Allen-Bradley ArmorBlock 16-channel IO-Link Hub User Manual
Allen-Bradley ArmorBlock 16-channel IO-Link Hub is a compact, rugged device designed for industrial environments. It expands the capabilities of your IO-Link master module with additional I/O channels, allowing you to connect more sensors and actuators. The hub features M12 connectors for easy wiring, and is available in configurations for digital inputs, outputs, or a combination of both. It's ideal for machines with moderate I/O concentration and offers diagnostic capabilities for improved machine health monitoring.
PDF
Download
Document
Advertisement
Advertisement
ArmorBlock 16-channel IO-Link Hub Catalog Numbers 1732IL-IB16M12, 1732IL-10X6M12, 1732IL-16CFGM12M12L User Manual Original Instructions ArmorBlock 16-channel IO-Link Hub User Manual Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. These labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). The following icon may appear in the text of this document. Identifies information that is useful and can help to make a process easier to do or easier to understand. 2 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Table of Contents About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Purpose of This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Chapter 1 ArmorBlock 16-channel IO-Link Hub ArmorBlock 16-Channel IO-Link Hubs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 IO-Link System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Module Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Chapter 2 Connect and Operate with IOLink Masters Operation with IO-Link Masters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Configure Parameters Activate or Deactivate Block Communication . . . . . . . . . . . . . . . . . . . . . . 13 Restore the IO-Link Hub to Factory Default Settings . . . . . . . . . . . . . . . 13 Configure IO-Link Device Parameters Using Message Instructions . . 13 About the IO-Link Device Parameter Object . . . . . . . . . . . . . . . . . . . . 13 Parameters and Identification Information . . . . . . . . . . . . . . . . . . . . . . . 14 View IO-Link Hub Identity Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Change Identification Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Description of Parameter Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Parameters for Operation Configuration . . . . . . . . . . . . . . . . . . . . . . 18 Parameters for Input Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Parameters for Input Latching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Parameters for Input Logic Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Parameters for Output Fault Values . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Parameters for Output Fault Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Chapter 3 Chapter 4 Diagnostic Properties Device Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Parameters for Device Config. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Parameters for General Diagnostic Settings . . . . . . . . . . . . . . . . . . . . 24 Device Status in Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Chapter 5 Download and Install IO-Link Device Descriptions Download the IO-Link Device Description. . . . . . . . . . . . . . . . . . . . . . . . . 29 Register an IODD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Appendix A Configure IO-Link Hub as a Generic IO-Link Device Input and Output Process Data for 1732IL-IB16M12. . . . . . . . . . . . . . . . . 31 Input Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Output Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 3 Table of Contents Input and Output Process Data for 1732IL-10X6M12 . . . . . . . . . . . . . . . . 32 Input Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Output Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Input and Output Process Data for 1732IL-16CFGM12M12L . . . . . . . . . . 32 Input Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Output Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Description of Process Data Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Configure IO-Link Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Tag Name Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Appendix B Interpret Status Indicators Status Indicator Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Status Indicator Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Appendix C Wire your IO-Link System Recommended Wiring Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Appendix D History of Changes Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 4 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Preface About This Publication This manual describes how to use the ArmorBlock® 16-Channel IO-Link hubs. Make sure that you are familiar with the following: • Use of a controller in a Logix 5000® control system • Studio 5000 Logix Designer® environment IMPORTANT You must use Studio 5000 Logix Designer, version 20 or later, to configure the ArmorBlock IO-Link hubs. Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in alignment with the movement toward inclusive language in technology. We are proactively collaborating with industry peers to find alternatives to such terms and making changes to our products and content. Please excuse the use of such terms in our content while we implement these changes. Summary of Changes This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes. Translated versions are not always available for each revision. Topic Updated template Added inclusive language acknowledgment Improved description of 1732IL-16CFGM12M12L power consumption Added Appendix D - History of Changes Added Index Page throughout 5 8 43 45 Who Should Use This Manual This manual is intended for trained and qualified personnel who are responsible for installing, configuring, and troubleshooting the ArmorBlock 16-Channel IO-Link hubs. Purpose of This Manual This manual provides information and describes the procedures that are used to configure, operate, and troubleshoot the ArmorBlock 16-Channel IO-Link hubs. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 5 Preface Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource ArmorBlock 16-Channel IO-Link Hubs Installation Instructions, publication 1732IL-IN001 ArmorBlock I/O Module Selection Guide, publication 1732-SG001 ArmorBlock I/O 8 Channel IO-Link Master Module User Manual, publication 1732E-UM007 POINT I/O 4 Channel IO-Link Master Module User Manual, publication 1734-UM020 Description Describes how to install and wire the ArmorBlock IO-Link hubs. Provides specifications, wiring diagrams, and module block diagrams for ArmorBlock I/O blocks, and IO-Link master and hubs. Describes how to use the ArmorBlock I/O 8-channel IO-Link Master Module. Describes how to use the POINT I/O™ 4-Channel IO-Link Master Module. Describes how to configure and use EtherNet/IP™ devices to communicate on the EtherNet/IP network. Describes basic Ethernet concepts, infrastructure components, and infrastructure features. Ethernet Reference Manual, publication ENET-RM002 Provides guidance on how to conduct security assessments, implement Rockwell Automation System Security Design Guidelines Reference Manual, publication SECURE-RM001 products in a secure system, harden the control system, manage user access, and dispose of equipment. Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Provides a quick reference tool for Allen-Bradley® industrial automation controls and assemblies. Specifications, publication IC-TD002 Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general Safety Guidelines for the Application, Installation, and Maintenance of Solid-State guidelines for the application, installation, and maintenance of solid-state control in the form of Control, publication SGI-1.1 individual devices or packaged assemblies incorporating solid-state components. Provides general guidelines for installing a Rockwell Automation industrial system. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Provides declarations of conformity, certificates, and other certification details. Product Certifications website rok.auto/certifications. EtherNet/IP Network Devices User Manual, publication ENET-UM006 You can view or download publications at rok.auto/literature. 6 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 1 ArmorBlock 16-channel IO-Link Hub Topic ArmorBlock 16-Channel IO-Link Hubs IO-Link System Before You Begin Module Overview ArmorBlock 16-Channel IO-Link Hubs Page 7 7 8 8 The ArmorBlock 16-Channel IO-Link hubs are used with an IO-Link master to add additional I/O into the system. They are suitable for use in machines and installations with moderate I/O concentration. The ArmorBlock 16-Channel IO-Link hubs are compact and well built for direct field service in tough industrial environments. The fully sealed housing is made of die-cast zinc to help protect electronic components from environmental factors. There are three IO-Link hubs with different channel configurations available – 16 digital inputs; 10 digital inputs and 6 digital outputs; and 16 configurable digital inputs/outputs. IO-Link hubs with digital outputs or configured with outputs feature an Output Fault Value function. This function enables you to configure the behavior of each output channel if there are interruptions or loss of communications. For electrical connection, the widely adopted M12 connector system is used with M12 A-coded connectors for I/O signals and an IO-Link interface. IO-Link System IO-Link technology is a worldwide open-standard protocol that integrates sensors into our Connected Enterprise® by connecting the IO-Link enabled device into an IO-Link master module. You can deliver data from the sensor directly into a control system efficiently. The flexibility of IO-Link capable sensors allows machines to operate more effectively by providing the controller with diagnostics. In addition to product detection, sensors provide detailed and accurate machine health status to improve uptime. The IO-Link system is a configuration of IO-Link masters, IO-Link hubs, and IO-Link enabled devices, such as sensors, actuators, and valves. The IO-Link master provides a network interface to the controller and controls the communication to the IO-Link enabled devices. The connection between masters, hubs, and devices can be achieved with a standard unshielded connection cable. You can connect the IO-Link devices directly to the ports of the IO-Link master. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 7 Chapter 1 ArmorBlock 16-channel IO-Link Hub Figure 1 - The IO-Link System Configuration Example 1 (Front) 2 (Rear) Studio 5000 Logix Designer ControlLogix® 5370 L3 PWR1 PWR2 1 2 3 4 1783-US4T1F 5 5 IO-Link sensor IO-Link master IO-Link sensor Stratix® 2000 IO-Link master Standard sensor IO-Link sensor IO-Link sensor IO-Link hub Standard sensor Standard sensor Standard sensor IO-Link hub IO-Link technology Before You Begin Before you use ArmorBlock 16-Channel IO-Link hubs, connect the IO-Link hub to the IO-Link master. For more information on the installation and connection of the IO-Link hub to the IO-Link master, see the ArmorBlock 16-Channel IO-Link Hubs Installation Instructions, publication 1732IL-IN001. Module Overview The ArmorBlock 16-Channel IO-Link hubs receive binary signals from the devices and transfer them to the controller through the IO-Link master. • 1732IL-IB16M12 has 16 digital inputs. • 1732IL-10X6M12 has 10 digital inputs and 6 digital outputs. • 1732IL-16CFGM12M12L has 16 channels that can be configured as either digital inputs or digital outputs. The ArmorBlock 16-Channel IO-Link hubs draw power from the following power connectors on the respective hubs. • 1732IL-IB16M12 draws module and sensor power from (L+/-). • 1732IL-10X6M12 draws module and sensor power from (L+/-), and output power from (2L+/-). • 1732IL-16CFGM12M12L draws module power from IO-Link connector (L+/-), sensor (US) and output power (UL) from M12 L-code connector. See ArmorBlock 16-Channel IO-Link Hubs Installation Instructions, publication 1732IL-IN001 for the specific pin out. 8 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 1 ArmorBlock 16-channel IO-Link Hub Figure 2 - ArmorBlock 16-Channel IO-Link Hubs 1732IL-IB16M12 1732IL-10X6M12 M12 style A-coded I/O connectors 1732IL-16CFGM12M12L M12 style A-coded I/O connectors M12 style L-coded power connector M12 style A-coded IO-Link connector M12 style A-coded IO-Link connector Functional earth(1) (1) Functional earth is provided for the grounding of field devices and is internally connected to each Pin 5 of the M12 style A-coded I/O ports. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 9 Chapter 1 ArmorBlock 16-channel IO-Link Hub Notes: 10 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 2 Connect and Operate with IO-Link Masters Topic Operation with IO-Link Masters Operation with IO-Link Masters Page 11 The ArmorBlock 16-Channel IO-Link hubs operate with IO-Link masters via the IO-Link connector. The IO-Link hubs feature 8 x M12 connectors that can support up to 16 digital channels. Each IO-Link hub takes one IO-Link channel from the IO-Link master. For more information on how to use the IO-Link master, see the respective IO-Link master user manual. If you are using an ArmorBlock IO-Link master, see the ArmorBlock I/O 8 Channel IO-Link Master Module User Manual, publication 1732E-UM007. If you are using a POINT I/O IO-Link Master module, see the POINT I/O 4 Channel IO-Link Master Module User Manual, publication 1734-UM020. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 11 Chapter 2 Connect and Operate with IO-Link Masters Notes: 12 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 3 Configure Parameters Topic Activate or Deactivate Block Communication Restore the IO-Link Hub to Factory Default Settings Parameters and Identification Information Description of Parameter Data Activate or Deactivate Block Communication Restore the IO-Link Hub to Factory Default Settings Page 13 13 14 17 IO-Link enables you to transfer all parameter data from the controller as a block. Activate block communication by using the command “ParamDownLoadStart”, index 0x02, subindex 0, 3. To deactivate block communication, use the command “ParamDownLoadEnd”, index 0x02, subindex 0, 4. For information on how to use a message instruction to get index information, see the ArmorBlock I/O 8 Channel IO-Link Master Module user manual, publication 1732E-UM007. You can restore your ArmorBlock IO-Link hub to factory default settings by performing one of the following: • Activate the IO-Link specified system command “Restore factory settings.” The command requires that 0x0082 is written to index 0x02, subindex 0. • Set output bit “ConfigRST” to “1”. You can also access the bit under index 0x0040, subindex 3, bit 2. • From the Diagnostics tab in the IO-Link master Add-on Profile (AOP), click “Restore Factory Settings”. Configure IO-Link Device Parameters Using Message Instructions Use message instructions to the IO-Link Device Parameter Object to read or change configuration parameters for IO-Link devices with IO-Link Device Description (IODD) Basic or Generic integration. For more information on how to create a message instruction, see the ArmorBlock I/O 8 Channel IO-Link Master Module user manual, publication 1732E-UM007. About the IO-Link Device Parameter Object IO-Link device configuration parameters include multiple sets of index/ subindex pairs, a length, and a data value that is sent to the IO-Link master through instances of the IO-Link Device Parameter Object. The IO-Link Device Parameter Object provides a mechanism for a CIP™ client to access parameters within an IO-Link device. Within this class, the instance number maps to an IO-Link index value. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 13 Chapter 3 Configure Parameters The details of each index and subindex depend entirely on the IO-Link device and are described in the IODD XML file for that device. Parameters and Identification Information The following tables show direct parameters, identification information, and device access locks for the ArmorBlock IO-Link hubs. These configuration settings are only available in 1732 (AOP) version 3.1.xx or later, and 1734 AOP version 2.1.xx or later. Not all indexes can be configured in the AOP. However, you can use CIP message instructions to configure all available indexes. View IO-Link Hub Identity Details In the Studio 5000 Logix Designer application, you can view the identity details of your ArmorBlock IO-Link hub from the IO-Link > Common tab. Figure 3 - Example of Common Tab in Studio 5000 Logix Designer Table 1 - Direct Parameter 1 Index 0x0000 14 Subindex Parameter 8 9 10 11 Vendor ID1 (MSB) Vendor ID2 (LSB) Device ID1 (MSB) Device ID2 12 Device ID3 (LSB) Access Data Length (Byte) Data Type Default Value 0x0002 RO Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 1 UINT8 0x00012A = 1732IL-IB16M12, 0x00012B = 1732IL-10X6M12, 0x00012C = 1732IL-16CFGM12M12L Chapter 3 Configure Parameters Table 2 - Device Access Locks Index Parameter 1 Parameters (write) Access (opt.) 0 2 Data storage lock Lock parameter upload 0 = Unlocked (default) 1 = Locked 0x00C 3 4 Local parameterization (opt.) Local user interface (opt.) Access Data Length (Byte) Subindex RW 1 bit Data Type Default Value Boolean 0 Change Identification Information You can change the application-specific tag and view the rest of the identity details for your ArmorBlock IO-Link hub from the IO-Link > Identification tab. Figure 4 - Example of Identification Tab in Studio 5000 Logix Designer Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 15 Chapter 3 Configure Parameters Table 3 - Identification – 1732IL-IB16M12 Index Subindex Parameter Access Data Length (Byte) Data Type Default Value 0x0010 Vendor Name Allen-Bradley 0x0011 Vendor Text 0x0012 0x0013 0x0014 0x0015 Product Name Product ID Product Text Serial Number Hardware Version Firmware revision Application Specific Tag Electrical Node ID Location Tag www.ab.com/sensors(1) 1732IL-IB16M12 1732IL-IB16M12 Series A IO-Link Hub, 16 Point Digital Input SV****** 0x0016 0 0x0017 0x0018 0x0019 0x001A 64 RO 16 String 1.0 64 1.011 RW 32 *** 32 *** 32 *** (1) Search for “Sensors” on the IO-Link Smart Devices with IO-Link Technology product page. Table 4 - Identification – 1732IL-10X6M12 Index Subindex Parameter Access Data Length (Byte) Data Type 0x0010 Vendor Name Allen-Bradley 0x0011 Vendor Text 0x0012 0x0013 Product Name Product ID 0x0014 Product Text 0x0015 Serial Number Hardware Version Firmware revision Application Specific Tag Electrical Node ID Location Tag www.ab.com/sensors(1) 1732IL-10X6M12 1732IL-10X6M12 Series A IO-Link Hub, 10 Point Digital Input, 6 Point Digital Output SV****** 0x0016 0x0017 0x0018 0x0019 0x001A 0 64 RO 16 String 1.0 64 1.011 RW 32 *** 32 *** 32 *** (1) Search for “Sensors” on the IO-Link Smart Devices with IO-Link Technology product page. 16 Default Value Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 3 Configure Parameters Table 5 - Identification – 1732IL-16CFGM12M12L Data Type Subindex Parameter 0x0010 Vendor Name Allen-Bradley 0x0011 Vendor Text 0x0012 0x0013 Product Name Product ID 0x0014 Product Text www.ab.com/sensors(1) 1732IL-16CFGM12M12L 1732IL-16CFGM12M12L Series A IO-Link Hub, 16 Configurable Digital input/ output SV****** 0x0015 0x0016 0x0017 0x0018 0x0019 0x001A 0 Access Data Length (Byte) Index 64 RO Serial Number Hardware Version Firmware revision Application Specific Tag Electrical Node RW ID Location Tag 16 String Default Value 1.0 64 1.011 32 *** 32 *** 32 *** (1) Search for “Sensors” on the IO-Link Smart Devices with IO-Link Technology product page. Description of Parameter Data You can view and configure the parameter tags for your ArmorBlock IO-Link hub from the IO-Link > Parameter tab. Figure 5 - Example of Parameter Tab in Studio 5000 Logix Designer Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 17 Chapter 3 Configure Parameters Table 6 - Device Parameters (Individual) Device Config General Diagnostic Settings Data Length (Byte) 1 1 Boolean Boolean 0 0 Input Filter Input Latching Input Logic Settings 16 16 16 UINT8 UINT8 UINT8 3 ms Off Normal Index Subindex Parameter 0x0040 0x0041 1…16 0x0043 0x0044 0x0045 1…16 Access RW Data Type Default Value 0x0046(1) Output