Allen-Bradley Basic Power Supply 10 A Reference Manual
Allen-Bradley 1606-XLB120E is a compact and versatile power supply designed for industrial applications. It boasts a wide input voltage range of 90-264V AC, making it suitable for use in various electrical systems. With an efficiency of up to 95.2%, it minimizes energy loss and optimizes performance. The power supply offers comprehensive protection features, including overload, short circuit, and over-temperature protection, ensuring reliable operation in demanding environments. Additionally, it features a DC-OK relay contact for preventive function monitoring, helping to avoid downtime.
PDF
Download
Document
Advertisement
Advertisement
Reference Manual Original Instructions Basic Power Supply 10 A Catalog Number 1606-XLB240E Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). Basic Power Supply 10 A Table of Contents Additional Resources Topic Page Topic Page Additional Resources 3 Hold-Up Time 11 Terminology and Abbreviations 4 DC OK Relay Contact 11 Product Overview 5 Efficiency and Power Loss 12 Front Side and User Elements 6 Lifetime Expectancy and Mean Time Between Failure (MTBF) 13 Protection Features 6 Functional Diagram 13 Safety Features 7 EMC 14 Installation Notes 7 Application Notes 15 Terminals and Wiring 7 Specifications 15 Installation Notes 7 Environment 19 Input 8 Dielectric Strength 20 DC-Input 9 Standards Compliance and Certifications 22 Input Inrush Current 9 Approximate Dimensions and Weight 23 Output 10 These documents contain additional information concerning related products from Rockwell Automation. Resource Description Switched Mode Power Supply Technical Data, publication 1606-TD002 Provides specifications and approximate dimensions for full line of switched mode power supplies. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, http:// www.rockwellautomation.com/global/certification/ overview.page Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 3 Basic Power Supply 10 A Terminology and Abbreviations 4 Term Definition 230V AC A figure with the unit (V AC) at the end is a momentary figure without any additional tolerances included. 50 Hz vs. 60 Hz As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz mains frequency. AC 120V parameters are valid for 60 Hz mains frequency. AC 230V A figure that is displayed with the AC or DC before the value represents a nominal voltage with standard tolerances included. for example: DC 12V describes a 12V battery, whether it is full (13.7V) or flat (10V) Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”. PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol. PELV Protection by extra-low voltage SELV Safety by extra-low voltage Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 Basic Power Supply 10 A Product Overview 1606-XLB Basic Power Supplies are compact, industrial grade power supplies that focus on the essential features needed in industrial applications. The mechanically robust housing is made of a high-grade, reinforced molded material, which permits the units to be used in ambient temperatures up to 70 °C (158 °F). This power supply features a wide input voltage range, which makes it suitable for global use. The addition of a DC-OK signal makes the power supply ideal for many industry applications such as: process, automation, and many other critical applications where preventive function monitoring can help to avoid long downtimes. The 1606-XLB240E power supply offers these features: • Wide input range, AC 100…240V • Active PFC • Cost optimized without compromising quality or reliability. • Small width of only 49 mm (1.93 in.) • Efficiency up to 95.2% • Full power between -25…+55 °C (-13…+131 °F) • DC-OK relay contact • 1-year warranty Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 5 Basic Power Supply 10 A Front Side and User Elements Figure 1 - Front Side of DC-UPS Letter Description A Input terminals - (screw terminals) N, L - Line input PE - Protective earth input B Output terminals - (screw terminals, two pins per pole) + Positive output – Negative (return) output C Output voltage potentiometer Guaranteed adjustment range: 24…28V Factory set: 24.1V D DC-OK status