Allen-Bradley Power Supply Reference Manual
Allen-Bradley Power Supply is a highly versatile redundancy module designed for building 1+1 and N+1 redundant systems, suitable for industrial control, office, communication, and instrumentation equipment. It features two input channels with up to 20A output current and a single output capable of carrying nominal currents up to 40A. With its low voltage drop and power losses, it provides a reliable solution for various applications.
PDF
Document
Advertisement
Advertisement
Reference Manual Bulletin 1606 Switched Mode Power Supplies Catalog Number: 1606-XLSRED40 Index Page 1. Intended Use .......................................................3 2. Installation Requirements...................................3 3. Input and Output Characteristics .......................4 4. Power Losses........................................................5 5. Lifetime Expectancy and MTBF...........................6 6. Terminals and Wiring..........................................7 7. Functional Diagram.............................................8 8. Front Side and User Elements.............................8 9. EMC......................................................................9 10. Environment ......................................................10 11. Protection Features ...........................................11 12. Safety Features ..................................................11 13. Dielectric Strength ............................................11 Page 14. Certifications .................................................... 12 15. Physical Dimensions and Weight ..................... 13 16. Accessories ........................................................ 14 17. Application Notes ............................................. 15 17.1. Recommendations for Redundancy.........15 17.2. Inductive and Capacitive Loads................15 17.3. Lateral Installation Clearances ............15 17.4. 1+1 Redundancy up to 20A......................16 17.5. N+1 Redundancy, Example with 60A ......16 17.6. Mounting Orientations ............................17 Terminology and Abbreviations • PE and + + symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol . • Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”. • T.b.d.—To be defined, value or description will follow later. • DC 24V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery whether it is full (13.7V) or flat (10V) • 24Vdc—A figure with the unit (Vdc) at the end is a momentary figure with no additional tolerance included. • may, shall, should—Three key words indicating, respectively: flexibility of choice with no implied preference, a mandatory requirement, flexibility of choice N+1 1+1 • 1+1 Redundancy—Use of two identical power supplies in parallel to provide Redundancy Redundancy AC AC AC AC AC AC AC AC continued operation following most failures in a single power supply. The two power supply outputs should be isolated from each other by using diodes or DC DC DC DC DC DC DC DC other switching arrangements. E.g. two 10A power supplies are needed to IN 1 IN 2 IN 1 IN 2 IN 1 IN 2 IN 1 IN 2 achieve a 10A redundant system. • N+1 Redundancy—Use of three or more identical power supplies in parallel OUT OUT OUT OUT to provide continued operation following most failures in a single power supply. All power supply outputs should be isolated from each other by using diodes or other switching arrangements. E.g. to achieve a 40A redundant system, five 10A Load Load power supplies are required in a N+1 redundant system. Bulletin 1606 Switched Mode Power Supplies Mosfet Redundancy Module For N+1 and 1+1 Redundant Systems Dual Input with Single Output Suitable for all Power Supplies Only 72mV Voltage Drop at 20A Output Current Only 2.15W Loss at 20A and 6.3W at 40A Output Current 160% (65A) Peak Load Capability Reverse Input Polarity Protection Full Power Between -40°C and +70°C Width only 36mm Rugged Metal Housing Easy Wiring: Distribution Terminal for Negative Pole Included 3 Year Warranty Description Specification Quick Reference The 1606-XLSRED40 is a redundancy module which can be used to build 1+1 and N+1 redundant systems. It is equipped with two input channels, which can be connected to power supplies with up to 20A output current and one output, which can carry nominal currents up to 40A. The module is suitable for power supplies with constant current overload behavior as well as any kind of “Hiccup” overload behavior. Input voltage Input voltage range Input current The novelty of this redundancy module is the utilization of mosfets instead of diodes for the decoupling of the two input channels. This reduces the heat generation and the voltage drop between input and output. The redundancy module does not require an additional auxiliary voltage and is self-sufficient