Allen-Bradley DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual
The Allen-Bradley DC/DC Converter - 48V/48V, 5 A, 240 W is a DIN rail mountable DC/DC converter providing a floating, stabilized, and galvanically isolated SELV/PELV output voltage. This unit is suited for nearly every situation with features like high efficiency, small size, wide operational temperature range, and power reserve.
PDF
Download
Document
Advertisement
Advertisement
DC/DC Converter - 48V/48V, 5 A, 240 W Catalog Number 1606-XLDF240F Reference Manual Original Instructions DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). 2 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 Table of Contents Terminology and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Requirements for the Supplying Source. . . . . . . . . . . . . . . . . . . . . . . . . 7 Input Inrush Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Soft Start Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Hold-up Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Efficiency and Power Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Functional Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Front Side and User Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Connection Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Daisy Chaining of Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Lifetime Expectancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Mean Time Between Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Electromagnetic Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Safety and Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Dielectric Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Approved, Fulfilled, or Tested Standards . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Regulatory Product Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Physical Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Wall/Panel Mount Bracket (Cat. No. 1606-XLC) . . . . . . . . . . . . . . . . . 17 Side Mount Bracket (Cat. No. 1606-XLA-S44) . . . . . . . . . . . . . . . . . . . 17 48V DC Redundancy Module (Cat. No. 1606-XLERED) . . . . . . . . . . 18 Buffer Module (Cat. No. 1606-XLSBUFFER) . . . . . . . . . . . . . . . . . . . . 18 Peak Current Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Output Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Battery Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Series Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Parallel Use to Increase Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Parallel Use for Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 1+1 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 N+1 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Use In a Tightly Sealed Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Mounting Orientations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 3 Table of Contents Notes: 4 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Terminology and Abbreviations Terms PE Descriptions The abbreviation for Protective Earth. PE has the same meaning as the symbol. The symbol for Protective Earth. Earth, Ground DC 48V 48V DC 50 Hz versus 60 Hz Max nom typ — (alone in table cell) This document uses the term “earth,” which is the same as the U.S. term “ground”. A value that is displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. For example, DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V). A value with the unit (V AC) at the end is a momentary value without any additional tolerances included. As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz mains frequency. AC 120V parameters are valid for 60 Hz mains frequency. Indicates a maximum value. Indicates a nominal value. Indicates a typical value. A dash alone in a table cell indicates that there is no information to be included in that cell. All values in this document are typical values under the following conditions unless otherwise noted: • 48V DC input voltage • 48V, 5 A output load • 25 °C (77 °F) ambient temperature • After a 5-minute run-in time Product Overview The 1606-XLDF240F is a DIN rail mountable DC/DC converter that provides a floating, stabilized, and galvanically separated SELV/PELV output voltage. The converter offers high efficiency, a small size, and a wide operational temperature range. It has a power reserve of 20% included, which can be used continuously at temperatures up to 45 °C (113 °F). High immunity to transients and power surges, low electromagnetic emission, and a large international approval package for various applications makes this unit suitable for nearly every situation. Product features: • 48V DC input • Isolated 48V DC output • Efficiency up to 95.1% • Width only 42 mm (1.65 in.) • 20% output power reserves • Full power between -25…+60 °C (-13…+140 °F) • Soft start function • Minimal inrush current surge • Reverse input polarity protection Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 5 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Specifications Attributes Output voltage nom Adjustment range Values Notes DC 48V — 48…56V Factory setting 48.0V 6…5.2 A Below 45 °C (113 °F) ambient 5…4.3 A At 60 °C (140 °F) ambient 3.8…3.2 A At 70 °C (158 °F) ambient Derate linearly between 45…70 °C (113…158 °F) 48V ±25% 5.3 A 7 A peak 95.1% — 12.4 W 7.7 ms -25…+70 °C (-13…+158 °F) 42 x 124 x 117 mm (1.65 x 4.88 x 4.61 in.) Without DIN rail 