indicator (green) On, when the output voltage is >18V E DC-OK Relay Contact (push-in terminals) Protection Features Attribute 1606-XLB240E Output protection Electronically protected against overload, no-load, and short circuits (1) Output overvoltage protection typ 30.5V DC max 32 V DC In case of an internal power supply anomaly, a redundant circuit limits the maximum output voltage. In such a case, the output shuts down and stays down until the input voltage is turned off and on again for at least 1 minute or until the green status indicator went off. Degree of protection IP 20 EN/IEC 60529 Caution: For use in a controlled environment according to CSA 22.2 No 107.1-01. Over-temperature protection yes Output shut-down with automatic restart Input transient protection MOV (Metal Oxide Varistor) Internal input fuse Included (1) If there is a protection event, audible noise can occur. 6 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 not user replaceable Basic Power Supply 10 A Safety Features Installation Notes Terminals and Wiring Attribute 1606-XLB240E Input/output separation SELV IEC/EN 60950-1 PELV double or reinforced insulation IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 Class of protection I PE (Protective Earth) connection required Isolation resistance > 5 MOhm input to output, 500V DC Touch current (leakage current) typ 0.30 mA/0.79 mA 100V AC, 50 Hz, TN-,TT-mains/IT-mains typ 0.42 mA/1.1 mA 120V AC, 60 Hz, TN-,TT-mains/IT-mains typ 0.67 mA/1.7 mA 230V AC, 50 Hz, TN-,TT-mains/IT-mains < 0.37 mA/0.94 mA 110V AC, 50 Hz, TN-,TT-mains/IT-mains < 0.54 mA/1.33 mA 132V AC, 60 Hz, TN-,TT-mains/IT-mains < 0.88 mA/2.18 mA 264V AC, 50 Hz, TN-,TT-mains/IT-mains • Use appropriate copper cables that are designed for minimum operating temperatures of: – 75 °C (167 °F) for ambient up to 55 °C (131 °F) minimum. – 90 °C (194 °F) for ambient up to 70 °C (158 °F) minimum. • Follow national installation codes and installation regulations. • Verify that all strands of a stranded wire enter the terminal connection. • Do not use the power supply without a PE connection. • Securely tighten unused terminal compartments. • Ferrules are allowed. The terminals are IP20 fingersafe constructed and suitable for field- and factory wiring. Attribute Input and Output DC-OK Signal Terminal type Screw terminals Push-in terminals Solid wire, max 6 mm2 1.5 mm2 Stranded wire, max 4 mm2 1.5 mm2 American Wire Gauge AWG 20-10 AWG 28-16 Wire diameter, max 2.8 mm (including ferrules) 1.6 mm (including ferrules) Wire stripping length 7 mm (0.28 in.) 7mm (0.28 in.) Screwdriver 3.5 mm slotted or cross-head No 2 Not required Recommended tightening torque 1 N•m, 9 lb•in Not applicable Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 7 Basic Power Supply 10 A Input Attribute 1606-XLB240E AC input nom 100…240V AC Auto-select, suitable for TN-, TT- and IT mains networks AC input range min 90…264V AC continuous operation min 264…300V AC < 500 ms max 300V AC continuous, IEC 62103 Allowed voltage L or N to earth Input frequency nom 50…60 Hz ±6% Turn-on voltage typ 81V AC at 24V 10 A, steady-state value, see Figure 2 Shut-down voltage typ 63V AC/71V AC at no load/nominal load, steady-state value, see Figure 2 External input protection See recommendations in External Input Protection on page 16. Attribute AC 100V AC 120V AC 230V Input current typ 2.60 A 2.17 A 1.18 A at 24V, 10 A, see Figure 3 Power factor(1) typ 0.99 0.98 0.93 at 24V, 10 A, see Figure 5 Crest factor(2) typ 1.6 1.7 2.0 at 24V, 10 A Start-up delay typ 400 ms 260 ms 200 ms see Figure 4 Rise time typ 60 ms at 24V, 10 A const. current load, 0 mF load capacitance, see Figure 4 typ 230 ms at 24V, 10 A const. current load, 5 mF load capacitance, see Figure 4 max 200 mV see Figure 4 Turn-on overshoot (1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit. (2) The crest factor is the mathematical ratio of the peak value to the T ms value of the input current waveform. Figure 4 - Turn-on Behavior, Definitions Rated input range max. 500ms Turn-on Shut-down POUT Input Voltage Start-up delay VIN 90V Figure 5 - Power Factor vs. Output Load Power Factor, typ. Input Current, typ. 1.00 a) 100Vac b) 120Vac