Allen-Bradley 1492 Analog and Digital I/O Conversion Module Installation Instructions
Allen-Bradley 1492 Analog and Digital I/O Conversion Module allows you to seamlessly convert legacy Allen-Bradley 1771 analog and digital I/O modules to compatible 1756 modules. This conversion eliminates the need to rewire field devices, simplifying your upgrade path and preserving existing wiring configurations. The module supports a diverse range of conversion scenarios, including single analog module to one or two 1756 analog modules, and two 1771, 8 pt. Digital I/O modules to a single 1756, 16 pt. Digital I/O module.
PDF
Download
Document
Advertisement
Advertisement
Analog and Digital I/O Conversion Module (Cat 1492-CM1771-LA004) I. Description This I/O Conversion Module provides for the conversion of (1) 1771, 8 Ch Analog I/O module to be converted to (1) or (2) 1756, 6 or 8 Ch Analog I/O module(s) and consists of the following: (1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005F8 or 1492-CONACAB010F8 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) (1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005K8 or 1492-CONACAB005L8 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) (1) Conversion Module: 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005F or 1492-CONACAB005K or 1492-CONACAB005L (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) (1) Conversion Module(s): 1492-CM1771-LA004 (1) Cable: 1492-CONACAB005T1 or 1492-CONACAB005T2 (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) This I/O Conversion Module also provides for the conversion of (2) 1771 Digital I/O modules that also use the 1771-WF swing arm. In this case, this I/O conversion modules provide for the conversion of (2) 1771, 8 pt. Digital I/O modules to be converted to (1) 1756, 16 pt. Digital I/O module and consists of the following: (2) 1771 Module (8pt) to (1) 1756 Module (16pt) (2) Conversion Modules: 1492-CM1771-LA004 (1) Cable: 1492-C005005XT (1) Conversion Mounting Assembly: 1492-MUA… (Table 1) These conversions are accomplished without the removal of any field wires from the existing 1771 Swing Arms. The existing 1771 Swing Arms fit directly onto the edge connector of the 1492 Conversion Modules. On one end of the 1492 Cable are (2) connectors for the Conversion Modules and on the other end is (1) Removable Terminal Block (RTB) for the 1756 I/O module. See the photos below. The I/O signals are routed through the 1492 Conversion Module(s) and the 1492 Cable(s) to the appropriate terminals on the 1756 I/O module(s) per the Wiring Diagrams in Section V. As standard, the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length. Refer to the footnotes in Table 2 for further details. WARNING PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E Printed in U.S.A. De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O chassis, and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel. (1) I. Description (Cont’d) Conversion Compatibility and Product I.D. Label 25-Pin Connector for cable 1492-CONACAB005_ 1492-CM1771-LA004 Conversion Module Cable 1492-CONACAB005T_ Conversion Compatibility and Product I.D. Label 25-Pin Connector for cable 1492-CONACAB005T_ Conversion Compatibility and Product I.D. Label 25-Pin Connector for cable 1492-C005005XT PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E (2) II. Installation The 1492 Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see Table 1 below). A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly. 1) Determine the quantity of each type of 1771 I/O modules used in the 1771 I/O Chassis to be converted. 