The Allen-Bradley ControlNet Ex Modular Repeater Adapter Fiber Repeater Module is a device that extends the range of ControlNet Ex networks in hazardous locations. It uses fiber optic cables to connect to other repeaters and allows for the interconnection of multiple ControlNet Ex nodes. The module can be mounted on a DIN rail and has various safety features to ensure reliable and safe operation. The device is designed to withstand challenging environments, making it suitable for applications in industries such as oil and gas, chemical processing, and power generation.
PDF
Download
Document
Advertisement
Advertisement
Installation Instructions ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Catalog Numbers 1797-RPA and 1797-RPFM Contents For Information About Important User Information About the ControlNet Ex Fiber Repeater Hub DIN-Rail Mount the 1797-RPA and -RPFM Installation in Zone 1 for CENELEC Installation in Division 1/Zone 1 for UL, C-UL and FM Electrostatic Charge European Community (EC) Directive Compliance Inputs/Outputs Wire the Modules Describing the ControlNet Ex System Diagram Certification Specific ControlNet Ex System Diagrams CENELEC Installation Label CENELEC ControlNet Ex System Diagram UL, C-UL ControlNet Ex System Diagram FM ControlNet Ex System Diagram Module Indicators About the Mounting Kit Repair Specifications - 1797-RPA Specifications - 1797-RPFM Mounting Dimensions See Page 2 4 5 8 8 9 9 12 13 15 17 18 19 20 22 24 26 26 27 29 31 Publication 1797-IN015G-EN-P - August 2017 2 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual we use notes to make you aware of safety considerations. WARNING IMPORTANT ATTENTION Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous voltage may be present. BURN HAZARD Labels may be located on or inside the equipment to alert people that surfaces may be dangerous temperatures. Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 3 ATTENTION Environment and Enclosure This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. Backplane Connector Cover Do not remove unless connecting to 1797-RPFM. Indicators 1797-RPA 1797-RPA COMM STATUS MODULE STATUS REPEATER ADAPTER PWR Label Here ControlNet Ex Tap Drop BNC Connector With Insulator Boot 1 2 3 4 +V -V +V -V Module Locking Tab Repeater Backplane Connector Power and Common Connections 41163 Publication 1797-IN015G-EN-P - August 2017 4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Backplane Connector Cover Do not remove unless connecting to 1797-RPFM. 1797-RPFM 1797-RPFM Label Here Chan 1 Recv Repeater Backplane Connector Chan 2 Xmit Recv Xmit 41267 Module Locking Tab About the ControlNet Ex Fiber Repeater Hub Use the repeater adapter (1797-RPA) and the fiber module (1797-RPFM) together to form a repeater hub within the hazardous area to extend the length of the ControlNet Ex segments to interlink systems all operating within the area. The 1797-RPA repeater adapter, configured with at least one repeater adapter, functions as the intelligent starter block for a multiport repeater. The 1797-RPFM is a nonintelligent fiber-to-backplane conversion device, converting glass-fiber infrared LED media signals to backplane signals for use by the 1797-RPA. A maximum of two 1797-RPFM modules may be used with one 1797-RPA adapter. Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 5 DIN-Rail Mount the 1797-RPA and -RPFM Refer to Mounting Dimensions on page 31. For panel mounting information, see publication 1794-5.13. ATTENTION This product is grounded through the DIN rail to the dedicated intrinsic safety ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (such as aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. 1. Position the module on a 35 x 7.5 mm DIN rail (A-B part number 199-DR1) at approximately a 30o angle. 41167 ATTENTION The DIN rail or mounting bracket must be appropriately connected to the dedicated intrinsic safety ground. 2. Hook the lip on the rear of the adapter onto the top of the DIN rail, and rotate the module onto the rail. 41166 Publication 1797-IN015G-EN-P - August 2017 6 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 3. Press the adapter down onto the DIN rail until flush. The locking tab should snap into position and lock the module to the DIN rail. ATTENTION Make certain that the adapter and fiber modules are secured together with DIN rail anchors. Failure to do so may result in the loss of communications, cause damage to the modules, or both. 4. If the adapter does not snap into position, use a screwdriver or similar device to move the locking tab down while pressing the module flush onto the DIN rail. Release the locking tab to lock the module in place. If necessary, push up on the locking tab to lock. 41168 5. Remove the adapter backplane connector cover. 