Allen-Bradley Switched Mode Power Supply Reference Manual
Allen-Bradley Switched mode power supply 1606-XLS960F is a high-efficiency DIN rail mounted unit offering reliable power for various applications. It boasts impressive efficiency, wide input voltage range, and compact size. The unit features BonusPower for short-term high power demands and high peak current capability for easy fuse tripping in demanding situations. The power supply is also well-suited for parallel use to boost output power or redundancy. With its comprehensive international approval package, the 1606-XLS960F is suitable for diverse industrial environments. This device is ideal for powering loads such as DC motors, capacitive loads, and other industrial equipment.
Advertisement
Advertisement
Switched Mode Power Supply Catalog Number 1606-XLS960F Reference Manual Original Instructions Switched Mode Power Supply Reference Manual Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. These labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). The following icon may appear in the text of this document. Identifies information that is useful and can help to make a process easier to do or easier to understand. 2 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Table of Contents Terminology and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Input Inrush Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Hold-up Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 DC-OK Relay Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Shutdown Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Remote Control of Output Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Efficiency and Power Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Functional Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Front Side and User Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Terminals and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Lifetime Expectancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Mean Time Between Failure (MTBF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Electromagnetic Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Safety Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Dielectric Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Certifications and Standards Compliance . . . . . . . . . . . . . . . . . . . . . . . . . 17 Approximate Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Repetitive Pulse Loading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Peak Current Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Back-feeding Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Inductive and Capacitive Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Charging of Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Output Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 External Input Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Parallel Use to Increase Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Parallel Use for Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Daisy Chain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Series Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Operation on Two Phases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Use in a Tightly Sealed Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Mounting Orientations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 1 Table of Contents Notes: 2 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Terminology and Abbreviations Terms PE Descriptions The abbreviation for Protective Earth. PE has the same meaning as the symbol. The symbol for Protective Earth. Earth, Ground AC 230V 230V AC 50 Hz versus 60 Hz Nom Typ — This document uses the term “earth”, which is the same as the U.S. term “ground”. A value that is displayed with the AC or DC before the value represents a nominal voltage with standard tolerances included. For example, DC 12V describes a 12V battery, no matter if it is full (13.7V) or flat (10V). A value with the unit (V AC or V DC) at the end is a momentary value without any additional tolerances included. Unless otherwise stated, AC 230V parameters are valid at 50 Hz mains frequency. Indicates a nominal value. Indicates a typical value. A dash alone in a table cell indicates that there is no information to be included in that cell. All values in this document are specified under the following conditions unless otherwise noted: • 48V, 20 A, 230V AC input voltage • 25 °C (77 °F) ambient temperature • After a 5 minutes run-in time Product Overview Figure 1 - 1606-XLS960F The 1606-XLS960F is a high-efficiency DIN rail power supply unit, which uses a synchronous rectification, a bridgeless PFC circuit, and additional design details to achieve a compact size. Large power reserves of 150% and builtin large sized output capacitors support the starting of heavy loads, such as DC motors or capacitive loads. Therefore, a unit from a lower wattage class can be used. The 1606-XLS960F power supply unit has a high immunity to transients and power surges, and has low electromagnetic emissions. The integrated input fuse, near-zero input inrush current, and diagnostic indicators simplify installation and usage. The 1606-XLS960F power supply unit features a large international approval package for various applications. Product features include: • AC 100…240V wide-range input • Width 125 mm (4.9 in.) • 95.0% full load and excellent partial load efficiencies • 50% BonusPower, 1440 W for up to 4 s Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 3 • 55 A high peak current for 10 ms, for easy fuse tripping • • • • • • • • • Safe HiccupPLUS overload mode Active PFC (Power Factor Correction) Negligible low-input inrush current surge Full power -25…+60 °C (-13…+140 °F) Current sharing feature for parallel use Remote control of output voltage DC-OK relay contact Shut-down input ATEX and IECEx approved Specifications Attributes Values Output voltage DC 48V Nominal Adjustment range 48…54V DC — Output current Output power Notes 20…17.8 A Continuous 30…26.7 A Short term (4 s) 960 W Continuous 1440 W Short term (4 s) Output ripple <150 mVpp 20 Hz…20 MHz Input voltage AC 100…240V -15/+10% Mains frequency 50…60 Hz ±6% AC input current 8.6/4.5 A At 120/230V AC Power factor 0.99/0.99 At 120/230V AC AC inrush current 17/11 A peak At 120/230V AC Efficiency 93.9/95.0% At 120/230V AC Losses 62.4/50.5 W At 120/230V AC Temperature range -25…+70 °C (-13…+158 °F) Operational Derating 24 W/1 °C (24 W/1.8 °F) (1) 60…70 °C (140…158 °F) Hold-up time 27/27 ms At 120/230V AC Dimensions 125 x 124 x 127 mm (4.92 x 4.88 x 5 in.) WxHxD Weight 1900 g (4.2 lb) — (1) Between 85…90V AC. See Environment on page 15. Catalog Numbers Cat. No. 1606-XLS960F 1606-XLC 1606-XLSBUFFER48 1606-XLSRED40HF 4 Descriptions Power supply (48…54V standard unit) Wall mount bracket Buffer unit Redundancy module Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 AC Input Attributes Input voltage Values Notes Nom AC 