c) 230Vac 2.5 2.0 a b c 1.0 c 0.85 a) 100Vac b) 120Vac c) 230Vac 0.80 0.5 0.75 0 1 2 3 4 5 6 7 8 9 10A Output Current 8 a b 0.95 0.90 1.5 0 Rise Time 264V 300Vac Figure 3 - Input Current vs. Output Load at 24V 3A - 5% Output Voltage Overshoot Figure 2 - Input Voltage Range, typ Output Current 0.70 1 2 3 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 4 5 6 7 8 9 10A Basic Power Supply 10 A DC-Input Do not operate the power supply with DC-input voltage. Input Inrush Current A NTC inrush limiter limits the input inrush current after turn-on of the input voltage. Attribute Inrush current(1) Inrush energy AC 100V AC 120V AC 230V Notes max 14.5 A peak 17 A peak 32 A peak 40 °C (104 °F) ambient, cold start typ 7 A peak 8.5 A peak 16 A peak 40 °C (104 °F) ambient, cold start typ 11.5 A peak 14 A peak 26 A peak 25 °C (77 °F) ambient, cold start max 0.2 A2s 0.3 A2s 1 A2s 40 °C (158 °F) ambient, cold start (1) The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Figure 6 - Input Inrush Current, Typical Behavior, 230V AC Input, 24V 10 A Output, 25°C (77 °F) Ambient Ipeak = 16A Ipeak = 16A Input current 5A/DIV Input current 5A/DIV Input voltage 500V/DIV Input voltage 500V/DIV Output voltage 20V/DIV Output voltage 20V/DIV 20ms/DIV 20ms/DIV Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 9 Basic Power Supply 10 A Output Attribute 1606-XLB240E Output voltage nom Adjustment range Notes DC 24V 24…28V guaranteed 30V(1) at clockwise end position of potentiometer typ 24.1V ±0.2%, at full load, cold unit Line regulation max 5 mV 90…264V AC Load regulation max 100 mV static value, 0A .. 10A, see Figure 7 Ripple and noise voltage max 100 mVpp 20 hz to 20 MHz, 50 Ohm Output current nom 10 A at 24V, below +55 °C (131 ° F) ambient temperature 6.25 A at 28V, below +55 °C (131 ° F) ambient temperature 8.6 A at 24V, at +70 °C (158 ° F) ambient temperature Factory settings Output power nom Overload behavior Short circuit current min Output capacitance 5.4 A at 28V, at +70 °C (158 ° F) ambient temperature 240 W ambient temperature < 55 ° C (131 ° F) 150 W ambient temperature < 70 °C (158 ° F) continuous current output voltage > 13V DC, see Figure 7 Hiccup PLUS mode output voltage < 13V DC, see Figure 7 11 A(2) load impedance 50mOhm, see Figure 7 max 15 A load impedance 50mOhm, see Figure 7 typ 4.8 A(3) average (R.M.S.) current, load impedance 50 mOhm, see Figure 7 typ 2 850 μF included inside the power supply (1) This is the maximum output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value that can be achieved. The typical value is about 28.5V. (2) Discharge current of output capacitors is not included. (3) Discharge current of output capacitors is not included. Figure 7 - Output Voltage vs. Output Current, typ Output Voltage Figure 8 - Short circuit (50 mOhm) on output, Hiccup Adjustment Range 28V Continuous current 24 Output Current Normal operation 20 13.5A 16 First pulse: 3s 12 HiccupPLUS mode 8 4 0 2.5 5 7.5 10 t 0 3s Output Current 0 10 Normal operation Short -circuit 7s 1s 12.5 15A Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 7s 1s 7s Basic Power Supply 10 A Hold-Up Time Type 24V, 5 A 24V, 10 A AC 100V AC 120V AC 230V Notes typ 65 ms 65 ms 65 ms See Figure 9 min 53 ms 53 ms 53 ms typ 32 ms 32 ms 32 ms min 26 ms 26 ms 26 ms Figure 9 - Hold-up Time vs. Input Voltage Figure 10 - Shut-down Behavior, Definitions Hold-up Time a) 24V 5A typ. c) 24V 10A typ. b) 24V 5A min. d) 24V 10A min. 80ms 70 60 50 40 30 20 10 0 Zero Transition Input Voltage a b c d - 5% Output Voltage Input Voltage 90 120 DC OK Relay Contact Hold-up Time 230Vac This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit that is connected in parallel to the power supply output such as a redundant application. Attribute 1606-XLB240E Contact closes As soon as the output voltage reaches 21.8V Contact opens As soon as the output voltage dips below 21.7V Contact ratings max 60V DC, 0.3 A; 30V DC, 1 A; 30V AC, 0.5 A resistive load min 1 mA at 5V DC min required load Isolation voltage See Dielectric Strength on page 21 Figure 11 - DC-OK Relay Contact Behavior Output Voltage 21.8V open closed Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 11 Basic Power