Allen-Bradley Power Supply - 48V, 10 A, Single-phase Input Reference Manual
Allen-Bradley Power Supply - 48V, 10 A, Single-phase Input is a cost-optimized power supply designed for high efficiency and reliability. This compact device offers active Power Factor Correction (PFC) and a wide operational temperature range, making it suitable for various applications. It features a 20% power reserve for continuous operation at elevated temperatures and can deliver three times the nominal output current for 12 ms, helping to trip fuses on faulty output branches.
PDF
Download
Document
Advertisement
Advertisement
Power Supply - 48V, 10 A, Single-phase Input Catalog Number 1606-XLE480FP Reference Manual Original Instructions Power Supply - 48V, 10 A, Single-phase Input Reference Manual Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). 2 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Table of Contents Terminology and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 DC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Input Inrush Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Hold-up Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 DC OK Relay Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Efficiency and Power Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Functional Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Front Side and User Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Connection Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Daisy Chaining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Lifetime Expectancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Mean Time Between Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Electromagnetic Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 EMC Immunity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 EMC Emission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Switching Frequencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Safety and Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Dielectric Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Other Fulfilled Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Physical Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Wall/Panel Mount Bracket. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 1606-XLSBUFFER48 Buffer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 1606-XLSRED40HF Dual Redundancy Module . . . . . . . . . . . . . . . . . 23 Peak Current Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Output Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Charging of Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Series Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Parallel Use to Increase Output Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Parallel Use for Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 1+1 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 N+1 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Operation On Two Phases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Use in a Tightly Sealed Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Mounting Orientations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 3 Table of Contents Notes: 4 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Terminology and Abbreviations Term, Abbreviation, Definition or Symbol PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol. The symbol for Protective Earth. This symbol has the same meaning as PE. Earth, Ground This document uses the term ‘earth’ which is the same as the U.S. term ‘ground.’ A value that is displayed with the AC or DC before the value represents a nominal voltage AC 230V with standard tolerances (usually ±15%) included. For example, DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V). A value with the unit (V AC) at the end is a momentary value without any additional 230V AC tolerances included. 50 Hz versus 60 Hz As long as not otherwise stated, AC 230V parameters are valid at 50 Hz mains frequency. typ A typical value. nom A nominal value. — (alone in a table A dash alone in a table cell indicates that there is no information to be included in that cell. cell) Product Overview Bulletin 1606-XLE power supplies are cost optimized without compromising quality, reliability, and performance. Bulletin XLE power supplies offer high efficiency, electronic inrush current limitation, active Power Factor Correction (PFC), and wide operational temperature range. The compact size is achieved using synchronous rectification, LLC technology, and other design details. The 1606-XLE480FP includes all essential basic functions. The device has a power reserve of 20% included, which can be used continuously at temperatures up to 45 °C (113 °F). The 1606-XLE480FP can deliver about three times the nominal output current for 12 ms, which helps to trip fuses on faulty output branches. The 1606-XLE480FP is suitable for a wide variety of applications because of its high immunity to transients and power surges, low electromagnetic emission, DC OK relay contact, and large international approval package. Product features: • • • • • • • • • • • • AC 100-240V wide-range input Width only 48 mm (1.89 in.) Efficiency up to 96.3% Excellent partial load efficiency 20% output power reserves Safe HiccupPLUS® overload mode Easy fuse breaking – three times nominal current for 12 ms Active power factor correction (PFC) Minimal inrush current surge Full power between -25…+60 °C (-13…+140 °F) DC OK relay contact Current sharing feature for parallel use Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 5 Specifications Attributes Values Notes Output voltage DC 48V Nominal Adjustment range Output current 48…56V Factory setting 48.0V 12.0…10.3 A Below 45 °C (113 °F) ambient 10.0…8.6 A At 60 °C (140 °F) ambient 7.5…6.5 A At 70 °C (158 °F) ambient Derate linearly between 45…70 °C (113…158 °F) AC Input voltage AC AC 100…240V Mains frequency 50…60 Hz -15%/+10% ±6% Input current AC 4.26 / 2.23 A At 120 / 230V AC Power factor 0.99 / 0.98 At 120 / 230V AC Input voltage DC DC 110…150V±20% — Input current DC 4.64 A At 110V DC AC Inrush current 10.0 A typ / 4.5 A typ at 120 / 230V AC Efficiency 