Allen-Bradley Power Supply - 48V, 5.4 A, 260 W, Single-phase Input Reference Manual
PDF
Download
Document
Advertisement
Advertisement
Power Supply - 48V, 5.4 A, 260 W, Single-phase Input Catalog Number 1606-XLE260F Reference Manual Original Instructions Power Supply - 48V, 5.4 A, 260 W, Single-phase Input Reference Manual Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). 2 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Table of Contents Terminology and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Input Inrush Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Hold-up Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 DC OK Relay Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Efficiency and Power Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Lifetime Expectancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Mean Time Between Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Functional Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Terminals and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Daisy Chaining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Front Side and User Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Electromagnetic Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Safety Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Dielectric Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Other Fulfilled Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Physical Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Side Mounting Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Wall/Panel Mount Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Redundancy Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 1606-XLSRED – 2 x 10 A Inputs, 1 x 20 A Output. . . . . . . . . . . . . . . . . 24 1606-XLSRED40HF – 2 x 20 A Inputs, 1 x 40 A Output . . . . . . . . . . . 24 Peak Current Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 External Input Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Back-feeding Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Output Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Parallel Use to Increase Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Parallel Use for Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Series Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Inductive and Capacitive Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Charging of Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Operation on Two Phases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Use In a Tightly Sealed Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Mounting Orientations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 3 Notes: 4 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Terminology and Abbreviations Terms PE Descriptions The abbreviation for Protective Earth. PE has the same meaning as the symbol. The symbol for Protective Earth. Earth, Ground AC 230V 230V AC 50 Hz versus 60 Hz nom typ — (alone in table cell) This document uses the term “earth” which is the same as the U.S. term “ground”. A value that is displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. For example, DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V). A value with the unit (V AC) at the end is a momentary value without any additional tolerances included. As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz mains frequency. AC 120V parameters are valid for 60 Hz mains frequency. Indicates a nominal value. Indicates a typical value. A dash alone in a table cell indicates that there is no information to be included in that cell. All parameters in this document are specified under the following conditions unless otherwise noted: • • • • 48V, 5.4 A output load 230V AC, 50 Hz input voltage 25 °C (77 °F) ambient temperature after a 5 minutes run-in time Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 5 Product Overview The 1606-XLE260F power supply is part of a series of high-end power supplies in a medium price range that do not compromise quality, reliability, or performance. The 1606-XLE260F features high efficiency, advanced inrush current limitation, active power factor correction (PFC), and a wide operational temperature range. The 1606-XLE260F includes all essential basic functions of a power supply. It has a power reserve of 10% up to 60 °C (140 °F) and 20% up to 45 °C (113 °F) included, even when used continuously. Additionally, the power supply can deliver three times the nominal output current for at least 12 ms, which helps to trip fuses on faulty output branches. The power supply has a wide variety of applications due to its high immunity to transients and power surges, low electromagnetic emission, DC OK relay contact, and large international approval package. Product features include the following: • • • • • • AC 100…240V wide-range input Width only 39 mm (1.54 in.) +10% (5.4 A) continuous current up to 60 °C (140 °F) +20% (6 A) continuous current up to 45 °C (113 °F) Efficiency up to 95.5% Excellent partial load efficiency • • • • • Safe HiccupPLUS Overload mode Active power factor correction (PFC) Minimal inrush current surge Full power between -25…+60 °C (-13…+140 °F) DC OK relay contact Figure 1 - 1606-XLE260F Power Supply 6 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Specifications Attributes Values Notes Output voltage DC 48V Nominal Adjustment range Output current 48…56V Factory setting 48.0V 6.0…5.2 A Below 45 °C (113 °F) ambient 5.4…4.6 A At 60 °C (140 °F) ambient 4.0…3.4 A At 70 °C (158 °F) ambient Derate linearly between 45…70 °C (113…158 °F) Input voltage AC AC 100…240V ±10% Mains frequency 50…60 Hz ±6% Input current AC 2.32 / 1.20 A At 120 / 230V AC Power factor 0.99 / 0.98 At 120 / 230V AC Input voltage DC DC 110…150V ±20% 2.51 A At 110V DC Input current DC Reduce output current to 5…4.3 A (48…56V) below 93.5V DC AC Inrush current 6 / 9 A pk At 40 °C (104 °F) 120/230V AC Efficiency 93.8 / 95.5% At 120 / 230V AC Losses 17.2 / 12.3 W At 120 / 230V AC Hold-up time 34 / 34 ms At 120 / 230V AC Temperature range -25…+70 °C (-13…+158 °F) — Size (w x h x d) 39 x 124 x 117 mm (1.54 x 4.88 x 4.61 in.) Without DIN rail Weight 600 g (1.3 lb) — Catalog Numbers Catalog Numbers 1606-XLE260F 1606-XLA-XLE 1606-XLA-S44 Descriptions Power supply Wall/panel mount bracket Side mount bracket Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 7 AC Input Attributes Values AC input AC input range Allowed voltage L or N to earth Notes Nom AC 100…240V Suitable for TN-, TT-, and IT mains networks — — Continuous operation Below 90V AC, reduce output current according to Figure 6 on page 9. Min 85…264V AC Min 264…300V AC For maximal 500 ms Max 300V AC Continuous according to IEC 62477-1 Input frequency Nom 50…60 Hz ±6% Turn-on voltage Typ 80V AC Steady-state value, see Figure 2 Typ 70V AC Steady-state value, see Figure 2 Typ 55V AC Dynamic value for maximal 250 ms Shut-down voltage See recommendations in External Input Protection on page 25. External input protection Values Attributes Input current Typ Notes AC 100V AC 120V AC 230V 2.82 A 2.32 A 1.20 A At 48V, 5.4 A, see Figure 4 (1) Typ 0.99 0.99 0.98 At 48V, 5.4 A, see Figure 5 (2) Typ 1.5 1.5 1.65 At 48V, 5.4 A Start-up delay Typ 300 ms 290 ms 240 ms See Figure 3 Typ 63 ms 63 ms 63 ms At 48V, 5.4 A constant current load, 0 mF load capacitance, see Figure 3 Power factor Crest factor Rise time Typ 210 ms 210 ms 210 ms At 48V, 5.4 A constant current load, 5 mF load capacitance, see Figure 3 Turn-on overshoot Max 200 mV 200 mV 200 mV See Figure 3 External input protection See recommendations in External Input Protection on page 25. (1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. (2) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform. Figure 3 - Turn-on Behavior, Definitions Rated input range POUT Turn-on Shut-down 500 ms max Input Voltage - 5% Output Voltage V IN 90V 264V 300V AC Figure 4 - Input Current Versus Output Current at 48V Output Voltage 2.5 2.0 (a) a) 100V AC b) 120V AC c) 230V AC (b) (c) (a) 0.95 (b) 0.85 (c) Output Current (a) 100V AC, (b) 120V AC, (c) 230V AC Output Current 0.75 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 A 8 1.0 0.8 0.5 0 Figure 5 - Power Factor Versus Output Current at 48V Output Voltage 0.9 1.5 1.0 Rise Time Power Factor, typ Input Current, typ 3A Start-up delay Overshoot Figure 2 - Input Voltage Range 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 A Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Figure 6 - Derating Requirements for AC Input Allowed Output Current at 48V 6A 5.4 A C B 5A A 4A 3A A: below 60°C ambient temperature B: below 55°C ambient temperature C: below 45°C ambient temperature 2A 1A 0 85 90 264V DC DC Input Voltage DC Input Attributes Values Notes DC input Nom DC 110…150V ±20% DC input range Min 88…180V DC Continuous operation, Below 93.5V DC, reduce output current according to Figure 8. DC input current Typ 2.51 A At 110V DC Allowed Voltage L/N to Earth Max 375V DC Continuous, according to IEC 62477-1 Turn-on voltage Typ 80V DC Steady state value Typ 70V DC Steady state value Typ 55V DC Dynamic value for maximal 250 ms Shut-down voltage When using the power supply with a DC input, follow these rules: • • • Use a battery or a similar DC source. A supply from the intermediate DC bus of a frequency converter is not recommended and can cause a malfunction or damage the unit. Connect +pole to L and –pole to N. Connect the PE terminal to an earth wire or to the machine ground. Figure 7 - Wiring for DC Input Figure 8 - Derating Requirements for DC Input Allowed Output Current at 48V Battery + 6A Power Supply AC L N PE 5.4 A C B 5A A 4A + 3A Load - A: below 60°C ambient temperature B: below 55°C ambient temperature C: below 45°C ambient temperature 2A 1A DC 0 88 93.5 187V DC DC Input Voltage Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 9 Input Inrush Current An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Values Attributes AC 100V Inrush current Inrush energy AC 120V AC 230V Notes Max 11 A pk 7 A pk 11 A pk At 40 °C (104 °F), cold start Typ 9 A pk 6 A pk 6 A pk At 25 °C (77 °F), cold start Typ 9 A pk 6 A pk 9 A pk At 40 °C (104 °F), cold start Max 0.1 A²s 0.1 A²s 0.4 A²s At 40 °C (104 °F), cold start Figure 9 - Typical Turn-on Behavior at Nominal Load, 120V AC Input, and 25 °C (77 °F) Ambient 50 ms/DIV Input current 2 A/DIV Input voltage 250V/DIV 6A Output voltage 40V/DIV Figure 10 - Typical Turn-on Behavior at Nominal Load, 230V AC Input, and 25 °C (77 °F) Ambient 6A 50 ms/DIV Input current 2 A/DIV Input voltage 500V/DIV Output voltage 40V/DIV 10 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Output Attributes Output voltage Adjustment range Values Notes Nom 48V — Min 48…56V Guaranteed value Max 58.0V This is the max output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not guaranteed that this value can be achieved. Factory settings Typ 48.0V ±0.2%, at full load and cold unit Line regulation Max 10 mV Between 85…300V AC Load regulation Max 50 mV Between 0…6 A, static value, see Figure 11 Ripple and noise voltage Max 50 mVpp Bandwidth 20 Hz…20 MHz, 50 Ω Nom 6.0 A(1) At 48V and an ambient temperature below 45 °C (113 °F), see Figure 25 on page 18 Nom 5.4 A At 48V and 60 °C (140 °F) ambient temperature, see Figure 11 Nom 4.0 A At 48V and 70 °C (158 °F) ambient temperature, see Figure 25 on page 18 Nom 5.2 A(1) At 56V and an ambient temperature below 45 °C (113 °F), see Figure 25 on page 18 Nom 4.6 A At 56V and 60 °C (140 °F) ambient temperature, see Figure 11 Nom 3.4 A At 56V and 70 °C (158 °F) ambient temperature, see Figure 25 on page 18 Typ 15 A For minimal 12 ms once every 5 seconds, see Figure 12. The output voltage stays above 40V. See Peak Current Capability on page 25 for more peak current measurements. For AC 100V mains, the pulse length is shorter than 12 ms. — Continuous current Output voltage above 26V DC, see Figure 11 — HiccupPLUS mode(2) Output voltage below 26V DC, see Figure 11 Output current Overload behavior Short-circuit current Output capacitance Min (3) 6.3 A Load impedance <90 mΩ, see Figure 13 Max 7.7 A(3) Load impedance <90 mΩ, see Figure 13 Max 2.2 A