500 g (1.1 lb) — Output current Input voltage DC Input current Input inrush current Efficiency Losses Hold-up time Temperature range Size (W x H x D) Weight Catalog Numbers Catalog Numbers 1606-XLDF240F 1606-XLC 1606-XLA-S44 DC Input Description DC/DC converter Wall or panel mount bracket; see page 17 Side mount bracket; see page 17 The input can be powered from batteries or similar DC sources. To maintain a SELV or PELV output, the source must be a PELV or SELV source, or an Isolated Secondary Circuit. Check for correct input polarity. The device does not operate when the voltage is reversed. Attributes DC input DC input range Allowed voltage L or N to earth Max Values 48V 36…60V DC 60V DC or 42.2V AC Allowed input ripple voltage Max 10 Vpp Turn-on voltage Shut-down voltage Typ Typ 35V DC 31V DC Input current Typ Nom Min 5.3 A 7A Startup delay Typ Rise time Typ 350 ms 50 ms 150 ms 6 Notes ±25% Continuous operation Continuous according to IEC 62477-1. In the frequency range from 47…500Hz, the momentary input voltage must always be within the specified limits. Steady-state value; see Figure 1 on page 7. Steady-state value; see Figure 1 on page 7. At 48V DC input and 48V, 5 A output load; see Figure 3 on page 7. At 36V DC input and 48V, 5 A output load; see Figure 3 on page 7. See Figure 1 on page 7. At 48V, 5 A constant current load, 0 mF load capacitance; see Figure 2 on page 7. At 48V, 5 A constant current load, 5 mF load capacitance; see Figure 2 on page 7. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Attributes Turn-on overshoot Values 500 mV Notes See Figure 2. Installed inside the device, external capacitors on the input Typ 1650 µF are allowed without any limitations. The device is designed, tested, and approved for branch circuits up to 50 A without an additional protection device. If an external fuse is used, do not use circuit breakers smaller than 10 A B- or C-Characteristic. Smaller circuit breakers can cause a nuisance tripping of the circuit breaker. Max Input capacitance External input protection Figure 1 - Input Voltage Range POUT Figure 2 - Turn-on Behavior, Definitions Rated input range Turn-on 15.5V DC 17.5V DC 18.0V DC 32.4V DC 35.0V DC -5% Output Voltage VIN Start-up Delay Rise Time Overshoot Shut-down Input Voltage Figure 3 - Input Current Versus Output Load Input Current (A), typ. 8 V DC t: 36 Inpu V DC t: 48 Inpu 6 4 2 0 1 2 3 4 5 6 Output Current (A) Requirements for the Supplying Source In certain circumstances, the input filter of the DC/DC converter can show a resonant effect, which is caused by the supplying network. When additional external input filters are used, a superimposed AC voltage can be generated on the input terminals of the DC/DC converter, which might cause a unit malfunction. Therefore, additional input filters are not recommended. To avoid the resonant effects, the minimal resistance of the supplying network that depends on the inductance of the input network, must be above the boundary curve in Figure 4. Resistance of the Supplying Network Figure 4 - External Input Filter Requirements to Avoid Filter Instabilities 1Ω 100 mΩ (a) (b) (a) max (b) typ 10 mΩ 1 mΩ 0.1 1 10 Inductance of the supplying network (mH) Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 7 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Input Inrush Current A negative temperature coefficient (NTC) resistor limits the input inrush current after turn-on of the input voltage. The inrush current is dependent on input voltage and ambient temperature. The output load has no impact on the inrush current value. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Attributes Inrush current Inrush energy Notes Max Values 10 Apeak Typ 7 Apeak Temperature independent Max 1 A2 s Figure 5 - Typical Input Inrush Current Behavior at Nominal Load and 25 °C (77 °F) Ambient Input Output Ambient temperature Input current Input voltage Output voltage Time basis Soft Start Feature Output 48V DC 48V, 5 A, constant current load 25 °C (77 °F) 2 A/DIV 10V/DIV 10V/DIV 100 ms/DIV After the DC/DC converter is turned on, the internal output current rises slowly to its nominal value. This method charges the output capacitors (internal and external capacitors) slowly and avoids high input currents during turn-on. High input currents can produce a high-voltage drop on the input wiring (especially with long and thin cables) which reduces the terminal voltage on the DC/DC converter. If the terminal voltage is below the shutdown voltage, the DC/DC converter will turn-off and will make a new startup attempt. This effect is avoided with the integrated soft start function. Please note that this function increases the rise time of the output voltage by a small amount. The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage and is designed to supply any kind of loads, including unlimited capacitive and inductive loads. The output is electronically protected against overload, no-load, and shortcircuits. If there is a protection event, an audible noise can occur. Attributes Output voltage Adjustment range Factory settings Line regulation Load regulation Ripple and noise voltage 8 Nom Min Values 48V 48…56V Max 58.0V Typ Max Max Max 48V 50 mV 200 mV 100 mVpp Notes — Guaranteed value This is the max output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not guaranteed that this value can be achieved. ±0.2%, at full load and cold unit. Between 36…60V DC input voltage variation. Between 0…5 A load variation, static value. Bandwidth 20 Hz…20 MHz, 50 Ω. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Output current Nom Overload behavior Overload/short-circuit current Output capacitance — Max Typ 6A 5A 3.8 A 5.2 A 4.3 A 3.2 A Continuous current 7A 1750 µF Back-feeding loads Max 63V At 48V and an ambient temperature below 45 °C (113 °F). At 48V and 60 °C (140 °F) ambient temperature. At 48V and 70 °C (158 °F) ambient temperature. At 56V and an ambient temperature below 45 °C (113 °F). At 56V and 60 °C (140 °F) ambient temperature. At 56V and 70 °C (158 °F) ambient temperature. — Continuous current, short-circuit impedance <90 mΩ. Included inside the power supply. The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off. The absorbing energy can be calculated according to the built-in, large-sized output capacitor. Figure 6 - Output Voltage Versus Output Current at 48V DC Input Voltage, Typical Figure 7 - Current Limitation Versus Input Voltage, (46V Constant Voltage Load), Typical Adjustment Range 56 7.0 Output Current (A) Output Voltage (V) 48 40 32 24 16 8 0 Hold-up Time 6.5 6.0 5.5 5.0 0 1 4 5 3 Output Current (A) 2 6 30 8 7 35 45 50 40 Input Voltage (V DC) 60 55 The input side of the DC/DC converter is equipped with a bulk capacitor that keeps the output voltage alive for a certain time period when the input voltage dips or is removed. The bulk capacitor can be discharged by loading the DC/DC converter on the output side or through a load that is parallel to the input. There is no protection in the DC/DC converter that helps prevent current from flowing back to the input terminals. If prevention is needed, use an external diode. At no load, the hold-up time can be up to several seconds. During this time, the green DC-OK lamp is also on. Attributes Values Notes 14 ms At 48V DC input voltage, 48V, 2.5 A output; see Figure 8. Min 11 ms At 48V DC input voltage, 48V, 2.5 A output; see Figure 8. Typ 7.7 ms At 48V DC input voltage, 48V, 0.5 A output; see Figure 8. Min 6.2 ms At 48V DC input voltage, 48V, 5 A output; see Figure 8. Typ Hold-up Time Figure 8 - Hold-up Time Versus Input Voltage (a) Hold-up Time (ms) 18 Figure 9 - Shutdown Test Setup (b) 15 + (c) 12 (d) 9 6 DC Source (a) 48V, 2.5A, typ. (b) 48V, 2.5A, min. (c) 48V, 5A, typ. (d) 48V, 5A, min. 3 0 36 40 44 48 52 S1 + + Output - - Input 1606-XLDF240F - Load 56 Input Voltage (V DC) Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 9 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Figure 10 - Shutdown Behavior, Definitions S1 opens Input Voltage Output Voltage -5% Hold-up Time Efficiency and Power Losses Attributes Efficiency Typ Average efficiency Typ Power losses Typ Values Notes 95.1% At 48V, 5 A 94.9% At 48V, 6 A (power boost) 94.6% 25% at 1.25 A, 25% at 2.5 A, 25% at 3.75 A, 25% at 5 A 2.1 W At no output load 6.7 W At 48V, 2.5 A 12.4 W At 48V, 5 A 15.5 W At 48V, 6 A The average efficiency is an assumption for a typical application where the power supply is loaded with the following: • 25% of the nominal load for 25% of the time • 50% of the nominal load for another 25% of the time • 75% of the nominal load for another 25% of the time • 100% of the nominal load for the rest of the time Figure 12 - Losses Versus Output Current at 48V Output and 48V DC Input Voltage, Typical 96 18 95 15 Power Loss (W) Efficiency Percentage (%) Figure 11 - Efficiency Versus Output Current at 48V Output and 48V DC Input Voltage, Typical 94 93 92 0 1 2 3 4 Output Current (A) 5 0 6 Figure 13 - Efficiency Versus Input Voltage at 48V, 10 A, Typical 96 16 95.5 15 95.0 94.5 94.0 1 2 3 4 Output Current (A) 5 6 Figure 14 - Losses Versus Input Voltage at 48V, 10 A, Typical Power Loss (W) Efficiency Percentage (%) 9 6 3 91 90 14 13 12 11 93.5 10 93.0 36 10 12 40 44 48 52 Input Voltage (V DC) 56 60 36 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 40 44 48 52 Input Voltage (V DC) 56 60 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Functional Diagram Figure 15 - Functional Diagram Output Voltage Regulator + Chassis Ground Input Fuse & Input Filter Reverse Polarity Protection & Inrush Limiter Output Filter Power Converter Output Over-voltage Protection Front Side and User Elements 1 1 3 + + DC ok Figure 16 - Front Side 2 VOUT 2 3 4 User Elements Output terminals (screw terminals) Dual terminals for the negative and positive pole. Both poles are internally connected. + Positive output - Negative (return) output Output voltage potentiometer Open the flap to set the output voltage; factory set is 48V. DC OK status light-emitting diode (LED) (green) On when the output voltage is >40V. Input terminals (screw terminals) + Positive input - Negative (return) input Protective Earth (PE) input 4 Connection Terminals The terminals are IP20 fingersafe constructed, and are suitable for field wiring and factory wiring. Attributes Input and Output Descriptions Type Screw terminals Solid wire 6 mm2 max Stranded wire 4 mm2 max American Wire Gauge AWG 20…10 Wire diameter max (including ferrules) 2.8 mm (0.11 in.) Wire stripping length Recommended tightening torque 7 mm (0.28 in.) 1 N•m (9 lb•in) Screwdriver 3.5 mm (0.14 in.) slotted or Phillips No 1 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 11 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Daisy Chaining of Outputs Daisy chaining (jumping from one DC/DC-converter output to the next) is permitted, as long