95.0% / 96.3% at 120 / 230V AC Losses 25.1 W / 18.4 W at 120 / 230V AC Hold-up time 32 ms typ / 32 ms typ at 120 / 230V AC Temperature range -25…+70 °C (-13…+158 °F) operational Size (w x h x d) 48 x 124 x 127 mm (1.89 x 4.88 x 5 in.) Without DIN rail Weight 830 g (1.83 lb) — All specifications in this document are specified at the following conditions unless otherwise noted: 230V AC, 50 Hz input voltage, 48V, 10 A output load, 25 °C (77 °F) ambient and after a 5 minutes run-in time. Catalog Numbers Catalog Numbers 1606-XLE480FP 1606-XLA-XLE 6 Descriptions Power Supply - 48V, 10 A, Single-phase Input Wall/panel mount bracket Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 AC Input The device is suitable to be supplied from TN-, TT-, and IT mains networks with AC voltage. For suitable DC supply voltages, see DC Input on page 8. Attributes Values Notes Nom AC 100-240V — Min 85-264V AC Continuous operation Min 264-300V AC Occasionally for maximal 500 ms Allowed voltage L or N to earth Max 300V AC Continuous, according to IEC 60664-1 Input frequency Nom 50–60 Hz ±6% AC input AC input range Turn-on voltage Typ 82V AC Steady-state value, see Figure 1 Shut-down voltage Typ 72V AC Steady-state value, see Figure 1 Values Attributes AC 100V AC 120V AC 230V Notes Input current Typ 5.15 A 4.26 A 2.23 A Power factor Typ 0.996 0.996 0.980 At 48V, 10 A, see Figure 3 At 48V, 10 A, see Figure 4 Crest factor Typ 1.65 1.63 1.63 At 48V, 10 A, The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform. Start-up delay Typ 450 ms 450 ms 450 ms See Figure 2 Typ 120 ms 120 ms 120 ms At 48V, 10 A constant current load, 0 mF load capacitance, see Figure 2 Typ 170 ms 170 ms 170 ms At 48V, 10 A constant current load, 10 mF load capacitance, see Figure 2 Max 500 mV 500 mV 500 mV In single use mode, see Figure 2 Turn-on overshoot Figure 1 - Input Voltage Range Figure 2 - Turn-on Behavior, Definitions Rated input range POUT Turn-on Shut-down 500 ms max Input Voltage - 5% Output Voltage V IN 85V Figure 4 - Power Factor Versus Output Current at 48V Output Voltage Power Factor, Typ Input Current, Typ a 6A b a) 100V AC b) 120V AC c) 230V AC 4 Rise Time 264V 300V AC Figure 3 - Input Current Versus Output Current at 48V Output Voltage 5 Start-up delay Ov ershoot Rise time a, b 1.0 c 0.95 0.9 3 c 2 a) 100V AC b) 120V AC c) 230V AC 0.85 0.8 1 Output Current 0 Output Current 0.75 1 2 3 4 5 6 7 8 9 10 11 12 A Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 1 2 3 4 5 6 7 8 9 10 11 12 A 7 DC Input The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit. Connect +pole to L, –pole to N and the PE terminal to an earth wire or to the machine ground. Attributes Values Notes DC input Nom DC 110…150V ±20% DC input range Min 88…180V DC Continuous operation DC input current Typ 4.64 A At 110V DC, at 24V, 20 A Allowed Voltage (+) or (-) input to Earth Max 375V DC Continuous according to IEC 60664-1 Turn-on voltage Typ 80V DC Steady state value Shut-down voltage Typ 70V DC Steady state value Figure 5 - Wiring for DC Input Battery Power Supply AC + L N + Load PE - DC Input Inrush Current An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Values Attributes Inrush current Inrush energy Notes AC 100V AC 120V AC 230V Max 15 A pk 12 A pk 5.5 A pk Temperature independent Typ 12 A pk 10 A pk 4.5 A pk Temperature independent Max 1 A2s 1 A2s 1 A2s Temperature independent Figure 6 - Typical Input Inrush Current Behavior at Nominal Load and 25 °C (77 °F) Ambient Input Current 5 A / DIV 230V AC Input 48V DC Output 8 100 mS/DIV Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Output The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage. The device is designed to supply any kind of loads, including capacitive and inductive loads. If large capacitors, such as electric double layer capacitors (EDLCs or UltraCaps) with a capacitance > 0.25 F are connected to the output, the unit might charge the capacitor in an intermittent mode. The output is electronically protected against overload, no-load, and short-circuits. If there is a protection event, audible noise can occur. Attributes Output voltage Adjustment range Factory setting output voltage Line regulation Load regulation Ripple and noise voltage Output current Fuse breaking current Overload behavior Overload/ short-circuit current Output capacitance Back-feeding loads Values Notes Nom 48V — Min 48…56V Guaranteed value Max 60V This is the max output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not guaranteed that this value can be achieved. Typ 48.0V ±0.2% in “single use” mode at full load, cold unit Typ 47.0V ±0.2% in “parallel use” mode at 10 A, cold unit (results to 46.6V ±0.2% at 12 A and 49.0V ±0.2% at no load) Max 10 mV Between 85…300V AC input voltage change Max 150 mV Between 0…10 A in “single use” mode, static value Typ 2000 mV Between 0…10 A in “parallel use” mode, static value, see Figure 8 on page 10 Max 50 mVpp Bandwidth 20 Hz…20 MHz, 50 Ω Nom 12 A(1) At 48V and an ambient temperature below 45 °C (113 °F) Nom 10 A At 48V and 60 °C (140 °F) ambient temperature Nom 7.5 A At 48V and 70 °C (158 °F) ambient temperature Nom 10.3 A(1) At 56V and an ambient temperature below 45 °C (113 °F) Nom 8.6 A At 56V and 60 °C (140 °F) ambient temperature Nom 6.5 A At 56V and 70 °C (158 °F) ambient temperature — Derate linearly between 45…70 °C (113…158 °F). Typ 30 A Up to 12 ms once every 5 seconds, see Figure 10 on page 10. The fuse breaking current is an enhanced transient current that helps to trip fuses on faulty output branches. The output voltage stays above 40V. — Continuous current For output voltage above 26V DC, see Figure 7 on page 10 — Intermittent current(2) For output voltage below 26V DC, see Figure 7 on page 10 Max 14.8 A Continuous current, see Figure 7 on page 10 Typ 15 A Intermitted current peak value for 2 s typ Load impedance 10 mΩ, see Figure 9 on page 10 Discharge current of output capacitors is not included. Max 4.7 A Intermitted current average value (R.M.S.) Load impedance 10 mΩ, see Figure 9 on page 10 Typ 2 500 μF Included inside the power supply 63V The unit is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off. The absorbing energy can be calculated according to the built-in large sized output capacitor. Max (1) This current is also available for temperatures up to 70 °C (158 °F) with a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes. (2) At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2 s. After this, the output is switched off for 18 s approx before a new start attempt is automatically performed. This cycle is repeated as long as the overload exists. If the overload has been cleared, the device operates normally. See Figure 9 on page 10. Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 9 Figure 7 - Output Voltage Versus Output Current, Typ Output Voltage (Single Use, Typ) Figure 8 - Output Voltage in Parallel Use Mode, Typ Output Voltage Adjustment Range 56V (Parallel Use, Typ) Adjustment Range 57V 48 55V 40 53V A 32 51V A: continuous current B: intermitted current 24 49V 16 45V 43V Output Current 0 2.5 5 7.5 Factory setting 47V B 8 0 10 12.5 15 17.5 20 A Output Current 2 0 Figure 9 - Short-circuit on Output, HiccupPLUS® Mode, Typ 6 4 10 8 12 A Figure 10 - Dynamic Overcurrent Capability, Typ Output Voltage (Dynamic Behavior, < 12 ms) 56V Output Current Normal operation 48 Normal operation Short -circuit Adjustment Range 40 15 A 32 24 t 0 2s 18 s 2s 18 s 2s 18 s 16 8 0 Output Current 0 10 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 5 10 15 20 25 30 35 A Hold-up Time The hold-up time is the time during which the output voltage of a power supply remains within specification following the loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The green DC OK lamp is also on during this time. Values Attributes AC 100V Hold-up Time AC 120V AC 230V Notes Typ 65 ms 65 ms 65 ms At 48V, 5 A, see Figure 11 Min 54 ms 54 ms 54 ms At 48V, 5 A, see Figure 11 Typ 32 ms 32 ms 32 ms At 48V, 10 A, see Figure 11 Min 24 ms 24 ms 24 ms At 48V, 10 A, see Figure 11 Figure 11 - Hold-up Time Versus Input Voltage Figure 12 - Shut-down Behavior, Definitions Hold-up Time Zero Transition 80 ms 70 60 50 40 30 20 10 0 48V, 5 A, typ 48V, 5 A, min 48V, 10 A, typ Hold-up Time Input Voltage 120 155 - 5% Output Voltage 48V, 10 A, min 85 DC OK Relay Contact Input Voltage 190 230V AC This feature monitors the output voltage on the output terminals of a running power supply. Attributes Descriptions Contact closes As soon as the output voltage reaches 90% typ of the adjusted output voltage level. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage. Short dips are extended to a signal length of 100 ms. Dips shorter than 1 ms are ignored. Switching hysteresis 2V Maximal 60V DC 0.3 A, 30V DC 1 A, 30V AC 0.5 A, resistive load Contact ratings Minimal permissible load: 1 mA at 5V DC Isolation voltage See Dielectric Strength on page 19. Figure 13 - DC OK Relay Contact Behavior V OUT = V ADJ 10% < 1 ms open > 1 ms closed 0.9* V ADJ 100 ms open closed Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 11 Efficiency and Power Losses Values Attributes Efficiency Average efficiency(1) Power losses Notes AC 100V AC 120V AC 230V Typ 94.4% 95.0% 96.3% Typ 94.2% 94.9% 96.2% At 48V, 12 A (Power Boost) 95.5% 25% at 2.5 A, 25% at 5 A, 25% at 7.5 A. 25% at 10 A At 48V, 10 A Typ 94.1% 94.6% Typ 2.7 W 2.4 W 2.4 W At 48V, 0 A Typ 14.2 W 12.5 W 10.6 W At 48V, 5 A Typ 28.5 W 25.1 W 18.4 W At 48V, 10 A Typ 35.4 W 31.0 W 22.7 W At 48V, 12 A (Power Boost) (1) The average efficiency is an assumption for a typical application where the power supply is loaded with: 25% of the nominal load for 25% of the time 50% of the nominal load for 25% of the time 75% of the nominal load for 25% of the time 100% of the nominal load for 25% of the time Figure 14 - Efficiency Versus Output Current at 48V, Typ Efficiency Power Losses 97% 96 95 94 93 92 91 90 89 40 W 35 30 25 20 15 10 5 0 (c) (b) (a) (a) 100V AC (b) 120V AC (c) 230V AC Output Current 2 3 4 5 6 7 8 9 10 (a) (a) 100V AC (b) 120V AC (c) 230V AC (b) (c) Output Current 0 1 2 3 4 5 6 7 11 12 A Figure 16 - Efficiency Versus Input Voltage at 48V, 10 A, Typ 8 9 10 11 12 A Figure 17 - Losses Versus Input Voltage at 48V, 10 A, Typ Efficiency Power Losses 97% 40 W 96 35 95 30 94 25 93 20 15 92 Input Voltage 91 100 120 12 Figure 15 - Losses Versus Output Current at 48V, Typ 180 Input Voltage 10 230 264V AC Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 100 120 180 230 264V AC Functional Diagram Figure 18 - Functional Diagram L N Input Fuse Input Filter Input Rectifier Active Inrush Limiter Temperature Shutdown PFC Converter Output Power Manager Power Converter Output Filter Output Voltage Regulator Output OverVoltage Protection Output Voltage Monitor + + Link for Parallel Use V OUT DC OK Status Indicator DC OK Relay DC OK Contact Front Side and User Elements Figure 19 - Front Side 2 3 4 5 6 User Elements 1 Input Terminals N, L: Line input PE symbol: Protective Earth input 2 Output Terminals + Positive output (two identical + poles) – Negative/ return output (three identical - poles) 3 Output Voltage Potentiometer Open the flap to adjust the output voltage. The factory setting is 48.0V 4 DC OK Status Indicator (green) On when the output voltage is >90% of the adjusted output voltage 5 “Parallel Use” “Single Use” Link Link the two terminal poles when power supplies are connected in parallel to increase the output power. To achieve a sharing of the load current between the individual power supplies, the “parallel use” regulates the output voltage in such a manner that the voltage at no load is approx 4% higher than at nominal load. See Parallel Use to Increase Output Power on page 27. 6 DC OK Relay Contact The DC OK relay contact is synchronized with the DC OK status indicator. See DC OK Relay Contact on page 11 for details. 