2) Select the applicable 1492 Conversion Modules from Table 2, Section III. 3) Review the Max Slots for I/O and Chassis Width data from the Table 1 below. 4) Select a 1756 I/O Chassis which has enough I/O Slots. NOTE: (2) I/O slots are required in the 1756 Chassis for conversions where (1) 1771 I/O module converts to (2) 1756 I/O modules. 5) Select the 1492 Conversion Mounting Assembly which has enough Conversion Module slots. NOTE: (2) Conversion Module slots are required in the 1492 Conversion Mounting Assembly for conversions where (2) 1771 I/O module convert to (1) 1756 I/O modules. NOTE: The 1492 Conversion Mounting Assembly has the same Height & Width foot-print as the 1771 Chassis and is designed to use the same mounting hardware. The combined Depth of the 1492 Conversion Mounting Assembly with the 1756 Chassis mounted on top is 10.25 inches (Controller w/key) or 10.0 inches (Controller w/o key). Dimension drawings are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly. - / 0 1 2 3 4 0 0 1 6 7 8 2 9 9 2 " # 6 : 2 d 5 . ; 9 > . ( % ! ! ! * ( ) , ' * % $ ( A ? 7 : 8 # % & " # ' $ ) $ % % $ $ + ( $ % $ % ) ' % % ) % * ) ) ) * $ + * ( $ $ ' , % ' ' $ ) ' * ' ) ' * & * # & ) % c & $ 1 " ) @ 8 $ : = ! ? ' $ 7 ? ? = < ' % ) * $ + & $ ' $ * ) ' & $ & * * & $ & * * & $ % ( * % ' % $ ) * $ + % $ $ * % ' * ) ' c 1771-A3B is not listed as it is used for 19 inch wide instrumentation panels. d Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power Supply. The CoverPlate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left justified, Right justified or Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly. PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E (3) III. Compatibility ^ B D E F G H I J K c d c d c c c e | c d d d c e P Q D c f d c g c d d h h h d i f e e j f l f l f x l t u c l m d c u e e t Q q r t k t s u u l t x u c f w v u w c v v c w y o d d g c e c g e z z g { { z { { v v { c c v v w x } | } | e o ~ { { { h { h d k x k Specification Dimensions Value 11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width) 300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width) Approximate Shipping Weight Storage Temperature Operating Temperature Operating Humidity Shock Non -operating Operating Operating Vibration Maximum Operating Voltage Max. Module Operating Current Per Point: Per Module: 250.6 g (0.55 lbs) (includes carton) -40 to +85 C (-40 to 185° F) 0 to 60 C (32 to 40° F) 5 to 95% at 60° C (non-condensing) 50g 30g 2g at 10 to 500Hz (Agrees with 1756 I/O module specification) 30 Vdc 2 Amps 12 Amps NOTICE Refer to the Wiring Diagram(s) for current limits for a specific configura- Agency Certifications UL Classified: Under UL File Number E113724 CSA CE : compliant for all applicable directives Pollution Degree Environmental Rating 2 IP20 PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E (4) w c Foot Notes: ①To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific 1771 and 1756 I/O modules involved. ②The 3 numbers indicate the length of the 1492 Cable. Recommended cable lengths of 0.5M are shown. Additional cable lengths are as follows: 1.0M = 1492-CONACAB010F/8 or 