Allen-Bradley 1492 1771-N Series I/O to 1756 ControlLogix I/O Installation Instructions
PDF
Download
Document
Advertisement
Advertisement
1771-N Series I/O to 1756 ControlLogix I/O (Cat 1492-CONACAB020N* and 1492-CONACAB050N*) I. Description of the Existing 1771-N Series I/O Wiring System The 1771-N Series High Resolution Isolated Analog I/O modules were designed to be used with 1771 Remote Termination Panels (RTPs) and connected by a 6ft or 15ft cable, as follows. Catalog Number: 1771-NC6 (6 ft) or 1771-NC15 (15 ft) cables. Variations of remote termination panels are used, depending on the type of module used. These are: Catalog Number 1771-RTP1 Description has cold junction compensation for thermocouples 1771-RTP3 incorporates resistors and fuses; used primarily for 4 - 20mA inputs when using ±5V inputs (Uses 5mm x 20mm fast acting 1/4A fuses such as Bussmann GMA-1/4, 250V / 250mA) 1771-RTP4 a general use block with straight-thru wiring that can be used for all applications except thermocouples 1771-RT41 a 4-channel block with cold junction compensation for thermocouples 1771-RT44 a general use 4-channel block with straight-thru wiring that can be used for all applications except thermocouples RTP4 and RT44 can be used with thermocouples if a method of odd junction compensation is provided at the interface of thermocouple and copper wires within the system The remote termination panels are designed for mounting on standard DIN 1 or DIN 3 mounting rails. Module Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Channel 8 1771-NIS 4 - 20mA 4 - 20mA 4 - 20mA 4 - 20mA 4 - 20mA 4 - 20mA 4 - 20mA 4 - 20mA 1771-NIV ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) 1771-NIV1 ±10V ±10V ±10V ±10V ±10V ±10V ±10V ±10V 1771-NIVR ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) RTD RTD RTD RTD 1771-NIVT ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) ±5V (±20mA) ±100mV / TC ±100mV / TC ±100mV / TC ±100mV / TC 1771-NR RTD RTD RTD RTD RTD RTD RTD RTD 1771-NT1 ±100mV / TC ±100mV / TC ±100mV / TC ±100mV / TC ±100mV / TC ±100mV / TC ±100mV / TC ±100mV / TC 1771-NT2 -5 / +55mV / TC -5 / +55mV / TC -5 / +55mV / TC -5 / +55mV / TC -5 / +55mV / TC -5 / +55mV / TC -5 / +55mV / TC -5 / +55mV / TC 1771-NOC 0 - 25mA out 0 - 25mA out 0 - 25mA out 0 - 25mA out 0 - 25mA out 0 - 25mA out 0 - 25mA out 0 - 25mA out 1771-NOV ±10V out ±10V out ±10V out ±10V out ±10V out ±10V out ±10V out ±10V out PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E Printed in U.S.A. (1) II. Description of the Conversion Solution This conversion from the 1771-N Series I/O to a 1756 ControlLogix I/O is accomplished simply by replacing the (2) existIng cables A & B with (1 or 2) of the following new 1492 cables. Each of these cables has a connector on one end that attaches directly to the existing 1771 RTP. On the other end of the new cable is (1) 1756 Removable Terminal Block (RTB) for connection to the new 1756 ControlLogix I/O Module. The I/O signals are routed from the existing 1771 RTP through the 1492 cables to the appropriate terminals on the 1756 I/O module, per the Wiring Diagrams in this Installation Manual. This allows the conversion to be completed without the removal of any field wires from the existing 1771-RTP. Cable Catalog Numbers: 1492-CONACAB020N1 1492-CONACAB020N34 1492-CONACAB020N2 1492-CONACAB020N44 1492-CONACAB020N3 1492-CONACAB020N54 1492-CONACAB020N4 1492-CONACAB020N74 1492-CONACAB020N5 1492-CONACAB020N7 Cable Catalog Numbers: 1492-CONACAB020N5 1492-CONACAB020N6 Cable Catalog Numbers: 1492-CONACAB020N68 PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (2) Cable Catalog Number: 1492-CONACAB020N8 1492-CONACAB020N88 1492-CONACAB020N38 1492-CONACAB020N78 1492-CONACAB020N48 1492-CONACAB020N18 III. Compatibility for I/O Modules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oot Notes: To understand any issues concerning I/O module compatibility refer to the Installation Manuals for the specific I/O modules involved. This conversion solution requires replacement of the exisiting (1) 1771-RTP1 interface module with (2) 1771-RT41 interface modules. Each 1771-RTP1 module has a cold junction compensation thermocouple attached to the interface module. These catalog numbers are for a 2.0M cable length. A 5.0M cable is also available. Change the 3 numerals in the middle of the catalog number from "020" to "050" (Example: 1492-CONACAB020N1 becomes 1492-CONACAB050N1). 