as the average output current through one terminal pin does not exceed 25 A. If the current is higher, use a separate distribution terminal block. Figure 17 - Daisy Chaining of Outputs Figure 18 - Using Distribution Terminals 25 A, max Output Output + ++ - - ++ - - Load DC/DC Converter DC/DC Converter Input Lifetime Expectancy - Input Output ++ - - Output ++ - - + DC/DC Converter DC/DC Converter Load Input Input - Distribution Terminals The Lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only states a maximum life of up to 15 years (131,400 hr). Any number that exceeds this value is a calculated theoretical lifetime, which can be used to compare devices. Attributes Lifetime expectancy Mean Time Between Failure Input 48V DC 160,000 hr 307,000 hr 112,000 hr 453,000 hr 868,000 hr 318,000 hr Notes At 48V, 5 A, and 40 °C (104 °F) At 48V, 2.5 A, and 40 °C (104 °F) At 48V, 6 A, and 40 °C (104 °F) At 48V, 5 A, and 25 °C (77 °F) At 48V, 2.5 A, and 25 °C (77 °F) At 48V, 6 A, and 25 °C (77 °F) Mean time between failure (MTBF) is calculated according to statistical device failures, and indicates reliability of a device. The MTBF value is a statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. An MTBF value of, for example, 1,000,000 hr means that statistically one unit fails every 100 hours if 10,000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50,000 hr or only for 100 hr. For these types of units, the Mean Time to Failure (MTTF) value is the same as the MTBF value. Attributes MTBF SN 29500, IEC 61709 MTBF MIL HDBK 217F 12 Input 48V DC 853 kHz 1512 kHz 285 kHz 421 kHz 71 kHz 97 kHz Notes At 48V, 5 A, and 40 °C (104 °F) At 48V, 5 A, and 25 °C (77 °F) At 48V, 5 A, and 40 °C (104 °F); Ground Benign GB40 At 48V, 5 A, and 25 °C (77 °F); Ground Benign GB25 At 48V, 5 A, and 40 °C (104 °F); Ground Fixed GF40 At 48V, 5 A, and 25 °C (77 °F); Ground Fixed GF25 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Electromagnetic Compatibility The electromagnetic compatibility (EMC) behavior of the device is designed for applications in industrial, residential, commercial, and light industrial environments. The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, and EN 61000-6-4. EMC immunity information is provided in the following table. Attributes Standards Electrostatic discharge EN 61000-4-2 Electromagnetic RF field EN 61000-4-3 Fast transients (Burst) EN 61000-4-4 Surge voltage on input EN 61000-4-5 Surge voltage on output EN 61000-4-5 Conducted disturbance EN 61000-4-6 Values Contact discharge Air discharge 80 MHz…2.7 GHz Input lines Output lines ++ - chassis ground ++ - chassis ground 0.15…80 MHz 8 kV 15 kV 20V/m 4 kV 2 kV 1 kV 2 kV 500V 1 kV 20V Criteria(1) Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A (1) Criterion A: The device shows normal operation behavior within the defined limits. Criterion C: Temporary loss of function is possible. The device can shut down. If it shuts down, it then restarts by itself. No damage or hazards for the device occur. EMC emission information is provided in the following table. Attributes Standards Conducted emission on input IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 lines Conducted emission on IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 output lines Radiated emission EN 55011, EN 55022, CISPR 11, CISPR 22 Notes Limits for local DC power networks fulfilled. (1) Class B This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: 1) this device cannot cause harmful interference, and 2) this device must accept any interference received, including interference that can cause undesired operation. (1) Not available at the time of publishing. Switching frequency information is provided in the following table. Attribute Values Notes Main converter 75…500 kHz Dependent on input voltage and output load Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 13 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Environment Attributes Values Notes Operational temperature -25…+70 °C (-13…+158 °F) The operational temperature is the ambient or surrounding temperature and is defined as the air temperature 2 cm (0.79 in.) below the device. Storage temperature -40…+85 °C (-40…+185 °F) For storage and transportation 3.2 W/1 °C (3.2 W/1.8 °F) Between 45…60 °C (113…140 °F) 6 W/1 °C (6 W/1.8 °F) Between 65…70 °C (140…158 °F) 15 W/1000 m (15 W/3280 ft) or 5 °C/1000 m (9 °F/3280 ft) For altitudes >2000 m (6562 ft), see Figure 20 Output derating Hardware does not control the derating. You must take this into consideration to stay below the derated current limits to help prevent overloading the unit. Humidity 5…95% r.H. According to IEC 60068-2-30. No condensation allowed. Atmospheric pressure 110…47 kPa See Figure 20 for details Altitude Up to 6000 m (19,685 ft) See Figure 20 for details Degree of pollution 2 According to IEC 62477-1, non-conductive Vibration sinusoidal(1) 2…17.8 Hz: ±1.6 mm (0.063 in.) 17.8…500 Hz: 2 g 2 hours / axis According to IEC 60068-2-6 Shock(1) 30 g 6 ms, 20 g 11 ms 3 bumps/direction 18 bumps in total According to IEC 60068-2-27 LABS compatibility As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is suitable for use in paint shops. Corrosive gases Compliant to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a service life of 10 years, minimum, in these environments. Audible noise Some audible noise can be emitted from the DC/DC converter during no load, overload, or short circuit. (1) Shock and vibration are tested in combination with DIN rails according to EN 60715, with a height of 15 mm (0.59 in.) and a thickness of 1.3 mm (0.05 in.). These tests are performed with the DC/DC converter in standard mounting orientation. 