Fault Value 16 UINT8 Low 0x0047(1) Output Fault Delay 16 UINT8 80 ms String 0 0x0048 1…16 User Serial Number 16 0x0060 1 Module Identification ID 1 0 (1) This index does not apply to 1732IL-IB16. Parameters for Operation Configuration These parameters are used to enter information that helps you to identify your module. Table 7 - Description of Operation Configuration Parameters Index Subindex Bit Number 0x0048 1…16 16 x 0…7 0x0049 1…16 16 x 0…7 0x0060 1 0…6 Parameter User serial number The value entered here is displayed in index 0x0015 (Serial Number). If there is no value entered here, the production serial number is displayed in 0x0015. Electrical Node ID Tag, ASCII text (Default: 16 x 0x00) Enter descriptions and tags for your device. Module Identification ID Assign numerical values to identify which modules are used or connected. This parameter is outside the data storage range. Parameters for Input Filter This parameter (FilterTime.Chxx) specifies the filter time for the module inputs. Each input can be configured individually. 18 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 3 Configure Parameters You can configure the filter times for each input channel from the device index 0x0043. Table 8 - Description of Index 0x0043 Index Subindex 1 2 3 4 5 6 7 8 0x0043 9 10 11 12 13 14 15 16 Bit Number 0…3 Channel Ch0 Ch1 Ch2 Ch3 Ch4 Ch5 Ch6 Ch7 Ch8 Ch9 Ch10 Ch11 Ch12 Ch13 Ch14 Ch15 IO Number I0, C0 I1, C1 I2, C2 I3, C3 I4, C4 I5, C5 I6, C6 I7, C7 I8, C8 I9, C9 I10, C10 I11, C11 I12, C12 I13, C13 I14, C14 I15, C15 Parameter Value 0 = Off 1 = 0.5 ms 2 = 1 ms 3 = 2 ms 4 = 3 ms (default) Parameters for Input Latching This parameter (LatchTime.Chxx) specifies the minimum time that the input stays in one value before switching to another. The minimum time is used when for both Input Logic-1 and Input Logic-0 status. You can configure the latch time for each input channel from the device index 0x0044. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 19 Chapter 3 Configure Parameters Table 9 - Description of Index 0x0044 Index Subindex 0x0044 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit Number Channel IO Number Parameter Value 0…3 Ch0 Ch1 Ch2 Ch3 Ch4 Ch5 Ch6 Ch7 Ch8 Ch9 Ch10 Ch11 Ch12 Ch13 Ch14 Ch15 I0, C0 I1, C1 I2, C2 I3, C3 I4, C4 I5, C5 I6, C6 I7, C7 I8, C8 I9, C9 I10, C10 I11, C11 I12, C12 I13, C13 I14, C14 I15, C15 0 = Off (default) 1 = 0.5 ms 2 = 1 ms 3 = 2 ms 4 = 3 ms Parameters for Input Logic Settings This parameter (Input Logic Settings.Chxx) determines whether the switched input is displayed as NO (normally open) or NC (normally closed). You can configure the logic for each input channel from the device index 0x0045. Table 10 - Description of Index 0x0045 Index 0x0045 20 Subindex 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit Number 0 Channel Ch0 Ch1 Ch2 Ch3 Ch4 Ch5 Ch6 Ch7 Ch8 Ch9 Ch10 Ch11 Ch12 Ch13 Ch14 Ch15 IO Number I0, C0 I1, C1 I2, C2 I3, C3 I4, C4 I5, C5 I6, C6 I7, C7 I8, C8 I9, C9 I10, C10 I11, C11 I12, C12 I13, C13 I14, C14 I15, C15 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Parameter Value 0 = NO (Normally open) (default) 1 = NC (Normally closed) Chapter 3 Configure Parameters Parameters for Output Fault Values This parameter (Fault Value.Chxx) determines the behavior of the digital outputs in there is a loss of communications. Each channel can be configured individually. IMPORTANT The Fault Value function is available only for 1732IL-10X6M12 and 1732IL-16CFGM12M12L. You can configure the value for each output channel from the device index 0x0046. Table 11 - Description of Index 0x0046 Index Subindex 1 2 3 4 5 6 7 8 0x0046 9 10 11 12 13 14 15 16 Bit Number 0…1 Channel Ch0 Ch1 Ch2 Ch3 Ch4 Ch5 Ch6 Ch7 Ch8 Ch9 Ch10 Ch11 Ch12 Ch13 Ch14 Ch15 IO Number C0 C1 C2 C3 C4 C5 C6 C7 C8 C9 O0, C10 O1, C11 O2, C12 O3, C13 O4, C14 O5, C15 Parameter Value 0 = Off (default) 1 = On Parameters for Output Fault Delay This parameter (Fault Delay.Chxx) sets the delay time before an output channel is monitored for possible fault conditions. The delay time starts after a change to the output channel status, and monitoring of the output starts only after the delay time expires. Any fault conditions that occur after this delay are reported as diagnostics. Each channel can be configured individually. IMPORTANT The Fault Delay function is available only for 1732IL-10X6M12 and 1732IL-16CFGM12M12L. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 21 Chapter 3 Configure Parameters You can configure the value for each output channel from the device index 0x0047. Table 12 - Description of Index 0x0047 Index 0x0047 22 Subindex 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Bit Number 0…15 Channel Ch0 Ch1 Ch2 Ch3 Ch4 Ch5 Ch6 Ch7 Ch8 Ch9 Ch10 Ch11 Ch12 Ch13 Ch14 Ch15 IO Number C0 C1 C2 C3 C4 C5 C6 C7 C8 C9 O0, C10 O1, C11 O2, C12 O3, C13 O4, C14 O5, C15 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Parameter Value 0…255 ms (default is 80 ms) Chapter 4 Diagnostic Properties Topic Device Status Device Status in Detail Page 23 25 The ArmorBlock IO-Link hubs provide diagnostic messages to identify the status of the device. Not all indexes can be configured in the AOP. However, you can use CIP message instructions to configure all available indexes. Device Status You can view and configure the diagnostic tags for your ArmorBlock IO-Link hub from the IO-Link > Diagnosis tab. Figure 6 - Example of Diagnosis Tab in Studio 5000 Logix Designer To restore your ArmorBlock IO-Link hub to factory default settings, click Restore Factory Settings. Table 13 - Description of Index 0x0024 Index Subindex Length 0x0024 0 Octet Parameter(1) Value Definition 0 Device is operating properly 1 Maintenance required 2 Out of specification Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 23 Chapter 4 Diagnostic Properties Table 13 - Description of Index 0x0024 (Continued) Index Subindex Length 0x0024 0 Octet Parameter(1) Value Definition 3 Functional check 4 Failure 5…255 Reserved (1) Read-only: Contains the status of the device. Parameters for Device Config You cannot access individual subindexes. Table 14 - Description of Index 0x0040 Index 0x0040 Subindex 1 Bit Number 0 2 1 3 2 4 5 6 7 8 3 4 5 6 7 Parameter Reserved: Do not use Digital Output Error Restart Mode(1) 0 = Disable, 1 = Enable (default) Factory Reset 0 = Disable, 1 = Enable (default) Reserved: Do not use (1) This parameter does not apply to 1732IL-IB16M12. Parameters for General Diagnostic Settings You cannot access individual subindexes. IMPORTANT The diagnostic function is available only for 1732IL-10X6M12 and 1732IL-16CFGM12M12L. Table 15 - Description of Index 0x0041 Index 0x0041 24 Subindex Bit Number 1 0 2 1 3 2 Diagnostic Parameter Device Diagnosis (for outputs) 0 = Disable, 1 = Enable (default) Diagnostics for inputs are always