6. Follow steps 1 to 4 to attach fiber modules to the DIN rail. 7. Once attached to the DIN rail, slide fiber modules to the left to mate with the adapter. Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 7 41169 IMPORTANT A DIN-rail end anchor (A-B part number 1492-EA35) must be used on the left side of the adapter and on the right side of the fiber module to keep the units from moving. 8. Make sure the last fiber module has its backplane connector cover in place. 9. Connect the adapter wiring as shown below in the Wiring section. IMPORTANT You can only attach two media modules to the repeater adapter. If you exceed the module limit, you may cause damage to the adapter or fiber modules and void the IS certification. Publication 1797-IN015G-EN-P - August 2017 8 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Installation in Zone 1 for CENELEC Modules must not be exposed to the environment. Provide a suitable metal enclosure. A label with this system marking must be attached near the main components of the system. If the system is installed in a cabinet, this label must be fixed inside the cabinet. Allen-Bradley 1 Allen-Bradley Dr. Mayfield Hts., OH USA ControlNet Ex System DMT 99 ATEX E 065 X II (1)2G Ex ia ib IIC 0102 -200C <= Ambient Temperature <= +700C Attention! Avoid electrostatic charging! WARNING Modules cannot be used in an intrinsically safe environment after they have been exposed to nonintrinsically safe signals. The fiber optic adapter type 1797-RPFM may be used in combination with the ControlNet adapter type 1797-RPA. Installation in Division 1/Zone 1 for UL, C-UL and FM This adapter must not be exposed to the environment. Provide a suitable metal enclosure. This adapter has a protection factor of IP20. WARNING This adapter cannot be used in an intrinsically safe environment after it has been exposed to nonintrinsically safe signals. Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 9 Make certain that you only connect ControlNet Ex adapters to other intrinsically safe system modules to maintain the integrity of the intrinsically-safe backplane. 41307 Electrostatic Charge Protect the system against electrostatic charge. Post a sign near this module: WARNING Avoid electrostatic charging. ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO DE CARGA ELETROSTÁTICA. For your convenience, a sign that can be cut out is included in this installation instruction. European Community (EC) Directive Compliance If this product has the CE mark it is approved for installation within the European Community or EEA regions. It has been designed and tested to meet the following directives. EMC Directive If this product has the CE mark it is approved for installation within the European Community or EEA regions. It has been designed and tested to meet the following directives. These products are tested to meet the Council Directive 2014/30/EU by applying the following standards: • EN 61000-6-4:2007, Electromagnetic Compatibility (EMC) - Part 6-4: Generic Standard for Industrial Environments (Class A) • EN 61000-6-2:2005, Electromagnetic Compatibility (EMC) - Part 6-2: Generic Standards - Immunity for Industrial Environments • EN 61326-1:2013 (Industrial), Electrical Equipment For Measurement, Control, and Laboratory Use - Industrial EMC Requirements Publication 1797-IN015G-EN-P - August 2017 10 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module European Hazardous Location Approval The following applies to products marked II (1)2 G • Are Equipment Group II, Equipment Category (1)2, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive 2014/34/EU. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details. • The type of protection is “Ex ib[ia] IIC T4” according to EN 60079-11. • Comply to Standards EN 60079-0:2006, EN 60079-11:2007, and EN 60079-26:2004, reference certificate number DMT 99 ATEX E 011 X. • Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are likely to occur occasionally. Such locations correspond to Zone 1 or 2 classification according to ATEX directive 2014/34/EU. IEC Hazardous Location Approval The following applies to products with the IECEx certification: • Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are likely to occur only infrequently and for short periods. Such locations correspond to Zone 1 or 2 classification to IEC 60079-0. • The type of protection is “Ex ib IIC T4” and “Ex ib[ia] IIC T4” according to IEC 60079-11. • Comply to Standards IEC 60079-0:2004, IEC 60079-11:2006, reference IECEx certificate number IECEx BVS 09.0021X. Special Conditions for Safe Use: The fibre optic adapter type 1797-RPFM* can only be use in combination with the ControlNet adapter type 1797-RPA*. Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 11 A warning sign shall be installed in the direct vicinity of this Fibre Optic Hub: “Warning - Avoid electrostatic charging.”. UL, C-UL Compliance If this product has the UL/C-UL mark, it has been designed, evaluated, tested, and certified to meet the following standards: • UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III Division 1, Hazardous (Classified) Locations • UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations • UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2 Hazardous (Classified) Locations • UL 61010, UL Standard for Safety Electrical Equipment For Measurement, Control, and Laboratory Use; Part 1: General Requirements • CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive Equipment for Use in Hazardous Locations • CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in Class I Hazardous Locations • CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres, Part 0: General Requirements • CSA-E79-11-95, Electrical Apparatus for Explosive Gas Atmospheres, Part 11: Intrinsic Safety “i” • CSA C22.2 No. 14-95, Industrial Control Equipment FM Compliance If this product has the FM mark, it has been designed, evaluated, tested, and certified to meet the following standards: • FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous (Classified) Locations General Requirements • FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified) Locations Publication 1797-IN015G-EN-P - August 2017 12 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module • FM C1. No.3615:1989, Explosionproof Electrical Equipment General Requirements • FM C1. No.3810:1989, 1995, Electrical and Electronic Test, Measuring and Process Control Equipment • ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment Inputs/Outputs Do not apply any nonintrinsically safe signals to the adapter or fiber modules. When using as an intrinsically safe electrical apparatus according to EN 60079-11, the European directives and regulations must be followed . Power Supply +V -V 1797-RPA Channel Network uC Bus Fiber Hub Bus uC 41309 Channel 1 Receiver Transmitter 1797-RPFM Bus Fiber Hub Bus Receiver Channel 2 Proc Transmitter 41310 Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 13 Wire the Modules 1. Connect the ControlNet Ex tap drop cable to the connector after removing the insulator boot. ControlNet Ex Coax Tap Insulator Ring Installed 41170 The tap drop BNC must have its insulator ring in position when inserted in the adapter BNC connector. IMPORTANT 2. Connect the fiber media to the fiber module by selecting either the left or right set of receive and transmit ports and attaching the receive and transmit fibers, as appropriate. Make note of which fiber is receive and which is transmit as they must be interchanged at the opposite end. IMPORTANT A-B Q UALITY A-B Allen-Bradley Q UALI TY 1797 - RPA A-B Allen-Bradley 1797 - RPFM Module Status Q UALITY A-B Allen-Bradley Comm Status Module Status PWR FIBER MODULE MEDIUM RANGE . PWR . 1797 - RPFM ControlNet Ex REPEATER ADAPTER . . . Allen-Bradley ControlNet Ex FIBER MODULE MEDIUM RANGE REPEATER ADAPTER Q UALI TY 1797 - RPA ControlNet Ex ControlNet Ex Comm Status . . . Chan 1 1 2 3 4 Chan 1 Chan 2 1 1 +V -V +V -V Receive Transmit 2 3 4 Chan 2 1 +V -V +V -V Recv Xmit Recv Xmit Recv Xmit Recv Xmit Transmit Receive 41311 Publication 1797-IN015G-EN-P - August 2017 14 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 3. Apply +V and -V power to the adapter through a removable terminal block from the Ex power supply. +V -V +V -V +V -V +V -V 41297 Screw terminals and spring terminals are provided. 4. Strip the +V and -V wires to a length so no bare conductor shows after inserting the wires into position. 