14 6 A Figure 20 - Output Power Versus Altitude B 5 4 A... Continuous B... Short term 3 2 1 0 -25 0 20 40 Ambient Temperature (°C) 60 70 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 Allowed Output Current at 48V Allowed Output Current (A) at 48V Figure 19 - Output Power Versus Ambient Temperature 6A C B 5A A 4A 3A 2A A... Ambient <60 °C B... Ambient <45 °C C... Short term 1A 0m 2000 m 4000 m 6000 m 110 kPa 80 kPa 62 kPa 47 kPa Altitude (Atmospheric Pressure) DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Safety and Protection Features Attributes Values Min Isolation resistance Min Min PE resistance Max Typ Max Output overvoltage protection Dielectric Strength — Class of protection Degree of ingress protection Over-temperature protection — — — Input transient protection — Internal input fuse — Touch current (leakage current) — Notes At delivered condition between input and output, measured 500 MΩ with 500V DC At delivered condition between input and PE, measured with 500 MΩ 500V DC At delivered condition between output and PE, measured with 500 MΩ 500V DC Resistance between PE terminal and the housing in the area of 0.1 Ω the DIN rail mounting bracket. 58V DC — 60V DC — If there is an anomaly inside the DC/DC converter, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart. III According to IEC 61140 IP20 According to EN/IEC 60529 Not included — Metal Oxide For protection values, see Electromagnetic Compatibility on Varistor page 13. (MOV) Included Non-user-replaceable, slow-blow, high-braking capacity fuse The leakage current, which is produced by the DC/DC converter itself, depends on the input voltage ripple and must be investigated in the final application. For a smooth DC input voltage, the produced leakage current is <100 µA. The output voltage is floating and has no ohmic connection to the ground. Double or reinforced insulation insulates the output to the input. It is recommended that either the + pole or the – pole be connected to the protective earth (PE) system. This helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur. The manufacturer conducts type and routine tests. Field tests can be conducted in the field with the appropriate test equipment, which applies the voltage with a slow ramp (2 seconds [s] up and 2 seconds down). Connect all phase-terminals together and all output poles before conducting the test. When testing, set the cutoff current settings to the value in the following table. Test or Setting Type test Routine test Field test Cutoff current setting Time 60 s 5s 5s — A 1500V AC 1500V AC 1000V AC 20 mA B 1500V AC 1500V AC 1000V AC 10 mA C 500V AC 500V AC 500V AC 12 mA Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 Input + - B Output A Chassis Ground C + - 15 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Approved, Fulfilled, or Tested Standards For the most current information, visit rok.auto/literature and use 1606-CT as your search criterion. Approval Names Approval Symbols Notes CE Declaration of Conformity The CE marking indicates conformance with the EMC Directive ANSI/UL 61010-2-201 (former UL 508) Listed as Open Type Device for use in Control Equipment UL Category NMTR, NMTR7 Ind. Cont. Eq. Registration for the Eurasian Customs Union market (Russia, Kazakhstan, Belarus) EAC TR Registration Regulatory Product Compliance Regulation Names RoHS Directive REACH Directive Physical Dimensions and Weight Regulation Symbols Notes Directive 2011/65/EU of the European Parliament and the Council of June 8th, 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment. Directive 1907/2006/EU of the European Parliament and the Council of June 1, 2007 regarding the Registration, Evaluation, Authorization, and Restriction of Chemicals (REACH). Attributes Width Height Values and Descriptions 42 mm (1.65 in.) 124 mm (4.88 in.) 117 mm (4.61 in.) Depth The DIN rail height must be added to the unit depth to calculate the total required installation depth. Weight 500 g (1.1 lb) Use 35 mm (1.38 in.) DIN rails according to EN 60715 or EN 50022 with a height of 7.5 mm DIN rail (0.295 in.) or 15 mm (0.59 in.). • Body: Aluminum alloy Housing material • Cover: Zinc-plated steel Keep the following mininmum installation clearances: • 40 mm (1.57 in.) on the top • 20 mm (0.79 in.) on the bottom • 5 mm (0.2 in.) on the left side Installation clearances(1) • 5 mm (0.2 in.) on the right side If the adjacent device is a heat source, increase the side clearances from 5 mm (0.2 in.) to 15 mm (0.59 in.). When the device is permanently loaded with less than 50%, the 5 mm side clearance can be reduced to zero. Penetration protection Small parts like screws and nuts with a diameter larger than 3.5 mm (0.14 in.). (1) The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid. 16 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Figure 21 - Dimensions, Front and Side Views Dimensions are in mm (in.) 25.4 (1) 8 (0.31) 124 (4.88) 5.5 (0.22) Accessories 19.1 (0.75) 42 (1.65) DIN Rail Depth 117 (4.6) The following accessories are available for the DC/DC converter. Wall/Panel Mount Bracket (Cat. No. 1606-XLC) This bracket mounts the device on a flat surface or panel without using a DIN rail. The bracket can be mounted without detaching DIN rail brackets. This bracket kit contains the two brackets that are needed for one device. Figure 22 - Cat. No. 1606-XLC Wall/Panel Mount Bracket Dimensions are in mm (in.). 