Average (R.M.S.) current, load impedance 50 mΩ, see Figure 13 Min 14.5 A Up to 12 ms, load impedance <90 mΩ, see Figure 12 Typ 16.0 A Up to 12 ms, load impedance <90 mΩ, see Figure 12 Typ 960 μF Included inside the power supply (1) Power Boost This power/ current is continuously allowed up to an ambient temperature of 45 °C (113 °F). Above 45 °C (113 °F), do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes. (2) HiccupPLUS Mode At heavy overloads (when output voltage falls below 26V), the power supply delivers continuous output current for 2 s. After this, the output is switched off for approx 18 s before a new start attempt is automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device operates normally. See Figure 13. (3) Discharge current of output capacitors is not included. Figure 11 - Output Voltage Versus Output Current, Typ Output Voltage Figure 12 - Dynamic Output Current Capability, Typ Output Voltage Adjustment Range 56V Continuous current 48 48 Factory setting 40 32 (dynamic behavior, < 12 ms) 56V Adjustment Range 40 32 24 24 Hiccup PLUS mode 16 8 0 16 8 0 Output Current 0 1 2 3 4 5 7 6 8 9 10 A Output Current 5 0 10 15 20 25 A Figure 13 - Short-circuit on Output, HiccupPLUS Mode, Typ Output Current Normal operation Normal operation Short -circuit 7A t 0 2s 18 s 2s 18 s 2s 18 s Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 11 Hold-up Time Values Attributes Hold-up time Notes AC 100V AC 120V AC 230V Typ 67 ms 67 ms 67 ms At 48V, 2.7 A, see Figure 14 Min 50 ms 50 ms 50 ms At 48V, 2.7 A, see Figure 14 Typ 34 ms 34 ms 34 ms At 48V, 5.4 A, see Figure 14 Min 26 ms 26 ms 26 ms At 48V, 5.4 A, see Figure 14 Figure 14 - Hold-up Time Versus Input Voltage Figure 15 - Shutdown Behavior, Definitions Hold-up Time a) 48V 2.7 A typ b) 48V 2.7 A min 80 ms 70 60 50 40 30 20 10 0 Input Voltage a b c d 120 155 Hold-up Time 190 230V AC This feature monitors the output voltage on the output terminals of a running power supply. Attributes Descriptions and Values Contact closes As soon as the output voltage reaches typ 90% of the adjusted output voltage level. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage. Short dips are extended to a signal length of 100 ms. Dips shorter than 1 ms are ignored. Switching hysteresis Typ 2V Maximal 60V DC 0.3 A, 30V DC 1 A, 30V AC 0.5 A, resistive load Contact ratings Minimal permissible load: 1 mA at 5V DC Isolation voltage See Dielectric Strength on page 20. Figure 16 - DC OK Relay Contact Behavior V OUT = V ADJ 10% < 1 ms open 12 - 5% Output Voltage Input Voltage 90 DC OK Relay Contact Zero Transition c) 48V 5.4 A typ d) 48V 5.4 A min > 1 ms closed 0.9* V ADJ 100 ms open closed Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Efficiency and Power Losses Values Attributes Efficiency Average efficiency(1) Power losses AC 230V Notes AC 100V AC 120V Typ 93.0% 93.8% 95.5% At 48V, 5.4 A Typ 92.7% 93.6% 95.4% At 48V, 6 A (Power Boost) Typ 92.8% 93.4% 94.5% 25% at 1.3 A, 25% at 2.6 A, 25% at 3.9 A. 25% at 5.4 A Typ 2.5 W 2.3 W 2.0 W At 48V, 0 A Typ 10.2 W 9.5 W 7.4 W At 48V, 2.7 A Typ 19.5 W 17.2 W 12.3 W At 48V, 5.4 A Typ 22.7 W 19.7 W 13.9 W At 48V, 6 A (Power Boost) (1) The average efficiency is an assumption for a typical application where the power supply is loaded with the following: • 25% of the nominal load for 25% of the time • 50% of the nominal load for 25% of the time • 75% of the nominal load for 25% of the time • 100% of the nominal load for 25% of the time Figure 17 - Efficiency Versus Output Current at 48V, Typ Figure 18 - Losses Versus Output Current at 48V, Typ Efficiency Power Losses 96% 30 W (c) 95 (a) 100V AC (b) 120V AC (c) 230V AC 25 94 (b) 93 (a) (a) 100V AC (b) 120V AC (c) 230V AC 92 91 Output Current 20 (a) (b) 15 (c) 10 5 Output Current 0 90 1 1.5 2 2.5 3 3.5 4 4.5 5 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 A 5.5 6 A Figure 19 - Efficiency Versus Input Voltage at 48V, 5.4 A, Typ Figure 20 - Losses Versus Input Voltage at 48V, 5.4 A, Typ Efficiency Power Losses 96% 22 W 95 20 94 18 93 16 92 14 12 91 Input Voltage 90 100 120 180 Input Voltage 10 230 264V AC 100 120 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 180 230 264V AC 13 Lifetime Expectancy The Lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only states a maximum life of up to 15 years (131,400 hr). Any number exceeding this value is a calculated theoretical lifetime, which can be used to compare devices. Values Attribute Lifetime expectancy Mean Time Between Failure Notes AC 100V AC 120V AC 230V 141,000 hr 158,000 hr 188,000 hr At 48V, 2.7 A and 40 °C (104 °F) 399,000 hr 446,000 hr 531,000 hr At 48V, 2.7 A and 25 °C (77 °F) 63,000 hr 77,000 hr 120,000 hr At 48V, 5.4 A and 40 °C (104 °F) 178,000 hr 219,000 hr 338,000 hr At 48V, 5.4 A and 25 °C (77 °F) 45,000 hr 57,000 hr 97,000 hr At 48V, 6 A and 40 °C (104 °F) 126,000 hr 161,000 hr 275,000 hr At 48V, 6 A and 25 °C (77 °F) Mean Time Between Failure (MTBF) is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF value is a statistical representation of the likelihood of a device to fail. An MTBF value of, for example, 1,000,000 hr means that statistically one unit fails every 100 hours if 10,000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50,000 hr or only for 100 hr. Values Attribute AC 100V MTBF SN 29500, IEC 61709 AC 230V 506,000 hr 523,000 hr 699,000 hr 897,000 hr 923,000 hr 1,201,000 hr At 48V, 5.4 A and 25 °C (77 °F) At 48V, 5.4 A and 40 °C (104 °F) 223,000 hr 224,000 hr 248,000 hr At 48V, 5.4 A and 40 °C (104 °F); Ground Benign GB40 303,000 hr 303,000 hr 339,000 hr At 48V, 5.4 A and 25 °C (77 °F); Ground Benign GB25 50,000 hr 51,000 hr 58,000 hr At 48V, 5.4 A and 40 °C (104 °F); Ground Fixed GF40 65,000 hr 65,000 hr 74,000 hr At 48V, 5.4 A and 25 °C (77 °F); Ground Fixed GF25 MTBF MIL HDBK 217F Functional Diagram Notes AC 120V Figure 21 - Functional Diagram L N Input Fuse Input Filter Input Rectifier Inrush Current Limiter PFC Converter Power Converter Output Filter Output Voltage Regulator Temperature Shutdown 14 Output Power Manager Output OverVoltage