100…240V Suitable for TN, TT, and IT mains networks — 90…264V AC Continuous operation — 85…90V AC <55 °C (131 °F) ambient temperature continuously allowed >55 °C (131 °F) ambient temperature short term or with output derating, see Figure 27 on page 16 — 60…85V AC Full power for up to 200 ms — 0…85V AC No damage to the unit — 264…300V AC <500 ms Input voltage range Allowed voltage L or N to earth Max 300V AC Continuous, IEC 62103 Input frequency Nom 50…60Hz ±6% Turn-on voltage Typ 80V AC Steady-state value, load independent, see Figure 2 Shut-down voltage Typ 74V AC Steady-state value, load independent, see Figure 2 External input protection — See External Input Protection on page 24. Values Attributes AC 100V AC 120V Notes AC 230V Input current Typ 10.5 A 8.6 A 4.5 A At 48V, 20 A, see Figure 4 Power factor (1) Typ 0.99 0.99 0.99 At 48V, 20 A, see Figure 5 Crest factor (2) Typ 1.47 1.53 1.56 At 48V, 20 A Startup delay Typ 800 ms 750 ms 700 ms See Figure 3 Rise time Turn-on overshoot Typ 16 ms 16 ms 16 ms At 48V, 20 A, resistive load, 0 mF, see Figure 3 Typ 55 ms 55 ms 55 ms At 48V, 20 A, resistive load, 20 mF, see Figure 3 Max 100 mV 100 mV 100 mV See Figure 3 (1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. (2) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform. Figure 2 - Input Voltage Range Input Voltage Turn-on Shut-down Rated Input Range - 5% Output Voltage V IN 74 80 85 Start-up Delay Input Current, Typ Figure 5 - Power Factor Versus Output Load at 48V Power Factor, Typ 12 A 1.0 A: 100 V AC B: 120 V AC C: 230 V AC 8 Rise Time 264V AC Figure 4 - Input Current Versus Output Load at 48V 10 Overshoot P OUT Figure 3 - Turn-on Behavior, Definitions A A B 0.95 B 0.9 6 C 4 C 0.8 2 Output Current 0 2 4 6 8 10 12 14 16 A: 100V AC B: 120V AC C: 230V AC 0.85 Output Current 0.75 18 20 A Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 2 4 6 8 10 12 14 16 18 20 A 5 Input Inrush Current The power supply unit is equipped with an active inrush current limitation circuit, which limits the input inrush current after turn-on to a negligible low value. The input current is smaller than the steady state input current. Values Attributes Inrush current (1) Inrush energy AC 100V AC 120V AC 230V Max 25 Apeak 22 Apeak 16 Apeak Typ 20 Apeak 17 Apeak 11 Apeak Max 5 A2 s 5 A2 s 5 A2 s Notes Over the entire temperature range; mains interruptions >1 s (1) The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Figure 6 - Typical Turn-on Behavior at Nominal Load - 25 °C (77 °F) Ambient Temperature Input Current 5 A/DIV Input 230V AC Output DC Input 48V DC 100 ms/DIV Do not operate this power supply unit with DC-input voltage. Use the 1606-XLE480FP-D unit instead. It can be necessary to run two 1606-XLE480EP-D units in parallel. Output Attributes Output voltage Adjustment range Factory setting Line regulation Values DC 48V — — 48…54V DC Guaranteed Max 56V DC (1) At clockwise end position of potentiometer Typ 48.0V DC ±0.2%, at full load, cold unit, in Single Use mode Typ 46.0V DC ±0.5%, at full load, cold unit, in Parallel Use mode Typ 48.0V DC At no load, cold unit, in Parallel Use mode Max 10 mV 85…300V AC Max 50 mV In Single Use mode: static value, 0 A 20 A, see Figure 7 on page 7 Typ 2000 mV In Parallel Use mode: static value, 0 A 20 A, see Figure 8 on page 7 Max 150 mVpp 20 Hz…20 MHz, 50 Ω Nom 20 A Continuously available at 48V, see Figure 7 on page 7 and Figure 8 on page 7 Nom 17.8 A Continuously available at 54V, see Figure 7 on page 7 and Figure 8 on page 7 Nom 30 A Short-term available BonusPower (2), at 48V for typical 4 s, see Figure 7 on page 7 and Figure 8 on page 7 Nom 26.7 A Short-term available BonusPower (2), at 54V for typical 4 s, see Figure 7 on page 7 and Figure 8 on page 7 Typ 55 A Up to 10 ms, output voltage stays above 40V, see Figure 10 on page 7. This peak current is available once every second. See Peak Current Capability on page 22. Load regulation Ripple and noise voltage Output current 6 Notes Nom Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Attributes Values Nom Output power Notes Continuously available at 48…54V 960 W (2) Short-term available BonusPower (2) at 48…54V Nom 1440 W BonusPower time Typ 4s Duration until the output voltage dips, see Figure 11 on page 8 BonusPower recovery time Typ 7s Overload free time to reset power manager, see Figure 12 on page 8 Overload behavior Short-circuit current Output capacitance — Continuous current Output voltage >40V DC, see Figure 7 — HiccupPLUS mode (3) Output voltage <40V DC, see Figure 7 Min 30 A (4) Max 35 A (4) Load impedance 50 mΩ, see Figure 9 Max 11.5 A Average (RMS) current, load impedance 50 mΩ, see Figure 9 Typ 62 A Up to 10 ms, load impedance <10 mΩ, see Figure 10 Typ 3700 µF Included in the power supply Load impedance 50 mΩ, see Figure 9 (1) Max output voltage that can occur at the clockwise end position of the potentiometer, due to tolerances. It is not a guaranteed value that can be achieved. The typical value is about 55V. (2) BonusPower, short-term power capability (up to typ 4 s): The power supply unit is designed to support loads with a higher short-term power requirement without damage or shutdown. The short-term duration is hardware controlled by an output power manager. This BonusPower is repeatedly available. See Repetitive Pulse Loading on page 20. If the power supply unit is loaded longer with the BonusPower than shown in Figure 11 on page 8, the maximum output power is automatically reduced to 960 W. If the power requirement is continuously above 960 W and the voltage falls below approximately 40V (due to the current regulating mode at overload), the unit shuts off and makes periodical restart attempts. This behavior is called HiccupPLUS mode, see Figure 9. If the voltage is above 40V, the unit continuously delivers current. (3) For up to 4 s of overloading, the power supply unit delivers continuous output current. After overloading, the output power reduces to nearly zero for approximately 17 s before a new start attempt is automatically performed. If the overload is cleared, the device operates normally. If the overload still exists, the output current is delivered for 2…4 s (depending on the overload) again followed by a 17 s rest time. This cycle repeats as long as the overload exists. During the off-period, a small rest voltage and a rest current are present on the output. (4) Discharge current of output capacitors is not included. Figure 7 - Output Voltage Versus Output Current in Single Use Mode, Typ Output Voltage Figure 8 - Output Voltage Versus Output Current in Parallel Use Mode, Typ Output Voltage Adjustment Range (Parallel Use, Typ) 56V 56V A 48 B A 40 Adjustment Range 54V B 52V 32 Continuously allowed 50V Continuously available B Short-term (4 s) then switching to curve A A 24 16 8 0 0 5 10 Hiccup Mode Factory setting 46V 44V 42V 15 20 Bonus Power 48V 25 0 35 A 30 10 5 15 Output Current Output Current y g (dynamic behavior, < 10 ms) 54V Normal operation Short -circuit 30 A Figure 