5. If you are using the spring terminals of the plug, insert a screwdriver into the slot and carefully pry until the spring clamp opens to accept the wire. WARNING Do not use any unused terminals on this adapter. Using these terminals as supporting terminals can result in damage to the module and unintended operation of your system. Make certain that you power this adapter with an intrinsically safe power supply. Do not exceed the values listed in the specifications for this adapter. Do not remove or replace a module when power is applied. Interruption of the bus can result in unintended operation or machine motion. If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 15 IMPORTANT Make sure all fiber modules are attached and secured prior to applying intrinsically safe power to the adapter. Failure to do so may cause damage to the adapter and modules. Describing the ControlNet Ex System Diagram A maximum of 48 ControlNet Ex nodes may be connected together by 250 m (820 ft) of coax cable and 48 taps. The distance to increases to 1000 m (3280 ft) when you use only 2 taps. See the table below for more information. The fiber media of the 1797-RPFM can be installed in a hazardous location (Zone 0, 1 or 2; Class I, Zones 0, 1, and 2; Class I, Division 1 and 2; Class II, Division 1 and 2; Class III, Division 1 and 2) to connect two 1797-RPFM modules or they can be installed through different locations into the nonhazardous location to connect the 1797-RPFM with any approved associated apparatus. All cables and fiber media that are not light blue must be marked as IS using the 1797-EXMK marking kit or other locally approved IS identification or segregation method. During the installation of the ControlNet Ex system, all metallic parts must be isolated to prevent an earth connection (high voltage withstanding of isolating material must be > 500V ac). Publication 1797-IN015G-EN-P - August 2017 16 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module System Catalog Diagram Name Number 1797-RPA 1797-RPA Catalog Name Description ControlNet Ex Modular Repeater Adapter 1797-RPFM ControlNet Ex Fiber Repeater Module, Medium Distance Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx Allows connection of a maximum of two devices per 1797-RPA and is powered directly by 1797-RPA Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx -each one with two redundant output channels that are connected to different ControlNet Ex networks (coax cables and 1797-TPx) Represents one ControlNet Ex node and is a simple capacitor (56 pF) with a coax connector Four types of connections available: S (straight t-tap), R (right angle t-tap), YS (straight y-tap), and YR (right angle y-tap) - a maximum of 48 taps can be connected together by coax trunk cable Simple resistor (75 Ω) with coax connector that must be on each end of the ControlNet Ex coax trunk for termination Maximum (functional) length between 2 1797-TPx is 1000 m (3280 ft) - each 1797-TPx reduces the (functional) coax cable length by 16.3 m (53.4 ft) Different standard cable couplers, such as 90o, 180o. 1797-RPFM 1797-ACNR15/B 1797-ACNR15/B Redundant Media ControlNet Ex Adapter CNet Ex Tap Trm 1797-TCAP ControlNet Ex Tap (Dummy) Terminator ControlNet Ex Tap 1797-TPx ControlNet Ex Coax Tap CNet Ex Trk Trm 1797-XT ControlNet Ex Trunk Terminator Coax Trunk Cable 1786-RG6 Quad-Shield, RG-6 75 Ω Coax Trunk Cable None Standard Coax Trunk Cable BNC Couplers None Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 17 Certified Equivalent ControlNet Ex System Diagram Items You may use these items as equivalents for the items shown on the system diagram. System Diagram Name Catalog Number Source 1797-RPA 1797-RPA Allen-Bradley 1797-RPFM 1797-RPFM Allen-Bradley 1797-ACNR15 1797-ACNR15 Allen-Bradley Coax Trunk Cable(1) 1786-RG6 Allen-Bradley 3092A(2) Belden Wire & Cable Co. 3092A with blue jacket Belden Wire & Cable Co. ControlNet Ex Tap 1797-TPx Allen-Bradley CNet Ex Trk Trm 1797-XT Allen-Bradley CNet Ex Tap Trm 1797-TCAP Allen-Bradley 1 In addition to these cable types, the following specification can be followed to allow additional types: Cable Impedance = 75 Ω + 3 Ω Cable Capacitance = <5.94 nF per 100 m Cable Resistance = >9.08 Ω per 100 m Cable Attenuation 0.2 MHz > 0.93 dB/100 m 5 MHz > 1.39 dB/100 m (-20…70 °C) 0.5 MHz > 0.95 dB/100 m 10 MHz > 1.86 dB/100 m 1 MHz > 1.07 dB/100 m 20 MHz > 2.73 dB/100 m 2 MHz > 1.16 dB/100 m 50 MHz > 4.33 dB/100 m 2 Belden Wire & Cable 1189A may be used, but with functional loss of communication distance, nodes, or both. Certification Specific ControlNet Ex System Diagrams The following pages include certification specific ControlNet Ex system diagrams and notes pertaining to these diagrams. Select either CENELEC, UL, C-UL, or