even in case of a short circuit across the output. Due to the low power losses, the unit is very slender and only requires 36mm width on the DIN rail. Large connection terminals allow for a safe and fast installation with a large international approval package. This unit is suitable for nearly every application. DC 12-28V 8.4-36.4Vdc ±30% 2x 0-20A 2x 20-32.5A 0-40A 40-65A 65A continuous for 5 seconds Output current continuous for 5 seconds at cont. overload or short circuit Input to output typ. 72mV input: 2x10A typ. 112mV input: 1x20A voltage drop typ. 140mV input: 2x20A Power losses typ. 700mW at no load typ. 2.15W input: 2x10A typ. 2.65W input: 1x20A typ. 6.3W input: 2x20A Temperature range -40°C to +70°C operational, no de-rating req. Dimensions 36x124x127mm*) WxHxD *) plus 4mm in depth for the screw terminal Certification Marks Catalog Numbers Redundancy 1606-XLSRED40 12-28V Standard unit Module 1606-XLC Wall/panel mount Accessory bracket IND. CONT. EQ. UL 508 IECEx ATEX II 3G Ex nA IIC T4 Gc 2 UL 60950-1 Marine All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 Class I Div 2 EMC, LVD Bulletin 1606 Switched Mode Power Supplies 1. Intended Use • This redundancy module is designed for installation in an enclosure and is intended for general use such as in industrial control, office, communication and instrumentation equipment. • This redundancy module can be used with any type of power supply as long as the maximum ratings are not exceeded. It is suitable for power supplies with constant current overload behavior as well as any kind of “Hiccup” overload behavior. • Do not use this redundancy module in equipment where malfunction may cause severe personal injury or threaten human life. • This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations. 2. Installation Requirements • • • • This device may only be installed and put into operation by qualified personnel. This device does not contain serviceable parts. If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection. Mount the unit on a DIN rail so that the input terminals are located on top and the output terminals on the bottom of the unit. For other mounting orientations, see derating requirements in the present document (refer to section 17.6). • This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%! • Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase the side clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply). See section 17.3 for further information in combination with poser supplies. SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing. - Turn power off before working on the device. Protect against inadvertent re-powering - Make sure that the wiring is correct by following all local and national codes - Do not modify or repair the unit - Do not open the unit as high voltages are present inside - Use caution to prevent any foreign objects from entering the housing - Do not use in wet locations or in areas where moisture or condensation can be expected - Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns. WARNING: EXPLOSION HAZARDS! Substitution of components may impair suitability for this environment. Do not disconnect the unit unless power has been switched off or the area is known to be non-hazardous. A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and meets the requirements of the EN 60079-15:2010. Notes for use in hazardous location areas: • The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2) environments and is evaluated according to EN 60079-0:2009 and EN 60079-15:2010. All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 3 Bulletin 1606 Switched Mode Power Supplies 3. Input and Output Characteristics Number of inputs Number of outputs Input voltage nom. 2 1 DC 12-28V ±30% Input voltage range Voltage drop, input to output typ. typ. typ. nom. nom. max max. nom. nom. max. max. max. typ. 8.4-36.4Vdc 140mV 72mV 112mV 2x 0-20A 2x 20-32.5A 2x 32.5A 1000A 40A 40-65A 65A Input current Peak input current Output current Reverse current Reverse voltage Output capacitance Note: The input circuitry must meet the SELV requirements stipulated by IEC/EN/UL 60950-1. at 2x20A, see Fig. 3-1 at 2x10A, see Fig. 3-1 at 1x20A, see Fig. 3-2 continuous for 5 seconds at continuous overload or short circuit for max. 1ms per input continuous for 5 seconds at continuous overload or short circuit 1mA 40Vdc 320μF at 24V, per input, -40°C to +70°C voltage applied to the output, continuously allowed Ensure that the continuous output current does not exceed 65A. Check the short-circuit current of the power sources and if the power source can deliver more than 65A together, use an appropriate fuse on the output. Fig. 3-1 Input to output voltage drop when both inputs draw current (typical 1+1 redundant case, when the output voltages of the two units are equal) 160mV 