10 - Dynamic Overcurrent Capability, Typ Output Voltage Normal operation 25 Output Current Figure 9 - Short-circuit on Output, HiccupPLUS Mode, Typ g 20 Adjustment Range 48 35 A 40 t 0 2s 17 s 2s 17 s 2s 17 s 32 24 16 8 0 Output Current 0 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 10 20 30 40 50 60 70 A 7 Figure 11 - Bonus Time Versus Output Power Figure 12 - BonusPower Recovery Time g Bonus Time 5s Limitation by Power Manager Power Demand max 4 100% min 3 t 2 Output Voltage 1 Recovery Time Bonus Power disabled Bonus Time Output Power 0 100 t 110 120 130 140 150 160 170% The BonusPower is available when power comes on and after the end of an output short circuit or output overload. Figure 13 - BonusPower After Input Turn-on Figure 14 - BonusPower After Output Short Short of Output Input Voltage Output Voltage Output Voltage Bonus Power 150% 100% Output Power Output Power 150% Bonus Power 100% Hold-up Time Values Attributes Hold-up Time AC 100V AC 120V AC 230V Typ 54 ms 54 ms 54 ms Min 45 ms 45 ms 45 ms Typ 27 ms 27 ms 27 ms Min 23 ms 23 ms 23 ms Figure 15 - Hold-up Time Versus Input Voltage Notes At 48V, 10 A, see Figure 15 At 48V, 20 A, see Figure 15 Figure 16 - Shutdown Behavior Definitions Hold-up Time Zero Transition 60 ms 48V, 10 A, typ 50 Input Voltage 48V, 10 A, min 40 30 48V, 20 A, typ 20 48V, 20 A, min 10 90 8 Hold-up Time Input Voltage 0 120 155 190 - 5% Output Voltage 230V AC Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 DC-OK Relay Contact This feature monitors the output voltage that the power supply unit produces. It is independent of any back-fed voltage from a unit that is connected in parallel to the power supply unit output. Action Notes Contact closes Once the output voltage reaches 90% of the adjusted output voltage Contact opens Once the output voltage dips more than 10% below the adjusted output voltage. Short dips are extended to a signal length of 250 ms. Dips shorter than 1 ms are ignored. Contact recloses Once the output voltage exceeds 90% of the adjusted voltage Contact ratings Max 60V DC at 0.3 A, 30V DC at 1 A, 30V AC at 0.5 A Resistive load Min 1 mA at 5V DC Min permissible load See Dielectric Strength on page 16. Isolation voltage Figure 17 - DC-OK Relay Contact Behavior y g V OUT = VADJ 10% > 1 ms < 1 ms open Shutdown Input closed 0.9* VADJ 250 ms open closed This feature allows a switch-off of the output of the power supply unit with a signal switch or an external voltage. The shutdown occurs immediately, while the turn-on is delayed up to 350 ms. In a shut-down condition, the output voltage is <4V and the output power is <0.5 W. The voltage between different minus pole output terminals must be below 1V when units are connected in parallel. In a series operation of multiple power supply units, only wiring option A with individual signal switches is allowed. IMPORTANT Option C requires a current sink capability of the voltage source. Do not use a blocking diode. The shut-down function has no safety feature included. Figure 18 - Activation of the Shut-down Input g Option A: Option B: 15 Shutdown 16 Input OFF: linked ON : open (via open collector) NC I 15 Shutdown 16 Input Option C: 15 Shutdown 16 Input NC (via external voltage + OFF: I > 0.3 mA ON : I < 0.1 mA - Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 OFF: U < 1V ON : U = 4…29V U - 9 Remote Control of Output Voltage You can use the shut-down input to adjust the output voltage remotely, typically between 44…54V DC. All other functions of the shut-down input remain the same. The control voltage is referenced to the main ground (negative output voltage). . Figure 19 - Remote Control of the Output Voltage Figure 20 - Applying the Control Voltage Output Voltage Potentiometer: 54V setting 48V setting 56V 52 48 44 40 36 32 28 24 15 Shutdown 16 Input + Control Voltage NC - 0 10V 5 Control Voltage To set the shutdown input to adjust the output voltage remotely: 1. Set the unit into Single Use mode. 2. Set the output voltage adjustment (48…54V) to the maximum desired voltage. 3. Apply a control voltage to reduce the output voltage. Efficiency and Power Losses Values Attributes Efficiency AC 100V AC 120V AC 230V Notes Typ 93.5% 93.9% 95.0% Average efficiency (1) Typ 92.9% 93.3% 93.9% 25% at 5 A, 25% at 10 A, 25% at 15 A, 25% at 20 A Typ 3.6 W 3.5 W 3.3 W With activated shut-down Typ 13.5 W 12.8 W 12.8 W At 48V, 0 A (no load) Typ 35.6 W 34.0 W 30.1 W At 48V, 10 A (half load) Typ 66.7 W 62.4 W 50.5 W At 48V, 20 A (full load) Power losses At 48V, 20 A (1) An assumption for a typical application where the power supply unit is loaded with 25% of the nominal load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time, and with 100% of the nominal load for the rest of the time. Figure 21 - Efficiency Versus Output Current at 48V, Typ Figure 22 - Losses Versus Output Current at 48V, Typ y Efficiency Power Losses 96% 95 94 93 92 91 90 89 88 230V AC 120V AC 100V AC Output Current 4 10 6 8 10 12 14 16 18 80 W 70 60 50 40 30 20 10 0 20 A Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 100V AC 120V AC 230V AC Output Current 0 2 4 6 8 10 12 14 16 16 20 A Figure 23 - Efficiency Versus Input Voltage at 48V, 20 A, Typ Efficiency Power Losses 95% 80 W 94 70 93 60 92 50 91 40 90 30 Input Voltage 89 85 Functional Diagram Figure 24 - Losses Versus Input Voltage at 48V, 20 A, Typ 120 155 Input Voltage 20 190 225 85 260V AC 120 155 190 225 260V AC Figure 25 - Functional Diagram Single / Parallel Output Voltage Regulator V OUT L N Input Fuse Input Filter Inrush Limiter Temperature Shutdown Bridgeless PFC Converter Output Power Manager Output Overvoltage Protection Power Converter Overload LED DC-ok LED Output Voltage Monitor DC-OK Relay Event Datalogger Shutdown Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 + + - Output Filter 13 14 DC-OK Contact 15 Shut-down Input and Remote 16 Control 11 Front Side and User Elements Figure 26 - Front Side A B D C 4854V Parallel Use Single Use QUALITY E DC ok F OVL C Allen-Bradley D 1606-XLS POWER SUPPLY 1606-XLS960F DC ok 18WM IND.CONT.EQ. 13 14 Shut- 15 Down 16 Input AC 200-240V N L E G H F DC 48V / 20A + + A B G H 12 User Elements Input terminals (screw terminals) N, L Line input …PE (protective earth) input Output terminals (screw terminals, two pins per pole) + Positive output - Negative (return) output Parallel Use/Single Use selector Set the jumper to Parallel Use when the power supply units are connected in parallel to increase the output power. To achieve a sharing of the load current between the individual units, the Parallel Use regulates the output voltage in such a manner that the voltage at no load is approximately 4% higher than at nominal load. See Parallel Use to Increase Output Power on page 24. A missing jumper is equal to a Single Use mode. Output voltage potentiometer Multi-turn potentiometer; open the flap to set the output voltage. Factory setting is 48V at full output current, Single Use mode. DC-OK status indicator (green) Shows on when the