1 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 13 Connection Terminals The terminals are IP20 fingersafe constructed and suitable for field wiring and factory wiring. Terminal Attributes Input Output Signal Terminals Type Screw termination Screw termination Push-in termination 2 max 2 max 6 mm 1.5 mm2 max Solid wire 6 mm Stranded wire 4 mm2 max 4 mm2 max 1.5 mm2 max American Wire Gauge AWG 20…10 AWG 20…10 AWG 24…16 Wire diameter max (including ferrules) 2.8 mm (0.1102 in.) 2.8 mm (0.1102 in.) 1.6 mm (0.0630 in.) Recommended tightening torque 1 N•m (9 lb•in) 1 N•m (9 lb•in) — Wire stripping length 7 mm (0.28 in.) 7 mm (0.28 in.) 7 mm (0.28 in.) Screwdriver 3.5 mm (0.1378 in.) slotted or cross-head No 2 3.5 mm (0.1378 in.) slotted or cross-head No 2 3 mm (0.1181 in.) slotted to open the spring Daisy Chaining Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current through one terminal pin does not exceed 25 A. If the current is higher, use a separate distribution terminal block as shown in Figure 21. Figure 20 - Daisy Chaining of Outputs Power Supply + + - - Output Figure 21 - Using Distribution Terminals Distribution Terminals Power Supply + + - - Output Load + - max 25 A continuous 14 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Power Supply + + - - Output Power Supply + + - - Output Load + - Lifetime Expectancy The lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor manufacturer specification. The manufacturer of the electrolytic capacitors only states a maximum life of up to 15 years (131,400 hr). Any number that exceeds this value is a calculated theoretical lifetime, which can be used to compare devices. Attribute Lifetime expectancy Mean Time Between Failure Values Notes AC 100V AC 120V AC 230V 52,000 hr 66,000 hr 110,000 hr At 48V, 10 A and 40 °C (104 °F) At 48V, 5 A and 40 °C (104 °F) 130,000 hr 152,000 hr 180,000 hr 33,000 hr 45,000 hr 89,000 hr At 48V, 12 A and 40 °C (104 °F) 148,000 hr 188,000 hr 311,000 hr At 48V, 10 A and 25 °C (77 °F) 368,000 hr 431,000 hr 509,000 hr At 48V, 5 A and 25 °C (77 °F) 93,000 hr 128,000 hr 251,000 hr At 48V, 12 A and 25 °C (77 °F) Mean Time Between Failure (MTBF) is calculated according to statistical device failures, and indicates reliability of a device. An MTBF value is a statistical representation of the likelihood of a device to fail and does not necessarily represent the life of a product. An MTBF value of, for example, 1,000,000 hr means that statistically one unit fails every 100 hours if 10,000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50,000 hr or only for 100 hr. For these types of units, the Mean Time To Failure (MTTF) value is the same value as the MTBF value. Attributes MTBF SN 29500, IEC 61709 Values AC 100V AC 120V AC 230V 430,000 hr 443,000 hr 540,000 hr At 48V, 10 A and 40 °C (104 °F) 790,000 hr 810,000 hr 973,000 hr At 48V, 10 A and 25 °C (77 °F) 207,000 hr 209,000 hr 244,000 hr At 48V, 10 A and 40 °C (104 °F); Ground Benign GB40 279,000 hr 283,000 hr 334,000 hr At 48V, 10 A and 25 °C (77 °F); Ground Benign GB25 44,000 hr 45,000 hr 54,000 hr At 48V, 10 A and 40 °C (104 °F); Ground Fixed GF40 58,000 hr 59,000 hr 72,000 hr At 48V, 10 A and 25 °C (77 °F); Ground Fixed GF25 MTBF MIL HDBK 217F Electromagnetic Compatibility Notes The electromagnetic compatibility (EMC) behavior of the device is designed for applications in industrial, residential, commercial, and light industry environments. The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, and EN 61000-6-4. Without additional measures to reduce the conducted emissions on the output (for example, by using a filter), the device is not suited to supply a local DC power network in residential, commercial, and light-industrial environments. No restrictions apply for local DC power networks in industrial environments. Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 15 EMC Immunity Attributes Standards Electrostatic discharge EN 61000-4-2 Electromagnetic RF field EN 61000-4-3 Fast transients (Burst) Surge voltage on input EN 61000-4-4 EN 61000-4-5 Criteria(1) Values Contact discharge 8 kV Criterion A Air discharge 15 kV Criterion A 80 MHz…2.7 GHz 20V/m Criterion A Input lines 4 kV Criterion A Output lines 2 kV Criterion A DC OK signal (coupling clamp) 2 kV Criterion A LN 2 kV Criterion A L PE, N PE 4 kV Criterion A +- 1 kV Criterion A Criterion A Surge voltage on output EN 61000-4-5 + / - PE 2 kV Surge voltage on DC OK EN 61000-4-5 DC OK signal PE 1 kV Criterion A Conducted disturbance EN 61000-4-6 0.15…80 MHz 20V Criterion A 0% of 100V AC 0V AC, 20 ms Criterion A 40% of 100V AC 40V AC, 200 ms Criterion C 70% of 100V AC 70V AC, 500 ms Criterion A Mains voltage dips EN 61000-4-11 0% of 200V AC 0V AC, 20 ms Criterion A 40% of 200V AC 80V AC, 200 ms Criterion A Criterion A 70% of 200V AC 140V AC, 500 ms Voltage interruptions EN 61000-4-11 0% of 200V AC (=0V) 5000 ms Criterion C Powerful transients VDE 0160 Over entire load range 750V, 0.3 ms Criterion A (1) The performance criteria include the following: Criterion A: The device shows normal operation behavior within the defined limits. Criterion C: Temporary loss of function is possible. The device may shut down and restart by itself. No damage or hazards for the device occur. EMC Emission Attributes Standards Notes Conducted emission input lines EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B Radiated emission EN 55011, EN 55022 Class B Harmonic input current EN 61000-3-2 Fulfilled for Class A equipment Fulfilled for Class C equipment in the load range from 4 to 12 A Voltage fluctuations, flicker EN 61000-3-3 Fulfilled, tested with constant current loads, non-pulsing This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Switching Frequencies 16 Type of Switching Frequency Values Notes PFC converter 100 kHz Fixed frequency Main converter 80…140 kHz Output load dependent Auxiliary converter 60 kHz Fixed frequency Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Environment Attributes Operational temperature Storage temperature Output derating Values Notes -25…+70 °C (-13…+158 °F) The operational temperature is the ambient or surrounding temperature and is defined as the air temperature 2 cm (0.79 in.) below the device. -40…+85 °C (-40…+185°F) For storage and transportation 6.4 W/1 °C (6.4 W/1.8 °F) Between 45…60 °C (113…140 °F) 12 W/1 °C (12 W/1.8 °F) Between 60…70 °C (140…158 °F) 0.66 A/1000 m (0.66 A/3281 ft) or 5 °C/1000 m (9 °F/3281 ft) For altitudes >2000 m (6560 ft), see Figure 23 The derating is not controlled by hardware. The user must ensure that the unit stays below the derated current limits to prevent the unit from overloading. Humidity 5…95% r.h. Atmospheric pressure 110…47 kPa See Figure 23 for details