Protection Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Output Voltage Monitor + + V OUT DC OK Status Indicator DC OK Relay DC OK Contact Terminals and Wiring The terminals are IP20 fingersafe constructed and suitable for field wiring and factory wiring. Attributes Values for both input and output terminals Values for DC OK signal terminals Type Screw terminals Push-in terminals Solid wire 2 6 mm max 1.5 mm2 max Stranded wire 4 mm2 max 1.5 mm2 max American Wire Gauge AWG 20…10 AWG 24…16 Wire diameter 2.8 mm max (0.11 in. max) (including ferrules) 1.6 mm max (0.06 in. max) (including ferrules) Wire stripping length 7 mm (0.28 in.) 7 mm (0.28 in.) Screwdriver 3.5 mm (0.14 in.) slotted or cross-head No Not required 2 Recommended tightening torque 1 N•m (9 lb•in) Not applicable For wiring, follow these rules: • • • • • Use appropriate copper cables that are designed for minimum operating temperatures of: - 60 °C (140 °F) for ambient up to 45 °C (113 °F) - 75 °C (167 °F) for ambient up to 60 °C (140 °F) - 90 °C (194 °F) for ambient up to 70 °C (158 °F) Follow national installation codes and installation regulations. Ensure that all strands of a stranded wire enter the terminal connection. Unused terminal compartments should be securely tightened. Ferrules are allowed. Daisy Chaining Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current through one terminal pin does not exceed 25 A. If the current is higher, use a separate distribution terminal block as shown in Figure 23. Figure 22 - Daisy Chaining of Outputs Power Supply + + - - Output Figure 23 - Using Distribution Terminals Distribution Terminals Power Supply + + - - Output Load + - Power Supply + + - - Output Power Supply + + - - Output Load + - max 25 A continuous Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 15 Front Side and User Elements Figure 24 - Front Side 1 2 User Elements Input Terminals (screw terminals) N, L Line input PE (Protective Earth) input 3 2 4 3 5 4 5 Output Terminals (screw terminals) Two identical + poles and three identical - poles. + Positive output – Negative (return) output Output Voltage Potentiometer Open the flap to adjust the output voltage. Factory set: 48.0V. DC OK Status Indicator (green) On when the output voltage is >90% of the adjusted output voltage. DC OK Relay Contact (spring-clamp terminals) Monitors the output voltage of the running power supply. See DC OK Relay Contact on page 12 for details. 1 16 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Electromagnetic Compatibility The power supply is suitable for applications in industrial, residential, commercial, and light industrial environments. Electromagnetic compatibility (EMC) immunity information, according to generic standards EN 61000-6-1 and EN 61000-6-2, is provided in the following table. Attributes Standards Electrostatic discharge EN 61000-4-2 Electromagnetic RF field EN 61000-4-3 Fast transients (Burst) EN 61000-4-4 Surge voltage on input EN 61000-4-5 Criteria(1) Values Contact discharge 8 kV Criterion A Air discharge 15 kV Criterion A 80 MHz…2.7 GHz 20V/m Criterion A Input lines 4 kV Criterion A Output lines 2 kV Criterion A DC OK signal (coupling clamp) 2 kV Criterion A LN 2 kV Criterion A L PE, N PE 4 kV Criterion A +- 1 kV Criterion A Criterion A Surge voltage on output EN 61000-4-5 + / - PE 2 kV Surge voltage on Signals EN 61000-4-5 DC OK signal PE 1 kV Criterion A Conducted disturbance EN 61000-4-6 0.15…80 MHz 20V Criterion A 0% of 100V AC 0V AC, 20 ms Criterion A 40% of 100V AC 40V AC, 200 ms Criterion C 70% of 100V AC 70V AC, 500 ms Criterion C Mains voltage dips EN 61000-4-11 Voltage interruptions EN 61000-4-11 0% of 200V AC 0V AC, 20 ms Criterion A 40% of 200V AC 80V AC, 200 ms Criterion A 70% of 200V AC 140V AC, 500 ms Criterion A 0% of 200V AC (=0V) 5000 ms Criterion C Dips on the input voltage according to SEMI F47 standard Voltage sags SEMI F47 0706 Powerful transients VDE 0160 80% of 120V AC (96V AC) 1000 ms Criterion A 70% of 120V AC (84V AC) 500 ms Criterion A 50% of 120V AC (60V AC) 200 ms Criterion A Over entire load range 750V, 0.3 ms Criterion A (1) Criterion A: The device shows normal operation behavior within the defined limits. Criterion C: Temporary loss of function is possible. The device may shut down. If it shuts down, it then restarts by itself. No damage or hazards for the device occur. EMC emission information, according to generic standards EN 61000-6-3 and EN 61000-6-4, is provided in the following table. Attributes Standards Conducted emission input lines EN 55011, EN 55015, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Notes Class B Conducted emission output lines(1) IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Limits for DC power port according to EN 61000-6-3 fulfilled Radiated emission EN 55011, EN 55022 Class B Harmonic input current EN 61000-3-2 Class A fulfilled between 0…6 A load Class C fulfilled between 2.5…6 A load Voltage fluctuations, flicker EN 61000-3-3 Fulfilled(2) This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. (1) For information only, not mandatory for EN 61000-6-3. (2) Tested with constant current loads, non-pulsing. Switching frequency information is provided in the following table. Attributes Values Notes PFC converter 110 kHz Fixed frequency Main converter 85…140 kHz Dependent on output load Auxiliary converter 60 kHz Fixed frequency Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 17 Environment Attributes Operational temperature (1) Storage temperature Values Notes -25…+70 °C (-13…+158 °F) Reduce output power according to Figure 25 -40…+85 °C (-40…+185 °F) For storage and transportation 1.9 W/1 °C (1.9 W/1.8 °F) Between 45…60 °C (113…140 °F) 6.5 W/1 °C (6.5 W/1.8 °F) Between 60…70 °C (140…158 °F) Humidity 5…95% r.h. According to IEC 60068-2-30 Do not energize while condensation is present Vibration sinusoidal(2) 2…17.8 Hz: ±1.6 mm (0.06 in.); 17.8…500 Hz: 2 g 2 hours / axis According to IEC 60068-2-6 Shock(2) 30 g 6 ms, 20 g 11 ms 3 bumps / direction, 18 bumps in total According to IEC 60068-2-27 0…2000 m (0…6560 ft) Without any restrictions 2000…6000 m (6560…20,000 ft) Reduce output power or ambient temperature, see Figure 26. 