Advertisement
Advertisement
Installation Instructions CEP7 DIN Rail or Panel Adapter Installation At the end of its life, this equipment should be collected separately from any unsorted municipal waste. 25 (CEP7-1EPB, CEP7-1EPD, CEP7-1EPE) WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free from contaminants. Follow NFPA70E requirements. Installation CEP7-1EPB CEP7-1EPD 1 2 4 3 "CLICK" See table below for wire torques CEP7-1EPE 4 1 3 2 "CLICK" CEP7-1EPB Panel Mount Dimensions in. [mm] CEP7 DIN Rail or Panel Adapter Installation CEP7-1EPD Panel Mount Dimensions Main Connections 2 CEP7-1EPE Panel Mount Dimensions Rated Insulation Voltage (Ui): 690V AC Rated Operational Voltage (Ue) IEC/UL: 690V AC / 600V AC CEP7-1EPB CEP7-1EPD CEP7-1EPE Wire Type # Wires Range Torque Range Torque Range Torque Flexible Stranded 1 Wire 2.5…6.0 mm² 1.5...16 mm² 4.0…35 mm² w/ Ferrule 2 Wires* (14...10 AWG) 1.5...10 mm² 4.0…25 mm² 2.5...10 mm² 1.8 N•m 1.5...16 mm² 2.3 N•m 4.0…35 mm² 4.6 N•m 1 Wire (14...8 AWG) (16 lb-in) (16...6 AWG) (20 lb-in) (12...1 AWG) (40 lb-in) Stranded / Solid 2.5…6.0 mm² 1.5...10 mm² 4.0…35 mm² 2 Wires* (14...10 AWG) (16…8 AWG) (12...2 AWG) *FOR MULTIPLE CONDUCTOR APPLICATIONS THE SAME SIZE AND STYLE WIRE MUST BE USED. Sprecher + Schuh maintains current product environmental information on its website at http://www.sprecherschuh.com/library/approvals/compliance.html Sprecher + Schuh, 15910 Int. Plaza Dr., Houston TX 77032, USA *PN-510683* Publication CEP7-IN045B-EN-E - March 2022, Supersedes CEP7-IN045A-EN-E - August 2019 PN-510683 DIR 10004184949 (Version 01) Copyright © 2022 Sprecher+Schuh, Inc. All Rights Reserved. Printed in USA. ">
Advertisement