Altitude Up to 6000 m (19,685 ft) See Figure 23 for details III According to IEC 60664-1 for altitudes up to 2000 m (6560 ft) II According to IEC 60664-1, for altitudes above 2000 m (6560 ft) Degree of pollution 2 According to IEC 62477-1, not conductive Vibration sinusoidal 2…17.8 Hz: ±1.6 mm (0.0630 in.) 17.8…500 Hz: 2 g 2 hours / axis According to IEC 60068-2-6 Shock 30 g 6 ms, 20 g 11 ms 3 bumps / direction 18 bumps in total According to IEC 60068-2-27 Overvoltage category According to IEC 60068-2-30 Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm (0.59 in.) and a thickness of 1.3 mm (0.0512 in.) and standard orientation. LABS compatibility As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is suitable for use in paint shops. Corrosive gases Tested according to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a service life of minimum 10years in these environments. Audible noise Some audible noise may be emitted from the power supply during no load, overload, or short circuit. Figure 22 - Output Current Versus Ambient Temp. Figure 23 - Output Current Versus Altitude Allowed Output Current at 48V Allowed Output Current at 48V 12 A 12 A B A 10 A C B 10 A A 7.3 A 7.5 A A ... Tamb < 60 °C B... Tamb < 45 °C C... Short term A: 90...264V AC, continuous B: short term (60 s max every 10 minutes) 0 -25 0 45 60 70 °C Ambient Temperature Altitude 0 m AP (1) 110 kPa 2000 m 80 kPa 6000 m 47 kPa (1) Atmospheric pressure Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 17 Safety and Protection Features Attributes Values Notes Min 500 MΩ At delivered condition between input and output, measured with 500V DC Min 500 MΩ At delivered condition between input and PE, measured with 500V DC Min 500 MΩ At delivered condition between output and PE, measured with 500V DC Min 500 MΩ At delivered condition between output and DC OK contacts, measured with 500V DC Max 0.1 Ω Resistance between PE terminal and the housing in the area of the DIN rail mounting bracket. Typ 58.5V DC — Max 60V DC — — If there is an internal anomaly, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart. Class of protection — I According to IEC 61140 A PE (Protective Earth) connection is required Degree of protection — IP 20 According to EN/IEC 60529 Isolation resistance PE resistance Output overvoltage protection Over-temperature protection — Included Output shuts down with automatic restart. Temperature sensors are installed on critical components inside the unit. These sensors turn off the unit in safety critical situations, such as when ambient temperature is too high, ventilation is obstructed, or the derating requirements are not followed. There is no correlation between the operating temperature and turn-off temperature since this is dependent on input voltage, load, and installation methods. Input transient protection — MOV (Metal Oxide Varistor) For protection values, see Electromagnetic Compatibility on page 15. Internal input fuse Touch current (leakage current) 18 — Included Not user-replaceable, slow-blow high-breaking capacity fuse Typ 0.12 mA / 0.31 mA At 100V AC, 50 Hz, TN-,TT-mains / IT-mains Typ 0.18 mA / 0.45 mA At 120V AC, 60 Hz, TN-,TT-mains / IT-mains Typ 0.30 mA / 0.76 mA At 230V AC, 50 Hz, TN-,TT-mains / IT-mains Max 0.16 mA / 0.38 mA At 110V AC, 50 Hz, TN-,TT-mains / IT-mains Max 0.23 mA / 0.55 mA At 132V AC, 60 Hz, TN-,TT-mains / IT-mains Max 0.39 mA / 0.94 mA At 264V AC, 50 Hz, TN-,TT-mains / IT-mains Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Dielectric Strength The output voltage is floating and has no ohmic connection to the ground. A double or reinforced insulation insulates the output to the input. The manufacturer conducts type and routine tests. Field tests can be conducted in the field using the appropriate test equipment, which applies the voltage with a slow ramp (2 s up and 2 s down). Connect all input-terminals together as well as all output poles before conducting the test. When testing, set the cutoff current settings to the value in the table below. We recommend that you connect either the + pole or the – pole to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur. Test or Setting Time A B(1) C Type test 60 s 2500V AC 3000V AC 1000V AC 500V AC Routine test 5s 2500V AC 2500V AC 500V AC 500V AC Field test 5s 2000V AC 2000V AC 500V AC 500V AC Cutoff current setting for field test — > 10 mA > 10 mA > 20 mA > 1 mA D (1) When testing input to DC OK, ensure that the maximal voltage between DC OK and the output is not exceeded (column D). We recommend connecting DC OK pins and the output pins together when performing the test. Figure 24 - Dielectric Strength Input DC-ok B L N B A (1) D Output Earth, PE C + - Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 19 Approvals Approval Names Approval Symbols Notes EC Declaration of Conformity The CE marking indicates conformance with the following directives: – RoHS Directive – EMC Directive – Low Voltage Directive (LVD) IEC 60950-1 2nd Edition planned CB Scheme, Information Technology Equipment IEC 61010-2-201 2nd Edition planned CB Scheme for electrical equipment for measurement, control, and laboratory use - Part 2-201: Particular requirements for control equipment ANSI/UL 61010-2-201 (former UL 508) planned Listed as Open Type Device for use in Control Equipment UL Category NMTR, NMTR7 E-File: NMTR(7).E56639 Ind. Cont. Eq. Registration for the Eurasian Customs Union market (Russia, Kazakhstan, Belarus) EAC TR Registration planned Other Fulfilled Standards Standard Names Standard Symbols Directive 1907/2006/EU of the European Parliament and the Council of June 1, 2007 regarding the Registration, Evaluation, Authorization, and Restriction of Chemicals (REACH) REACH Directive IEC/EN 61558-2-16 (Annex BB) 20 Notes Safety Isolating Transformer Safety Isolating Transformers corresponding to Part 2-6 of the IEC/EN 61558 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Physical Dimensions and Weight Attributes Descriptions Width 48 mm (1.89 in.) Height 124 mm (4.88 in.) Depth 127 mm (5.0 in.) The DIN rail height must be added to the unit depth to calculate the total required installation depth. Weight 830 g (1.83 lb) DIN rail Use 35 mm (1.38 