enabled. DO Actuator Supply Voltage Fault 0 = Disable, 1 = Enable (default) Actuator Supply Voltage Fault 0 = Disable, 1 = Enable (default) Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 4 Diagnostic Properties Table 15 - Description of Index 0x0041 (Continued) Index Subindex 4 5 6 7 8 0x0041 Bit Number 3 4 5 6 7 Diagnostic Parameter Reserved: Do not use Table 16 - Diagnosis Based on 0x0041 Parameter Settings Actuator Supply Voltage NOK = Supply <5V OK = Supply >18V DO Actuator Supply Actuator Supply DO Actuator Supply Actuator Supply Voltage Voltage Fault Voltage Fault Voltage Fault Fault Diagnosis Parameter Value Parameter Value Diagnosis NOK 0 NOK 0 0 Yes(1) Yes 1 Yes(1) No Yes NOK 1 0 No(1) NOK 1 1 No(1) No OK 0 0 Yes(2) Yes 1 Yes(2) No 0 No(2) Yes 1 No(2) No OK 0 OK 1 OK 1 (1) There must be at least one output set logically. (2) There must be at least one output set logically, and an overload or short-circuit is detected. Device Status in Detail Table 17 describes the status of the device in detail. These indexes cannot be configured in the AOP, but you can configure them by using CIP message instructions. Table 17 - Description of Index 0x0025 Index 0x0025 Subindex 1…24 Length Array T Parameter(1) Subindex Object Name 1 Error_Warning_1 2 Error_Warning_2 3 Error_Warning_3 4 Error_Warning_4 : : n Error_Warning_n Data Type 3 octets 3 octets 3 octets 3 octets : 3 octets Comment All octets 0x00: no error/warning Octet 1: Event qualifier(2) Octet 2, 3: Event code(3) : (1) Read-only: Contains the detailed status of the device. (2) See Table 18 for more information about event qualifiers. (3) See Table 19 for more information about event codes for peripheral errors. Table 18 - Event Qualifier Bits Description b7…b6 Mode Parameters Value Definition 0 Reserved 1 Event single shot 2 Event disappears 3 Event appears Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 25 Chapter 4 Diagnostic Properties Table 18 - Event Qualifier (Continued) Bits Description b5…b4 Type b3 Source b2…b0 Instance Parameters Value Definition 0 Reserved 1 Notification 2 Warning 3 Error 0 Device (remote) 1 Master (local) 0 Unknown 1…3 Reserved 4 Application 5…7 Reserved Table 19 - Event Codes for Peripheral Errors Event Code Type Device Status 0x5111 Warning 2 Description(1) Low voltage sensor (US) 0x5112(2) Warning 2 Low voltage actuator (UAUX) 0x7710 Error 4 Sensor error (short-circuit) 0x8CA0(1)(3) Error 4 Sensor error (short-circuit) (1)(2) Error 4 Sensor error (short-circuit) 0x8CA2(1)(2) Error 4 Sensor error (short-circuit) (1)(2) Error 4 Sensor error (short-circuit) 0x8CA4(1)(2) Error 4 Sensor error (short-circuit) 0x8CA5(1)(2) Error 4 Sensor error (short-circuit) (1)(2) Error 4 Sensor error (short-circuit) (1)(2) Error 4 Sensor error (short-circuit) (1)(2) 0x8CB0 Error 4 Output error C0 0x8CB1(1)(2) Error 4 Output error C1 (1)(2) 0x8CB2 Error 4 Output error C2 0x8CB3(1)(2) Error 4 Output error C3 0x8CB4(1)(2) Error 4 Output error C4 (1)(2) Error 4 Output error C5 (1)(2) 0x8CB6 Error 4 Output error C6 0x8CB7(1)(2) Error 4 Output error C7 (1)(2) Error 4 Output error C8 (1)(2) Error 4 Output error C9 0x8CBA(1) Error 4 Output error C10/O0 (1) 0x8CBB Error 4 Output error C11/O1 (1) 0x8CBC Error 4 Output error C12/O2 0x8CBD(1) Error 4 Output error C13/O3 (1) 0x8CBE Error 4 Output error C14/O4 (1) Error 4 Output error C15/O5 0x8CA1 0x8CA3 0x8CA6 0x8CA7 0x8CB5 0x8CB8 0x8CB9 0x8CBF (1) For output errors, Cxx and Oxx indicate the channel/output number. (2) These event codes do not apply to 1732IL-IB16M12. (3) These event codes do not apply to 1732IL-10X6M12. 26 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 4 Diagnostic Properties Table 20 - Error Codes for Access Management Error Codes for Access Management 0x8011 0x8012 0x8023 0x8033 0x8034 0x8035 Description Index is not available Subindex is not available Access denied Parameter length overrun Parameter length underrun Function not available Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 27 Chapter 4 Diagnostic Properties Notes: 28 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Chapter 5 Download and Install IO-Link Device Descriptions Topic Download the IO-Link Device Description Page 29 An IO-Link Device Description (IODD) file is a set of multiple files including a file in XML format, which describes all parameters that are associated with the device. The IODD set also includes graphic image files of the device and the vendor logo. Download the IO-Link Device Description You can find the matching device description file for every ArmorBlock IO-Link module from the following locations: • Product Compatibility and Download Center (PCDC): rok.auto/pcdc. • IO-Link community download area: https://ioddfinder.io-link.com/. ATTENTION: We recommend that you download and install the most up-todate version of the relevant IODD from the PCDC or the community download area. For more information about the registration and the addition of IODD to the IO-Link channel, see the respective IO-Link Master user manual. Register an IODD Before you proceed with this task, take note that: • Only IODD files that are based on IO-Link specification v1.0.1 or v1.1 can be registered. • You need administrator rights for the machine where the AOP is installed to be able to register an IODD file. To register an IODD file: 1. From the IO-Link tab, in the Channel tree, right-click on the IO-Link channel. 2. Select Register IODD. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 29 Chapter 5 Download and Install IO-Link Device Descriptions The following dialog box appears. 3. Click Register IODD. The following dialog box appears. 4. Locate the IODD XML file, and then click Open. The previous dialog box displays with the tree list view of registered IODD files. 5. Click Exit. 30 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Appendix A Configure IO-Link Hub as a Generic IO-Link Device Topic Input and Output Process Data for 1732IL-IB16M12 Input and Output Process Data for 1732IL-10X6M12 Input and Output Process Data for 1732IL-16CFGM12M12L Configure IO-Link Devices Tag Name Conventions Description of Process Data Terms Page 31 32 32 33 34 33 This appendix describes how to assign process data from the controller to the I/O channels of your IO-Link hub. It also shows the process data length and the structure of the data. You do not need to configure the IO-Link hub as a generic IO-Link device if you register the IODD and use a specific IO-Link hub catalog number. To register the IODD files, see Register an IODD on page 29. You are not allowed to change the process data length. Input and Output Process Data for 1732IL-IB16M12 Input Data The 1732IL-IB16M12 hub provides up to 4 bytes of input data. The input process image is mapped in the first 2 bytes (bytes 0 and 1) as shown in the following table. Table 21 - Input Process Data – 1732IL-IB16M12 Byte 0 Byte 1 Bit 7 I14 I15 Bit 6 I12 I13 Bit 5 I10 I11 Byte 2 PortError Byte 3 UserConfig Module_ID Bit 4 I8 I9 Bit 3 Bit 2 I6 I4 I7 I5 ModuleOutpu ModuleInput Error tError(1) Bit 1 Bit 0 I2 I0 I3 I1 ModuleActuato ModuleSensorPwrLow rPwrLow(1) (1) These parameters do not apply to 1732IL-IB16M12. Output Data The 1732IL-IB16M12 hub also provides up to 4 bytes of output data. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 31 Appendix A Configure IO-Link Hub as a Generic IO-Link Device Table 22 - Output Process Data – 1732IL-IB16M12 Byte 0 Byte 1 Byte 2 Byte 3 Input and Output Process Data for 1732IL-10X6M12 Bit 7 — — — ConfigRST Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 — Input Data The 1732IL-10X6M12 hub provides up to 4 bytes of input data. The input process image is mapped in the first 2 bytes (bytes 0 and 1) as shown in the following table. Table 23 - Input Process Data – 1732IL-10X6M12 Byte 0 Byte 1 Bit 7 — — Bit 6 Bit 5 Byte 2 PortError Byte 3 UserConfig Module_ID Bit 4 I8 I9 Bit 3 Bit 2 Bit 1 Bit 0 I6 I4 I2 I0 I7 I5 I3 I1 ModuleOutp ModuleInput ModuleActuat ModuleSensorPwrLo utError Error orPwrLow w Output Data The 1732IL-10X6M12 hub also provides up to 4 bytes of output data. The output process image is mapped in the first 2 bytes (bytes 0 and 1) as shown in the following table. Table 24 - Output Process Data – 1732IL-10X6M12 Byte 0 Byte 1 Byte 2 Byte 3 Input and Output Process Data for 1732IL-16CFGM12M12L Bit 7 O4 O5 — ConfigRST Bit 6 O2 O3 Bit 5 O0 O1 Bit 4 — — Bit 3 Bit 2 Bit 1 Bit 0 — Input Data The 1732IL-16CFGM12M12L hub provides up to 4 bytes of input data. The input process image is mapped in the first 2 bytes (bytes 0 and 1) as shown in the following table. Table 25 - Input Process Data – 1732IL-16CFGM12M12L 32 Byte 0 Byte 1 Bit 7 C14 C15 Byte 2 PortError Byte 3 UserConfig Bit 6 C12 C13 Bit 5 C10 C11 Bit 4 C8 C9 Module_ID Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Bit 3 Bit 2 C6 C4 C7 C5 ModuleOutpu ModuleInput tError Error Bit 1 C2 C3 ModuleActuato rPwrLow Bit 0 C0 C1 ModuleSenso rPwrLow Appendix A Configure IO-Link Hub as a Generic IO-Link Device Output Data The 1732IL-16CFGM12M12L hub also provides up to 4 bytes of output data. The output process image is mapped in the first 2 bytes (bytes 0 and 1) as shown in the following table. Table 26 - Output Process Data – 1732IL-16CFGM12M12L Byte 0 Byte 1 Byte 2 Byte 3 Description of Process Data Terms Bit 7 C14 C15 — ConfigRST Bit 6 C12 C13 Bit 5 C10 C11 Bit 4 C8 C9 Bit 3 C6 C7 Bit 2 C4 C5 Bit 1 C2 C3 Bit 0 C0 C1 — Table 27 lists the definition for terms that are used in the input process data and output process data tables for the ArmorBlock IO-Link hubs. Table 27 - Description of Terms in Process Data Tables Process Data I0…I15 O0…O4 C0…C15 ModuleSensorPwrLow Definition Refers to the status of the input channel. Refers to the status of the output channel. Refers to the status of the configurable channel. System/sensor power supply voltage is < 18V ModuleActuatorPwrLow(1) ModuleInputError Output power supply voltage is < 18V ModuleOutputError PortError Module_ID UserConfig ConfigRST (1) Sensor error (short-circuit or overload) Output error (short-circuit or overload) When ModuleSensorPwrLow is true, the value of PortError is 1 (Byte 2, bits 4…7). Individual port error is not available. ID byte for identification of a module change. 0 = not used, Module_ID = 1…127 Possible values 1 Parameters are configured with non-default values. 0 Parameters are using default values. Reset to factory settings for configuration 50 ms after detection of the signal “1”. (1) This parameter does not apply to 1732IL-IB16M12. Configure IO-Link Devices You can configure a generic IO-Link device using Studio 5000 Logix Designer. The following example shows how to configure the 1732IL-IB16M12 as a generic IO-Link device. 1. In the channel tree, right-click on the IO-Link channel, and then select Change. Alternatively, click Change on the working pane. The Change Channel Configuration dialog box displays. 2. Click the button in the Change Device column for the IO-Link channel. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 33 Appendix A Configure IO-Link Hub as a Generic IO-Link Device The Select IO-Link Device dialog box displays. 3. Select Generic Device from the tree and click Create. 4. From the Edit Generic Device Properties dialog box, type the following values in the correct text boxes, and click OK. Vendor ID: 2 Device ID: 298 Input Length: 4 Output Length: 4 Tag Name Conventions The module tag names use defined naming conventions. The conventions are as follows: Tag name examples = IOL:I.Ch3.ModuleSensorPwrLow and IOL:I.Ch3Ch8 • IOL = name of the IO-Link master in your system • I = tag type The possible tag types are I (input) and O (output). 34 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Appendix A • • • Configure IO-Link Hub as a Generic IO-Link Device Ch3 = channel number of the IO-Link master ModuleSensorPwrLow = tag function Ch8 = channel number of the IO-Link hub In this case, ModuleSensorPwrLow signifies that the sensor power supply voltage is less than 18V. For a list of tag functions available for the IO-Link hub, see Description of Terms in Process Data Tables on page 33. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 35 Appendix A Configure IO-Link Hub as a Generic IO-Link Device Notes: 36 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Appendix B Interpret Status Indicators Topic Status Indicator Overview Status Indicator Descriptions Status Indicator Overview Page 37 38 See Table 7 to identify the location of the status indicators. Figure 7 - Status Indicators 1732IL-IB16M12 1732IL-10X6M12 Channel status indicators Power supply status indicator IO-Link status indicator 1732IL-16CFGM12M12L Channel status indicators Power supply status indicator IO-Link status indicator Actuator power supply status indicator Diagnostic status indicator Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Actuator power supply status indicator Diagnostic status indicator Power supply status indicator IO-Link status indicator 37 Appendix B Interpret Status Indicators Status Indicator Descriptions Table 28 describes the meaning of colors and flashes produced by the status indicators. Table 28 - Status Indicators and Descriptions Status Indicator IO-Link status Sensor power/Module supply status Output power supply status(1) I/O status (1 status indicator per channel) Diagnostic status(1) Color Off Flashing green Green Red Off Green Red Off Green Red Off Yellow for even channels; White for odd channels Red Off Red (1) These indicators do not apply to 1732IL-IB16M12. 