15 W/1000 m (15 W/3281 ft) or 5 °C/1000 m (9 °F/3281 ft) Above 2000 m (6500 ft), see Figure 26 Output derating Altitude Altitude derating III According to IEC 62477-1 for altitudes up to 2000 m (6500 ft) II According to IEC 62477-1 for altitudes from 2000…6000 m (6560…20,000 ft) Degree of pollution 2 According to IEC 62477-1, not conductive LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for use in paint shops. Overvoltage category Corrosive gases ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4 Audible noise Some audible noise may be emitted from the power supply during no load, overload, or short circuit. (1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2 cm (0.79 in.) below the unit. (2) Tested in combination with DIN rails according to EN 60715 with a height of 15 mm (0.59 in.) and a thickness of 1.3 mm (0.05 in.) and standard orientation. Figure 25 - Output Current Versus Ambient Temperature Figure 26 - Output Current Versus Altitude Allowed Output Current at 48V Allowed Output Current at 48V 6A B 6A 5A A 5A 4A 4A 3A 3A 2A 2A A: 90...264V AC, continuous B: short term 1A A: Tamb < 60 °C B: Tamb < 50 °C C: Tamb < 40 °C D: Short term 1A 0 0 -25 0 20 40 60 70 °C Ambient Temperature 18 D C B A Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 0 2000 m 4000 m 6000 m Altitude Protection Features Attributes Values Notes Output protection — Electronically protected against overload, no-load, and short-circuits. If there is a protection event, audible noise may occur. Typ 58.5V DC 60V DC max If there is an internal power supply defect, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart. Degree of protection IP 20 EN/IEC 60529 Penetration protection > 4 mm (0.16 in.) Example: screws, small parts Over-temperature protection Yes Output shutdown with automatic restart. The temperature sensor is installed on critical components inside the unit and turns off the unit in safety-critical situations. For example, when derating requirements are not observed, there is a high ambient temperature, ventilation is obstructed, or the mounting orientation derating is not followed. There is no correlation between the operating temperature and turn-off temperature since this is dependent on input voltage, load, and installation methods. Input transient protection MOV (Metal Oxide Varistor) For protection values see Electromagnetic Compatibility on page 17. Internal input fuse Included Non-user-replaceable, slow-blow, high-braking capacity fuse Output overvoltage protection Safety Features Attributes Values Notes Double or reinforced galvanic isolation Input / output separation Class of protection Isolation resistance PE resistance Touch current (leakage current) SELV IEC/EN 60950-1 PELV IEC/EN 60204-1, EN 62477-1, IEC 60364-4-41 I PE (Protective Earth) connection required > 500 MΩ At delivered condition between input and output, measured with 500V DC > 500 MΩ At delivered condition between input and PE, measured with 500V DC > 500 MΩ At delivered condition between output and PE, measured with 500V DC > 500 MΩ At delivered condition between output and DC OK contacts, measured with 500V DC < 0.1 Ω Resistance between PE terminal and the housing in the area of the DIN rail mounting bracket. Typ 0.14 mA / 0.36 mA At 100V AC, 50 Hz, TN-,TT-mains / IT-mains Typ 0.20 mA / 0.50 mA At 120V AC, 60 Hz, TN-,TT-mains / IT-mains Typ 0.33 mA / 0.86 mA At 230V AC, 50 Hz, TN-,TT-mains / IT-mains Max 0.18 mA / 0.43 mA At 110V AC, 50 Hz, TN-,TT-mains / IT-mains Max 0.26 mA / 0.61 mA At 132V AC, 60 Hz, TN-,TT-mains / IT-mains Max 0.44 mA / 1.05 mA At 264V AC, 50 Hz, TN-,TT-mains / IT-mains Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 19 Dielectric Strength The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment, which applies the voltage with a slow ramp (2 s up and 2 s down). Connect all input-terminals together and all output poles before conducting the test. When testing, set the cutoff current settings to the value in the following table. To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole, or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur. Test or Setting Time A B C Type test 60 s 2500V AC 4000V AC 1000V AC D 500V AC Factory test 5s 2500V AC 2500V AC 500V AC 500V AC Field test 5s 2500V AC 2000V AC 500V AC 500V AC Cutoff current setting — > 10 mA > 10 mA > 20 mA > 1 mA Figure 27 - Dielectric Strength Input DC OK 13 B (1) L N 14 B A D Output Earth, PE C + - (1) When testing input to DC OK, ensure that the max voltage between DC OK and the output is not exceeded (column D). We recommend connecting DC OK pins and the output pins together when performing the test. 20 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Approvals Approval Names Approval Symbols Notes The CE marking indicates conformance with the following European regulations: • EMC Directive • Low Voltage Directive (LVD) • ATEX Directive EC Declaration of Conformity IEC 60950-1 2nd Edition CB Scheme, Information Technology Equipment UL 508 Listed for use as Industrial Control Equipment; U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01); E-File: E56639 IND. CONT. EQ. 2nd Edition Recognized for use as Information Technology Equipment, Level 5; U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950-1); E-File: QQGQ(2,8). E168663 Applicable for altitudes up to 2000 m (6560 ft). ANSI / ISA 12.12.01-2015 Class I Div 2 Recognized for use in Hazardous Location Class I Div 2 T4 Groups A,B,C,D systems; U.S.A. (ANSI / ISA 12.12.01-2015) and Canada (C22.2 No. 213-M1987) EN 60079-0, EN 60079-15 ATEX Approval for use in hazardous locations Zone 2 Category 3G. Number of ATEX certificate: EPS 15 ATEX 1 101 X The power supply must be built-in, in an IP54 enclosure. UL 60950-1 II 3G Ex nA nC IIC T4 Gc IECEx IEC 60079-0, IEC 60079-15 Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc locations. Number of IECEx certificate: IECEx EPS 15.0079X Marine GL (Germanischer Lloyd) classified Environmental category: C, EMC2 Marine and