1492-CONACAB010K/8 or 1492-CONACAB010L/8 1.0M = 1492-CONACAB010T1 or 1492-CONACAB010T2 ③The 6 numbers indicate the cable length of each portion of the 1492 Cable. Recommended cable lengths of 0.5M / 0.5M are shown. Additional cable lengths are as follows: 1.0M / 1.0M = 1492-C010010XT 0.5M / 1.0M = 1492-C005010XT 1.0M / 0.5M = 1492-C010005XT ④These cables have a maximum operating voltage of 30VDC, 2A maximum per pin, 12A maximum per cable. (Operating specifications are when installed in the Conversion System base / cover-plate assembly) h { c c c x c I F P i IV. Conversion Module Specifications I E Y c j F j [ I h Y F g h { k k h { { g h { { ~ h h { { ~ h { { { ~ z { { { ~ z o { ~ z [ a ~ o [ _ ~ z o z ] z z h P z o z V z o } U z o z } { o o z } { G z | | o \ z } | T z } | o o e F } | o e e x | o o e x x w o o e x w w v e x w v v c e x w v c e x w v c v x w v v { w v c { { v c v { z c c v { { g W v { { g e P v { { z e c z G { { z g O { z g e c d e N z g e d d d c d g e c c d H e c d d c c c d d c y d d c M d d y B E d c y H d c o o e c c o V [ c y y e U Z y o e x Y y o e T y o x x w o e x P o e e w w v e x x v X e x w c x x w v f E w v c i v c x H v c f c c u t W c u r l L u t K u r r t s s q J r t q r i ~ p q f f | q P q o e p p G n i i o n o O m i h h n m n N n i i h d d m m n k c k l m B H k f f k l l k k S M f j j R L f k f f C K k j e k j f e k J f e i j f I i h e H i i h d i G h c c g F d g f E c g f e c t f e G g f e c d e O g f e c N f e c d d e c d d l B H c d d c d d d d c B M d c d C L c c C ` b V. Wiring Diagrams Conversion: 1771-IL(1) to 1756-IF8I (1) (CURRENT) There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING £ Ú Û Ü Ý Þ ß à Ú Û ¤ Ú á â ã Ý £ ¡ ¢ £ ¤ ¥ ¥ ¢ ¦ § ¨ ¨ ä å ã Ý æ ç è é ê ë ì í ë © ª « ¬ ­ ® ¯ ° ± ® ± ² ³ ³ ´ µ c ¶ 4-Wire Transmitter + Power Supply Channel0 Channel0 Channel1 Channel1 Channel2 Channel2 Channel3 Channel3 + - Transmitter - + 2-Wire Transmitter Channel4 Channel4 Channel5 Channel5 Channel6 Channel6 Channel7 Channel7 - 18 17 16 15 14 13 12 11 10 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 · ¸ ¹ À Æ Å Æ Å Æ · ¾ ½ Æ Â ¸ ¾ ¹ À · ¹ Æ ¹ Æ È È È Å » ¿ É 20 22 19 21 28 30 27 29 É ¹ Æ Â Ã Å È ¹ Æ ¼ ½ É È Å Æ É ¹ È É ¼ Ç ¸ ¹ º » ¼ 3 d Ê Ë Î Ë Õ Ê × Ì Ö Í Î Ê Ë Ï Ë Ê Ð Ì Ñ Ø Ò Ó Ô SH d Õ 1 2 7 8 9 10 15 16 17 18 Ö Ù c Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M) d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF8I [1492-CONACAB005K8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud. e The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration in the 1756-IF8I. f Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E (5) Iin_CH0 RTN_CH0 Iin_CH1 RTN_CH1 Iin_CH2 RTN_CH2 Iin_CH3 RTN_CH3 É ¼ ½ Á Æ Å ¹ Æ ½ ¼ Ã É Å Å º ¼ Å Â È ½ ½ ¼ Ã ¼ Ç · Á ¼ ¼ Ã Â ¼ Ã ¹ Æ º ¿ Á ¼ Ã Á Â À » ¼ ¼ À Å ½ Å º ¼ Â À Á ½ ¹ ¸ ¿ Á ½ É ¼ ¸ Ä À 4 6 3 5 12 14 11 13 ¿ ¿ ¼ À È Ç ¼ ¼ ¾ º ½ ¹ Æ Å ½ ¼ ¿ ¾ ¾ ½ ¼ ¼ ½ ½ É Ç ¼ ¼ ¼ Ã È ¸ ¾ » Â ¹ Å Ä 9 8 7 6 5 4 3 2 1 º Á Iin_CH4 RTN_CH4 Iin_CH5 RTN_CH5 Iin_CH6 RTN_CH6 Iin_CH7 RTN_CH7 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. 