in.) DIN rails according to EN 60715 or EN 50022 with a height of 7.5 mm (0.2953 in.) or 15 mm (0.59 in.). Housing material Body: Aluminum alloy Cover: Zinc-plated steel Installation clearances Keep the following min installation clearances. On top: 40 mm (1.57 in.). On bottom: 20 mm (0.79 in.). On the left and right sides: 5 mm (0.20 in.). If the adjacent device is a heat source, increase the side clearances to 15 mm (0.59 in.). When the device is permanently loaded with less than 50%, the side clearances can be reduced to zero. Penetration protection Small parts like screws and nuts with a diameter larger than 5 mm (0.20 in.) Figure 25 - Front View Figure 26 - Side View All dimensions in mm Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 21 Accessories This section covers accessories that can be used with the power supply. Wall/Panel Mount Bracket This bracket is used to mount the power supply on a wall or panel without using a DIN rail. The power supply can be mounted on the bracket without detaching the DIN rail brackets of the power supply. In the following figures, when a power supply is shown mounted on the bracket, it is a 1606-XLE480EP power supply. Figure 27 - Left Front Isometric View Figure 28 - Right Front Isometric View Figure 29 - Right Back Isometric View Figure 30 - Wall/Panel Mounting, Front View Figure 31 - Hole Pattern for Wall Mounting Figure 32 - Wall/Panel Mounting, Side View All dimensions in mm 22 All dimensions in mm Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 All dimensions in mm 1606-XLSBUFFER48 Buffer Module The 1606-XLSBUFFER48 buffer module is a supplementary device for DC 48V power supplies. It delivers power to bridge typical mains failures or extends the hold-up time after the AC power is turned off. When the power supply provides a sufficient voltage, the buffer module stores energy in the integrated electrolytic capacitors. When the mains voltage is lost, the stored energy is released to the DC-bus in a regulated process. The buffer module can be added in parallel to the load circuit at any given point and does not require any control wiring. One buffer module can deliver 20 A additional current and can be added in parallel to increase the output ampacity or the hold-up time. 1606-XLSRED40HF Dual Redundancy Module The 1606-XLSRED40HF is a dual redundancy module, which can be used to build 1+1 or N+1 redundant systems. The device is equipped with two 20 A nominal input channels, which are individually decoupled using MOSFET technology. The output can be loaded with a nominal 40 A continuous current. Using MOSFETs instead of diodes reduces heat generation, losses, and voltage drop between input and output. Due to these advantages, the unit is narrow and only requires 46 mm (1.81 in.) width on the DIN rail. The device does not require an additional auxiliary voltage and is self-powered even if there is a short circuit across the output. It requires suitable power supplies on the input, where the sum of the continuous short circuit current stays below 45 A. This is typically achieved when the power supplies are featured with an intermittent overload behavior (Hiccup Mode). See Parallel Use for Redundancy on page 28 for wiring information. Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 23 Peak Current Capability The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short-term currents. Peak current capability helps to start load that have a high demand for current. Solenoids, contactors, and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current. The same situation applies when starting a capacitive load. Peak current capability also helps achieve the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. If there is a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner. This avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The following three examples show typical voltage dips for resistive loads. Figure 33 - 20 A Peak Current for 50 ms, Typ (2x the nom current) Figure 34 - 50 A Peak Current for 5 ms, Typ (5x the nom current) 48V Output Voltage 48V Output Voltage Figure 35 - 30 A Peak Current for 12 ms, Typ (3x the nom current) 48V 45V 32V 50 A 36V Output Voltage 30 A 20 A 12 ms Output Current 0A 10 ms/DIV 0A 1 ms/DIV Output Current 0A Output Current 1 ms/DIV The DC OK relay might trigger when the voltage dips more than 10% for longer than 1 ms. Attributes Peak current voltage dips 24 Values Notes Typ From 48…36V At 20 A for 50 ms, resistive load Typ From 48…39V At 50 A for 2 ms, resistive load Typ From 48…32V At 50 A for 5 ms, resistive load Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Output Circuit Breakers Standard miniature circuit breakers (MCBs or UL 1077 circuit breakers) are commonly used for AC-supply systems and can also be used on 48V branches. MCBs are designed to help protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe, regardless of whether the MCB opens or not. To avoid voltage dips and undervoltage situations in adjacent 24V branches that are supplied by the same source, a fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10 ms is necessary corresponding roughly to the ride-through time of PLCs. This requires power supplies with high current reserves and large output capacitors. Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to flow. The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross section and wire length. The following table of test results shows the maximal wire length for a fast (magnetic) tripping. The wire length is always two times the distance to the load (+ and – wire). 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 C-2A 85 m (278.8 ft) 117 m (383.8 ft) 165 m (541.3 ft) >200 m (656.1 ft) C-3A 54 m (177.1 ft) 85 m (278.8 ft) 117 m (383.8 ft) 176 m (577.4 ft) C-4A 35 m (114.8 ft) 48 m (157.4 ft) 65 m (213.2 ft) 107 m (351.0 ft) C-6A 13 m (42.6 ft) 19 m (62.3 ft) 25 m (82.0 ft) 39 m (127.9 ft) C-8A 4 m (13.1 ft) 7 m (22.9 ft) 9 m (29.5 ft) 14 m (45.9 ft) C-10A 3 m (9.8 ft) 6 m (19.6 ft) 8 m (26.2 ft) 13 m (42.6 ft) C-13A — 1 m (3.2 ft) 1 m (3.2 ft) 1 m (3.2 ft) B-6A 36 m (118.1 ft) 52 m (170.6 ft) 75 m (246.0 ft) 116 m (380.5 ft) B-10A 12 m (39.3 ft) 20 m 65.6 ft) 25 m (82.0 ft) 39 m (127.9 ft) B-13A 9 m (29.5 ft) 13 m (42.6 ft) 17 m (55.7 ft) 28 m (91.8 ft) B-16A 2 m (6.5 ft) 3 m (9.8 ft) 5 m (16.4 ft) 6 m (19.6 ft) Figure 36 - Test Circuit for Wire Length Max Power Supply MCB Load + AC + Wire length DC - S1 - S1... Fault simulation switch Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 25 Charging of Batteries The power supply can be used to charge lead-acid or maintenance free batteries. Four 12V SLA or VRLA batteries are needed in series connection. Instructions for charging batteries: 1. Use only matched batteries when putting 12V types in series. 