38 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Description Power off. IO-Link communication is running. Port is starting up (pre-operate). Hardware fault. Power supply is off. Power supply is operating normally. Power supply is < 18V ±1V. Power supply is off. Power supply is operating normally. Power supply is < 18V ±1V. The input or output is in the off state. The input or output is in the on state. Hardware fault. No error message exists. Module diagnosis available. Appendix C Wire the IO-Link System Topic Recommended Wiring Configurations Recommended Wiring Configurations Page 39 Figure 8, Figure 9, and Figure 10 show how to connect your IO-Link master to ArmorBlock IO-Link hubs. For more information on the types of cables and receptacles available, see the ArmorBlock I/O Module Selection Guide, publication 1732-SG001. Figure 8 - Example of Wiring from ArmorBlock IO-Link Master to ArmorBlock IO-Link Hub ArmorBlock IO-Link hub Patchcord Female connector ArmorBlock IO-Link master Male connector 1 1 2 2 3 4 3 4 5 1732IL-10X6M12 889D-F5ACD4M-x-SW(1) 1732E-8IOLM12R View into connector View into connector 2 3 4 5 1 Pin 1 2 3 4 5 Value +24V DC (L+) +24V DC (2L+) GND (L-) C/Q (IO-Link) GND (2L-) 1 2 Description Supply voltage from IO-Link master Additional supply voltage Reference potential to L+ IO-Link data channel Reference potential for additional supply voltage 5 3 4 Pin Description (2) Sensor source voltage 1 2 3 4 5 IO-Link, input/output B Return IO-Link, input/output A PE (1) x represents the length of cable in meters (1, 2, 5, 10). (2) SSV (Pin 1) of the IO-Link master supports a maximum of 500 mA per channel/1 A per port. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 39 Appendix C Wire the IO-Link System Figure 9 - Example of Wiring from ArmorBlock IO-Link Master to ArmorBlock IO-Link Hub with Additional Power Supply ArmorBlock IO-Link master Splitter 879D-F4D5M Power supply Female connector Suggested cables and receptacles •889D-M4AC-1 (Male patchcord) •871A-TS4-DM1 (Male IDC) Female connector 1 2 3 4 1 2 3 4 5 1732E-8IOLM12R 4 3 2 1 Male connector View into connector 5 Description 1 + 2 + 3 - 4 - Cross pins 1 and 4 Suggested cables and receptacles •889D-M4AC-1 (Male patchcord) •871A-TS4-DM1 (Male IDC) View into connector Suggested cables and receptacles •889D-F5AC-1 (Female patchcord) •871A-TS5-D1 (Female IDC) 2 1 Pin ArmorBlock IO-Link hub 3 4 Pin Description 1 Sensor source voltage 2 IO-Link, input/output B 3 Return 4 IO-Link, input/output A 5 PE 1607-XT 1732IL-10X6M12 View into connector 3 4 5 1 40 2 Pin Value Description 1 +24V DC (L+) Supply voltage from IO-Link master 2 +24V DC (2L+) Additional supply voltage 3 GND (L-) Reference potential to L+ 4 C/Q (IO-Link) IO-Link data channel 5 GND (2L-) Reference potential for additional supply voltage Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Appendix C Wire the IO-Link System Figure 10 - Example of Wiring from POINT I/O IO-Link Master to ArmorBlock IO-Link Hub POINT I/O IO-Link master ArmorBlock IO-Link hub 1 2 C CH 3 4 5 +24V DC GND 1734-4IOL 1732IL-10X6M12 0 1 CH 0 CH 1 CH 2 CH 3 2 3 4 6 View into connector 5 5 C C V V 3 4 1 2 7 Channel Common Voltage 0 4 6 1 5 7 2 4 6 3 5 7 Pin Value Description 1 +24V DC (L+) Supply voltage from IO-Link master 2 +24V DC (2L+) Additional supply voltage 3 GND (L-) Reference potential to L+ 4 C/Q (IO-Link) IO-Link data channel 5 GND (2L-) Reference potential for additional supply voltage Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 41 Appendix C Wire the IO-Link System Notes: 42 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Appendix D History of Changes This appendix contains the new or updated information for each revision of this publication. These lists include substantive updates only and are not intended to reflect all changes. Translated versions are not always available for each revision. 1732IL-UM001C-EN-P, September 2019 Change Corrected Figure 2 callout for M12 style L-coded power connector. Added reference to message instructions in publication 1732E-UM007. Corrected parameter description for Data storage lock in Table 2. Corrected descriptions in Table 19 - Event Codes for Peripheral Errors. Correct Status Indicator Overview callouts. 1732IL-UM001B-EN-P, April 2019 Change Added description of features of new IO-Link hubs. Updated Module Overview with features of new IO-Link hubs. Updated description of Operation with IO-Link masters. Added method to restore IO-Link hub to factory settings. Added section about configuring indexes using CIP messaging. Updated Parameters and Identification topic with new tables for 1732IL-10X6M12 and 1732IL-16CFGM12M12L. Grouped indexes 0x0048, 0x0049, and 0x0060 together based on new AOP version. Updated section Parameters for Input Filter. Updated section Parameters for Input Latching. Updated section Parameters for Input Logic Settings. Added section Parameters for Output Fault Values. Added section Parameters for Output Fault Delay. Updated section Device Status. Moved section Parameters for Device Config and added section Parameters for General Diagnostic Settings to Chapter 4. Updated table Event Codes for Peripheral Errors. Updated Appendix A with new topics for 1732IL-10X6M12 and 1732IL-16CFGM12M12L. Updated tables in Description of Parameter Data Terms with information for 1732IL-10X6M12 and 1732IL-16CFGM12M12L. Added topic Tag Name Conventions. Updated table Status Indicators and Description with new information for 1732IL-10X6M12 and 1732IL-16CFGM12M12L. Added Appendix C, Wire your IO-Link System. Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 43 Appendix D History of Changes Notes: 44 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 Index Numerics 1732IL-10X6M12 power 8 1732IL-16CFGM12M12L power 8 1732IL-IB16M12 power 8 A access parameters 13 access lock device 15 access management error code 27 A-coded M12 connector 7 activate IO-Link system command 13 actuator low voltage 26 additional I/O add 7 AOP Add-on Profile 14 application event 26 application specific tag 15 assign process data 31 B basic integration 13 behavior configure 7 block communication 13 C cable type 39 cables types 39 change identification information 15, 15 - 17 channel configurations 7 CIP message instructions 25 colors status indicators 38 communication block 13 configuration diagram 39 parameters 13 configuration settings 14 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 configurations channel 7 configure generic IO-Link device 33 configure as generic IO-Link device 31 - 33 configure behavior 7 configure diagnostic tags 23 configure parameter tags 17 connect IO-Link master 39 connect directly IO-Link devices 7 connect IO-Link hub 39 Connected Enterprise sensors 7 connector female 39 IO-Link 8 M12 A-coded 9 M12 L-code 8 M12 L-coded 9 male 39 power 8 connectors M12 7 M12 A-coded 7 D deactivate block communication 13 description parameter