23 24 25 26 31 32 33 34 35 36 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. V. Wiring Diagrams Conversion: 1771-IL (1) to 1756-IF8I (1) (VOLTAGE) There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING ó * + , - . / 0 * + ô * 1 2 3 - ó î ï ð ñ ò ó ô î õ õ î ò ö ÷ ø ø 4 5 3 - ï 6 ù 4-Wire Transmitter + Power Supply Vout_CH0 RTN_CH0 Vout_CH1 RTN_CH1 Vout_CH2 RTN_CH2 Vout_CH3 RTN_CH3 + - Transmitter - Vout_CH4 RTN_CH4 Vout_CH5 RTN_CH5 Vout_CH6 RTN_CH6 Vout_CH7 RTN_CH7 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 d % ' & ! ( " # $ 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 þ 2 6 1 5 10 14 9 13 18 22 17 21 26 30 25 29 SH d % 3 3 4 7 8 11 12 15 16 19 20 Conversion Module Installation and Application Considerations c Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M) d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF8I [1492-CONACAB005L8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud. e The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration f Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E (6) : ; < = ; Vout_CH4 RTN_CH4 Vout_CH5 RTN_CH5 Vout_CH6 RTN_CH6 Vout_CH7 RTN_CH7 & of module wiring, features and configuration details. 9 Vout_CH0 RTN_CH0 Vout_CH1 RTN_CH1 Vout_CH2 RTN_CH2 Vout_CH3 RTN_CH3 ) in the 1756-IF8I. 8 7 c ÿ þ ý ü û ú N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. 23 24 27 28 31 32 33 34 35 36 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. Conversion: 1771-IL to 1756-IF6I (Current) V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Conversion Module 1492-CM1771-LA004 Cable 1492-CONACAB005Kc 1756-IF6I 4-Wire Transmitter + Power Supply Transmitter - + 2-Wire Transmitter - + - Channel0 Channel0 Channel1 Channel1 Channel2 Channel2 Channel3 Channel3 Channel4 Channel4 Channel5 Channel5 Channel6 Channel6 Channel7 Channel7 d 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 > 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 ? @ G A H L M @ L L D M @ M G D D @ A B C ? C C A D G D H L M I > N @ ? E C C H M M M C @ @ O M J P O P 1 2 7 8 P O P @ O A B C A IN-0/I RET-0 IN-1/I RET-1 IN-2/I RET-2 IN-3/I RET-3 P IN-0/V IN-1/V IN-2/V IN-3/V C F G L L C C ? K D I L @ J C O D M C I J @ L L J C H ? F I M K C J H G L > E I G H P C F H D 3 5 4 6 9 11 10 12 F F C G O N C C E A D E E D C F D D C C C L C C P N ? E J O M K B I @ I O J 17 19 18 20 15 16 C P IN-4/I RET-4 IN-5/I RET-5 IN-4/V IN-5/V SH d 1771-WF Swing Arm From 1771-IL Conversion Module Installation and Application Considerations c Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M) d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005K] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud. e The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I. f Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E [Reference Doc: 41171-030] (7) V. Wiring Diagrams WARNING Conversion: 1771-IL to 1756 -IF6I (Voltage) There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. Conversion Module 1492-CM1771-LA004 + Power Supply 2-Wire Transmitter + Transmitter - - Channel0 Channel0 Channel1 Channel1 Channel2 Channel2 Channel3 Channel3 Channel4 Channel4 Channel5 Channel5 Channel6 Channel6 Channel7 Channel7 Cable 1492-CONACAB005Lc 18 17 16 15 14 13 12 11 10 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 Q R S T Z [ _ ` _ ` S a W _ ` a Q R W S ^ V V Y ` Q R ^ X ` ` b _ V c S S b b c c c ` S b c V T V U V V V T 3 4 13 14 17 18 Y Z [ _ ` S W \ ] _ _ _ V S R W W V V b V W \ ] a ` S T [ ] \ ] [ U V Z \ Z _ T R _ W 4 7 11 8 12 9 10 15 19 16 20 V [ [ c V \ ] Z Z b Y [ W 1 5 2 Y Y V Z W S V V X T Y ` X X W V V _ X c V W W V R V V b ^ X U \ ] ` S \ b 1756-IF6I ] V c IN-0 RET-0 IN-1 RET-1 IN-2 RET-2 IN-3 RET-3 NO