140mV 120mV 100mV 80mV 60mV 40mV 20mV 0mV Voltage Drop, typ I1 A 24V,20A B A... 25°C B... 60°C + A V U1 Input 1 IOUT A Output Variable Load, 0-40A UOUT V - I2 A 24V,20A + V U2 Input / Output Current Output: 0 Input: 0 Output XLSRED40 Input 2 - 10A 30A 20A 40A 2x5A 2x10A 2x15A 2x20A I1 = I2 U1 = U2 Voltage Drop = U1 - UOUT Fig. 3-2 Input to output voltage drop when only one input draws current 160mV 140mV 120mV 100mV 80mV 60mV 40mV 20mV 0mV Voltage Drop, typ. + A... 25°C B... 60°C V U1 B A Output Current 0 4 I1 A 24V,20A 5A 10A 15A 20A Output XLSRED40 Input 1 IOUT A Output Variable Load, 0-20A UOUT V - Not used or power supply with lower voltage Input 2 Voltage Drop = U1 - UOUT All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 Bulletin 1606 Switched Mode Power Supplies 4. Power Losses Power losses typ. typ. typ. DC 24V 2.15W 6.3W 2.6W Standby power losses typ. 0.35W typ. 0.7W input: 2x10A input: 2x20A input: 1x20A, (only one input is connected to input voltage) at no output current, (only one input is connected to input voltage) at no output current, (both inputs are connected to input voltages) Fig. 4-1 Power losses when both inputs draw equal current Power Losses, typ. 7W 6.0 5.0 4.0 3.0 2.0 1.0 0 24V,20A + e.g. 24.5V A... 25°C B... 60°C B A V U1 + Output Current 0 5 15 10 20 25 30 35 40A Output XLSRED40 Input 1 IOUT A Output Variable Load, 0-40A UOUT V - 24V,20A e.g. 24.5V I1 A I2 A V U2 Input 2 - I1 = I2 U1 = U2 Losses = ( U1 * I1 + U2 * I2 ) - UOUT * IOUT Fig. 4-2 Power losses when only one input is used Power Losses, typ. 4W 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0 24V,20A + I1 A V U1 A... 25°C B... 60°C Output XLSRED40 Input 1 IOUT A Output Variable Load, 0-20A UOUT V - B A Input 2 Output Current 0 2.5 5 7.5 10 12.5 15 17.5 20A Losses = U1 * I1 - UOUT * IOUT Note: As soon as voltage is applied on input 2, an additional 0.35W will be consumed. It is not relevant whether this channel contributes to the output current or not. All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 5 Bulletin 1606 Switched Mode Power Supplies 5. Lifetime Expectancy and MTBF The redundancy module has two input channels which are completely independent from each other. Each control circuit, auxiliary voltage source, or other circuitry in the module are designed separately for each input. The dual input redundancy module can be considered as two single redundancy modules combined together in one housing. The only common point is the circuit trace that ties the two separate circuits together at the output. The MTBF figures below are for the entire dual input module. If the MTBF number of only one path is needed, simply double the value from the table. Input / output current conditions Lifetime expectancy*) MTBF**) SN 29500, IEC 61709 MTBF**) MIL HDBK 217F Input: 2x10A Output: 20A 649 000h *) 1 835 000h *) 3 386 000h 5 667 000h 116 000h 155 000h 612 000h 813 000h Input: 2x20A Output: 40A 246 000h *) 696 000h *) 2 706 000h 4 686 000h 97 000h 128 000h 522 000h 687 000h at 24V and 40°C at 24V and 25°C at 24V 40°C at 24V 25°C Ground Fixed GF40 (24V and 40°C) Ground Fixed GF25 (24V and 25°C) Ground Benign GB40 (24V and 40°C) Ground Benign GB25 (24V and 25°C) *) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices. **) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit has been running for 50 000h or only for 100h. 6 All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 Bulletin 1606 Switched Mode Power Supplies 6. Terminals and Wiring Type Solid wire Stranded wire American Wire Gauge Max. wire diameter Wire stripping length Screwdriver Recommended tightening torque Input Screw termination IP20 Finger safe construction. Suitable for field installation. 0.5-6mm2 0.5-4mm2 20-10 AWG 2.8mm (including ferrule) 7mm / 0.275inch 3.5mm slotted or Pozidrive No 2 0.8Nm, 7lb.in Output Screw termination IP20 Finger safe construction. Suitable for field installation. 0.5-16mm2 0.5-10mm2 22-8 AWG 5.2mm (including ferrule) 12mm / 0.5inch 3.5mm slotted or Pozidrive No 2 1.2Nm, 10.6lb.in To connect the chassis to ground, use a ring-type terminal (ring cable lug) which is suitable for a M4 screw and connect it to the chassis ground terminal on top of the unit. Instructions: a) The external circuitry of all terminals must meet the safety requirements stipulated by IEC/EN/UL 60950-1: SELV. b) Use appropriate copper cables that are designed for minimum operating temperatures of: 60°C for ambient up to 45°C and 75°C for ambient up to 60°C and 90°C for ambient up to 70°C minimum. c) Follow national installation codes and installation regulations! d) Ensure that all strands of a stranded wire enter the terminal connection! e) Screws of unused terminal compartments should be securely tightened. f) Ferrules are allowed. g) Do not connect or disconnect the wires from the terminals