Supply 10 A Efficiency and Power Loss Attribute AC 100V AC 120V AC 230V Notes Efficiency typ 93.2% 94.0 % 95.2 % at 24V, 10 A Average efficiency(1) typ 92.7% 93.1 % 93.9 % 25% at 2.5 A 25% at 5 A 25% at 7.5 A 25% at 10 A Power losses typ 4.0 W 4.0 W 3.4 W at 24V, 0A typ 9.0 W 8.5 W 7.5 W at 24V, 5 A typ 17.5 W 15.3 W 12.1 W at 24V, 10 A (1) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time. Figure 12 - Efficiency vs. Output Current, typ Figure 14 - Power Losses vs. Output Current at 24V, typ Power Losses Efficiency 96% 95 (c) 94 (b) (a) 93 (a) 100Vac (b) 120Vac (c) 230Vac 92 91 Output Current 90 2 4 5 6 7 3 8 9 (a) 100Vac (b) 120Vac (c) 230Vac (a) (b) (c) Output Current 0 10A Figure 13 - Efficiency vs. Input Voltage at 24V, 10 A, typ 2 4 6 7 8 9 10A Figure 15 - Power Losses vs. Input Voltage at 24V, 10 A Efficiency Power Losses 96% 20W 95 18 94 16 93 14 92 12 10 91 Input Voltage 90 100 120 12 24W 21 18 15 12 9 6 3 0 180 230 264Vac Input Voltage 8 100 120 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 180 230 264Vac Basic Power Supply 10 A Lifetime Expectancy and Mean Time Between Failure (MTBF) Attribute Lifetime expectancy MTBF (2) (1) SN 29500, IEC 61709 AC 100V AC 120V AC 230V Notes 89 000 h 93 000 h 103 000 h at 24V, 5 A and 40 °C (158 °F) 252 000 h 262 000 h 291 000 h at 24V, 5 A and 25 °C (77 °F) 47 000 h 55 000 h 74 000 h at 24V, 10 A and 40 °C (158 °F) 133 000 h 156 000 h 209 000 h at 24V, 10 A and 25 °C (77 °F) pending at 24V, 10 A and 40 °C (104 °F) at 24V, 10 A and 25 °C (77 °F) MIL HDBK 217 F at 24V, 10 A and 40 °C (104 °F) ; Ground Benign GB40 at 24V, 10 A and 25 °C (77 °F) ; Ground Benign GB25 at 24V, 10 A and 40 °C (104 °F) ; Ground Fixed GF40 at 24V, 10 A and 25 °C (77 °F) ; Ground Fixed GF25 (1) The Lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400 h). Any number exceeding this value is a calculated theoretical lifetime that can be used to compare devices. (2) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of for example, 1 000 000 h means that statistically one unit fails every 100 hours if 10 000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50 000 h or only for 100 h. Functional Diagram Figure 16 - Functional Diagram L N Input Fuse Input Filter Input Rectifier Inrush Current Limiter PFC Converter Power Converter Output Filter + + - DC-ok Relay DC-ok Contact DC-ok LED Temperature Shutdown Output OverVoltage Protection Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 Output Voltage Regulator VOUT 13 Basic Power Supply 10 A EMC EMC Immunity According to Generic Standards EN 61000-6-1 and EN 61000-6-2 Criterion(1) Electrostatic discharge EN 61000-4-2 contact discharge air discharge 8kV 8kV Criterion A Criterion A Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A Fast transients (Burst) EN 61000-4-4 input lines output lines DC-OK signal (coupling clamp) 4 kV 2 kV 2 kV Criterion A Criterion A Criterion A Surge voltage on input EN 61000-4-5 L ->N L ->PE, N ->PE 2 kV 4 kV Criterion A Criterion A Surge voltage on output EN 61000-4-5 + ->+/- ->PE 500V 1 kV Criterion A Criterion A Surge voltage on DC-OK EN 61000-4-5 DC-OK signal… PE 1 kV Criterion A Conducted disturbance EN 61000-4-6 0.15…80 MHz 10V Criterion A Mains voltage dips EN 61000-4-11 0% of 120V AC 40% of 120V AC 40% of 120V AC 70% of 120V AC 0% of 200V AC 40% of 200V AC 70% of 200V AC 0V AC, 20 ms 48V AC, 200 ms 48V AC, 500 ms 84V AC, 20 ms 0V AC, 20 ms 80V AC, 200 ms 140V AC, 500 ms Criterion A Criterion C >7 A Criterion A <7 A Criterion A Criterion A Criterion C Criterion A Voltage interruptions EN 61000-4-11 0% of 220V AC (=0V) 5000 ms Criterion C Voltage sags SEMI F47 0706 dips on the input voltage according to SEMI F47 standard Powerful transients VDE 0160 80% of 120V AC (96V AC) 70% of 120V AC (84V AC) 50% of 120V AC (60V AC) 50% of 120V AC (60V AC) 1000ms 500ms 200ms 200ms Criterion A Criterion A Criterion C >8 A Criterion A <8 A over entire load range 750V, 0.3ms Criterion A (1) Criterion A: Power supply shows normal operation behavior withing the defined limits. Criterion C: Temporary loss of function is possible. Power supply can shut down and restart by itself. No damage or hazard for the power supply occurs. EMC Emission According to Generic Standards: EN 61000-6-3, EN 610000-6-4 Conducted emission input lines EN 55011, EN 55022 FCC Part 15 CISPR 11, CISPR 22 Conducted emission output lines(1) IEC/CISPR 16-1-2 , IEC/CISPR 16-2-1 limits for DC power port according EN 61000-6-3 not fulfilled Radiated emission EN 55011, EN 55022 Class B Harmonic input current EN 61000-3-2 Fulfilled for class A equipment Voltage fluctuations, flicker EN 61000-3-3 Fulfilled(2) Class B This device complies with FCC Part 15 rules.Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. (1) For information only, not mandatory for EN 61000-6-3. (2) Tested with constant current loads, non-pulsing. 14 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 Basic Power Supply 10 A Peak Current Capability Application Notes The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short-term currents. This helps to start current demanding loads. Solenoids, contactors, and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current. The same situation applies when starting a capacitive load. The peak current capability also delivers the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. If there is a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner. This avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The following two examples show typical voltage dips: Figure 17 - Peak Load with 2x the Nominal Current for 50 ms, typ Figure 18 - Peak Load with 5x the Nominal Current for 5 ms, typ 24V 24V Output Voltage Output Voltage 14.9V 50A 20A 3.7V Output Current 0A Output Current 0A 10ms/DIV 1ms/DIV 20A Peak load (resistive) for 50ms Output voltage dips from 24V to 14.9V. 50A Peak load (resistive) for 5ms Output voltage dips from 24V to 3.7V. Peak Current Capability Voltage Dip Peak Load Peak current voltage dips typ 24…14.9V at 20 A for 50 ms, resistive load typ 24…7.1V at 50 A for 2 ms, resistive load typ 24…3.7V at 50 A for 5 ms, resistive load Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 15 Basic Power Supply 10 A Back Feeding Loads Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force). This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off. The maximum allowed feed-back-voltage is 35V DC. The absorbing energy can be calculated according to the built-in large sized output capacitor that is specified in Output on page 10. External Input Protection The unit is tested and approved for branch circuits up to 30 A (UL) and 32 A (IEC). An external protection is only required if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local regulations can apply. If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 10A B-characteristic or 6A C-characteristic breaker should be used. Parallel Use to Increase Output Power Do not use the power supply in parallel to increase the output power. Parallel Use for Redundancy Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is automatically able to support the load current without any interruption. Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a case, the defect unit becomes a load for the other power supplies and the output voltage can not be maintained any more. This can only be avoided by utilizing decoupling diodes that are included in the redundancy module. 16 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 Basic Power Supply 10 A Recommendations for building redundant power systems: – Use the DC-OK signal contact to monitor the individual power supply units. – Use separate input fuses for each power supply. – Use separate mains systems for each power supply whenever it is possible. – It is desirable to set the output voltages of all units to the same value (± 100 mV) or leave it at the factory setting. Series Operation Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150V DC. Voltages with a potential above 60V DC are not SELV any more and can be dangerous. Such voltages must be installed with a protection against touching. Earthing of the output is required when the sum of the output voltage is above 60V DC. Avoid return voltage (for example, from a decelerating motor or battery) which is applied to the output terminals. Keep an installation clearance of 15 mm (0.59 