46 (1.81) 42 (1.65) 23 (0.9) 4 x Ø 5.5 (0.25) 123 (4.84) 133 (5.24) 145 124 (5.71) (4.88) Side Mount Bracket (Cat. No. 1606-XLA-S44) This bracket mounts the device sideways with or without using a DIN rail to save installation depth. The two aluminum brackets and the black plastic slider of the device must be detached so that the steel bracket can be mounted. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 17 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual For sideway DIN rail mounting, mount the removed aluminum brackets and the black plastic slider on the side mount bracket. Figure 23 - Cat. No. 1606-XLA-S44 Side Mount Bracket Dimensions are in mm (in.). 54 (2.13) 48 (1.9) 42 (1.65) 14 (0.55) 43 (1.7) 104 (4.1) 135 (5.31) 124 (4.88) 4 x Ø 5.2 (0.2) Side Mounting With DIN rail Brackets Side Mounting Without DIN rail Brackets 48V DC Redundancy Module (Cat. No. 1606-XLERED) This dual redundancy module can be used to build 1+1 or N+1 redundant systems. The device is equipped with two input channels, each 10 A nominal, which are individually decoupled by using diode technology. The output can be loaded with nominal 20 A. The device does not require an additional auxiliary voltage and is self-powered, even in case of a short circuit across the output. The device has a monitoring circuit included and is the perfect choice when the power supply has no DC-OK function. Two light-emitting diode (LEDs) and two relay contacts signal when one of the two input voltages is not in range due to a nonfunctioning or disconnected power supply. 1606-XLERED The unit is slender and only requires 32 mm (1.26 in.) width on the DIN rail. Buffer Module (Cat. No. 1606-XLSBUFFER) This buffer module is a supplementary device for 48V DC/DC converters. It delivers power to bridge typical supply voltage faults or extends the hold-up time after turn-off of the input power. In times when the DC/DC converter provides sufficient voltages, the buffer module stores energy in integrated electrolytic capacitors. If there is a supply voltage fault, then this energy is released again in a regulated process. 1606-XLSBUFFER 18 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual The buffer module does not require any control wiring. It can be added in parallel to the load circuit at any given point. One buffer module can deliver 20 A additional current. Buffer modules can be added in parallel to increase the output ampacity or the hold-up time. Peak Current Capability The unit can deliver peak currents (up to several milliseconds), which are higher than the specified short-term currents. This capability helps to start current-demanding loads. Solenoids, contactors, and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current. The same situation applies when starting a capacitive load. The peak current capability also achieves the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. If there is a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner. This avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. Figure 24 and Figure 25 show two typical voltage dips. Figure 24 - 10 A Resistive Peak Load for 50 ms, Typ (2x the Nominal current) Attribute Peak current voltage dips Output Circuit Breakers Typ Figure 25 - 25 A Resistive Peak Load for 5 ms, Typ (5x the Nominal current) Values 48V dips to 32V 48V dips to 28V 48V dips to 13V Notes At 10 A for 50 ms and resistive load At 25 A for 2 ms and resistive load At 25 A for 5 ms and resistive load Standard miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly used for AC-supply systems and can also be used on 48V branches. MCBs are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe, regardless of whether the MCB opens or not. To avoid voltage dips and undervoltage situations in adjacent 24V branches that are supplied by the same source, a fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10 ms is necessary, corresponding roughly to the ride-through time of programmable logic controllers (PLCs). This shutdown requires power supplies with high current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufficiently small for the current to flow. The best current reserve in the power supply does not help if Ohm’s Law does not permit current flow. The following table has typical test results showing which B- and C-Characteristic MCB’s magnetically trip depending on the wire cross section and wire length. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 19 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual The following test results indicate the maximal wire length for a magnetic (fast) tripping. The wire length is always two times the distance to the load (+ and – wire). DC/DC Converter DC MCB Load + + Wire length DC S1... Fault simulation switch Battery Charging S1 - MCB Type C-2A C-3A C-4A C-6A B-6A B-10A Test Results for Wire Length, Max 0.75 mm2 (19 AWG) 43 m (141.1 ft) 21 m (68.9 ft) 9 m (29.5 ft) 3 m (9.8 ft) 11 m (36.1 ft) 2 m (6.6 ft) 1 mm2 (18 AWG) 54 m (177.2 ft) 28 m (91.9 ft) 11 m (36.1 ft) 3 m (9.8 ft) 13 m (42.7 ft) 2 m (6.6 ft) 1.5 mm2 (16 AWG) 82 m (269 ft) 41 m (134.5 ft) 15 m (49.2 ft) 4 m (13.1 ft) 20 m (65.6 ft) 3 m (9.8 ft) 2.5 mm2 (14 AWG) 117 m (383.9 ft) 66 m (216.5 ft) 23 m (75.5 ft) 6 m (19.7 ft) 30 m (98.4 ft) 4 m (13.1 ft) The device can be used to charge lead-acid or maintenance free batteries. Four 12V SLA or VLRA batteries are needed in series connection. IMPORTANT Use only matched batteries when putting 12V types in series. Do not use the device for battery charging in mounting orientations other than the standard mounting orientation, or in any other condition where a reduction of the output current is required (for example, altitude). To charge batteries, perform the following steps. 