4 These cables have a maximum operating voltage of 30VDC , 2A maximum per pin, 12A maximum per cable. Wiring diagram for these are identical. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (3) Conversion: 1771-NOC (1) To 1756-OF8I (1) (Current) Using Existing 1771-RTP3 or RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP3 or 1771-RTP4 2 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 CURRENT LOAD R1 I1 O1 S1 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 V W X Y Z [ \ ] ^ 1492-CONACAB020N88 Cable”B” 15 4 18 d e f g h n l j a k m i j h h k 7 21 o h 29 RTN_7 p 27 OUT_7/I 30 RTN_6 h d e f g h n l d e f g h n _ j ` a k a m b 28 OUT_6/I h c 21 RTN_5 10 24 i j _ 13 a ` d 19 OUT_5/I 22 RTN_4 q a b e c f g 20 OUT_4/I h Cable”A” 15 4 18 7 21 10 24 d e f g h n l j a k m i j h h k o h 11 OUT_3/I 14 RTN_2 h d e f g h n l d e f g h n _ i _ d j ` a a j ` a a k b m 12 OUT_2/I 5 RTN_1 h c 3 OUT_1/I 6 RTN_0 q b e 13 RTN_3 p c f g 4 OUT_0/I h 13 3 1 2 7 8 9 10 15 16 17 18 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 23 24 25 26 31 32 33 34 35 36 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. cable does not connect to these terminals. [Reference Doc: DIR 10002306650] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (4) V. Wiring Diagrams Conversion: 1771-NOC (1) To 1756-OF8 (1) (Current, Non-Isolated) Using Existing 1771-RTP3 or RTP4 Interface Module There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP3 or 1771-RTP4 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 CURRENT LOAD B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 1756-OF8 1492-CONACAB020N8 Cable “B” 15 4 18 w x y z { } t ~ | } { { ~ { 20 I-OUT-7 { 16 I-RTN 7 21 22 w x y z { w x y z { r } t ~ { 14 I-OUT-6 10 24 | } r 13 t s t u v t w s u x 10 I-OUT-5 6 I-RTN v y z { 4 I-OUT-4 Cable “A” 15 4 18 7 21 10 24 w x y z { { } t ~ | } { { ~ { 19 I-OUT-3 15 I-RTN w x y z { w x y z { r } t ~ { 13 I-OUT-2 | r } s t t s t u v u 9 I-OUT-1 5 I-RTN v 13 w x y z 3 I-OUT-0 { Conversion Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. RTN terminals are internally connected on the 1756-OF8. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. The 1771-NOC module provides channel to channel isolation, the 1756-OF8 does not. A conversion from 1771-NOC to an isolated 1756-OF8I is available. [Reference Doc: 41171-079] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (5) Conversion: 1771-NOC (1) To 1756-OF6CI (2) (Current, Isolated) Using Existing 1771-RTP3 or RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP3 or RTP4 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 + R1 I1 O1 S1 CURRENT LOAD - B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 Cable “B” 1492-CONACAB020N1 N/A N/A 1756-OF6CI N/A 15 4 18 7 21 10 24 8 11 10 24 13 OUT-0 1756-OF6CI RTN-3 OUT-3 RTN-2 7 OUT-2 6 RTN-1 1 8 11 RTN-2 OUT-1 RTN-0 12 OUT-3 2 5 RTN-3 7 OUT-2 6 RTN-1 Cable “A” 1492-CONACAB020N1 N/A 7 21 N/A 4 18 N/A 15 12 13 2 5 OUT-1 RTN-0 1 OUT-0 Conversion Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for modules RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 41171-072] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (6) Conversion: 1771-NIS (1) To 1756-IF8I (1) (Current) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 2 24VDC SUPPLY CURRENT LOAD + CURRENT LOAD + 24VDC SUPPLY N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 4 - 1492-CONACAB020N38 CABLE “B” N/A N/A 15 16 ¥ ¦ ­ § ¨ « © ¯ ¬ ° ® © ± © ¢ 18 19 ª « © © ¥ ¬ ¦ § ¨ © ¯ ­ « ¬ ® © ¢ 21 22 ¥ ¦ § ¨ © ¯ ¡ ª ¢ 24 25 ¢ £ ¤ « ¥ ² ¦ ¡ § ¢ ¨ © £ ¤ N/A 18 19 21 22 24 25 29 27 RTN_7 30 28 RTN_6 21 19 RTN_5 22 20 RTN_4 13 11 RTN_3 14 12 RTN_2 5 3 RTN_1 6 4 RTN_0 1 2 7 8 9 10 15 16 17 18 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. IN_7/I/SRC IN_6/I/SRC IN_5/I/SRC IN_4/I/SRC CABLE “A” N/A 15 16 ¥ ¦ ­ § ¨ « © ¯ ¬ ® ° © ± © ¢ ª « © ¥ © ¦ ¬ § ¨ © ¯ ­ « ¬ ® © ¢ ¥ ¦ § ¨ © ¯ ¡ ª ¢ £ ¤ « ¢ ¥ ² ¦ ¡ ¢ § £ ¨ © ¤ 3 Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. IN_3/I/SRC IN_2/I/SRC IN_1/I/SRC IN_0/I/SRC 23 24 25 26 31 32 33 34 35 36 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. for module RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 10002306457] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (7) Conversion: 1771-NIS (1) To 1756-IF6CIS (2) (Current) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 24VDC SUPPLY CURRENT LOAD + CURRENT LOAD + 24VDC SUPPLY - R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 Cable “B” 1492-CONACAB020N2 N/A N/A 1756-IF6CIS N/A 15 16 18 19 21 22 24 25 Ä ½ ³ ¸ 24 25 Â ½ ´ ´ ¹ ¿ ½ Ã ½ » ¹ º º À ´ µ ¶ Æ Á ¹ ´ Ä ½ 12 I-RTN-3 10 I-OUT-3 Å 11 I-RTN-2 9 I-OUT-2 » Á ³ Â ½ Ã ³ ´ µ ¶ · Ä ½ À Á ¸ ¾ ½ ³ ¸ I-RTN-1 I-OUT-1 Â 5 3 I-RTN-0 I-OUT-0 1756-IF6CIS Å ¿ ¼ 6 4 · ½ Cable “A” 1492-CONACAB020N2 N/A 21 22 Á ¸ ¾ N/A 18 19 Å À ¼ N/A 15 16 ½ ¿ Â ½ ´ ´ ¹ ¿ ½ Ã ½ » ¹ º º À ´ µ ¶ Æ Á ¹ ´ ½ 12 I-RTN-3 10 I-OUT-3 Å 11 I-RTN-2 9 I-OUT-2 » Á ³ Ä Â ½ Ã ³ ´ µ ¶ · 6 4 I-RTN-1 I-OUT-1 5 3 I-RTN-0 I-OUT-0 · ½ Â Conversion Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 41171-073] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (8) Conversion: 1771-NIV (1) To 1756-IF8I (1) (Current) Using Existing 1771-RTP3 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP3 4 2 + 24VDC SUPPLY CURRENT LOAD CURRENT LOAD + - 24VDC SUPPLY N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 - 1492-CONACAB020N38 CABLE “B” N/A N/A 15 16 Ô Õ Ü Ö × Ú Ø Þ Û ß Ý Ø Ç à Ø Ñ 18 19 Ù Ú Ø Ø Ô Õ Û Ö × Ø Þ Ü Ú Û Ý Ø Ñ 21 22 Ô Õ Ö × Ø Þ Ï Ù Ñ 24 25 Ð Ñ Ò Ó Ú Ô á Õ Ï Ð Ö Ñ × Ø Ò Ó N/A 18 19 21 22 24 25 É Ê Ë Ì Í 29 27 RTN_7 30 28 RTN_6 21 19 RTN_5 22 20 RTN_4 13 11 RTN_3 14 12 RTN_2 5 3 RTN_1 6 4 RTN_0 1 2 7 8 9 10 15 16 17 18 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. Î Ì IN_7/I/SRC IN_6/I/SRC IN_5/I/SRC IN_4/I/SRC CABLE “A” N/A 15 16 È Ô Õ Ü Ö Ú × Ø Þ Û ß Ý Ø à Ø Ñ Ù Ú Ø Ô Ø Õ Û Ö × Ø Þ Ü Ú Û Ý Ø Ñ Ô Õ Ö × Ø Þ Ï Ù Ñ Ô Ï Ð Ñ Ò Ó Ú á Õ Ð Ñ Ö Ò × Ø Ó 3 Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 IN_3/I/SRC IN_2/I/SRC IN_1/I/SRC IN_0/I/SRC 23 24 25 26 31 32 33 34 35 36 cable does not connect to these terminals. [Reference Doc: 10002306458] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (9) N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. V. Wiring Diagrams Conversion: 1771-NIV (1) To 1756-IF6I (2) (Current) Using Existing 1771-RTP3 Interface Module There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP3 24VDC SUPPLY CURRENT LOAD CURRENT LOAD + + 24VDC SUPPLY - N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 Cable “B” 1492-CONACAB020N3 N/A 1756-IF6I N/A 15 16 ç è ï 18 19 ì ò ë ó 12 RTN-3 10 IN-3/I 8 IN-3/V ë î é ä ê ë ñ ï ê ë ñ â í ã ä î ä ð å 11 RTN-2 9 IN-2/I 7 IN-2/V ë æ ô è ã ñ ð é è í â ë ë è ç é ä ê ç è ï ì é í ä æ í ë ç í é ä é å 5 3 1 RTN-0 IN-0/I IN-0/V ò ë 1756-IF6I ó 12 RTN-3 10 IN-3/I 8 IN-3/V ë ê ë ñ ï ê ë ñ â í ã ä ä î å ð 11 RTN-2 9 IN-2/I 7 IN-2/V ë æ ô è ã RTN-1 IN-1/I IN-1/V î é ä ç ñ ð ë è ì ë î è ç â ê 6 4 2 ë å Cable “A” 1492-CONACAB020N3 N/A 24 25 ë ì N/A 21 22 í ê î ç 24 25 18 19 ä ç 21 22 15 16 é í ê 6 4 2 RTN-1 IN-1/I IN-1/V 5 3 1 RTN-0 IN-0/I IN-0/V ë æ Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 41171-074] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (10) Conversion: 1771-NIV (1) To 1756-IF8I (1) (Voltage) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 4 2 + VOLTAGE LOAD - VOLTAGE LOAD N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 1492-CONACAB020N78 CABLE “B” N/A N/A 15 16 þ 18 19 ÿ 21 22 þ ÿ 24 25 ý þ ÿ N/A 15 16 21 22 24 25 ö ÷ ø ù ú û 29 