CONNECT NO CONNECT IN-4 RET-4 IN-5 RET-5 NO CONNECT NO CONNECT NO CONNECT NO CONNECT NO CONNECT NO CONNECT SH d d 1771-WF Swing Arm From 1771-IL Conversion Module Installation and Application Considerations c Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M) d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005L] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud. e The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I. f Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E [Reference Doc: 41171-029 ] (8) Conversion: 1771-IL (1) to 1756-IF6I (2) (Current) V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Conversion Module 1492-CM1771-LA004 + Power Supply 4-Wire Transmitter + Transmitter - - 2-Wire Transmitter + Channel0 Channel0 Channel1 Channel1 Channel2 Channel2 Channel3 Channel3 Channel4 Channel4 Channel5 Channel5 Channel6 Channel6 Channel7 Channel7 - d 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Cable 1492-CONACAB005T1c 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 d e f m g n r s o f r s q f e i m n r s o t e f q e i i n s i g j u j j r s s f i i f f u s p v r r s o f p i u u v 1 2 7 8 v v f u g h i g IN-0/I RET-0 IN-1/I RET-1 IN-2/I RET-2 IN-3/I RET-3 v IN-0/V IN-1/V IN-2/V IN-3/V i l m r o p i d k o s h i i n r p p n m r j o n j j l l n 1756-IF6I 3 5 4 6 9 11 10 12 l l m m i i i j g i i m v i e k k k g u t d k j j f j j j i l s r i i i i r i v t e k p u s q h f o u p 17 19 18 20 15 16 i v IN-4/I RET-4 IN-5/I RET-5 IN-4/V IN-5/V SH d 1756-IF6I 1771-WF Swing Arm From 1771-IL 3 5 4 6 9 11 10 12 1 2 7 8 17 19 18 20 15 16 IN-0/I RET-0 IN-1/I RET-1 IN-2/I RET-2 IN-3/I RET-3 IN-0/V IN-1/V IN-2/V IN-3/V IN-4/I RET-4 IN-5/I RET-5 IN-4/V IN-5/V Conversion Module Installation and Application Considerations c Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M) d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T1] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud. e The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I. f Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. g This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility. [Reference Doc: 41171-032] PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E (9) V. Wiring Diagrams WARNING Conversion: 1771-IL (1) to 1756-IF6I (2) (Voltage) There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. Conversion Module 1492-CM1771-LA004 + Power Supply 4-Wire Transmitter + Transmitter - - 2-Wire Transmitter + Channel0 Channel0 Channel1 Channel1 Channel2 Channel2 Channel3 Channel3 - Channel4 Channel4 Channel5 Channel5 Channel6 Channel6 Channel7 Channel7 d 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Cable 1492-CONACAB005T2c 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 w x y z y y w x | x y x ~ z | | y y { | | y 6 7 11 8 12 9 10 15 19 16 20 z 3 4 13 14 17 18 y | w | y } | } | } } y | z | { | | z | } } y x | } 1756-IF6I 1 5 2 | z } | | ~ | ~ } | ~ ~ } | x | } } | | ~ { | SH 1756-IF6I d 1 5 2 1771-WF Swing Arm From 1771-IL IN-0 RET-0 IN-1 RET-1 IN-2 RET-2 IN-3 RET-3 NO CONNECT NO CONNECT IN-4 RET-4 IN-5 RET-5 NO CONNECT NO CONNECT NO CONNECT NO CONNECT NO CONNECT NO CONNECT 4 7 11 8 12 9 10 15 19 16 20 3 4 13 14 17 18 IN-0 RET-0 IN-1 RET-1 IN-2 RET-2 IN-3 RET-3 NO CONNECT NO CONNECT IN-4 RET-4 IN-5 RET-5 NO CONNECT NO CONNECT NO CONNECT NO CONNECT NO CONNECT NO CONNECT Conversion Module Installation and