offshore applications EAC TR Registration Registration for the Eurasian Customs Union market (Russia, Kazakhstan, Belarus) Other Fulfilled Standards Regulation Names Regulation Symbols Notes RoHS Directive Directive 2011/65/EU of the European Parliament and the Council of June 8, 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment. REACH Directive Directive 1907/2006/EU of the European Parliament and the Council of June 1, 2007 regarding the Registration, Evaluation, Authorization, and Restriction of Chemicals (REACH) IEC/EN 61558-2-16 (Annex BB) Safety Isolating Transformer Safety Isolating Transformers corresponding to Part 2-6 of the IEC/EN 61558 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 21 Physical Dimensions and Weight Attributes Values and Descriptions Width 39 mm (1.54 in.) Height 124 mm (4.88 in.) Depth 117 mm (4.61 in.) The DIN rail height must be added to the unit depth to calculate the total required installation depth. Weight 600 g (1.3 lb) DIN rail Use 35 mm (1.38 in.) DIN rails according to EN 60715 or EN 50022 with a height of 7.5 mm (0.30 in.) or 15 mm (0.59 in.). Housing material Body: Aluminum alloy Cover: Zinc-plated steel Installation clearances Keep the following installation clearances when the device is loaded permanently with more than 50% of the rated power: 40 mm (1.57 in.) on top, 20 mm (0.79 in.) on the bottom, 5 mm (0.20 in.) on the left side and 5 mm (0.20 in.) on the right side. If the adjacent device is a heat source, such as another power supply, increase the side clearances from 5 mm (0.20 in.) to 15 mm (0.59 in.). Figure 28 - Front View Figure 29 - Side View All dimensions in mm Side Mounting Bracket This bracket is used to mount the power supply sideways with or without a DIN rail. The two aluminum brackets and the black plastic slider of the unit have to be detached, so that the steel brackets can be mounted. For sideways DIN rail mounting, the removed aluminum brackets and the black plastic slider must be mounted on the steel bracket. Figure 30 - Side Mounting with DIN Rail Brackets 22 Figure 31 - Side Mounting without DIN Rail Brackets Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Wall/Panel Mount Bracket This bracket is used to mount the power supply on a wall or panel without using a DIN rail. The bracket can be mounted without detaching the DIN rail brackets. All dimensions in the following figures are in millimeters. Figure 32 - Left Front Isometric View Figure 33 - Right Front Isometric View Figure 34 - Right Back Isometric View Figure 35 - Wall/Panel Mounting, Front View Figure 36 - Hole Pattern for Wall Mounting Figure 37 - Wall/Panel Mounting, Side View Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 23 Redundancy Modules This section provides information about redundancy modules that can be used with the power supply. 1606-XLSRED – 2 x 10 A Inputs, 1 x 20 A Output The 1606-XLSRED is a dual redundancy module, which has two diodes as decoupling devices included. It can be used for various purposes. The most popular application is to configure highly reliable and truly redundant power supply systems. Another application is the separation of sensitive loads from non-sensitive loads. This avoids the distortion of the power quality for the sensitive loads, which can cause controller failures. The 1606-XLSRED does not require an additional auxiliary voltage and is selfpowered even if there is a short circuit across the output. The unit is slender and only requires 32 mm (1.26 in.) width on the DIN rail. 1606-XLSRED40HF – 2 x 20 A Inputs, 1 x 40 A Output The 1606-XLSRED40HF is equipped with two input channels, which are individually decoupled by using MOSFET technology. Using MOSFETs instead of diodes reduces the heat generation and the voltage drop between input and output. The 1606-XLSRED40HF does not require an additional auxiliary voltage and is self-powered even in case of a short circuit across the output. Due to the low power losses, the unit is slender and only requires 46 mm (1.81 in.) width on the DIN rail. Figure 38 - Typical 1+1 Redundant Configuration for 5 A with the 1606-XLSRED Redundancy Module Figure 39 - Typical 1+1 Redundant Configuration for 5 A with the 1606-XLSRED40HF MOSFET Redundancy Module Failure Monitor - - - + + 48-56V DC OK + + +- +- IN 1 IN 2 Failure Monitor - - - + + - - - 48-56V DC OK 48-56V DC OK DC OK DC OK Power Supply Power Supply DC OK Redundancy Module Power Supply OUT L N PE I + - L N PE L N PE I I 48V, 5 A Load L N PE 24 + + + - + - Input Input 2 1 DC OK Redundancy Module Output + - - 48-56V DC OK Power Supply - L N PE I 48V, 5 A Load L N PE Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Peak Current Capability The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short-term currents. This helps to start loads that have a high demand for current. Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current (including the PowerBoost). The same situation applies when starting a capacitive load. The peak current capability also ensures the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. If there is a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner. This avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The following two examples show typical voltage dips for resistive loads: Figure 40 - 10.8 A Peak Current for 50 ms, Typ (two times the nominal current) Figure 41 - 27 A Peak Current for 5 ms, Typ (five times the nominal current) Output Voltage 48V Output Voltage 48V Figure 42 - 16 A Peak Current for 12 ms, Typ (three times the nominal current) 48V 27 A 30.5V 25.3V 16 A 19.3V 10.8 A 12 ms Output Current 0A Output Current 0A 10 ms/DIV Output Voltage 1 ms/DIV Output Current 0A 10 ms/DIV The DC OK relay triggers when the voltage dips more than 10% for longer than 1 ms. Attribute Peak current voltage dips External Input Protection Values Notes Typically dips from 48V to 30.5V At 10.8 A for 50 ms, resistive load Typically dips from 48V to 30.0V At 27 A for 2 ms, resistive load Typically dips from 48V to 25.3V At 27 A for 5 ms, resistive load The unit is tested and approved for branch circuits up to 30 A (UL) and 32 A (IEC). An external protection is only required if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In some countries, local regulations might apply. If an external fuse is used, minimum requirements must be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 6 A B- or CCharacteristic breaker should be used. Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 25 Back-feeding Loads Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against back electro magnetic force (back EMF). This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off. The maximum allowed feed-back-voltage is 63V DC. The maximum allowed feed-back peak current is 21 A. Higher currents can temporarily shut down the output voltage. The absorbing energy can be calculated according to the builtin large sized output capacitor which is specified in Output on page 11. Output Circuit Breakers Standard miniature circuit breakers (MCBs or UL 1077 circuit breakers) are commonly used for AC-supply systems and may also be used on 48V branches. MCBs are designed to help protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the wiring is considered thermally safe regardless of whether the MCB opens or not. To avoid voltage dips and undervoltage situations in adjacent 48V branches that are supplied by the same source, a fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10 ms is necessary corresponding roughly to the ride-through time of PLCs. This requires power supplies with high current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to flow. The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following table has typical test results showing which B- and CCharacteristic MCBs magnetically trip depending on the wire cross-sectional area and wire length. The maximal wire length includes both the length of wire to the load and the length back (+ and – wire lengths combined, as shown in Figure 43). 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 C-2A 42 m (137 ft) 49 m (160 ft) 59 m (193 ft) 109 m (357 ft) C-3A 13 m (42 ft) 24 m (78 ft) 28 m (91 ft) 42 m (137 ft) Figure 43 - Test Circuit Power Supply MCB Load + AC + Wire length DC - S1 - S1: Fault simulation switch 26 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Parallel Use to Increase Output Power 1606-XLE260F power supplies can be paralleled to increase the output power. The output voltage of all power supplies shall be adjusted to the same value (±100 mV) with the same load conditions on all units, or the units can be left with the factory settings. The power supply does not have a feature that balances the load current between the power supplies. Usually the power supply with the higher adjusted output voltage draws current until it goes into current limitation. This means no harm to this power supply as long as the ambient temperature stays below 40 °C (104 °F). If more than three units are connected in parallel, a fuse or circuit breaker with a rating of 10 A or 12 A is required on each output. Alternatively, a diode or redundancy module can also be used. Energize all units simultaneously to avoid the overload HiccupPLUS mode. If the output was in HiccupPLUS mode due to overload or short circuits, and the required output current is higher than the current of one unit, then you may need to cycle the input power (turn-off for at least 5 seconds). Restrictions: Keep an installation clearance of 15 mm (0.59 in.) (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in parallel in any condition where a derating of the output current is required, such as the following: • • mounting orientations other than the standard mounting orientation (terminals on bottom of the unit) altitude Leakage current, EMI, inrush current, and harmonics increase when using multiple power supplies. Figure 44 - Parallel Use to Increase Output Power Unit A AC DC + + Unit B AC DC Load + - - Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 27 Parallel Use for Redundancy Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two decoupled power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is automatically able to support the load current without any interruption. Redundant systems for a higher power demand are usually built in an N+1 method. For example five power supplies, each rated for 5 A are paralleled to build a 20 A redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also Parallel Use to Increase Output Power on page 27. Always use a redundancy module to decouple power supplies from each other. This helps prevent a defective power supply from becoming a load for the other power supplies, which helps ensure that the output voltage is maintained. Further information and wiring configurations can be found in Redundancy Modules on page 24. Recommendations for building redundant power systems: • • Use separate input fuses for each power supply. Monitor the individual power supply units. Therefore, use the DC OK relay contact of the power supply. It is desirable to set the output voltages of all units to the same value (± 100 mV) or leave it at the factory setting. • Figure 45 - Parallel Use for Redundancy Failure Monitor + + - - - 48-56V DC OK DC OK Power Supply L N PE I + + + - + - Input Input 2 1 DC OK Redundancy Module Output + - - - 48-56V DC OK Power Supply - L N PE I 48V, 5 A Load L N PE 28 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Series Operation Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150V DC. Voltages with a potential above 60V DC are not SELV anymore and can be dangerous. Such voltages must be installed with a protection against touching. Earthing of the output is required when the sum of the output voltage is above 60V DC. Avoid return voltage (for example, from a decelerating motor or battery) which is applied to the output terminals. Restrictions: Keep an installation clearance of 15 mm (0.59 in.) (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard mounting orientation (terminals on bottom of the unit). Leakage current, EMI, inrush current, and harmonics increase when using multiple power supplies. Figure 46 - Series Operation Unit A AC DC + + Unit B AC DC Inductive and Capacitive Loads Load + - Earth (see notes) The unit is designed to supply any kind of loads, including capacitive and inductive loads. If very large capacitors, such as electric double layer capacitors (EDLCs or “UltraCaps”) with a capacitance larger than 0.5 F, are connected to the output, the unit might charge the capacitor in the HiccupPLUS mode (see Output on page 11). Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 29 Charging of Batteries The power supply can be used to charge lead-acid or maintenance free batteries (SLA or VRLA batteries). Four 12V batteries are needed in series. Instructions for charging batteries: • Set output voltage (measured at no load and at the battery end of the cable) precisely to the end-of-charge voltage. End-of-charge voltage 55.6V 55.0V 54.3V 53.6V Battery temperature 10 °C (50 °F) 20 °C (68 °F) 30 °C (86 °F) 40 °C (104 °F) • Use a 10 A or 12 A circuit breaker (or blocking diode) between the power supply and the battery. Ensure that the output current of the power supply is below the allowed charging current of the battery. Use only matched batteries when putting 12V types in series. Ensure that the ambient temperature of the power supply stays below 40 °C (104 °F). The return current to the power supply (battery discharge current is typ 1.8 mA when the power supply is switched off (except in case a blocking diode is used). • • • • Operation on Two Phases The power supply can also be used on two-phases of a three-phase-system. Such a phase-to-phase connection is allowed as long as the supplying voltage is below 240V+10%. Figure 47 - Operation On Two Phases Power Supply L1 Center Tap L2 30 240V +10% max L3 AC L N PE DC Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 Use In a Tightly Sealed Enclosure When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure is higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. The power supply is placed in the middle of the box, and no other heat producing items are inside the box. The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 1 cm (0.39 in.). Attributes Enclosure size Values Case A Case B Case C Case D 110 x 180 x 165 mm (4.33 x 7.09 x 6.50 in.) Rittal Typ IP66 Box PK 9516 100, plastic 110 x 180 x 165 mm (4.33 x 7.09 x 6.50 in.) Rittal Typ IP66 Box PK 9516 100, plastic 180 x 180 x 165 mm (7.09 x 7.09 x 6.50 in.) Rittal Typ IP66 Box PK 9519 100, plastic 180 x 180 x 165 mm (7.09 x 7.09 x 6.50 in.) Rittal Typ IP66 Box PK 9519 100, plastic Input voltage 230V AC 230V AC 230V AC 230V AC Load 48V, 4.3 A; (=80%) 48V, 5.4 A; (=100%) 48V, 4.3 A; (=80%) 48V, 5.4 A; (=100%) Temperature inside the box 43.7 °C (110.66 °F) 48.6 °C (119.48 °F) 40.9 °C (105.62 °F) 45.0 °C (113 °F) Temperature outside the box 24.1 °C (75.38 °F) 25.4 °C (77.72 °F) 23.9 °C (75.02 °F) 25.0 °C (77 °F) Temperature rise 19.6 K (35.28 °F) 23.2 K (41.76 °F) 17.0 K (30.6 °F) 20.0 K (36 °F) Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 31 Mounting Orientations Mounting orientations other than Mounting Orientation A (Standard Orientation) require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply. Therefore, mounting orientations B, C, D, and E are displayed with two different derating curves for continuous operation: • • Curve A1: Recommended output current. Curve A2: Maximum allowed output current (results in approximately half the lifetime expectancy of A1). Output Current 6A OUTPUT A1 4.5 Figure 48 - Mounting Orientation A: Standard Orientation Power Supply 3.0 1.5 Ambient Temperature 0 INPUT 10 20 30 40 50 60 °C 50 60 °C 50 60 °C 50 60 °C 50 60 °C Output Current 6A A1 INPUT 4.5 Figure 49 - Mounting Orientation B: Upside Down A2 Power Supply 3.0 1.5 Ambient Temperature OUTPUT 0 10 20 30 40 Output Current 6A A1 4.5 Figure 50 - Mounting Orientation C: Table-top Mounting A2 3.0 1.5 Ambient Temperature 0 10 20 30 40 Output Current 6A OUTPUT Power Supply INPUT Figure 51 - Mounting Orientation D: Horizontal with Input on the Left 4.5 A1 A2 3.0 1.5 Ambient Temperature 0 10 20 30 40 A1 A2 Output Current INPUT 4.5 Power Supply OUTPUT 6A Figure 52 - Mounting Orientation E: Horizontal with Input on the Right 3.0 1.5 Ambient Temperature 0 10 32 Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 20 30 40 Power Supply - 48V, 5.4 A, 260 W, Single-phase Input Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Switched Mode Power Supply Specifications Technical Data, publication 1606-TD002 Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Specifications, publication IC-TD002 Description Provides specifications for Bulletin 1606 products and applications. Provides a quick reference tool for Allen-Bradley industrial automation controls and assemblies. Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general guidelines for the application, installation, and maintenance of solid-state control in Safety Guidelines for the Application, Installation, and Maintenance of the form of individual devices or packaged assemblies incorporating solid-state Solid-State Control, publication SGI-1.1 components. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details. You can view or download publications at rok.auto/literature. Rockwell Automation Publication 1606-RM112A-EN-P - September 2020 33 Rockwell Automation Support Use these resources to access support information. Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC) Find help with how-to videos, FAQs, chat, user forums, and product notification updates. Access Knowledgebase articles. Locate the telephone number for your country. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/support rok.auto/knowledgebase rok.auto/phonesupport rok.auto/literature rok.auto/pcdc Documentation Feedback Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. Waste Electrical and Electronic Equipment (WEEE) At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur Publication 1606-RM112A-EN-P - September 2020 Copyright © 2020 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">
Advertisement