1. Verify that the ambient temperature of the device is below 45 °C (113 °F). 2. Set the output voltage, which is measured at no load and at the battery end of the cable, precisely to the end-of-charge voltage. End-of-charge voltage Battery temperature 55.6V 10 °C (50 °F) 55V 20 °C (68 °F) 54.3V 30 °C (86 °F) 53.6V 40 °C (104 °F) 3. Use a 10 A circuit breaker or blocking diode between the device and the battery. 4. Verify that the output current of the device is below the allowed charging current of the battery. The return current to the device (battery discharge current) is typically 6 mA when the device is switched off (except when a blocking diode is used). Series Operation Devices of the same type can be connected in series for higher output voltages. You can connect as many units in series as needed, if the sum of the output voltage does not exceed 150V DC. Voltages with a potential above 60V DC must be installed with protection against touching. Avoid return voltage (for example, from a decelerating motor or battery) that is applied to the output terminals. Unit A Input Keep a left/right installation clearance of 15 mm (0.6 in.) between two power supplies. Do not install the power supplies on top of each other. Do not use power supplies in series and in mounting orientations other than the standard mounting orientation. Output Unit B Input Output + + + Load - - Electromagnetic interference (EMI) and inrush current increase when you use multiple devices. 20 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Parallel Use to Increase Output Power Devices can be connected paralleled to increase the output power. You can adjust the output voltage to the same value (±100 mV) with the same load conditions on all devices, or the devices can be left with the factory settings. The ambient temperature cannot exceed 45 °C (113 °F). If more than three devices are connected in parallel, a fuse or circuit breaker with a rating of 10 A is required on each output. A diode or redundancy module can also be used. Unit A Input Output Unit B Input + + + Load - Keep a left/right installation clearance of Output 15 mm (0.6 in.) between two power supplies. Do not install the power supplies on top of each other. Do not use devices in parallel in mounting orientations other than the standard mounting orientation, or in any other condition where a reduction of the output current is required (for example, altitude). EMI and inrush current increase when you use multiple devices. Parallel Use for Redundancy These devices can be parallel used for two types of redundancy. For a wiring example of either redundancy configuration, see Figure 26 and Figure 27, both on page 22. 1+1 Redundancy Devices can be paralleled for 1+1 redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one device fails. The simplest way is to put two devices in parallel. This is called a 1+1 redundancy. In case one device fails, the other one is automatically able to support the load current without any interruption. It is essential to use a redundancy module to decouple devices from each other. This redundancy helps prevent the defective unit from becoming a load for the other device, which helps confirm that the output voltage can be maintained. EMI and inrush current increase when you use multiple devices. The following recommendations are for building 1+1 redundant power systems: • Whenever possible, use separate supply systems for each device. • Monitor the outputs of each device. Use the DC-OK lamp or the DC-OK contact, which are included in the Cat. No. 1606-XLERED Redundancy Module. • Set the output voltages of all devices to the same value (± 100 mV), or leave them at the factory setting. • The ambient temperature cannot exceed 70 °C (158 °F). N+1 Redundancy Redundant systems for a higher power demand are built in an N+1 method, such as four devices with each rated for 10 A are paralleled to build a 30 A redundant system. EMI and inrush current increase when you use multiple devices. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 21 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual The following recommendations are for building N+1 redundant power systems: • Keep a left/right installation clearance of 15 mm (0.6 in.) between two devices, and do not install the devices on top of each other. • Do not use devices in parallel in mounting orientations other than the standard mounting orientation or in any other condition, where a reduction of the output current is required. • The ambient temperature cannot exceed 45 °C (113 °F). Figure 26 - 1+1 Redundant Configuration for 5 A Load Current With a Dual Redundancy Module Figure 27 - N+1 Redundant Configuration for 15 A Load Current With Multiple DC/DC Converters and Redundancy Modules Failure Monitor Failure Monitor Input Input I 1 2 Input ok Redundacy Module Output Output DC/DC