in.) (left/right) between two power supplies and avoid installing the power supplies on top of each other. Pay attention that leakage current, EMI, inrush current, harmonics increase when using multiple power supplies. Figure 19 - Series Operation Unit A AC DC + + Unit B AC DC Load + - Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 Earth (see notes) 17 Basic Power Supply 10 A Inductive and Capacitive Loads The unit is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance larger than 2.0 F are connected to the output, the unit might charge the capacitor in the HiccupPLUS mode, see Output on page 10. Charging of Batteries Do not use the power supply to charge batteries. Operation on Two Phases The power supply can also be used on two-phases of a three-phase-system. Such a phase-to-phase connection is allowed as long as the supplying voltage is below 240V+10%. Figure 20 - Operation on Two Phases Power Supply 240V +10% max. L1 L3 AC L Fuse L2 internal fuse N PE DC Use in a Tightly Sealed Enclosure When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure is higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure. The power supply is placed in the middle of the box; no other heat producing items are inside the box. • Enclosure – Rittal Type IP66 Box PK 9516 100 – Plastic – 110 x 180 x 165 mm (4.33 x 7.09 x 6.50 in.) • Input – 230V AC 18 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 Basic Power Supply 10 A Attribute Load(1) Case A Case B 24V, 10 A 24V, 8 A (=80%) (2) 48.6 °C (199.4 °F) 43.7 °C (110.1 °F) Temperature outside the box 24.9 °C (76.8 °F) 24.9 °C (76.8 °F) Temperature rise 23.7 K 18.8 K Temperature inside the box (1) Load is placed outside the box. (2) In the middle of the right side of the power supply with a distance of 1 cm (0.39 in.) Specifications Attribute 1606-XLB240E Output Voltage 24V DC Adjustment range 24…28V DC Output Current 10 A at 24V, amb <55°C (131°F) 6.25 A at 24V, amb <70°C (158 °F) 8.6 A at 28V, amb <55°C (131°F) 5.4 A at 28V, amb <70°C (158 °F) 240 W ambient <55°C (131°F) 150 W ambient <70°C (158 °F) Output ripple < 100 mVpp 20 Hz…20 MHz AC Input voltage 100…240V AC ±10% Mains frequency 50…60Hz ±6% AC Input current 2.17 A/1.18 A at 120/230V AC Power factor 0.98/0.93 at 120/230V AC AC Inrush current 14A/26A peak at 120/230V AC, 40°C (104 °F) Efficiency 94.0%/95.2% at 120/230V AC Losses 15.3W/12.1W at 120/230V AC Temperature range -25 …+70 °C (-13…+158 °F) operational Derating 6W/°C 55…70 °C (131…158 °F) Hold-up time typ 32 ms/ 32 ms at 120/230V AC Dimensions 49 x 124 x 124 mm ( WxHxD Weight 540 g/1.2 lb Output power Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 Notes 19 Basic Power Supply 10 A Environment Attribute 1606-XLB240E Notes Operational temperature(1) -25… +70 °C (14...158 °F) reduce output power, see Figure 21. Storage temperature -40… +85°C (-40…185 °F) for storage and transportation Output derating 6W/°C 50°…70 °C (131…158 °F) 5...95% r.h. IEC 60068-2-30 Vibration sinusoidal 2…17.8 Hz: ±1.6 mm (0.06 in.); 17.8…500Hz: 2 g 2 hours/axis IEC 60068-2-6 Shock(4) 30 g 6ms, 20 g 111ms 3 bumps/direction, 18 bumps in total IEC 60068-2-27 Altitude 0…2000 m (0…6 560 ft) without any restrictions 2000…6000 m (6 560… 20,000 ft) reduce output power or ambient temperature, see Figure 22. IEC 62103, EN 50178, overvoltage category II Altitude derating 15 W/1000 m or 5 °C/1000 m > 2000 m (6500 ft), see Figure 22. Overvoltage category III IEC 62103, EN 50178, altitudes up to 2000 m II altitudes from 2000 m to 6000 m Degree of pollution 2 IEC 62103, EN 50178, not conductive LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for use in paint shops. Humidity(2) (3) (1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2 cm (0.79 in.) below the unit. (2) Do not energize while condensation is present. (3) Tested on a DIN Rail with a thickness of 1.3 mm (0.05 in.) (4) Tested on a DIN Rail with a thickness of 1.3 mm (0.05 in.) Figure 21 - Output Current vs. Ambient Temperature Allowed Output Current at 24V Allowable Output Current at 24V 10A 12A 7.5A 10A 6.3A 8A 5.0A C B A 6A 4A 2.5A Ambient Temperature 0 -25 20 Figure 22 - Output Current vs. Altitude -10 0 +20 +40 +55 +70°C A... Tamb < 55°C