25 RTN_7 30 26 RTN_6 21 17 RTN_5 22 18 RTN_4 13 9 RTN_3 14 10 RTN_2 5 1 RTN_1 6 2 RTN_0 3 4 7 8 11 12 15 16 19 20 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. ü ú IN_7/V IN_6/V IN_5/V IN_4/V CABLE “A” N/A 18 19 õ þ ÿ þ ÿ ý þ ÿ 3 IN_3/V IN_2/V IN_1/V IN_0/V 23 24 27 28 31 32 33 34 35 36 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 10002306478] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (11) V. Wiring Diagrams Conversion: 1771-NIV (1) To 1756-IF6I (2) (Voltage) Using Existing 1771-RTP4 Interface Module There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 VOLTAGE LOAD + VOLTAGE LOAD + R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 1756-IF6I Cable “B” 1492-CONACAB020N7 N/A N/A N/A 15 16 19 18 ! 11 RTN-2 7 IN-2V $ " $ 24 25 Cable “A” 1492-CONACAB020N7 N/A 21 22 ! 5 1 RTN-0 IN-0V " 1756-IF6I 12 RTN-3 8 IN-3V RTN-1 IN-1V # 6 2 N/A 18 19 N/A 15 16 12 RTN-3 8 IN-3V ! 24 25 " # 22 21 ! 11 RTN-2 7 IN-2V $ " $ 6 2 RTN-1 IN-1V 5 1 RTN-0 IN-0V Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-080] (12) V. Wiring Diagrams Conversion: 1771-NIV (1) To 1756-IF6I (1) (Voltage) And 1756-IF6I (1) (Current) Using Existing 1771-RTP4 Interface Module There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 VOLTAGE LOAD + CURRENT LOAD + R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 1756-IF6I Cable “B” 1492-CONACAB020N7 (Voltage) N/A N/A N/A 15 16 19 18 1 2 / & * ) 3 ) 8 6 ) ) ( ) ( 1 5 2 + & + 24 25 * ) 5 ( , - . 7 6 2 RTN-1 IN-1V 5 1 RTN-0 IN-0V + % ( , - & ' ( . ) * Cable “A” 1492-CONACAB020N3 (Current) N/A N/A 24 25 3 6 N/A 21 22 11 RTN-2 7 IN-2V 7 ' ' 18 19 12 RTN-3 8 IN-3V 0 0 4 22 21 15 16 ) / 1 2 / & * ) 3 ) 12 RTN-3 10 IN-3/I 8 IN-3/V 0 / ) 8 1756-IF6I 0 6 ) ) 11 RTN-2 9 IN-2/I 7 IN-2/V 7 4 ) ( 1 ( ' 5 2 + & + * ) 3 ( , - . 6 ' 5 7 6 4 2 RTN-1 IN-1/I IN-1/V 5 3 1 RTN-0 IN-0/I IN-0/V + % ( , - & ' ( . ) * Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-039] (13) V. Wiring Diagrams Conversion: 1771-NIV (1) To 1756-IF6I (1) (Current) And 1756-IF6I (1) (Voltage) Using Existing 1771-RTP4 Interface Module There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 CURRENT LOAD + Voltage LOAD + N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 Cable “B” 1492-CONACAB020N3 (Current) 1756-IF6I N/A N/A 15 16 > ? F @ A D B H E I G B J 12 RTN-3 10 IN-3/I 8 IN-3/V B ; 18 19 C D B > B E ? @ A B H F D E G 11 RTN-2 9 IN-2/I 7 IN-2/V B ; 21 22 > ? > 9 : 24 25 @ ; A H : ; < = 6 4 2 RTN-1 IN-1/I IN-1/V 5 3 1 RTN-0 IN-0/I IN-0/V B < = Cable “A” 1492-CONACAB020N7 (Voltage) N/A 21 22 B K ? N/A 18 19 A D ; 24 25 15 16 @ 9 C > ? F @ A D B H E G I B J 12 RTN-3 8 IN-3V B ; C D B > B ? E @ A B H F D E G 11 RTN-2 7 IN-2V B ; > ? @ A B H 9 C ; 9 : ; < = D > K ? : ; @ < 1756-IF6I A 6 2 RTN-1 IN-1V 5 1 RTN-0 IN-0V B = Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-038] (14) V. Wiring Diagrams Conversion: 1771-NR (1) To 1756-IRT8I (1) (RTD) Using Existing 1771-RTP4 Interface Module There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 4 2 RTD TRANSMITTER RTD TRANSMITTER R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 N/A L M N O P Q R S T Q 1492-CONACAB020N48 Cable “B” N/A N/A 15 16 Z [ e 4 18 19 ^ d e ` W a c ` ^ ^ a i j ^ f V V 31 IN_7(+)/A 30 IN_6/RTD C 28 IN_6(-)/B ^ Z [ \ ] ^ d b Z [ \ ] ^ d U ` _ ^ 34 IN_7/RTD C 32 IN_7(-)/B _ U 10 24 25 13 ] f b k 7 21 22 \ ^ i j ` W a W X c ^ 27 IN_6(+)/A 26 IN_5/RTD C 24 IN_5(-)/B Y a W g U V W X h \ i V Z ` V [ 23 IN_5(+)/A 22 IN_4/RTD C 20 IN_4(-)/B 19 IN_4(+)/A Y ^ \ ] ] ^ N/A N/A Cable “A” N/A 15 16 4 18 19 7 21 22 10 24 25 13 Z [ e \ ^ ] ^ d ` W a c _ ` ^ ^ a i j ^ V V 15 IN_3(+)/A 14 IN_2/RTD C 12 IN_2(-)/B [ \ ] ^ d b Z [ \ ] ^ d U ` _ i ` j W V W X h \ i V [ ` V W W a X c ^ 11 IN_2(+)/A 10 IN_1/RTD C 8 IN_1(-)/B Y a g U Z f ^ Z U ^ 18 IN_3/RTD C 16 IN_3(-)/B b k e f 7 IN_1(+)/A 6 IN_0/RTD C 4 IN_0(-)/B 3 IN_0(+)/A Y ^ \ ] ] ^ 1 2 5 9 13 17 21 3 N.C. N.C. N.C. N.C. N.C. N.C. N.C. 25 29 33 35 36 N.C. N.C. N.C. N.C. N.C. Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 10002306848] (15) Conversion: 1771-NR (1) To 1756-IR6I (2) (RTD) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 2 RTD TRANSMITTER RTD TRANSMITTER R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 N/A N/A Cable “B” 1492-CONACAB020N4 1756-IR6I N/A 15 16 12 RTN-3 10 IN-3/B 4 18 19 8 IN-3/A 11 RTN-2 9 IN-2/B 7 21 22 7 10 24 25 13 N/A N/A N/A 15 16 4 18 19 7 21 22 10 24 25 13 5 3 1 Cable “A” 1492-CONACAB020N4 q r | s u t u { u } 12 RTN-3 10 IN-3/B w n x z v w u u x u m m u 8 IN-3/A 11 RTN-2 9 IN-2/B q r s t u { y q r s t u { l w n x z u 7 l w v w n m n o s m r m n o p x IN-2/A 6 RTN-1 4 IN-1/B ~ l q 2 IN-1/A RTN-0 IN-0/B IN-0/A 1756-IR6I } y | IN-2/A 6 RTN-1 4 IN-1/B p u s 5 3 1 t t u 2 IN-1/A RTN-0 IN-0/B IN-0/A Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-075] (16) V. Wiring Diagrams Conversion: 1771-NT1 (1) or 1771-NT2 (1) To 1756-IRT8I (1) (Thermocouple) Using Existing 1771-RT41 (2) Interface Module There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RT41 4 2 THERMOCOUPLE + SH W1 R4 I4 S4 O4 R3 I3 S3 O3 R1 I1 O1 S1 1756-IRT8I Cable “B” B1 A1 B2 B3 A2 A3 B4 B5 A4 A5 Thermocouple R2 I2 S2 O2 1 1492-CONACAB020N68 B6 B7 A6 A7 B8 B9 A9 A8 15 16 White/Red 18 19 Green 14 White/Violet 35 CJC1 1 White/Grey 36 CJC1 21 22 White/Black Brown 24 IN_5(-)/B 23 IN_5(+)/A 24 25 Black 32 IN_7(-)/B 31 IN_7(+)/A Red 28 IN_6(-)/B 27 IN_6(+)/A Yellow 20 IN_4(-)/B 19 IN_4(+)/A Violet 3 Interface Module 1771-RT41 4 2 THERMOCOUPLE + SH W1 R4 I4 S4 O4 R3 I3 S3 O3 B1 A1 B2 B3 A2 A3 B4 B5 A4 A5 Thermocouple R2 I2 S2 O2 R1 I1 O1 S1 B6 B7 A6 A7 B8 B9 A9 A8 Cable “A” 15 16 White/Red 18 19 Green 14 White/Violet 1 CJC0 1 White/Grey 2 CJC0 21 22 White/Black Brown 8 IN_1(-)/B 7 IN_1(+)/A 24 25 Black 16 IN_3(-)/B 15 IN_3(+)/A Red 12 IN_2(-)/B 11 IN_2(+)/A Yellow 4 IN_0(-)/B 3 IN_0(+)/A Violet 3 5 6 9 10 13 14 17 N.C. N.C. N.C. N.C. N.C. N.C. N.C. 18 21 22 25 26 29 30 Interface Module Installation and Application Considerations 33 34 Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. cable does not connect to these terminals. This conversion solution requires replacement of the exisiting (1) 1771-RTP1 interface module with (2) 1771-RT41 interface modules. Each 1771-RTP1 and RT41 module has there own cold junction compensation thermocouple attached to the interface module. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 10002306849] (17) Conversion: 1771-NT1 (1) To 1756-IT6I (2) (Thermocouple) Using Existing 1771-RT41 (2) Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RT41 THERMOCOUPLE + SH W1 R4 I4 S4 O4 R3 I3 S3 O3 B1 A1 B2 B3 A2 A3 B4 B5 A4 A5 Cable “B” 1492-CONACAB020N5 15 16 White/Red 18 19 Green 12 RTN-3 11 IN-3 Red 10 RTN-2 9 IN-2 Yellow 14 Thermocouple R2 I2 S2 O2 R1 I1 O1 S1 10 CJC+ 1 B6 B7 A6 A7 B8 B9 A9 A8 1756-IT6I 14 CJC- 21 22 White/Black Brown 24 25 Black Violet 8 7 RTN-1 IN-1 6 5 RTN-0 IN-0 3 Interface Module 1771-RT41 THERMOCOUPLE + SH W1 R4 I4 S4 O4 R3 I3 S3 O3 B1 A1 B2 B3 A2 A3 B4 B5 A4 A5 Cable “A” 1492-CONACAB020N5 15 16 White/Red 18 19 Green Red Yellow 14 Thermocouple R2 I2 S2 O2 R1 I1 O1 S1 1756-IT6I 12 RTN-3 8 IN-3 11 RTN-2 7 IN-2 10 CJC+ 1 B6 B7 A6 A7 B8 B9 A9 A8 14 CJC- 21 22 White/Black Brown 24 25 Black Violet 6 2 RTN-1 5 1 RTN-0 IN-0 IN-1 Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. This conversion solution requires replacement of the exisiting (1) 1771-RTP1 interface module with (2) 1771-RT41 interface modules. Each 1771-RTP1 and RT41 module has there own cold junction compensation thermocouple attached to the interface module. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-076] (18) Conversion: 1771-NOV (1) To 1756-OF8I (1) (Voltage) Using Existing 1771-RTP3 or 1771-RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP3 or 1771-RTP4 2 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 VOLTAGE LOAD + W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 1492-CONACAB020N18 Cable”B” 15 4 18 7 21 10 24 25 OUT_7/V 30 RTN_6 26 OUT_6/V 21 RTN_5 17 OUT_5/V 22 RTN_4 29 RTN_7 13 18 OUT_4/V Cable”A” 15 4 18 7 21 10 24 9 OUT_3/V 14 RTN_2 10 OUT_2/V 5 RTN_1 1 OUT_1/V 6 RTN_0 13 RTN_3 2 OUT_0/V 13 3 1 2 7 8 9 10 15 16 17 18 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. 