voltage on the output terminals is >90% of the adjusted output voltage. Overload status indicator (red) • Shows on when the voltage on the output terminals is <90% of the adjusted output voltage, or if there is a short circuit in the output. • Flashes when the shutdown is activated or the unit is switched off due to over-temperature. • Input voltage is required. DC-OK relay contact The DC-OK relay contact is synchronized with the DC-OK status indicator. See DC-OK Relay Contact on page 9. Shutdown and Remote Control input Allows the power supply unit to be shut down; can be activated with a switch contact or an external voltage. The remote control input allows for adjustment of the output voltage between 44…54V. See Shutdown Input on page 9 and Remote Control of Output Voltage on page 10. Indicators (LEDs) Overload LED DC-OK LED DC-OK Contact Normal mode OFF ON Closed During BonusPower OFF ON Closed Overload (Hiccup mode) Flashing OFF Open Output short circuit Flashing OFF Open Temperature shut-down Flashing OFF Open Active shut-down input Flashing OFF Open No input power OFF OFF Open Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Terminals and Wiring The terminals are IP20 fingersafe constructed and suitable for field and factory wiring. Attributes Type Solid wire Values Input Output Screw termination Screw termination 0.5…6 mm 2 0.5…16 mm DC-OK, Shutdown 2 Spring clamp termination 0.15…1.5 mm2 Stranded wire 0.5…4 mm2 0.5…10 mm2 0.15…1.5 mm2 American Wire Gauge 20…10 AWG 22…8 AWG 26…14 AWG Max wire diameter 2.8 mm (0.11 in.) (1) 5.2 mm (0.2 in.) (1) 1.5 mm (0.06 in.) (1) Wire stripping length 7 mm (0.28 in.) 12 mm (0.5 in.) 7 mm (0.28 in.) Screwdriver 3.5 mm (0.138 in.) or 5 mm 3 mm (0.12 in.), to open 3.5 mm (0.138 in.), slotted (0.2 in.), slotted or the spring or cross-head, No 2 cross-head, No 2 Recommended torque 1 N•m (9 lb•in) 2.3 N•m (20.5 lb•in) — (1) Includes ferrules. Wiring instructions: • Use the appropriate copper cables that are designed for the minimum operating temperatures: - 60 °C (140 °F) for an ambient temperature up to 45 °C (113 °F). - 75 °C (167 °F) for an ambient temperature up to 60 °C (140 °F). - 90 °C (194 °F) for an ambient temperature up to 70 °C (158 °F). • Follow national installation codes and installation regulations. • Confirm that all strands of a stranded wire enter the terminal connection. • Do not use the unit without PE connection. • Unused terminal compartments must be securely tightened. • Ferrules are allowed. Lifetime Expectancy Attribute Calculated lifetime expectancy Values Notes AC 100V AC 120V AC 230V 299,000 hr (1) 305,000 hr (1) 327,000 hr (1) At 48V, 10 A and 25 °C (77 °F) 106,000 hr (1) 108,000 hr 116,000 hr At 48V, 10 A and 40 °C (104 °F) 180,000 hr (1) 193,000 hr (1) 253,000 hr (1) At 48V, 20 A and 25 °C (77 °F) 64,000 hr 68,000 hr 90,000 hr At 48V, 20 A and 40 °C (104 °F) (1) The minimum operating hours (service life). The lifetime expectancy of the built-in electrolytic capacitors determines the service life. Lifetime expectancy is specified in operational hours and is calculated according to the manufacturer specification of the capacitor. The manufacturer of the electrolytic capacitors lists a maximum life of up to 15 years (131,400 hr). Any number that exceeds this value is a calculated theoretical lifetime, which can be used to compare devices. Mean Time Between Failure (MTBF) MTBF is calculated according to statistical device failures, and indicates the reliability of a device. It is the statistical representation of the likelihood of a unit to fail; it does not necessarily represent the life of a product. An MTBF value of, for example, 1,000,000 hr means that statistically one unit fails every 100 hours if 10,000 units are installed in the field. However, the running time of individual failed units cannot be determined. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 13 Attribute MTBF SN 29500, IEC 61709 MTBF MIL HDBK 217F Ground Benign MTBF MIL HDBK 217F Ground Fixed Electromagnetic Compatibility Values AC 230V Notes AC 100V AC 120V 491,000 hr 481,000 hr 537,000 hr At 48V, 20 A and 25 °C (77 °F) 274,000 hr 269,000 hr 300,000 hr At 48V, 20 A and 40 °C (104 °F) 170,000 hr 171,000 hr 183,000 hr At 48V, 20 A and 25 °C (77 °F); Ground Benign GB25 126,000 hr 127,000 hr 137,000 hr At 48V, 20 A and 40 °C (104 °F); Ground Benign GB40 36,000 hr 36,000 hr 39,000 hr At 48V, 20 A and 25 °C (77 °F); Ground Fixed GF25 27,000 hr 27,000 hr 30,000 hr At 48V, 20 A and 40 °C (104 °F); Ground Fixed GF40 The power supply unit is suitable for applications in an industrial environment and in a residential, commercial, and light industry environment without any restrictions. EMC Immunity According to Generic Standards EN 61000-6-1 and EN 61000-6-2 Attributes Standards Electrostatic discharge EN 61000-4-2 Electromagnetic RF field EN 61000-4-3 Fast transients (burst) Surge voltage on input Surge voltage on output EN 61000-4-4 EN 61000-4-5 EN 61000-4-5 Surge voltage on signal lines EN 61000-4-5 Conducted disturbance Mains voltage dips Voltage interruptions EN 61000-4-6 EN 61000-4-11 EN 61000-4-11 Criteria (1) Values Contact discharge 8 kV Criterion A Air discharge 15 kV Criterion A 80 MHz…2.7 GHz 20V/m Criterion A Input lines 4 kV Criterion A Output lines 2 kV Criterion A Signal lines (coupling clamp) 2 kV Criterion A LN 2 kV Criterion A L PE, N PE 4 kV Criterion A +- 1 kV Criterion A + / - PE 1 kV Criterion A DC-OK signal PE 1 kV Criterion A Shut-down input PE Not relevant due to wire length (2) 0.15…80 MHz 20V Criterion A 0% of 100V AC 0V AC, 20 ms Criterion A 40% of 100V AC 40V AC, 200 ms Criterion C 70% of 100V AC 70V AC, 500 ms Criterion A 0% of 200V AC 0V AC, 20 ms Criterion A 40% of 200V AC 80V AC, 200 ms Criterion A 70% of 200V AC 140V AC, 500 ms Criterion A 0% of 200V AC (=0V) 5000 ms Criterion C Dips on the input voltage according to SEMI F47 standard Voltage sags Powerful transients SEMI F47 VDE 0160 80% of 120V AC (96V AC) 1000 ms Criterion A 70% of 120V AC (84V AC) 500 ms Criterion A 50% of 120V AC (60V AC) 200 ms Criterion A Over entire load range 750V, 1.3 ms Criterion B (3) (1) Criterion A: Power supply shows normal operation behavior within the defined limits. Criterion B: Output voltage dips between 48…42V for 5 ms. Criterion C: Temporary loss of function is possible. The power supply unit can automatically shut down and restart without damage or hazards to itself. (2) Do not use longer wires than 30 m (98.42 ft) for the shutdown input or use an additional protection. (3) Criterion A is fulfilled for output current up to 15 A. 14 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 EMC Emission According to Generic Standards EN 61000-6-3 and EN 61000-6-4 Attributes Standards Notes Conducted emission input lines EN 55011, EN 55032, FCC Part 15, CISPR 11, CISPR 32 Class B Conducted emission output lines IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 10 dB higher than average limits for DC power port according to EN 61000-6-3 (1) Radiated emission EN 55011, EN 55032 Class B Harmonic input current EN 61000-3-2 Fulfilled for class A equipment Voltage fluctuations, flicker EN 61000-3-3 Fulfilled (2) This device complies with FCC Part 15 rules. Operation is subjected to following conditions: • This device must not cause harmful interference. • This device must accept any interference received, including interference that can cause undesired operation. (1) Restrictions apply for applications in residential, commercial, and light-industrial environments where local DC power networks, according to EN 61000-6-3, are involved. No restrictions for all kinds of industrial applications. (2) Tested with constant current loads, non-pulsing. The power supply unit has four converters with four different switching frequencies, which are included. One frequency is nearly constant; others are input voltage and load dependent. Switching Frequency Switching Frequency Values Notes 1 105 kHz Resonant converter, nearly constant 2 1...150 kHz Boost converter, input voltage, and load dependent 3 1...100 kHz PFC converter, input voltage, and load dependent 4 25...45 kHz Auxiliary converter, input voltage, and load dependent Environment Attributes Values Notes Operational temperature (1) -25…+70 °C (-13…+158 °F) Reduce output power according to Figure 27 on page 16 Storage temperature -40…+85 °C (-40…+185 °F) For storage and transportation Output derating 24 W/1 °C (24 W/1.8 °F) Between 60…70 °C (140…158 °F) 5…95% r.H. IEC 60068-2-30 Humidity (2) Vibration sinusoidal Shock Altitude Altitude derating Overvoltage category Degree of pollution 2…17.8 Hz: ±1.6 mm (0.063 in.) (3) 17.8…500 Hz: 1 g (0.04 oz) 2 hours/axis 15 g (0.53 oz) 6 ms, 10 g (0.35 oz) 11 ms (3) 3 bumps/direction, 18 bumps in total IEC 60068-2-6 IEC 60068-2-27 0…2000 m (0…6560 ft) Without any restrictions 2000…6000 m (6560…20,000 ft) Reduce output power or ambient temperature, see Figure 28 on page 16 IEC 62103, EN 50178, overvoltage category II 60 W/1000 m (7.5 W/3280 ft), or 5 °C/1000 m (9 °F/3280 ft) >2000 m (6500 ft), see Figure 28 on page 16 III IEC 62103, EN 50178, altitudes up to 2000 m (6500 ft) II Altitudes from 2000…6000 m (6500…20,000 ft) 2 IEC 62103, EN 50178, not conductive (1) The same as the ambient temperature and is defined as the air temperature 20 mm (0.79 in.) below the unit. (2) Do not energize while condensation is present. (3) Higher levels are allowed when using the 1606-XLC wall mounting bracket. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 15 Figure 27 - Output Current Versus Ambient Temperature Figure 28 - Output Current Versus Altitude Allowed Output Current at 48V Allowed Output Current at 48V 30 A 30 A short-term (4 s) 25 A 20 20 continuous 15 B 10 -25 0 20 A A: Tamb <60 °C B: Tamb <50 °C C: Tamb <40 °C 5 Ambient Temperature 0 continuous 15 A: 90…264V AC B: 85…90V AC 10 5 short-term (4 s) 25 60 70 °C 0 2000 C Altitude 0 40 B 4000 6000 m Protection Features Attributes Values Output protection Electronically protected against overload, no-load, and short-circuits (1) Output overvoltage protection Notes 58.8V DC typ If there is an internal power supply anomaly, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart. 60V DC max Degree of protection IP 20 EN/IEC 60529 (2) Penetration protection >5 mm (0.2 in.) For example, screws and small parts Over-temperature protection Yes Output shutdown with automatic restart Input transient protection MOV Metal Oxide Varistor Internal input fuse Included Not user-replaceable (1) An audible noise occurs if there is a protection event. (2) For use in a controlled environment according to CSA 22.2 No 107.1-01. Safety Features Attributes Input/output separation (1) Values Notes SELV IEC/EN 60950-1 PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 Class of protection I PE connection not required. Isolation resistance >100 MΩ Input to output, 500V DC PE resistance <0.1 Ω — Touch current (leakage current) Typ 0.39 mA/1.0 mA Typ 0.56 mA/1.43 mA 120V AC, 60 Hz, TN-, TT-mains/IT-mains 100V AC, 50 Hz, TN-, TT-mains/IT-mains Typ 0.90 mA/2.25 mA 230V AC, 50 Hz, TN-, TT-mains/IT-mains Max 0.50 mA/1.21 mA 110V AC, 50 Hz, TN-, TT-mains/IT-mains Max 0.71 mA/1.73 mA 132V AC, 60 Hz, TN-, TT-mains/IT-mains Max 1.18 mA/2.28 mA 264V AC, 50 Hz, TN-, TT-mains/IT-mains (1) Double or reinforced insulation. Dielectric Strength 16 The output voltage is floating and has no ohmic connection to the ground. The manufacturer conducts type and factory tests. Field tests can be conducted with the appropriate test equipment, which applies the voltage with a slow ramp (2 s up and 2 s down). Connect all input terminals together and connect all output poles before conducting the test. When testing, set the cutoff current settings to the values in the following table. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Figure 29 - Dielectric Strength Input DC-OK B (a) L N 13 Test or Setting Time A B C D Type test 60 s 2500V AC 3000V AC 500V AC 500V AC Factory test 5s 2500V AC 2500V AC 500V AC 500V AC Field test 5s 2000V AC 2000V AC 500V AC 500V AC Cutoff current setting — >20 mA >20 mA >40 mA >1 mA 14 B A D Output Earth, PE C +/- Shut-down 15/16 (a) When input to DC-OK is tested, confirm that the max voltage between DC-OK and the output is not exceeded (column D). We recommend connecting DC-OK pins and the output pins together when performing the test. To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we recommend that you connect the protective earth system to the + pole, the – pole, or any other part of the output circuit. This connection helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur. Certifications and Standards Compliance Names Notes (1) Symbols UL 508 IND. CONT. EQ. UL Certificate Listed equipment for category NMTR - Industrial Control Equipment Applicable for US and Canada UL 60950-1 UL Certificate Recognized component for category QQGQ - Information Technology Equipment Applicable for US and Canada ATEX Agency Certificate (Bureau Veritas) (1) EN 60079-0 Explosive atmospheres - General requirements EN 60079-7, EN 60079-15 Equipment protection by type of protection "e" and "n" Temperature Code: T3 Type of Protection: nA nC IECEx IECEx Certificate (1) IEC 60079-0 Explosive atmospheres - General requirements IEC 60079-7, IEC 60079-15 Equipment protection by type of protection "e" and "n" Temperature Code: T3 Type of Protection: nA nC Class I Div 2 CSA Certificate Power Supplies for Hazardous Location Applicable for Canada and US CSA Class: 5318-01 (Canada), 5318-81 (US) Temperature Code: T3 Groups: A, B, C, and D Marine (DNV GL) DNV-GL Certificate DNV-GL Type approved product Temperature: Class D Humidity: Class B Vibration: Class C EMC: Class A Enclosure: Class A Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 17 Names Symbols Notes (1) EC Declaration of Conformity The CE marking indicates conformance with the following: – EMC Directive – Low Voltage Directive (LVD) – RoHS directive REACH Directive Manufacturer's