Application Considerations c Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T2] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud. e The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I. f Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. g This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility. [Reference Doc: 41171-031] PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E (10) V. Wiring Diagrams WARNING There are several key application considerations and system sp cations (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation. ¿ À Á Â Ã Ä Å ¿ À ¿ Æ Ç È Â Cable ± 2-Wire RTD 3-Wire RTD Channel1 - C Channel1 - B Channel1 - A Channel2 - C Channel2 - B Channel2 - A Channel3 - C Channel3 - B Channel3 - A Channel4 - C Channel4 - B Channel4 - A Channel5 - C Channel5 - B Channel5 - A Channel6 - C Channel6 - B Channel6 - A d 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 e ² ³ ´ £ ¤ £ ¡ ¤ ¤ ¦ £ ¤ ¥ ¢ £ ¤ ¥ ¤ £ ¤ ¦ ¦ § § § ¦ § £ ¦ ¢ ¤ ¤ § £ £ ¤ ¦ £ ¡ ¡ ¤ ¡ ¡ £ ¡ § ¹ £ ¸ · § ¶ ¦ ¥ ¢ µ ¡ ¦ § SH e d ¶ ¹ º ¨ » » ¼ ½ ¾ © ª « ¬ ­ ® ¯ ° ­ c 6 4 3 10 8 7 14 12 11 18 16 15 22 20 19 26 24 23 1 2 5 9 13 17 21 25 27 IN_0/RTD C IN_0(-)/B IN_0(+)A IN_1/RTD C IN_1(-)/B IN_1(+)/A IN_2/RTD C IN_2(-)/B IN_2(+)/A IN_3/RTD C IN_3(-)/B IN_3(+)/A IN_4/RTD C IN_4(-)/B IN_4(+)/A IN_5/RTD C IN_5(-)/B IN_5(+)/A N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. 28 29 30 31 32 33 34 35 36 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. Conversion Module Installation and Application Considerations c Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M) d shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IRT8I [1492-CONACAB005F8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud. e f Refer to your 1771-IR and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and [Reference Doc: 10002306208] PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E (11) V. Wiring Diagrams WARNING Conversion: 1771-IR to 1756-IR6I There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. Conversion Module 1492-CM1771-LA004 Channel1 - C Channel1 - B Channel1 - A Channel2 - C Channel2 - B Channel2 - A Channel3 - C Channel3 - B Channel3 - A Channel4 - C Channel4 - B Channel4 - A Channel5 - C Channel5 - B Channel5 - A Channel6 - C Channel6 - B Channel6 - A 2-Wire RTD 3-Wire RTD Cable 1492-CONACAB005Fc 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 d É Ê Ë Ò Ì Ó × Ø × Ø Ë Ø Ø É Ð Ï × Ø Ô É Ù Ë Ê Ð Î Í Î Ï × Õ Ø Ú Ø Î Û × Ø Î Ë Ë Ú Ú Û Û Ë Ú Û Î Ì Ñ Ó Ø Ô × Õ Î Ú Ë Ï Ì Î Ò × Ô Õ Î Ê Ö Î Ø Î Ô Ë Ï × Õ Î Ó Ø Ì Ñ Ó Õ Ó Ò Í Î Î Ò Ï × Ì Î Ô Ò Ó Ï Ë Ê Ñ Ó Ï Û Î Ê Ö Ò Ñ Ñ Î Ò Ú Ù Î Î Ð Ì Ï Ë × Ï Ð Ð Ï Î Ñ Ï Ï Û Î Î × Î Î Î Ê Ð Õ Ú Ù Ö Í Ô Ë Ô Ú Õ Î Û Û 1756-IR6I 5 3 1 6 4 2 11 9 7 12 10 8 19 17 15 20 18 16 RTN-0/C IN-0/B IN-0/A RTN-1/C IN-1/B IN-1/A RTN-2/C IN-2/B IN-2/A RTN-3/C IN-3/B IN-3/A RTN-4/C IN-4/B IN-4/A RTN-5/C IN-5/B IN-5/A SH d 1771-WF Swing Arm From 1771-IR Conversion Module Installation and Application Considerations c Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). d SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IR6I [1492-CONACAB005F] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud. e The 1771-IR input configuration was software configured, as is the 1756-IR6I. Please ensure the correct configuration in the 1756-IR6I. f Refer to your 1771-IR and 1756-IR6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E [Reference Doc: 41170-950] (12) V. Wiring Diagrams Conversion: 1771-OQ (2) to 1756-OB16I (1) There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Conversion Module 1492-CM1771-LA004 LOAD + LOAD Not Used DC-1 OUTPUT-0 DC-1 OUTPUT 1 OUTPUT 2 DC-2 OUTPUT 3 DC-2 DC-3 OUTPUT-4 DC-3 OUTPUT 5 OUTPUT 6 DC-4 OUTPUT 7 DC-4 Not Used Cable 1492-C005005XTc 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Ü Ý Þ å ß æ ë ç ê ë Þ ê ê ë â â ê à á é Ý á á ß â á ä â æ ç Ý é Þ Ý ã ß á î î î Þ ë í î á ß ä å æ ë à á á ê í í í ê Þ ë Þ ë Þ ë â î ê ê á è á è á ì Ü í â ê á è ç Þ ë ß ë ç á è æ Þ ê ç å Ý å á è æ æ â Ü ã ç å å á ì ä æ î Cable “A” ä ä á ß â í á á ã å á ä Þ ë ã ã â â á á ê â â î á Ý ã á á è í ì é à ç Þ á è í Conversion Module 1492-CM1771-LA004 LOAD + LOAD 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Cable “B” 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Ü Ý Þ å ß æ ë ê ë ã â ë ê ë Þ ê Ü ã Þ Ý á â æ ë ç Ý Þ Ý ã â í â â ê Þ í ë Þ ë í ë 33 34 35 36 á è î ê ê Þ ë ß á á í î DC-1 OUTPUT-8 DC-1 OUTPUT 9 OUTPUT 10 DC-2 OUTPUT 11 DC-2 DC-3 OUTPUT-12 DC-3 OUTPUT 13 OUTPUT 14 DC-4 OUTPUT 15 DC-4 NOT USED NOT USED NOT USED NOT USED î Þ î í î à á á ß ä å æ ë á ç Þ á è DC-1 OUTPUT-0 DC-1 OUTPUT 1 OUTPUT 2 DC-2 OUTPUT 3 DC-2 DC-3 OUTPUT-4 DC-3 OUTPUT 5 OUTPUT 6 DC-4 OUTPUT 7 DC-4 á ì Ü é ç 18 17 20 19 21 22 23 24 26 25 28 27 29 30 31 32 á è æ ß á á è æ ç ë ê è ä ç å à á ä å ê â ê ß á á å æ â ä ä æ â î á Ý é ã å í ì á á å ß ä ã ã â â á á ê î á â â á Ý á á è í ì é à ç Þ ê 2 1 4 3 5 6 7 8 10 9 12 11 13 14 15 16 î 1771-WF Swing Arm From 1771-OQ Not Used DC-1 OUTPUT-8 DC-1 OUTPUT 9 OUTPUT 10 DC-2 OUTPUT 11 DC-2 DC-3 OUTPUT-12 DC-3 OUTPUT 13 OUTPUT 14 DC-4 OUTPUT 15 DC-4 Not Used 1756-OB16I Þ ç í á è î 1771-WF Swing Arm From 1771-OQ Conversion Module Installation and Application Considerations c This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OB16I RTB. Each cable can be either 0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion d The 1771-OQ module output resistive current limits versus 1756-OB16I limits are as follows: a) Current/Point b) Current/Module c) Surge Current/Point 1771-OQ 2.25A 9A 4A for 10ms 1756-OB16I w/ 1492-C005005XT 2A 8A 4A for 10ms e The 1771-OQ is rated 10V to 32V DC. The 1756-OB16I is rated 10V to 30V DC. f Refer to your 1771-OQ and 1756-OB16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E [Reference Doc: 41171-033] (14) PN-114290 DIR 10000060101 (Version 04) Publication 1492-IN048C-EN-E PN-114290 ">
Advertisement
Key features
- Legacy 1771 to 1756 conversion
- Supports Analog & Digital I/O
- Eliminates field rewiring
- Flexible configuration options
- Compatible with 1771 Swing Arms
- Modular design
- Easy installation
- Compact footprint
Frequently asked questions
The 1492 Conversion Module supports conversion of 1771 Analog I/O modules (8 Ch) to 1756 Analog I/O modules (6 or 8 Ch). It also allows converting two (2) 1771, 8 pt. Digital I/O modules to one (1) 1756, 16 pt. Digital I/O module
No, field wiring remains intact. The 1771 Swing Arms fit directly onto the edge connector of the 1492 Conversion Modules, preserving existing connections.
Standard cable lengths are 0.5M. Additional cable lengths of 1.0M are available for both analog and digital conversions.
The 1492 Cables have a maximum operating voltage of 30VDC, with a maximum current of 2A per pin and 12A per cable.