23 24 25 26 31 32 33 34 35 36 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 10002306686] (19) V. Wiring Diagrams Conversion: 1771-NOV (1) To 1756-OF6VI (2) (Voltage) Using Existing 1771-RTP3 or RTP4 Interface Module There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP3 or RTP4 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 VOLTAGE LOAD + R1 I1 O1 S1 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 Cable “B” 1492-CONACAB020N1 N/A N/A 1756-OF6VI N/A 15 4 18 ¤ ¥ ¦ § ¨ ® ¬ ª ¡ « ­ © ª ¨ ¨ « 7 21 10 24 ¨ 8 11 ¥ ¦ § ¨ ® ¬ ¤ ¥ ¦ § ¨ ® ª ¡ ª ¢ ¥ ¦ § 10 24 ¤ ¥ ¦ § ¨ ® ¬ ª ¡ « ­ © ª ¨ ¨ « ¯ ¨ ¥ ¦ § ¨ ® ¬ ¥ ¦ § ¨ ® © ª ¡ ¡ ª ¡ ¡ « ¢ ­ £ 13 ¤ ¥ ¦ § 1 OUT-0 1756-OF6VI RTN-3 OUT-3 RTN-2 7 OUT-2 6 RTN-1 ¨ £ ± ¢ RTN-2 OUT-1 RTN-0 8 11 ¤ OUT-3 2 5 12 ° ¨ ¤ RTN-3 7 OUT-2 6 RTN-1 ¨ Cable “A” 1492-CONACAB020N1 N/A 7 21 ­ £ ¨ N/A 4 18 « ¢ £ N/A 15 ¡ ¡ ± ¡ ¤ 12 ° ¨ ¤ © 13 ¯ ¨ 2 5 OUT-1 RTN-0 1 OUT-0 Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-081] (20) Conversion: 1771-NIV1 (1) To 1756-IF8I (1) (Voltage) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 4 2 VOLTAGE LOAD + VOLTAGE LOAD + N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 N/A N/A 15 16 É Ê Ç » ¿ ¾ Ë ¾ È Ç ¾ 18 19 Ä È Å ¾ ¾ Æ Ì ¾ 21 22 ½ É ½ ¼ À » 24 25 Í Ê À ¿ ¾ Ë ½ Á Â Ã Å ¼ Í Æ À º ½ Á Â » ¼ ½ Ã ¾ ¿ N/A 18 19 21 22 24 25 ³ ´ µ ¶ · ¸ ¹ · 29 25 RTN_7 30 26 RTN_6 21 17 RTN_5 22 18 RTN_4 13 9 RTN_3 14 10 RTN_2 5 1 RTN_1 6 2 RTN_0 3 4 7 8 11 12 15 16 19 20 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. IN_7/V IN_6/V IN_5/V IN_4/V CABLE “A” N/A 15 16 ² 1492-CONACAB020N78 CABLE “B” É Ê Ç » ¿ ¾ Ë ¾ È Ç ¾ Ä È Å ¾ ¾ Æ Ì ¾ ½ É ½ ¼ Ê À » À Í ¿ ¾ Ë ½ Á Â Ã Å ¼ Í Æ À º ½ Á Â » ¼ ½ Ã ¾ ¿ 3 IN_3/V IN_2/V IN_1/V IN_0/V 23 24 27 28 31 32 33 34 35 36 N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. N.C. Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 10002306486] (21) Conversion: 1771-NIV1 (1) To 1756-IF6I (2) (Voltage) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 VOLTAGE LOAD + VOLTAGE LOAD + R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 1756-IF6I Cable “B” 1492-CONACAB020N7 N/A N/A N/A 15 16 Ý Þ Û 18 19 Ï Ò Ø Ù à 21 22 Ò ß Û Ò Ò Ò Ñ Ð Þ Ô Ú Ñ Ï Ù Ó Ð 11 RTN-2 7 IN-2V á Ò ß á Ô Ñ Õ Ö Î Ï Ð Ñ Ô 24 25 Ö × Ó Cable “A” 1492-CONACAB020N7 N/A 21 22 Õ Ý Þ Û Ï Ò Ø Ó Ò ß Û Ò Ñ Ý 5 1 RTN-0 IN-0V 1756-IF6I 12 RTN-3 8 IN-3V Ò Ò RTN-1 IN-1V Ü Ü Ù à 6 2 × Ò N/A 18 19 Ñ Ú N/A 15 16 Ü 12 RTN-3 8 IN-3V Ò Ý 24 25 Ó Ü Ñ Ò Ú Ð á Þ Ï Ô Ù Ð Ô Ñ Õ Ö Î Ï Ð Ñ Ó 11 RTN-2 7 IN-2V Ò ß á Ô Ñ Õ Ö × Ú 6 2 RTN-1 IN-1V 5 1 RTN-0 IN-0V × Ò Ó Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (22) [Reference Doc: 41171-078] Conversion: 1771-NT2 (1) To 1756-IT6I2 (2) (Thermocouple) Using Existing 1771-RT41 (2) Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RT41 THERMOCOUPLE + SH W1 R4 I4 S4 O4 R3 I3 S3 O3 B1 A1 B2 B3 A2 A3 B4 B5 A4 A5 Cable “B” 1492-CONACAB020N6 15 16 White/Red 18 19 Green 12 RTN-3 11 IN-3 Red 10 RTN-2 9 IN-2 Yellow 14 Thermocouple R2 I2 S2 O2 R1 I1 O1 S1 B6 B7 A6 A7 B8 B9 A9 A8 1756-IT6I2 13 CJC+ 1 21 22 White/Black Brown 24 25 Black Violet 4 CJC- 8 7 RTN-1 6 5 RTN-0 IN-0 IN-1 Interface Module 1771-RT41 THERMOCOUPLE + SH W1 R4 I4 S4 O4 R3 I3 S3 O3 B1 A1 B2 B3 A2 A3 B4 B5 A4 A5 Cable “A” 1492-CONACAB020N6 15 16 White/Red 18 19 Green R2 I2 S2 O2 R1 I1 O1 S1 B6 B7 A6 A7 B8 B9 A9 A8 10 RTN-2 9 IN-2 Yellow 1 21 22 White/Black Brown 24 25 Black 1756-IT6I2 12 RTN-3 11 IN-3 Red 14 Thermocouple Violet 3 CJC+ 4 CJC- 8 7 RTN-1 IN-1 6 5 RTN-0 IN-0 Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. This conversion solution requires replacement of the exisiting (1) 1771-RTP1 interface module with (2) 1771-RT41 interface modules. Each 1771-RTP1 and RT41 module has there own cold junction compensation thermocouple attached to the interface module. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-077] (23) Conversion: 1771-NIVR (1) To 1756-IF8I (1) (Voltage), 1756-IRT8I (1) (RTD) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams WARNING using these components (conversion module, cable and input module). Read and understand these considerations before installation. Interface Module 1771-RTP4 RTD TRANSMITTER VOLTAGE LOAD + N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 1492-CONACAB020N44 1756-IRT8I CABLE “B” N/A N/A 15 16 ñ ò ï 4 18 19 ö î æ æ ó ï å å ÷ î ð ä õ 15 IN_3(+)/A 14 IN_2/RTD C 12 IN_2(-)/B ò ã ç æ ó ö ñ ò ã ç æ ó è í ä ì æ æ æ ñ è 10 24 25 13 æ 18 IN_3/RTD C 16 IN_3(-)/B é í ô ç ð í ì 7 21 22 ã æ õ í é é î ê ÷ é ê â ã ä å ò 21 22 24 25 7 IN_1(+)/A IN_0/RTD C IN_0(-)/B IN_0(+)/A ë æ 6 4 3 ç ã ç æ 1492-CONACAB020N74 1756-IF8I CABLE “A” N/A 18 19 11 IN_2(+)/A 10 IN_1/RTD C 8 IN_1(-)/B ø å N/A 15 16 æ ë î é è ñ í å ñ ò ï ã æ ì í ô ç æ ó ï æ ð 13 RTN_3 9 IN_3/V ð æ æ å ñ å æ î ä õ ò ã è í ä è å é ê â ã ä å ç 14 RTN_2 10 IN_2/V æ ó õ è å é ê ë î 5 1 RTN_1 IN_1/V 6 2 RTN_0 IN_0/V ë æ ç Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E (24) [Reference Doc: 10002306496] Conversion: 1771-NIVR (1) To 1756-IR6I (1) (RTD), 1756-IF6I (1) (Voltage) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams WARNING There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. Interface Module 1771-RTP4 RTD TRANSMITTER VOLTAGE LOAD + N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 Cable “B” 1492-CONACAB020N4 N/A 1756-IR6I N/A 15 16 ú 4 18 19 þ ý ü ü û ú þ ý ú ÿ þ ý ÿ 21 22 24 25 7 ý ü ù ú û ý ú 5 3 1 þ þ ý Cable “A” 1492-CONACAB020N7 ú þ ý 12 RTN-3 8 IN-3V ý ý ý ü ü 11 RTN-2 7 IN-2V û ú ÿ ÿ ü ù ú þ ý ÿ ü û û 1756-IF6I ý ý 2 IN-1/A RTN-0 IN-0/B IN-0/A ü IN-2/A 6 RTN-1 4 IN-1/B ÿ N/A 18 19 ü û N/A 15 16 8 IN-3/A 11 RTN-2 9 IN-2/B ý ý ý 10 24 25 13 ý 12 RTN-3 10 IN-3/B 7 21 22 ý ý ü 6 2 RTN-1 IN-1V 5 1 RTN-0 IN-0V ý þ Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-082] (25) V. Wiring Diagrams Conversion: 1771-NIVR (1) To 1756-IF8I (1) (Current), 1756-IRT8I (1) (RTD) Using Existing 1771-RTP4 Interface Module WARNING using these components (conversion module, cable and input module). Read and understand these considerations before installation. Interface Module 1771-RTP4 RTD TRANSMITTER CURRENT LOAD + N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 1492-CONACAB020N44 1756-IRT8I CABLE “B” N/A N/A 15 16 4 18 19 7 21 22 $ % 15 IN_3(+)/A 14 IN_2/RTD C 12 IN_2(-)/B $ ! 10 24 25 13 18 IN_3/RTD C 16 IN_3(-)/B # ! % 11 IN_2(+)/A 10 IN_1/RTD C 8 IN_1(-)/B " & $ 6 4 3 1492-CONACAB020N34 N/A 18 19 21 22 24 25 1756-IF8I CABLE “A” N/A 15 16 7 IN_1(+)/A IN_0/RTD C IN_0(-)/B IN_0(+)/A ! 13 RTN_3 11 IN_3/I/SRC 14 RTN_2 12 IN_2/I/SRC " 5 3 RTN_1 IN_1/I/SRC 6 4 RTN_0 IN_0/I/SRC Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 10002306490] (26) Conversion: 1771-NIVR (1) To 1756-IR6I (1) (RTD), 1756-IF6I (1) (Current) Using Existing 1771-RTP4 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP4 RTD TRANSMITTER VOLTAGE LOAD + N/A R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 N/A SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 Cable “B” 1492-CONACAB020N4 N/A 1756-IR6I N/A 15 16 , 4 18 19 0 6 7 0 8 12 RTN-3 10 IN-3/B ) 3 2 5 0 0 0 0 ( , - 8 IN-3/A 11 RTN-2 9 IN-2/B 3 ( ; . = / 0 6 4 2 ) 3 5 0 7 , - ' 2 1 . ; 2 / 0 6 = ) ' ( ) * ( ) * : . ; ( - 3 - 4 1 . 2 ) . 2 0 , 5 3 1 / / 0 2 . ) 0 8 12 RTN-3 10 IN-3/I 8 IN-3/V 0 / 0 6 4 / 0 6 ' 2 ( ) ) 3 * 5 11 RTN-2 9 IN-2/I 7 IN-2/V 0 + 9 - ( 7 1756-IF6I 3 ) , 6 5 . - 1 0 0 - , ' / 3 2 IN-1/A RTN-0 IN-0/B IN-0/A + 0 Cable “A” 1492-CONACAB020N3 , IN-2/A 6 RTN-1 4 IN-1/B + 9 ' , N/A 24 25 2 < N/A 21 22 / 8 1 10 24 25 13 18 19 . 