Converter DC/DC Converter Input Input Output Load I Redundacy Module Output Output DC/DC Converter DC/DC Converter Input Input Output I I Input Input 1 2 1 2 Input ok Redundacy Module Output - Functional Earth Use In a Tightly Sealed Enclosure I + - Input Input 1 2 1 2 Input ok Optional DC/DC Converter Input Input 1 2 Optional DC/DC Converter I + Output Optional Output Load Functional Earth When the device is installed in a tightly sealed enclosure, the temperature inside the enclosure is higher than outside. In such situations, the inside temperature defines the ambient temperature for the device. In the following test setup, the device is placed in the middle of the enclosure, and no other heat-producing items are inside the enclosure. The load is placed outside the enclosure. The temperature sensor inside the box is placed in the middle of the right side of the DC/DC converter with a distance of 1 cm (0.39 in.). The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. Attributes Enclosure size Input voltage Load Temperature inside the box Temperature outside the box Temperature rise 22 Values Case A Case B 110 x 180 x 165 mm 110 x 180 x 165 mm (4.33 x 7.09 x 6.50 in.) (4.33 x 7.09 x 6.50 in.) Rittal Typ IP66 Box Rittal Typ IP66 Box PK 9516 100, plastic PK 9516 100, plastic 48V DC 48V DC 48V, 4 A (=80%) 48V, 5 A (=100%) 43.5 °C (110.3 °F) 48.1 °C (118.6 °F) 26.2 °C (79.2 °F) 26.6 °C (79.8 °F) 17.3 °C (31.1 °F) 21.5 °C (38.8 °F) Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The listed lifetime and MTBF values from this data sheet apply only for the standard mounting orientation. The following curves indicate the allowed output currents for altitudes up to 2000 m (6562 ft). Figure 28 - Mounting Orientation A (upright; standard) Allowed Output Current (A) at 48V Output DC/DC Converter 6 5 3.8 0 Input 45 Ambient Temperature (°C) 60 70 60 70 60 70 60 70 Figure 29 - Mounting Orientation B (upside down) Allowed Output Current (A) at 48V Input DC/DC Converter Output 6 4 0 30 Ambient Temperature (°C) Allowed Output Current (A) at 48V Figure 30 - Mounting Orientation C (table-top) 6 3.5 0 25 Ambient Temperature (°C) Output DC/DC Converter Input Allowed Output Current (A) at 48V Figure 31 - Mounting Orientation D (horizontal with input on the left) 6 3.5 0 25 Ambient Temperature (°C) Allowed Output Current (A) at 48V Input DC/DC Converter Figure 32 - Mounting Orientation E (horizontal with input on the right) Output Mounting Orientations 6 3.5 0 25 Ambient Temperature (°C) Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 60 70 23 DC/DC Converter - 48V/48V, 5 A, 240 W Reference Manual Notes: 24 Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 DC Power Supply - 24V, 3.8 A, 90 W, Single-phase Input Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource System Security Design Guidelines Reference Manual, SECURE-RM001 Description Provides guidance on how to conduct security assessments, implement Rockwell Automation products in a secure system, harden the control system, manage user access, and dispose of equipment. Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Provides a quick reference tool for Allen-Bradley industrial automation controls and assemblies. Specifications, publication IC-TD002 Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general Safety Guidelines for the Application, Installation, and Maintenance of Solid-State guidelines for the application, installation, and maintenance of solid-state control in the form of Control, publication SGI-1.1 individual devices or packaged assemblies incorporating solid-state components. Provides general guidelines for installing a Rockwell Automation industrial system. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details. You can view or download publications at rok.auto/literature. Rockwell Automation Publication 1606-RM124A-EN-P - September 2021 25 Rockwell Automation Support Use these resources to access support information. Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC) Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support Access Knowledgebase articles. rok.auto/knowledgebase Locate the telephone number for your country. rok.auto/phonesupport Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature Download firmware, associated files (such as AOP, EDS, and DTM), and access product release rok.auto/pcdc notes. Documentation Feedback Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. Waste Electrical and Electronic Equipment (WEEE) At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur Publication 1606-RM124A-EN-P - September 2021 Copyright © 2021 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">
Advertisement
Key Features
- DIN rail mountable
- Floating SELV/PELV output
- High efficiency
- Wide operational temperature range
- Power reserve
- Compact size
- Soft start
- Low inrush current
- Reverse polarity protection
- Overload, no-load, and short-circuit protection
Frequently Answers and Questions
What is the output voltage range of this DC/DC converter?
The output voltage range is 48…56V with a factory setting of 48.0V.
What is the maximum output current for this DC/DC converter?
The maximum output current is 7A peak, but the continuous current depends on the ambient temperature: 6A below 45 °C (113 °F), 5A at 60 °C (140 °F), and 3.8A at 70 °C (158 °F).
What is the efficiency of this DC/DC converter?
The efficiency is up to 95.1% at 48V, 5A output.