2. Ensure that the ambient temperature of the power supply stays below 40 °C (104 °F). 3. Use a 15 A or 16 A circuit breaker or a blocking diode between the power supply and the battery. 4. Ensure that the output current of the power supply is below the allowed charging current of the battery. 5. The return current to the power supply is typically 6 mA. This return current can discharge the battery when the power supply is switched off except in case a blocking diode is used. 6. Set the device to Parallel Use mode. Adjust the output voltage precisely to the end-of-charge voltage, measured at no load and at the battery end of the cable. Series Operation End-of-charge voltage 55.6V 55.0V 54.3V 53.6V Battery temperature 10 °C (50 °F) 20 °C (68 °F) 30 °C (86 °F) 40 °C (104 °F) Devices of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150V DC. Voltages with a potential above 60V DC must be installed with a protection against touching. Avoid return voltage (for example, from a decelerating motor or battery) which is applied to the output terminals. Keep an installation clearance of 15 mm (0.59 in.) (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use power supplies in series in mounting orientations other than the standard mounting orientation. Leakage current, EMI, inrush current, and harmonics increase when using multiple devices. Figure 37 - Series Operation Unit A Input + Output + Unit B Load Input + - - Output 26 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Parallel Use to Increase Output Power Devices can be paralleled to increase the output power. To parallel the devices to increase power, you must do one of the following: • • Set the output voltage of all devices to the same value (±100 mV) in “Single Use” mode with the same load conditions on all devices. Leave the devices with the factory settings. After the devices are set, set each device to Parallel Use mode, in order to achieve load sharing. The Parallel Use mode regulates the output voltage in such a manner that the voltage at no load is approximately 4% higher than at nominal load. The ambient temperature is not allowed to exceed 60 °C (140 °F). If more than three devices are connected in parallel, a fuse or circuit breaker with a rating of 15 A or 16 A is required on each output. Alternatively, a diode or redundancy module can also be used. Energize all devices simultaneously. If the output was in overload or short circuits, and the required output current is higher than the current of one unit, it might be necessary to cycle the input power. To cycle the input power, turn off the device and keep off for at least 5 seconds. Keep an installation clearance of 15 mm (0.59 in.) (left / right) between two devices and avoid installing devices on top of each other. Do not use devices in parallel in the following conditions: • • The device is mounted in an orientation other than the standard mounting orientation. Any condition where a reduction of the output current is required, such as altitude. Leakage current, EMI, and inrush current increase when using multiple devices. Figure 38 - Parallel Use to Increase Output Power Unit A Input + Output + Unit B Load Input + - - Output Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 27 Parallel Use for Redundancy This section includes 1+1 Redundancy and N+1 Redundancy. 1+1 Redundancy Devices can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one device fails. The simplest way is to put two devices in parallel. This is called a 1+1 redundancy. In case one device fails, the other one is automatically able to support the load current without any interruption. It is essential to use a redundancy module to decouple devices from each other. Decoupling helps ensure that the output voltage is maintained. Decoupling accomplishes this by preventing a defective device from becoming a load for the other device. 1+1 redundancy allows ambient temperatures up to 70 °C (158 °F). Leakage current, EMI, inrush current, and harmonics increase when using multiple devices. Recommendations for building redundant power systems: • • • • • 28 Use separate input fuses for each device. Use separate mains systems for each device whenever it is possible. Monitor the individual devices. Therefore, use the DC OK signal of the device. It is desirable to set the output voltages of all devices to the same value (± 100 mV) or leave it at the factory setting. Set the devices into “Parallel Use” mode. Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 N+1 Redundancy Redundant systems for a higher power demand are usually built in a N+1 method. For example, four devices, each rated for 10 A, are paralleled to build a 30 A redundant system. Leakage current, EMI, inrush current, and harmonics increase when using multiple devices. Keep an installation clearance of 15 mm (0.59 in.) (left / right) between two devices and avoid installing the devices on top of each other. Do not use devices in parallel in mounting orientations other than the standard mounting orientation or in any other condition, where a reduction of the output current is required. For N+1 redundancy the ambient temperature is not allowed to exceed 60 °C (140 °F). See the following figures for wiring examples. Figure 39 - 1+1 Redundant Configuration for 10 A Load Current with a 1606-XLSRED40HF Dual Redundancy Module Figure 40 - N+1 Redundant Configuration for 30 A Load Current with Multiple Power Supplies and 1606-XLSRED40HF Dual Redundancy Modules Failure Monitor Failure Monitor - Output 48V,10 A DCOK Power Supply + - + - + + - Input Input 2 1 Output 48V,10 A