data 17 - 22 details identity 14, 15 device access lock 15 description file 29 device status 23, 25 devices IO-Link enabled 7 diagnosis parameter settings 25 diagnostic tags 23 diagnostic status indicator 37 diagnostic tags configure 23 die-cast zinc housing 7 direct parameter 14 direct parameters 14 E earth functional 9 45 Index error output 26 sensor 26 error codes access management Access denied 27 Function not available 27 Index not available 27 Parameter length overrun 27 Parameter length underrun 27 Subindex not available 27 error event 26 event qualifiers application 26 error 26 local master 26 notification 26 remote device 26 reserved 26 unknown event 26 warning 26 F factory default settings Restore Factory Settings 23 female connector 39 fully sealed housing 7 functional earth 9 G generic integration 13 generic IO-link 31 grounding field devices 9 H housing die-cast zinc 7 fully sealed 7 hub IO-Link 7, 39 I I/O concentration moderate 7 I/O signals 7 identification 1732IL-10X6M12 16 1732IL-16CFGM12M12L 17 1732IL-IB16M12 16 information 14 identification information 15 - 17 change 15, 15 - 17 identify device status 23 identity details 15 index details 14 46 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 index value map 13 indexes 25 information identification 14 input process image 31 instance number 13 instruction message 13 integration basic 13 generic 13 interface IO-Link 7 IO 7 IODD basic 13 generic 13 integration 13 IO-Link Device Description 13, 29 register 29 XML file 14 IODD file 30 IO-Link channel 11 connector 8, 11 device 33 devices 7 hub 7, 15, 17, 39 catalog number 31 identity details 14 restore 13 hubs 7, 8, 11 index 14 interface 7 master 7, 8, 11, 39 master module 7 module 29 open-standard 7 subindex 14 system 7 system command 13 system configuration 8 technology 7 IO-Link channel 11 IO-Link connector 11 IO-Link device parameter object 13 IO-Link Device Description IODD 13, 29 IO-Link enabled devices 7 IO-Link hub 11 digital outputs 7 output features configured 7 restore 13 IO-Link master 11 IO-Link status indicator 37 L low voltage actuator 26 sensor 26 Index M M12 A-coded 7, 9 connector 9 L-code 8 L-coded 9 M12 A-coded connector 7 M12 connector 7 M12 L-code connector 8 male connector 39 map IO-Link index value 13 master IO-Link 8, 39 master event 26 message instruction 13 module location remote I/O modules 7, 13, 17, 23, 25 module tag names 34 modules 1732IL-10X6M12 8 1732IL-16CFGM12M12L 8 1732IL-IB16M12 8 N names module tag 34 notification event 26 number instance 13 O output error 26 overrun parameter length 27 P parameter direct 14 parameter data description 17 - 22 transfer 13 parameter length overrun 27 parameter length underrun 27 Parameter Object IO-Link device 13 parameter settings diagnosis 25 Parameter tab Studio 5000 Logix Designer 17 parameter tags configure 17 view 17 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 parameters access 13 device config 24 device configuraton 13 direct 14 general diagnostic settings 24 input filter 18 input latching 19 input logic settings 20 operation cofiguration 18 output fault delay 21 output fault values 21 parameter object 13 Patchcord 39 patchcord configuration 39 power connector 8 power supply status indicator 37 process data assign 31 input 33 output 33 process image input 31 Product Compatibility and Download Center PCDC 29 R receptacle type 39 receptacles types 39 recommended wiring 39 register IODD 29 - 30 register IODD 29 remote device event 26 remote I/O modules 7, 13, 17, 23, 25 reserved event 26 restore IO-Link hub 13 S sensor low voltage 26 sensor error 26 sensors Connected Enterprise 7 settings configuration 14 general diagnostic 24 status device 25 status indicator diagnostic 37 IO-Link 37 power supply 37 status indicator colors 38 status indicators identify 37 interpret 38 47 Index subindex 24 details 14 system IO-Link 7 system command activate 13 system configuration IO-Link 8 T tag application 15 terms input process data 33 output process data 33 transfer parameter data 13 type cable 39 receptacle 39 types of cables 39 types of receptacles 39 U underrun parameter length 27 unknown event 26 V view parameter tags 17 W warning event 26 wire ArmorBlock IO-Link master 40 POINT I/O IO-Link master 41 wire ArmorBlock IO-Link 39 wiring configurations 39 recommended 39 X XML file IODD 14 48 Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 ArmorBlock 16-channel IO-Link Hub User Manual Rockwell Automation Publication 1732IL-UM001D-EN-P - June 2022 49 Rockwell Automation Support Use these resources to access support information. Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC) Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support Access Knowledgebase articles. rok.auto/knowledgebase Locate the telephone number for your country. rok.auto/phonesupport Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature Download firmware, associated files (such as AOP, EDS, and DTM), and access product release rok.auto/pcdc notes. Documentation Feedback Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. Waste Electrical and Electronic Equipment (WEEE) At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Allen-Bradley, ArmorBlock, Connected Enterprise, ControlLogix, expanding human possibility, FactoryTalk, Logix 5000, POINT I/O, Rockwell Automation, Stratix, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc. CIP and EtherNet/IP are trademarks of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Connect with us. Publication 1732IL-UM001D-EN-P - June 2022 Supersedes Publication 1732IL-UM001C-EN-P - September 2019 Copyright © 2022 Rockwell Automation, Inc. All rights reserved. ">
Advertisement
Key features
- 16 digital channels
- Compact design
- Rugged construction
- M12 connectors
- IO-Link compatible
- Diagnostic capabilities
- Output Fault Value (for output models)
- Output Fault Delay (for output models)
Frequently asked questions
The hub comes in three configurations: 1732IL-IB16M12 with 16 digital inputs, 1732IL-10X6M12 with 10 digital inputs and 6 digital outputs, and 1732IL-16CFGM12M12L with 16 configurable digital inputs/outputs.
The hub connects to the IO-Link master through the M12 connector. For specific wiring instructions, refer to the ArmorBlock 16-Channel IO-Link Hubs Installation Instructions, publication 1732IL-IN001.
The hub can be used to connect IO-Link enabled devices, such as sensors, actuators, and valves.
The hub provides diagnostic messages to identify the status of the device. This includes information about communication errors, device health, and the status of input and output channels.
These settings can be configured through the IO-Link master module using the Studio 5000 Logix Designer software. Refer to the documentation for your IO-Link master module for detailed instructions.