B... Tamb < 45°C C... Tamb < 35°C 2A Altitude 0 0 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 2000 4000 6000m Basic Power Supply 10 A Dielectric Strength The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests can be conducted in the field using the appropriate test equipment, which applies the voltage with a slow ramp (2 s up and 2 s down). Connect all input-terminals together and all output poles before conducting the test. When testing, set the cutoff current settings to the value in the following table. Type test 60 s A B C D 2500V AC 3000V AC 1000V AC 500V AC Factory test 5s 2500V AC 2500V AC 500V AC 500V AC Field test 5s 2000V AC 2000V AC 500V AC 500V AC Cutoff current setting > 15 mA > 15 mA > 20 mA > 1 mA Figure 23 - Dielectric Strength Input DC-ok B *) L N B A D Output Earth, PE C + - To meet the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur. Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 21 Basic Power Supply 10 A Standards Compliance and Certifications EC Declaration of Conformity The CE Marking indicates conformance with the low voltage and EMC Directive. EN 60950-1, EN 61000-6 UL 508 Listed for use as Industrial Control Equipment ;U.S.A. (UL 508) and Canada (C22.2 No. 14-15); File: E56639 UL 60950-1 Recognized for use as Information Technology Equipment, U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950); File: E 168663. RCM Declaration of Conformity C-tick is for products intended for sale and use within the Australian market. EAC EAC is for products intended for sale and use within the Russian market. 22 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 Basic Power Supply 10 A Approximate Dimensions and Weight Attribute Value Width 49 mm (1.93 in.) Height 124 mm (4.88 in.) (1) 124 mm (4.88 in.) Depth Weight 540 g (1.21 lb) DIN rail Use 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15 mm (0.30 or 0.59 in.). Plastic Material of Housing Flame retardant Polycarbonate (PC) - UL94-V0 Vicat softening temperature specified with 149 °C (300 °F ) according to ASTM D1525 Installation Clearances Keep the following installation clearances: 40 mm (1.57 in.) on top, 20 mm (0.79 in.) on the bottom, 5 mm (0.20 in.) on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15 mm (0.59 in.) in case the adjacent device is a heat source (for example, another power supply). (1) The DIN rail height must be added to the unit depth to calculate the total required installation depth. Dimensions are in mm (in.). Figure 24 - Front View 49 (1.93) 125 (4.92) 124 (4.88) Figure 25 - Side View 116.65 (4.59) Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 23 Basic Power Supply 10 A Notes: 24 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 . Rockwell Automation Support Use the following resources to access support information. Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates. https://rockwellautomation.custhelp.com/ Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page Direct Dial Codes Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page Literature Library Installation Instructions, Manuals, Brochures, and Technical Data. http://www.rockwellautomation.com/global/literature-library/overview.page Product Compatibility and Download Center (PCDC) Get help determining how products interact, check features and capabilities, and find associated firmware. http://www.rockwellautomation.com/global/support/pcdc.page Technical Support Center Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf. Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 1606-RM056A-EN-P - December 2016 Copyright © 2016 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">
Advertisement
Key features
- Wide input voltage range
- Active PFC
- High efficiency
- DC-OK relay contact
- Compact size
- Global use
- Industrial grade
Frequently asked questions
The input voltage range is AC 100…240V, making it suitable for global use.
The output current is 10 A at 24V, below +55 °C (131 ° F) ambient temperature.
Yes, it has several protection features including overload, short circuit protection, output overvoltage protection, and over-temperature protection.
The hold-up time is typically 32ms at 120V AC and 230V AC.