o o DCOK Redundancy Module - + opt ional I L - Output 48V,10 A o o DCOK Power Supply Power Supply Output Input L N PE + + - - Input Input L N PE L N PE 10 A Load I I + - + - + + - Input Input 2 1 Output 48V,10 A o o DCOK Redundancy Module - - + + + - - Output 48V,10 A o o Power Supply Output opt ional + + - DCOK Power Supply Input Input L N PE L N PE + - + - + + - Input Input 2 1 Output 48V,10 A o o DCOK Redundancy Module - o o Power Supply Output Input - + L N PE 30 A Load I I I L N N PE PE Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 29 Operation On Two Phases The power supply can be used on two-phases of a three-phase-system. Such a phase-to-phase connection is allowed as long as the supplying voltage is below 240V+10%. Ensure that the wire, which is connected to the N-terminal, is appropriately fused. The maximum allowed voltage between a Phase and the PE must be below 300V AC. Figure 41 - Operation on Two Phases Power Supply L1 240V +10% max AC L3 L N PE DC L2 Use in a Tightly Sealed Enclosure When the device is installed in a tightly sealed enclosure, the temperature inside the enclosure is higher than outside. In such situations, the inside temperature defines the ambient temperature for the device. In the following test setup, the device is placed in the middle of the box, no other heat producing items are inside the box. The load is placed outside the box. The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 1 cm (0.39 in.). The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. Attributes Enclosure size 30 Values Case A Case B 180 x 180 x 165 mm (7.09 x 7.09 x 6.50 in.) Rittal Typ IP66 Box PK 9519 100, plastic 180 x 180 x 165 mm (7.09 x 7.09 x 6.50 in.) Rittal Typ IP66 Box PK 9519 100, plastic Input voltage 230V AC 230V AC Load 48V, 8 A; (=80%) 48V, 10 A; (=100%) Temperature inside the box 45.7 °C (114.26 °F) 50.6 °C (123.08 °F) Temperature outside the box 24.6 °C (76.28 °F) 25.6 °C (78.08 °F) Temperature rise 21.1 K (37.98 °F) 25.0 K (45 °F) Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Mounting Orientations Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The lifetime and MTBF values in this document apply only for the standard mounting orientation. The following curves give an indication for allowed output currents for altitudes up to 2000 m (6560 ft). Allowed Output Current at 48V Figure 42 - Orientation A Standard Orientation OUTPUT 12 A 10 A Power Supply 7.5 A 0 INPUT +45 +60 +70 °C Ambient Temperature Allowed Output Current at 48V 12 A INPUT Figure 43 - Mounting Orientation B Upside Down 7.5 A Power Supply 0 +60 OUTPUT +30 +70 °C Ambient Temperature Allowed Output Current at 48V 12 A Figure 44 - Mounting Orientation C Table-top Mounting 6.5 A 0 +60 +25 +70 °C Ambient Temperature Allowed Output Current at 48V 12 A OUTPUT Power Supply INPUT Figure 45 - Mounting Orientation D Horizontal Rotated Clockwise 6.5 A 0 +60 +25 +70 °C Ambient Temperature Allowed Output Current at 48V INPUT Power Supply Figure 46 - Mounting Orientation E Horizontal Rotated Counterclockwise OUTPUT 12 A 6.5 A 0 +25 +60 +70 °C Ambient Temperature Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 31 Notes: 32 Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 Power Supply - 48V, 10 A, Single-phase Input Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Switched Mode Power Supply Specifications Technical Data, publication 1606-TD002 Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Specifications, publication IC-TD002 Description Provides specifications for Bulletin 1606-XL, -XLE, -XLP, and -XLS products and applications. Provides a quick reference tool for Allen-Bradley industrial automation controls and assemblies. Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general guidelines for the application, installation, and maintenance of solid-state control in Safety Guidelines for the Application, Installation, and Maintenance of the form of individual devices or packaged assemblies incorporating solid-state Solid-State Control, publication SGI-1.1 components. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. Product Certifications website, rok.auto/certifications. You can view or download publications at rok.auto/literature. Rockwell Automation Publication 1606-RM103A-EN-P - July 2020 33 Rockwell Automation Support Use these resources to access support information. Technical Support Center Knowledgebase Local Technical Support Phone Numbers Literature Library Product Compatibility and Download Center (PCDC) Find help with how-to videos, FAQs, chat, user forums, and product notification updates. Access Knowledgebase articles. Locate the telephone number for your country. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/support rok.auto/knowledgebase rok.auto/phonesupport rok.auto/literature rok.auto/pcdc Documentation Feedback Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback. Waste Electrical and Electronic Equipment (WEEE) At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur Publication 1606-RM103A-EN-P - July 2020 Copyright © 2020 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">
Advertisement
Key Features
- High Efficiency
- Active PFC
- Wide Input Voltage
- Power Reserve
- Compact Size
- DC OK Relay Contact
- International Approvals
Frequently Answers and Questions
What is the output voltage adjustment range of the Allen-Bradley Power Supply - 48V, 10 A, Single-phase Input?
The output voltage adjustment range is 48V to 56V. The factory setting is 48V.
What is the maximum output current of the Allen-Bradley Power Supply - 48V, 10 A, Single-phase Input at 60°C (140°F) ambient temperature?
The maximum output current at 60°C (140°F) ambient temperature is 10A.
How long is the hold-up time of the Allen-Bradley Power Supply - 48V, 10 A, Single-phase Input at 48V and 10A load?
The hold-up time at 48V and 10A load is typically 32ms.
What is the purpose of the DC OK relay contact on the Allen-Bradley Power Supply - 48V, 10 A, Single-phase Input?
The DC OK relay contact monitors the output voltage and closes when the output voltage reaches 90% of the adjusted output voltage level. It opens when the output voltage dips below 90% of the adjusted output voltage.