FM and follow the requirements of that diagram as you configure and install your system. Publication 1797-IN015G-EN-P - August 2017 18 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module CENELEC Installation Label A label with this system marking must be attached near the main components of the system. If the system is installed in a cabinet, this label must be fixed inside the cabinet. Allen-Bradley 1 Allen-Bradley Dr. Mayfield Hts., OH USA ControlNet Ex System DMT 99 ATEX E 065 X II (1)2G Ex ia ib IIC 0102 -200C <= Ambient Temperature <= +700C Attention! Avoid electrostatic charging! CENELEC 1797-RPA, -RPFM I/O Entity Parameters Terminals Uo (V) Io (mA) Groups Co (μF) Lo (μH) Male Bus Connector 5.4 400 IIB/IIC 65 10 Publication 1797-IN015G-EN-P - August 2017 30670CE Hazardous Area Zone 0 Safe Area Ch0 fiber CNet Ex tap trm Ci<68 pF Li negl. Li < 1100 uH Li < 560 nH Ci < 60 pF ControlNet Ex tap Power Supply Ui=9.5V, Ii=1 A, Ci=<120 nF, Li=negligible Li < 1100 uH Node 1 75 Ohm 1W Ci negl. Li negl. CNet Ex trk trm Uo=5.4V, Io=201 mA, F-3>500 kHz . Ch1 fiber Ch0 fiber ControlNet Ex tap . . Ch1 fiber ChA Uo=5.4V, Io=160 mA, F-3>500 kHz ControlNet Ex tap Ci=<120 nF, Li=negligible ChB Uo=5.4V, Power Supply Io=160 mA, Ui=9.5V, F-3>500kHz Ii=1 A, 1 Node 3 1797-ACNR15/* or RSD-GW-Ex2.CN Flexbus Uo=5.4V, Io=400 mA, Po=2.16 W, Co=65 μF, Lo=10 μH ChA Uo=5.4V, Io=160 mA, F-3>500 kHz ControlNet Ex tap 75 Ohm 1W Ci negl. Li negl. Flexbus Uo=5.4V, Io=400 mA, Po=2.16 W, Co=65 μF, Lo=10 μH CNet Ex trk trm ChB Uo=5.4V, Io=160 mA, Power Supply F-3>500 kHz Ui=9.5V, Ii=1 A, Ci=<120 nF, Li=negligible Node 4 ... 48 1797-ACNR15/* or RSD-GW-Ex2.CN Protect the system against electrostatic charge. Post a sign near the main components of the system: Attention! Avoid electrostatic charge. For the transmittal between the safe area and the hazardous area only optical glass-fibers are permitted. The diameter of a single glass-fiber must be >6um. The power density of the transmitter diode must be <5mW/mm2. The ControlNet Ex System is an intrinsically safe system according to EN 50039. When installing the system, the certificate of conformity and the national installation regulations must be heeded. The components of the ControlNet Ex system and the interconnections are shown on the installation drawing (Pub. 1797-RM001). *RG6-CNet is defined as: Cable Impedance=75 Ohm + or -3 Ohm Cable Capacitance<6nF per 100 m Cable Resistance>9.08 Ohm per 100 m Cable Attenuation (-20to+70 oC) 0.2 MHz > 0.93 dB/100 m 5 MHz > 1.39 dB/100 m 0.5 MHz > 0.95 dB/100 m 10 MHz >1.86 dB/100 m 1 MHz > 1.07 dB/100 m 20 MHz > 2.73 dB/100 m coax trunk cable coax trunk cable The Coax Trunk Cable is permitted to have a minimum length of 1,000m with only 2 connected ControlNet Ex Cable type 1189A, Taps dropping to only 250m with the maximum allowed connected ControlNet Ex Taps of 48. 3092A, or 3092A Blue from manufacturer The ambient temperature range of the ControlNet Ex system is -20 to +70 oC. Belden Wire or type Near the main components of the system a plate with the system marking must be attached. If RG6-CNet* the system is installed in a cabinet the plate must be fixed on the inside of the cabinet door. . . Hazardous Area Zone 0 Node 2 1797-RPFM/* or 1797-RPA/* or 1797-RPFM/* or RSD-CFA-Ex.CN RSD-FC-Ex2.CN 3km RSD-FC-Ex2.CN 3 km ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 19 CENELEC ControlNet Ex System Diagram Publication 1797-IN015G-EN-P - August 2017 Publication 1797-IN015G-EN-P - August 2017 Hazardous (Classified) Location Zone 0, 1 or 2, IIC Class I, Zones 0, 1 and 2, Groups IIC, IIB, IIA Class I Division 1 and 2, Groups A, B, C, D Class II, Division 1 and 2, Groups E, F, G Class III, Division 1 and 2 Non-Hazardous Location 1786-RPFM or any associated apparatus where the light emitting diode output is <5mW/mm2 CNet Ex tap trm 2 ControlNet Ex tap . Ch1 . Ch1 5 coax trunk cable 4 Ch0 fiber optic cable 1797-RPFM The ambient temperature range of the ControlNet Ex system is -20 to +70oC. CNet Ex trk trm ControlNet Ex tap Node 1 2 Ch0 1797-RPFM Power Supply Vmax=9.5V, Imax=1 A, Ci<120 nF, Li=0 To any approved device or associated apparatus with Entity Concept 1 parameters of Voc<9.5V and Isc<1 A Node 2 1797-RPA 2 ChA coax trunk cable 2 connection to associated apparatus with entity concept parameters listed in Table 1. 