0 4 7 21 22 15 16 - 7 . / * 6 4 2 RTN-1 IN-1/I IN-1/V 5 3 1 RTN-0 IN-0/I IN-0/V 0 + Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-083] (27) V. Wiring Diagrams Conversion: 1771-NIVT (1) To 1756-IF8I (1) (Voltage), 1756-IRT8I (1) (Thermocouple) Using Existing 1771-RTP1 Interface Module WARNING using these components (conversion module, cable and input module). Read and understand these considerations before installation. Interface Module 1771-RTP1 4 2 THERMOCOUPLE + SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 Cable “B” 1492-CONACAB020N54 15 16 White/Red 18 19 Green 21 22 White/Black 24 25 Black 16 IN_3(-)/B 15 IN_3(+)/A Red 12 IN_2(-)/B 11 IN_2(+)/A Yellow Brown Violet VOLTAGE LOAD + W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 8 7 IN_1(-)/B 4 3 IN_0(-)/B IN_0(+)/A 10 CJC+ CJC- 14 14 Thermocouple 1756-IRT8I IN_1(+)/A 1 Cable “A” 1492-CONACAB020N74 15 16 18 19 21 22 24 25 M N K ? C B O B 13 RTN_3 9 IN_3/V L K B H 1756-IF8I L I B B J @ Q 14 RTN_2 10 IN_2/V P B A M A N D ? D C B O A E F G I @ Q J 5 1 RTN_1 IN_1/V 6 2 RTN_0 IN_0/V D > A E F ? @ A G B C 3 Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 10002306594] (28) Conversion: 1771-NIVT (1) To 1756-IT6I (1) (Thermocouple), 1756-IF6I (1) (Voltage) Using Existing 1771-RTP1 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP1 4 2 THERMOCOUPLE + Cable “B” 1492-CONACAB020N5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 15 16 White/Red 18 19 Green 21 22 White/Black 24 25 Black 1756-IT6I 12 RTN-3 11 IN-3 Red 10 RTN-2 9 IN-2 Yellow Brown Violet CABLE “B” VOLTAGE LOAD + W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 RTN-1 6 5 RTN-0 IN-0 10 CJC+ CJC- 14 14 Thermocouple 8 7 IN-1 1 Cable “A” 1492-CONACAB020N7 15 16 18 19 21 22 24 25 a b _ S V \ V c _ V ` 12 RTN-3 8 IN-3V ` ] d W V V U a 1756-IF6I U V ^ T e b S X ] T X U Y Z R S T U W 11 RTN-2 7 IN-2V V c e X U Y Z [ ^ 6 2 RTN-1 IN-1V 5 1 RTN-0 IN-0V [ V W Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 41171-084] (29) Conversion: 1771-NIVT (1) To 1756-IF8I (1) (Current), 1756-IRT8I (1) (TC) Using Existing 1771-RTP1 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP1 4 2 THERMOCOUPLE + SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 Cable “B” 1492-CONACAB020N54 15 16 White/Red 18 19 Green 21 22 White/Black 24 25 Black 16 IN_3(-)/B 15 IN_3(+)/A Red 12 IN_2(-)/B 11 IN_2(+)/A Yellow Brown Violet CURRENT LOAD + W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 8 7 IN_1(-)/B 4 3 IN_0(-)/B IN_0(+)/A 10 CJC+ CJC- 14 14 Thermocouple 1756-IRT8I IN_1(+)/A 1 Cable “A” 1492-CONACAB020N34 15 16 18 19 21 22 24 25 k l s q p q m h o k h o m h o w 13 RTN_3 11 IN_3/I/SRC u n o s q u f h g r h t i 14 RTN_2 12 IN_2/I/SRC o j x l g v o r n l q k u t m k p o o l f n r m i 1756-IF8I n 5 3 RTN_1 IN_1/I/SRC 6 4 RTN_0 IN_0/I/SRC o j 3 Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E [Reference Doc: 10002306504] (30) Conversion: 1771-NIVT (1) To 1756-IT6I (1) (Thermocouple), 1756-IF6I (1) (Current) Using Existing 1771-RTP1 Interface Module V. Wiring Diagrams There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation. WARNING Interface Module 1771-RTP1 4 2 THERMOCOUPLE + SH W2 W3 R8 I8 S8 O8 R7 I7 S7 O7 R6 I6 S6 O6 R5 I5 O5 S5 Cable “B” 1492-CONACAB020N5 B1 B2 B3 B4 B5 A4 A5 B8 B9 A6 A7 B12 B13 A8 A9 B16 B17 A10 A11 15 16 White/Red 18 19 Green 21 22 White/Black 24 25 Black 12 RTN-3 8 IN-3 Red 11 RTN-2 7 IN-2 Yellow CURRENT LOAD + A1 A2 A3 B12 B13 A12 A13 B14 B15 A14 A15 B16 B17 A16 A17 B18 B19 A19 A18 RTN-1 IN-1 5 1 RTN-0 IN-0 10 CJC+ CJC- Violet 14 14 W1 CR CL R4 I4 S4 O4 R3 I3 S3 O3 R2 I2 S2 O2 R1 I1 O1 S1 6 2 Brown CABLE “B” Thermocouple 1756-IT6I 1 Cable “A” 1492-CONACAB020N3 N/A N/A N/A 15 16 18 19 ~ 21 22 24 25 { ~ { ~ { 12 RTN-3 10 IN-3/I 8 IN-3/V y z ~ y 1756-IF6I | z { { | 11 RTN-2 9 IN-2/I 7 IN-2/V } 6 4 2 RTN-1 IN-1/I IN-1/V 5 3 1 RTN-0 IN-0/I IN-0/V } Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row. Follow your PLC Analog User Manual for proper shield grounding instructions. Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 41171-085] PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E Printed in U.S.A. (31) PN-107134 DIR 10000165561 (Version 02) Publication 1492-IN104C-EN-E Printed in U.S.A. (32) ">