-4-2: ±6 kV direct and indirect contact discharges ±8 kV air discharges IEC 61000-4-3: 10V/m with 1 kHz 80% AM 3 s dwell time from 80…6000 MHz 10V/m with 200 Hz 50% Pulse 100% AM 3 s dwell time at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM 3 s dwell time at 1890 MHz Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 11 FLEX I/O Very High-speed Counter Module Installation Instructions Environmental Specifications (Continued) Attribute Value IEC 61000-4-4: ±2 kV @ 5 kHz on power ports ±2 kV @ 5 kHz on signal ports ±4 kV @ 5 kHz & 100 kHz on earth port IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports with IO coupling ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports with IO coupling ±2 kV line-earth(CM) on shielded ports with HVO coupling IEC 61000-4-6: 10V rms with 1 kHz sine wave 80% AM 3 s dwell time from 0.15…80 MHz on power and earth port 10V rms with 1 kHz sine wave 80% AM 3 s dwell time from 0.15…80 MHz on shielded ports EFT/B immunity Surge transient immunity Conducted RF immunity Bridge and Deck Zone: 10V rms with 1 kHz sine wave 80% AM 3 s dwell time at sensitive frequencies on power, signal, and earth port Certifications Certifications (when product is marked)(1) CE RCM KC Morocco Value European Union 2014/30/EU EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61131-2; Programmable Controllers EN 61000-6-4; Industrial Emissions European Union 2011/65/EU RoHS, compliant with: EN 50581; Technical documentation Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Arrêté ministériel n° 6404-15 du 29 ramadan 1436 (1) See the Product Certification link at rok.auto/certifications for Declarations of Conformity, Certificates, and other certification details. Derating Curve 30 29 24 20 Input Voltage (V) 10 0 0 10 20 25 30 40 50 55 Ambient Temperature o C The area within the curve represents the safe operating range for the module under various conditions of user supplied 24V DC supply voltages and ambient temperatures. This includes all possible mounting positions, including inverted horizontal. 12 Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 60 FLEX I/O Very High-speed Counter Module Installation Instructions Additional Resources These documents contain more information about related products from Rockwell Automation. You can view or download publications at rok.auto/literature. Resource FLEX I/O Very High-speed Counter Module User Manual, publication 1794-UM010 FLEX I/O and FLEX I/O-XT Selection Guide, publication 1794-SG002 Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, rok.auto/certifications Description Describes how to configure and use a FLEX I/O Very High-speed Counter module. Provides specifications for selecting FLEX I/O and FLEX I/O-XT™ products. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. Rockwell Automation Publication 1794-IN067E-EN-P - March 2024 13 Rockwell Automation Support Use these resources to access support information. Technical Support Center Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product notification updates. Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/support rok.auto/phonesupport Technical Documentation Center Quickly access and download technical specifications, installation instructions, and user manuals. rok.auto/techdocs Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature Product Compatibility and Download Center (PCDC) Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/pcdc Documentation Feedback Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. Waste Electrical and Electronic Equipment (WEEE) At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Allen-Bradley, expanding human possibility, FactoryTalk, FLEX, FLEX I/O-XT, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. ControlNet is a trademark of ODVA, Inc Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 1794-IN067E-EN-P - March 2024 | Supersedes Publication 1794-IN067D-EN-P - May 2022 Copyright © 2024 Rockwell Automation, Inc. All rights reserved. ">
Advertisement
Key Features
- High-speed counting
- Multiple input channels
- Configurable filters
- Programmable outputs
- Ethernet interface
- Allen-Bradley compatibility
- Industrial environment suitability
Frequently Answers and Questions
What is the maximum input frequency the module can handle?
The maximum input frequency for the module depends on the filter selection and the encoder type. For example, with no filters, the maximum input frequency is 1.0 MHz for counter and encoder X1, 500 kHz for encoder X2, and 250 kHz for encoder X4.
How many outputs does the module have?
The module has two isolated groups of two outputs each, with a maximum current capacity of 0.5 A @ 5V DC or 1.0 A @ 12…24V DC.
What are the different output control options?
The module supports various output control methods, including forced output, compare match, and pulse-width modulation (PWM).