1 Maximum devices=8. any IS device with entity concept parameters Vmax, Imax Ci, Li) appropriate for ControlNet Ex tap CNet Ex trk trm 30670 Hazardous (Classified) Location Class I, Zones 1 and 2, Groups IIC, IIB, IIA Class I Division 1 and 2, Groups A, B, C, D Class II, Division 1 and 2, Groups E, F, G Class III, Division 1 and 2 ControlNet Ex tap 2 3 Power Supply Vmax=9.5V, Imax=1 A, To any approved device or Ci<120 nF, associated apparatus with Li=0 Entity Concept 1 parameters of Voc=9.5V and Isc=1 A ChB 1 Node 4 ... 48 1797-ACNR15 ChA any IS device with entity concept parameters Vmax, Imax Ci, Li) appropriate for connection to associated apparatus with entity 1 concept parameters listed in Table 1. Maximum devices=8. Power Supply Vmax=9.5V, Imax=1 A, To any approved device or Ci<120 nF, associated apparatus with Li=0 Entity Concept 1 parameters of Voc=9.5V and Isc=1A ChB 1 Node 3 1797-ACNR15 Hazardous (Classified) Location Zone 1 or 2, IIC Class I, Zones 1 and 2, Groups IIC, IIB, IIA Class I Division 1 and 2, Groups A, B, C, D 20 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module UL, C-UL ControlNet Ex System Diagram ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 21 UL, C-UL ControlNet Ex System Requirements The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus. Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6. WARNING: Substitution of components may impair intrinsic safety. AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque. If fiber optic cable is provided with a metal shield, it must be connected to a dedicated intrinsic safety ground in the nonhazardous location and tied back in the hazardous location or be connected to a ground in the hazardous location and tied back in the nonhazardous location. The glass fiber must have a minimum diameter of 6 μm. UL, C-UL, FM 1797-RPA, -RPFM I/O Entity Parameters Terminals Vt (V) It (mA) Groups Ca (μF) La (μH) Male Bus Connector 5.8 400 A to G 3.0 3.0 Publication 1797-IN015G-EN-P - August 2017 Publication 1797-IN015G-EN-P - August 2017 Hazardous (Classified) Location Class I, Zone 0 Group IIC Class I Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1 Any associated apparatus where the light emitting diode output is <5 mW/mm2 or total <1 mW. or Any associated apparatus where the light emitting diode output is <5 mW/mm2 or total <1 mW. 1786-RPFM CNet Ex trk trm CNet Ex tap trm ControlNet Ex tap Node 1 2 11 ControlNet Ex tap 2 Ch0 1797-RPFM From FM approved 1797-PS2N Node 2 1797-RPA Vmax=9.5V, Imax=1 A, Ci<=120 nF, Li=0 Non-Hazardous Location Ch1 . . Ch1 5 ChA coax trunk cable 2 ChB ControlNet Ex tap 2 ChA CNet Ex trk trm 30670 1 For connection to other I/O modules, refer to General FM Certification Information in Publication 1797-RM001. Vmax=9.5V, Imax=1 A, Ci<=120 nF, Li=0 From FM approved 1797-PS2N 2 ControlNet Ex tap ChB 1 Node 4 ... 48 1797-ACNR15 Hazardous (Classified) Location Class I, Zones 1, Groups IIC Class I Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1 coax trunk cable Vmax=9.5V, Imax=1 A, Ci<=120 nF, Li=0 From FM approved 1797-PS2N 3 The ambient temperature range of the ControlNet Ex system is -20 to +70oC. For connection to other I/O modules, refer to General 1 FM Certification Information in Publication 1797-RM001. Node 3 1797-ACNR15 Any associated apparatus where the light emitting diode output is <5mW/mm2 or total <1mW. 4 Ch0 fiber optic cable 1797-RPFM Hazardous (Classified) Location Class I, Zone 1, Group IIC Class I Division 1, Groups A, B, C, D 22 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module FM ControlNet Ex System Diagram ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 23 FM ControlNet Ex Requirements The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus. Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6. WARNING: Substitution of components may impair intrinsic safety. If fiber optic cable is provided with a metal shield, it must be connected to a dedicated intrinsic safety ground in the nonhazardous location and tied back in the hazardous location or be connected to a ground in the hazardous location and tied back in the nonhazardous location. The glass fiber must have a minimum diameter of 6 μm. The ControlNet Ex tap must be connected directly to the module (no additional cable may be connected). Must be FM approved. Total coax trunk cable length is limited to 1000 m (3280 ft) with up to 2 ControlNet Ex taps connected and to 250 m (820 ft) with the maximum allowed ControlNet Ex taps of 48. For ControlNet Ex taps between 2 and 48 use: 1000 m (3280 ft) - 16.3 m (53.4 ft) x (number of taps - 2) to find the maximum allowed cable length. Publication 1797-IN015G-EN-P - August 2017 24 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Module Indicators The following explains the indications seen on the 1797-RPA and 1797-RPFM modules. 