Statement EU-Directive regarding the Registration, Evaluation, Authorization, and Restriction of Chemicals EAC TR Registration Registration for the Eurasian Customs Union market (Russia, Kazakhstan, Belarus) (1) Product certification information (including Certificates and Declarations of Conformity) can be found at rok.auto/certifications. Approximate Dimensions and Weight Attributes Values and Descriptions Width 125 mm (4.92 in.) Height 124 mm (4.88 in.) Depth 127 mm (0.5 in.) (1) Weight 1900 g (4.2 lb) DIN rail Use 35 mm (1.38 in.) DIN rails according to EN 60715 or EN 50022 with a height of 7.5 mm (0.30 in.) or 15 mm (0.59 in.). Housing material Aluminum body, steel cover Installation clearances Top: 40 mm (1.57 in.) Bottom: 20 mm (0.79 in.) Left/right: 5 mm (0.2 in.) (2) (1) Add the DIN rail height to the unit depth to calculate the total required installation depth. (2) Increase the 5 mm (0.2 in.) to 15 mm (0.59 in.) in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%, the 5 mm (0.2 in.) can be reduced to zero. Figure 31 - Side View [mm (in.)] Height 124 (4.88) Figure 30 - Front View [mm (in.)] 40 (1.57) 19.1 (0.75) 75.4 (2.97) 40.5 (1.54) Width 125 (4.92) 18 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Width 127 (5.0) DIN Rail Depth Accessories 1606-XLC Wall Mounting Bracket This bracket is used to mount specific units onto a flat surface without using a DIN rail. Figure 32 - Wall Mounting Bracket Attached to Unit Figure 33 - Wall Mounting Bracket 1606-XLSBUFFER48 Buffer Module This buffer module is a supplementary device for DC 48V power supply units. The module delivers power to bridge typical mains failures or extends the holdup time after turn-off of the AC power. In times when the power supply unit provides sufficient voltages, the buffer module stores energy in integrated electrolytic capacitors. If there is a mains voltage fault, this energy is released again in a regulated process. The buffer module does not require any control wiring. It can be added in parallel to the load circuit at any given point. Buffer modules can be added in parallel to increase the output ampacity or the hold-up time. Figure 34 - Buffer Module Figure 35 - Buffer Module in Parallel p AC pp Power Supply DC p Buffer Unit(s) Load + - 1606-XLSRED40HF Redundancy Module The 1606-XLSRED40HF redundancy module is equipped with two input channels of 20 A each, which are individually decoupled by using mosfet technology. The output current is up to 40 A. Mosfets are used instead of diodes to reduce the heat generation and voltage drop between input and output. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 19 The 1606-XLSRED40HF redundancy module does not require an additional auxiliary voltage and is self-powered, even if there is a short circuit across the output. Due to the low-power losses, the module is slender and only requires a 46 mm (1.81 in.) wide DIN rail. Figure 36 - Redundancy Module Figure 37 - Typical 1+1 Redundant Configuration for 20 A with a Dual Redundancy Module 48V 20 A Load 1606-XLS960F 48…54V 960 W Power Supply + DCOK Single Use AC Input N PE 1606-XLS960F 48…54V 960 W Power Supply - Output Parallel Use L Failure Monitor 48V, 20A + + I - - 1606-XLSRED40HF Redundancy Module Input 1 Parallel Use DCOK Single Use Input 2 AC Input + - + - L N PE 48V, 20 A + + - - I L N PE Repetitive Pulse Loading A load current is not typically constant and varies over time. The power supply unit is designed to support loads with a higher short-term power requirement without damage or shutdown, or BonusPower. An output power manager controls the short-term duration. BonusPower is repeatedly available. If the BonusPower load lasts longer than the hardware controller allows, the output voltage will dip and the next BonusPower is available after the BonusPower recovery time has elapsed (see Output on page 6). To avoid voltage dips, follow the following rules: • The power demand of the pulse must be below 150% of the nominal output power. • The duration of the pulse power must be shorter than the allowed BonusPower time (see Output on page 6). • The average (RMS) output current must be below the specified continuous output current. If the RMS current is higher, the unit responds with a thermal shutdown after a time. Use the maximum duty cycle curve in Figure 39 on page 21 to check if the average output current is below the nominal current. • The duty cycle must be below 0.75. 20 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Figure 38 - Repetitive Pulse Loads, Definitions Figure 39 - Maximum Duty Cycle Curve g P 0 = 10% P 0 = 50% P 0 = 75% Duty Cycle PPEAK TPEAK 0.75 T0 0.6 max 150% 0.4 100% P 0 = 100% 0.2 P0 P PEAK 0 100 110 DutyCycle = 1 120 130 140 150% 1 P0 Base load (W) PPEAK Pulse load (above 100%) T0 Duration between pulses (s) TPEAK Pulse duration (s) T0 = Tpeak Tpeak + T0 Tpeak - (DutyCycle x Tpeak) DutyCycle Example Repetitive Pulse Calculation A load is powered continuously with 480 W (= 50% of the rated output load). Occasionally a peak power of 1440 W (= 150% of the rated output load) is needed for 1 second. How often can this pulse be supplied without overloading the power supply? 1. Make a vertical line at PPEAK = 150% and a horizontal line where the vertical line crosses the P0 = 50% curve. Read the maximum duty cycle from the duty cycle-axis (= 0.37) 2. Calculate the required pause (base load) length T0 3. The result is the required pause length = 1.7 s 4. Max repetition rate = pulse + pause length = 2.7 s T0 = Tpeak - (DutyCycle x Tpeak) DutyCycle = 1 s - (0.37 x 1 s) 0.37 = 1.7 s Additional Examples for Pulse Load Compatibility PPEAK P0 TPEAK 1440 W 960 W 1s T0 >25 s 1440 W 0W 1s >1.3 s 1200 W 480 W 1s >0.75 s 1440 W 480 W 0.1 s >0.16 s 1440 W 480 W 1s >1.6 s 1440 W 480 W 3s >4.9 s Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 21 Peak Current Capability The power supply unit can deliver peak currents (up to several milliseconds) which are higher than the specified short-term currents. Peak current capability helps to start current-demanding loads. Solenoids, contactors, and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current (including the BonusPower). The same situation applies when starting a capacitive load. The peak current capability also achieves the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. If there is a short or an overload in one branch circuit, the fuse or circuit breaker needs a certain amount of overcurrent to open in a timely manner. This safety avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large-sized output capacitors of the power supply unit. The capacitors get discharged during such an event, which causes a voltage dip on the output. Figure 40 and Figure 41 show typical voltage dips. Figure 40 - Peak Loading with 2x the Nominal Current for 50 ms, Typ Figure 41 - Peak Loading with 5x the Nominal Current for 5 ms, Typ 48V 48V 37.9V 40 A 28.9V 100 A 0A 0A 10 ms/DIV Peak load 40 A (resistive load) for 50 ms. Output voltage: 48V dips to 37.9V IMPORTANT 1 ms/DIV Peak load 100 A (resistive load) for 5 ms. Output voltage: 48V dips to 28.9V The DC-OK relay triggers when the voltage dips more than 10% for longer than 1 ms. Peak Current Voltage Dips Back-feeding Loads Attributes Values Typ 48…37.9V Notes At 40 A for 50 ms, resistive load Typ 48…34.9V At 100 A for 2 ms, resistive load Typ 48…28.9V At 100 A for 5 ms, resistive load Loads such as decelerating motors and inductors can feed voltage back to the power supply unit. This feature is also called return voltage immunity, or resistance against Back Electromagnetic Force (Back EMF). This power supply unit is resistant and does not show malfunctions when a load feeds back voltage to the unit, regardless of whether the unit is on or off. The maximum allowed feed back voltage is 63V DC. The absorbing energy can be calculated according to the built-in large-sized output capacitor, which is specified in Output on page 6. 