Installation Instructions
Original Instructions
Kinetix 5700 DC-bus Link Kits
Catalog Numbers 2198-BARCON-55DC200, 2198-BARCON-85DC200, 2198-BARCON-100DC200,
2198-BARCON-165DC200, 2198-BARCON-220DC200, 2198-BARCON-275DC200, 2198-BARCON440DC200, 2198-KITCON-ENDCAP200
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is
not intended to reflect all changes. Translated versions are not always available for each revision.
Topic
Page
Added ArmorKinetix™ System Power Interface Module (PIM) catalog numbers to the table in support of the
ArmorKinetix drive.
1
The Kinetix® 5700 DC-bus link kits are used to extend DC-bus power from drive-to-drive in DC-bus multi-axis
configurations. DC-bus links are rated for 208 A, maximum bus-bar current.
DC-bus Link Kit Applications
DC-bus Link Kit
Cat. No.
Kinetix 5700 Drive
Module Type
Kinetix 5700 Drive Module
Cat. No.
Description
2198-BARCON-55DC200
Dual-axis inverter
2198-D006-ERSx, 2198-D012-ERSx,
2198-D020-ERSx, 2198-D032-ERSx,
2198-PIM070
DC-bus link, 55 mm, 208 A
2198-BARCON-85DC200 (1)
2198-BARCON-100DC200
Dual-axis inverter
2198-D057-ERSx
Single-axis inverter
2198-S086-ERSx, 2198-S130-ERSx
Single-axis inverter
2198-S160-ERSx
iTRAK® power supply
2198-W25K-ER
2198-BARCON-165DC200
2198-BARCON-275DC200
2198-RP088
Regenerative Bus Supply
2198-BARCON-440DC200
DC-bus link, 85 mm, 208 A
DC-bus link, 100 mm, 208 A
DC-bus link, 165 mm, 208 A
2198-RP200
DC-bus link, 275 mm, 208 A
2198-RP263, 2198-RP312
DC-bus link, 440 mm, 208 A
2198-BARCON-220DC200
Single-axis inverter
2198-S263-ERSx, 2198-S312-ERSx
DC-bus link, 220 mm, 208 A
2198-KITCON-ENDCAP200
DC-bus supply
2198-P031, 2198-P070, 2198-RP088,
2198-P141, 2198-RP200, 2198-P208,
2198-RP263, 2198-RP312
DC-bus end caps, 208 A
(1)
When two or three 2198-P208 DC-bus supplies are connected in parallel, one 85 mm DC-bus link is required for each additional power supply.
See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002, for detailed information on wiring, applying
power, troubleshooting, and integration with Logix 5000™ controllers.
Install the DC-bus Links
ATTENTION: To avoid hazard of electrical shock, perform all mounting and wiring of the
Kinetix 5700 drives and DC-bus link kits before applying power. Once power is applied, connector
terminals can have voltage present even when not in use.
IMPORTANT
When the shared-bus connection system is used, the zero-stack tab and cutout must be
engaged between adjacent drive modules.
The DC-bus connection system is comprised of two components:
• DC-bus links that are inserted between drive modules to extend the DC bus from drive to drive
• DC-bus end caps that are inserted into the first and last drive modules to cover the exposed DC-bus
connector on both ends of the bus
This example configuration illustrates the shared DC-bus connection system and consists of one 2198-P208 DC-bus
power supply, one 2198-S160-ERSx single-axis inverter, one 2198-S086-ERSx single-axis inverter, and one
2198-D006-ERSx dual-axis inverter.
Zero-stack Tab
and Cutout Engaged
DC-bus Link, 85 mm
End Caps (2)
DC-bus Link, 100 mm
(seated)
DC-bus Link, 55 mm
Lower Pivot
Latch
DC Link Latched
Kinetix 5700 Drive System
DC power supply is
mounted leftmost
followed by drive with
largest amp rating.
DC-bus Power Supply
(1)
Align the DC-bus link
lower pivots with the
latches and push
downward until they
latch.
Upper Pivot
DC-bus Link Latch Example (1)
Dual-axis Inverter, 55 mm
Single-axis Inverter, 85 mm
Single-axis Inverter, 100 mm
DC-bus links latch on both sides when inserted into the DC-bus connectors. To remove the DC-bus link, verify that there is no bus voltage present,
depress both sets of upper pivots to unlatch the lower pivots, and hold the DC-bus link firmly while pulling upward.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.
For technical support, visit rok.auto/support.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE
Yönetmeliğine Uygundur
Allen-Bradley, ArmorKinetix, expanding human possibility, iTRAK, Kinetix, Logix 5000, and Rockwell Automation are trademarks of
Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 2198-IN007D-EN-P - February 2023 | Supersedes Publication 2198-IN007C-EN-P - October 2018
Copyright © 2023 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
1535120000
DIR 1000xxxxxx (Version
00)
">