1797-RPA Indicators The figure below identifies indicators on the repeater adapter. 1797-RPA Comm Status 1797-RPA COMM STATUS MODULE STATUS Module Status Module Power Status REPEATER ADAPTER PWR 1 2 3 4 +V -V +V -V 41174 Power Indicator If This Indicates Steady Green Power is applied. Off No power is applied. Comm and Module Status Indicators for the 1797-RPA Module If Both Are This Indicates Alternately Red/Green The adapter is being powered-up or reset. The LEDs alternately flash red and green for about 5 s. Steady Green Normal operation. Off The unit is not powered. Check the module power status. Red There is an adapter fault. If the fault indication is caused by a jabber condition, the fault indication will automatically be cleared when the jabber condition is removed from the coax or fiber port. If a jabber condition is not causing the fault, replace the repeater adapter. Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 25 If Either Is The Respective Segment (1 or 2) is Flashing Green/Off Experiencing temporary network errors. The situation will normally correct itself. If the situation persists, troubleshoot your nodes and cable system. When troubleshooting your cable system, make sure: • all BNC connector pins are properly sealed. • all taps are A-B taps. • all terminators are 75 Ω and are installed at both ends of all segments. Flashing Red/Off Experiencing a high level of network errors. This may indicate a broken cable, broken tap, or missing segment terminator. Important: The indicators will flash red/off when a system has no network activity. This would be normal for a system that has no ControlNet nodes installed or enabled. 1797-RPFM Indicators The figure below identifies indicators on the fiber module. 1797-RPFM 1797-RPFM Chan 1 Channel 1 Status Channel 2 Status Recv Chan 2 Xmit Recv Xmit 41312 1797-RPFM Comm and Status Indicators If Both Are This Indicates Off There is no power or the module is faulted. Green The channel is operational. Flashing Green/Off There is no data activity on the associated channel. Publication 1797-IN015G-EN-P - August 2017 26 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module About the Mounting Kit Use the optional 1794-NM1 mounting kit to mount your system on a panel or wall without a DIN rail. 1794-NM1 Mounting Kit with 18 screws (2 screws for the adapter and 2 screws for each module). 30238 Repair The adapter and fiber module are not field-repairable. Any attempt to open this adapter or fiber module will void the warranty and the IS certification. If repair is necessary, return the modules to the manufacturer. IMPORTANT For detailed certification information, refer to the FLEX Ex System Certification Reference Manual, publication 1797-RM001. Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 27 Specifications - 1797-RPA I/O Capacity 2 fiber modules IS Media Type Ex ib IIB/IIC T4, AEx ib IIC T4, Class I, Division 1 Groups A to G T4 IS Module Type Ex ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 Groups A to D T4 Communication Rate 5 Mbps ControlNet Ex BNC Oscillation powered by: Uo < 5.4V dc Io < 201 mA ac coupled with high-pass filter f > 500 kHz Indicators Comm - green/red Module - green/red Power - green Output (Intrinsically Safe) (30 Pin Male TTL Bus Connector) Manufacturer specific bus Uo < 5.4V Io < 201 mA Po < 1.09 W Lo < 0.45 mH Co < 71 μF Isolation Path Bus to Power Supply Adapter to Adapter ControlNet Ex Node to Other Nodes ControlNet to Power Supply Galvanic to DIN EN 60079-11 Galvanic functional Galvanic functional Galvanic to DIN EN 60079-11 Power Supply (-V, +V Intrinsically Safe) Ui < 9.5V dc Ii < 1 A Pi < 9.5 W Li = negligible Ci < 120 nF Power Consumption 8.5 W Power Dissipation 8.5 W Thermal Dissipation 29 BTU/hr Conductors Wire Size 4 mm2 (12 gauge) stranded max 1.2 mm (3/64 in.) insulation max Dimensions Metric Imperial 94 mm x 94 mm x 91 mm (3.7 in. x 3.7 in. x 3.58 in.) Publication 1797-IN015G-EN-P - August 2017 28 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Weight Approximately 200 g Environmental Conditions Operational Temperature -20…70 oC (-4…158 oF) Storage Temperature -40…85 oC (-40…185 oF) Relative Humidity 5…95% noncondensing Shock Operating Tested 15 g peak acceleration, 11 (±1) ms pulse width Nonoperating Tested 15 g peak