22 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Inductive and Capacitive Loads The unit is designed to supply any kind of loads, including unlimited capacitive and inductive loads. If extreme large capacitors, such as EDLCs (electric double layer capacitors or UltraCaps) with a capacitance of >1F are connected to the output, the unit can charge the capacitor in the HiccupPLUS mode (see Output on page 6). Charging of Batteries This power supply unit is not recommended to charge lead-acid or maintenance free batteries. The recommended end-of-charge voltage of 55V at 20 °C (68 °F) for four 12V VRLA lead-acid batteries in series cannot be supplied from the 1606-XLS960F power supply unit. Output Circuit Breakers Standard miniature circuit breakers, such as MCB or UL1077, are commonly used for AC-supply systems and can be used on DC branches. MCB circuit breakers are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB circuit breaker are adapted to the wire size that is used, the wiring is considered thermally safe, regardless of whether the MCB opens. To avoid voltage dips and undervoltage situations in adjacent 48V branches that are supplied by the same source, a fast magnetic tripping of the MCB circuit breaker is desired. A shutdown within 10 ms is necessary, which corresponds roughly to the ride-through time of the PLC. A quick shutdown requires power supply units with high current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufficiently small for the current to flow. The following table contains typical test results that show which B- and C-characteristic MCB circuit breakers magnetically trip, depending on the wire cross section and wire length. Figure 42 - Test Circuit MCB Power Supply Load + AC + Wire length DC S1 - - S1 Fault simulation switch Maximal Wire Length for a Fast Magnetic Tripping [m (ft)] (1) MCB Wire Length by Gauge 0.75 mm² (18 AWG) 1.0 mm² (17 AWG) 1.5 mm² (16 AWG) 2.5 mm² (14 AWG) 68 (223.1) 89 (292) >100 (328.1) >100 (328.1) C-3A 53 (173.9) 75 (246.1) >100 (328.1) >100 (328.1) C-4A 44 (144.4) 57 (187) 88 (288.7) >100 (328.1) C-6A 18 (5901) 25 (82) 38 (124.7) 58 (190.3) C-8A 9 (29.5) 12 (39.4) 18 (59.1) 24 (78.7) C-10A 8 (26.2) 11 (36.1) 16 (52.5) 23 (75.5) C-2A C-13A 4 (13.1) 5 (16.4) 8 (26.2) 12 (39.4) B-6A 39 (128) 50 (164.0) 74 (242.8) >100 (328.1) B-10A 21 (68.9) 29 (95.1) 44 (144.4) 68 (223.1) B-13A 13 (42.7) 21 (68.9) 34 (111.5) 52 (170.6) B-16A 7 (23) 9 (29.5) 13 (42.7) 17 (55.8) B-20A 2 (6.6) 3 (9.8) 4 (13.1) 5 (16.4) (1) Consider twice the distance to the load or cable length when calculating the total wire length (+ and – wire). Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 23 External Input Protection The unit is tested and approved for branch circuits up to 30 A (US) and 32 A (IEC). An external protection is required only if the supplying branch has an ampacity greater than the approved circuit amperage. Check local codes and local requirements. In some countries, local regulations might apply. If an external fuse is used, minimum requirements must be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 16 A B- or C-characteristic breaker must be used, when the unit is used at AC 100V and AC 120V mains voltages (including AC 230V). If the unit is used only at AC 230V mains, a 10 A B- or C-characteristic breaker is sufficient. Parallel Use to Increase Output Power Power supply units from the same series can be paralleled to increase the output power. The output voltage must be adjusted to the same value (±100 mV) in Single Use mode with the same load conditions on all units, or the units can be left with the factory settings. After the adjustments, move the jumper on the front of the unit from Single Use to Parallel Use to achieve load sharing. The Parallel Use mode regulates the output voltage so that the voltage at no load is approximately 4% higher than at nominal load. See Output on page 6. If no jumper is plugged in, the unit is in Single Use mode. The factory setting is also Single Use mode. Figure 43 - Parallel Use to Increase Output Power Unit A AC DC + + Unit B AC DC Load + - - If more than three units are connected in parallel, a fuse or circuit breaker with a rating of 30 A or 32 A is required on each output. Alternatively, use a diode or redundancy module. Energize all units simultaneously to avoid the overload HiccupPLUS mode. If the output was in HiccupPLUS mode due to overload or short circuits and the required output current is higher than the current of one unit, turn off the power for at least 5 seconds. Keep a left and right installation clearance of 15 mm (0.59 in.) between the two power supply units and avoid installing the units on top of each other. Do not use power supply units in parallel in mounting orientations other than in the standard mounting orientation (terminals on the bottom of the unit). Do not use the power supply units in parallel in any other condition where a derating of the output current is required, such as in altitudes above 60 °C (140 °F). Understand that leakage current, EMI, inrush current, and harmonics increase when using multiple power supply units. 