acceleration, 11 (±1) ms pulse width Vibration Tested 2 g @ 10…500 Hz per IEC 68-2-6 Agency Certification CENELEC II (1) 2G ib[ia] IIC T4 UL, C-UL Class I Division 1 Groups A to D T4 Class I Zone 1 AEx ib IIC T4 FM Class I Division 1 Groups A to D T4 Class I Zone 1 AEx ib IIC T4 INMETRO IECEx BR-Ex ia/ib IIB/IIC T4 Ex ib IIC T4 and Ex ib[ia] IIC T4 Certificates CENELEC DMT 99 ATEX E011 X UL, C-UL UL File Number E197983 Class I Division 1 Hazardous FM FM Certificate Number 3009806 FM INMETRO 05/UL-BRAE-0011X IECEx IECEx BVS 09.0021X Publication 1797-IN015G-EN-P - August 2017 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 29 Specifications - 1797-RPFM IS Media Type Ex ia IIB/IIC T4, AEx ia IIC T4, Class I, Division 1 Groups A to G T4 IS Module Type Ex ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 Groups A to D T4 Communication Rate 5 Mbit/s Approximate Fiber Media Length 3 km Fiber Type 62.5…125 mm Fiber Termination Type ST (plastic or ceramic) Fiber Operating Wavelength 1300 nm Optical Power Budget 13.3 dB Fiber Optic Transmitter Ch1 and Ch2 Optical peak output power Poptical < 1 mW Indicators Channel 1 status - green Channel 2 status - green Input (Intrinsically Safe) (30 Pin Female TTL Bus Connector) Ui < 5.4V Ii < 201 mA Pi < 1.1 W Li < 15 μH Ci < 41 μF Output (Intrinsically Safe) (30 Pin Male TTL Bus Connector) Uo < 5.4V Io < 201 mA Po < 1.1 W Lo < 0.45 mH Co < 71 μF Isolation Path Bus to ControlNet Galvanic to DIN EN 60079-11 Power Consumption Included in 1797-RPA Power Dissipation Included in 1797-RPA Thermal Dissipation Included in 1797-RPA Weight Dimensions Approximately 100 g Metric Imperial 94 mm x 94 mm x 91 mm (3.7 in. x 3.7 in. x 3.58 in.) Publication 1797-IN015G-EN-P - August 2017 30 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Environmental Conditions Operational Temperature -20…70 oC (-4…158 oF) Storage Temperature -40…85 oC (-40…185 oF) Relative Humidity 5…95% noncondensing Shock Operating Tested 15 g peak acceleration, 11 (±1) ms pulse width Nonoperating Tested 15 g peak acceleration, 11 (±1) ms pulse width Vibration Tested 2 g @ 10…500Hz per IEC 68-2-6 Agency Certification CENELEC II (1) 2G ib[ia] IIC T4 UL, C-UL Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib [ia] IIC T4 FM Class I Division 1 Groups A-D T4 Class I Zone 1 AEx ib IIC T4 INMETRO IECEx BR-Ex ia/ib IIB/IIC T4 Ex ib IIC T4 and Ex ib[ia] IIC T4 Certificates CENELEC DMT 99 ATEX E011 X UL, C-UL UL File Number E197983 Class I Division 1 Hazardous FM FM Certificate Number 3009806 FM INMETRO 05/UL-BRAE-0011X IECEx IECEx BVS 09.0021X Publication 1797-IN015G-EN-P - August 2017 87 (3.4) 50 (2.0) . Comm Status Q UALITY A-B Module Status Allen-Bradley 94 (3.7) 2 3 4 +V -V +V -V 1 PWR REPEATER ADAPTER ControlNet Ex 1797 - RPA . . Q UALI TY A-B Recv Xmit Allen-Bradley Chan 1 Chan 2 94 (3.7) Recv Xmit FIBER MODULE MEDIUM RANGE ControlNet Ex 1797 - RPFM . QUALI TY A- B Recv Xmit Allen-Bradley Chan 1 Chan 2 94 (3.7) Recv Xmit 80 (3.2) 41426 mm (in.) FIBER MODULE MEDIUM RANGE ControlNet Ex 1797 - RPFM ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 31 Mounting Dimensions Publication 1797-IN015G-EN-P - August 2017 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com. Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running. United States 1.440.646.3434 Monday – Friday, 8am – 5pm EST Outside United States Please contact your local Rockwell Automation representative for any technical support issues. New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned. United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process. Outside United States Please contact your local Rockwell Automation representative for return procedure. Allen-Bradley, Rockwell Automation, ControlLogix, RSLinx, TechConnect, and FLEX I/O are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Publication 1797-IN015G-EN-P - August 2017 Supersedes Publication 1797-5.15 - June 2010 PN-455768 Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Fiber optic communication
- DIN rail mount
- Intrinsically safe
- Hazardous location rated
- Extends network range
- Supports multiple nodes
Frequently asked questions
This module extends the range of ControlNet Ex networks in hazardous locations by using fiber optic cables to connect to other repeaters.
A maximum of two 1797-RPFM modules may be used with one 1797-RPA adapter.
The maximum (functional) length between 2 1797-TPx is 1000 m (3280 ft) - each 1797-TPx reduces the (functional) coax cable length by 16.3 m (53.4 ft).