24 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Parallel Use for Redundancy Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two power supply units in parallel. This type of redundancy is called a 1+1 redundancy. In case one power supply unit fails, the other unit automatically supports the load current without any interruption. Redundant systems for a higher power demand are built in an N+1 method. For example, five power supply units, each rated for 20 A, are paralleled to build an 80 A redundant system. For N+1 redundancy, the same restrictions apply as for increasing the output power, see Parallel Use to Increase Output Power on page 24. IMPORTANT This redundant system does not cover failures such as an internal short circuit in the secondary side of the power supply unit. In such a case, the defective unit becomes a load for the other power supply units and the output voltage cannot be maintained. This defective unit load can only be avoided by using redundancy modules that include decoupling devices, such as diodes or mosfets. See 1606-XLSRED40HF Redundancy Module on page 19. Recommendations for building redundant power systems: • Use separate input fuses for each power supply unit to increase the reliability of the redundant system. • Set the unit into Parallel Use mode. • Monitor the individual units. Use the DC-OK relay contact of the 1606-XLS960F power supply unit. • Set the output voltages of all units to the same value (±100 mV) or leave output voltages at the factory setting. Daisy Chain A daisy chain (a jump from one power supply unit output to the next) is allowed as long as the average output current through one terminal pin does not exceed 54 A. If the current is higher, use a separate distribution terminal block as shown in Figure 45. Figure 44 - Daisy Chain of Outputs Power Supply + + -- Output Figure 45 - Using Distribution Terminals Distribution Terminals Power Supply + + -- Output Power Supply Load + - + + -- Output Power Supply + + -- Output Load + - Max 25 A Continuous Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 25 Series Operation Figure 46 - Series Operation Power supplies of the same type can be connected in series for higher output voltages. Connect as many units in series as needed, providing the sum of the output voltage does not exceed 150V DC. Voltages with a potential above 60V DC can be dangerous and are no longer SELV. Such voltages must be installed with a protection against being touched. Unit A AC + - DC + Unit B Load AC - + - DC Earth Earthing of the output is required when the sum of the output voltage is above 60V DC. Avoid return voltage (for example, from a decelerating motor or battery) which is applied to the output terminals. Keep a left and right installation clearance of 15 mm (0.59 in.) between two power supply units and avoid installing the units on top of each other. Do not use power supply units in series in mounting orientations other than the standard mounting orientation (terminals on the bottom of the unit). Understand that leakage current, EMI, inrush current, and harmonics increase when using multiple power supply units. Operation on Two Phases Figure 47 - Operation on Two Phases Power Supply L1 L2 26 max L +10% N 240V L3 AC PE The power supply unit can be used on two phases of a three-phase system, as long as the supplying voltage is below 240V+10%. internal fuse DC Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 Use in a Tightly Sealed Enclosure When the power supply unit is installed in a tightly sealed enclosure, the temperature inside the enclosure is higher than outside of the enclosure. In such situations, the inside temperature defines the ambient temperature for the power supply unit. The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. These measurements are taken with the power supply unit in the middle of the enclosure, with no other heatproducing items inside the enclosure. Attributes Values Enclosure size 254 x 180 x 165 mm (4.88 x 7.09 x 6.50 in.) Rittal Typ IP66 Box PK 9522 100, plastic Input voltage 230V AC Load 48V, 16 A; (=80%) (1) Temperature inside enclosure 65.6 °C (150.08 °F) (2) Temperature outside enclosure 24.1 °C (75.38 °F) Temperature rise 41.5K (1) The load is placed outside the box. (2) Temperature in the middle of the right side of the power supply unit with a distance of 20 mm (0.79 in.). Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 27 Mounting Orientations Mounting orientations, other than all terminals on the bottom, require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply unit. Figure 48…Figure 52 on page 28 show two derating curves for continuous operation. • Curve A1: Recommended output current. • Curve A2: Max allowed output current (results in approximately half the lifetime expectancy of A1). Output Current A1 20 A 15 Figure 48 - Mounting Orientation A: Standard Orientation Power Supply 10 5 INPUT Ambient Temperature 0 OUTPUT 10 20 30 40 50 60 °C 50 60 °C 50 60 °C Output Current INPUT OUTPUT Figure 49 - Mounting Orientation B: Upside Down 20 A 15 A2 10 A1 Power Supply 5 Ambient Temperature 0 10 20 30 40 Output Current 20 A 15 Figure 50 - Mounting Orientation C: Table-top Mounting A2 A1 10 5 Ambient Temperature 0 10 20 30 40 Output Current 20 A 15 OUTPUT Power Supply INPUT Figure 51 - Mounting Orientation D: Horizontal CW A2 10 A1 5 Ambient Temperature 0 10 20 30 40 50 60 °C Output Current OUTPUT 15 A2 A1 10 INPUT Figure 52 - Mounting Orientation E: Horizontal CCW Power Supply 20 A 5 Ambient Temperature 0 10 28 Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 20 30 40 50 60 °C Switched Mode Power Supply Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Switched Mode Power Supply Specifications Technical Data, publication 1606-TD002 1606-XLS960F Installation Instructions, publication 1606-IN029 System Security Design Guidelines Reference Manual, SECURE-RM001 Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Specifications, publication IC-TD002 Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control, publication SGI-1.1 Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, rok.auto/certifications Description Provides specifications for Bulletin 1606 products and applications. Provides basic specifications and installation instructions. Provides guidance on how to conduct security assessments, implement Rockwell Automation products in a secure system, harden the control system, manage user access, and dispose of equipment. Provides a quick reference tool for Allen-Bradley® industrial automation controls and assemblies. Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general guidelines for the application, installation, and maintenance of solid-state control in the form of individual devices or packaged assemblies incorporating solid-state components. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. You can view or download publications at rok.auto/literature. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021 29 Rockwell Automation Support Use these resources to access support information. Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC) Find help with how-to videos, FAQs, chat, user forums, and product notification updates. Access Knowledgebase articles. Locate the telephone number for your country. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/support rok.auto/knowledgebase rok.auto/phonesupport rok.auto/literature rok.auto/pcdc Documentation Feedback Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. Waste Electrical and Electronic Equipment (WEEE) At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Publication 1606-RM028A-EN-P - September 2021 Supersedes Publication XXXX-X.X.X - Month Year PN-XXXXXX-XX Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">
Advertisement
Key features
- High Efficiency
- Wide Input Voltage
- BonusPower
- High Peak Current
- Parallel Use
- Compact Size
- DIN Rail Mount