below -25°C (-13°F). All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 7 Bulletin 1606 Switched Mode Power Supplies 7. Functional Diagram Fig. 7-1 Functional diagram control + + - - Input 1 Output Chassis Ground + Input 2 - control 8. Front Side and User Elements Fig. 8-1 Front side A Output Terminals (screw terminals) B Chassis Ground Terminals To be connected on the top side of the housing with a ring-type terminal (ring cable lug) which is suitable for a M4 screw. Connection of the chassis is optional and not required since the unit fulfils the requirements according to protection class III. C Input Terminals for Input 1 (screw terminals) D Input Terminals for Input 2 (screw terminals) A B Chassis Ground 8 All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 Bulletin 1606 Switched Mode Power Supplies 9. EMC The redundancy module is suitable for applications in industrial environment as well as in residential, commercial and light industry environment without any restrictions. A detailed EMC report is available on request. EMC Immunity Electrostatic discharge Electromagnetic RF field Fast transients (Burst) Surge voltage on input lines According generic standards: EN 61000-6-1 and EN 61000-6-2 EN 61000-4-2 Contact discharge 8kV Air discharge 15kV EN 61000-4-3 80MHz-2.7GHz 20V/m EN 61000-4-4 Input lines 2kV Output lines 2kV 500V EN 61000-4-5 + 1kV Chassis ground +/- Surge voltage on output lines EN 61000-4-5 Conducted disturbance Power-frequency magnetic field *) EN 61000-4-6 EN 61000-4-8 + +/Chassis ground 0.15-80MHz 50Hz Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A Criterion A 500V 1kV Criterion A Criterion A 20V 30A/m Criterion A Criterion A Criteria: A: Redundancy module shows normal operation behavior within the defined limits. Notes: *) A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall elements, electrodynamic microphones, etc. According generic standards: EN 61000-6-3 and EN 61000-6-4 IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 limits for DC power ports according EN 61000-6-3 fulfilled *) Radiated emission EN 55011, EN 55022 Class B This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. EMC Emission Conducted emission *) For information only, not mandatory for EN 61000-6-3. Provided, that power sources connected on the inputs fulfill the requirements too. Switching frequency The internal auxiliary supply is generated with a boost converter. The switching frequency is typ. 16kHz. All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 9 Bulletin 1606 Switched Mode Power Supplies 10. Environment Operational temperature *) Storage temperature Humidity **) Vibration sinusoidal Shock Altitude -40°C to +70°C (-40°F to 158°F) -40 to +85°C (-40°F to 185°F) 5 to 95% r.H. 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g 2 hours / axis 30g 6ms, 20g 11ms 3 bumps / direction, 18 bumps in total 0 to 2000m (0 to 6 560ft) 2000 to 6000m (6 560 to 20 000ft) for storage and transportation IEC 60068-2-30 IEC 60068-2-6 IEC 60068-2-27 without any restrictions reduce output power or ambient temperature, see Fig. 10-2 2.5A/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 10-2 not applicable The concept of the overvoltage category is used for equipment energized directly from the low voltage mains (IEC 60664-1 §4.3.3.2.1). 2 IEC 62103, EN 50178, not conductive The unit does not release any silicone or other LABS-critical substances and is suitable for use in paint shops. Altitude de-rating Over-voltage category Degree of pollution LABS compatibility *) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. **) Do not energize in the presence of condensation. Fig. 10-1 Output current vs. ambient temp. Allowed Output Current 65A 65A at overload / short circuit 50 40 overload / short circuit 50 normal mode 30 20 20 10 10 Ambient Temperature 0 20 normal mode 40 30 0 -40 -25 10 Fig. 10-2 Output current vs. altitude Allowed Output Current 40 A A... Tamb < 70°C B... Tamb < 60°C C... Tamb < 50°C 0 60 70°C 0 2000 B C Altitude 4000 6000m All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 Bulletin 1606 Switched Mode Power Supplies 11. Protection Features Output over-current protection Reverse input polarity protection Degree of protection Penetration protection Over-temperature protection Input transient protection Output transient protection Internal input fuse not included included unit does not start when input voltage is reversed IP 20 > 3.6mm not included not included included not included EN/IEC 60529 e.g. screws, small parts no galvanic separation III < 0.1Ohm Mosfet between input and output PE (Protective Earth) or chassis connection not required between housing and chassis-ground terminal see EMC section 12. Safety Features Input / output separation Class of protection PE resistance 13. Dielectric Strength The input and output voltages have the same reference, are floating and have no ohmic connection to ground. Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect input/output terminals together before conducting the test. When testing, set the cut-off current settings to the value in the table below. Fig. 13-1 Dielectric strength Type test In- / Output + - Chassis A 60s A 500Vac Factory test 5s 500Vac Field test 5s 500Vac Cut-off current setting > 2mA All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 11 Bulletin 1606 Switched Mode Power Supplies 14. Certifications EC Declaration of Conformity Complies with - CE EMC directive, - CE Low-voltage directive The CE mark indicates conformance with the - ATEX directive 94/9/EC (Equipment and protection systems intended for use in potentially explosive atmospheres) UL 508 Listed E56639 for use in the U.S.A. (UL 508) and Canada (C22.2 No. 14-95). Industrial Control Equipment UL 60950-1 RECOGNIZED E168663 for use in the U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950) INformation Technology Equipment, Level 3 CSA 22.2 No 107,1-01 CSA Certified under File NUmber 2400020; CERTIFIED for use in the U.S.A. (ISA 12.12.01) and Canada (C22.2 No. 213) Hazardous Location Class I Div. 2 - Groups A, B, C, D ISA 12.12.01, CSA C22.2 No. 213 RECOGNIZED UNDER FILE NUMBER E244404 for use in the U.S.A. (ISA 12.12.01) and Canada (C22.2 No 213) Hazardous Location Class I Div. 2 - Groups A, B, C, D Approval for use in hazardous locations Zone 2 Category 3G. Number of ATEX Certificate: EPS 11 ATEX 1 312 X The redundancy module must be built-in in an IP54 enclosure. ATEX II 3G Ex nA IIC T4 Gc Marine GL GL (Germanischer Lloyd) classified for marine and offshore applications. Environmental category: C, EMC2. See below for link to Certificate. Marine Rina RINA (Registro Italiano Navale) certified. See below for the link to Certificate. GOST R GOST R certification is applicable for products intended for sale and use within Russia. See below for link to Certificate. C-TICK C-tick compliance is for products intended for sale and use within the Australian market. See below for the link to the C-tick Declarations of Conformity. Product certification information (including Certificates and Declarations of Conformity) can be found at www.ab.com/certifications. 12 All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 Bulletin 1606 Switched Mode Power Supplies 15. Physical Dimensions and Weight Weight DIN Rail Installation Clearances 340g / 0.75lb Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. The DIN rail height must be added to the unit depth (127mm) to calculate the total required installation depth. See section 2. Fig. 15-1 Front view Fig. 15-2 Side view All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 13 Bulletin 1606 Switched Mode Power Supplies 16. Accessories 1606-XLC Wall mounting bracket This standard bracket is used to mount the 1606-XLSRED40 redundancy module on a wall, without a DIN rail. Fig. 16-1 1606-XLC Wall mounting bracket 14 Fig. 16-2 Assembled wall mounting bracket All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 Bulletin 1606 Switched Mode Power Supplies 17. Application Notes 17.1. Recommendations for Redundancy Recommendations for the configuration of redundant power systems: - Use separate input fuses for each power supply. - Use three-phase power supplies to gain functional safety if one phase fails. - When single-phase power supplies are utilized connect them to different phases or mains circuits if possible. - Set the power supply in “Parallel-Use” mode if this feature is available - It is desirable to set the output voltages of all power supplies to the same value. 17.2. Inductive and Capacitive Loads The unit is designed to supply any kind of load, including unlimited capacitive and inductive loads. 17.3. Lateral Installation Clearances The minimum clearance recommendations are defined in section 2. Normally, the following installation clearance are recommended: 40mm on top, 20mm on the bottom, 5mm on the left and right sides when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply). The clearance between the power supplies and the redundancy module can be reduced to zero under the following conditions: - 1+1 redundancy application with maximum 20A output current. - The power supplies are from the XLS family. - The redundancy module is placed between the two power supplies. - The output voltage is set to the same level on both power supplies. + - + - ++ - - DC24V,20A OK Input Input 2 1 1606XLSRED40 Power Supply Redundancy Module ++ - - DC24V,20A OK Power Supply Output L1 L2 L3 PE + - L1 L2 L3 PE 20A Load 0mm All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 0mm 15 Bulletin 1606 Switched Mode Power Supplies 17.4. 1+1 Redundancy up to 20A 1+1 Redundancy up to 20A requires two 20A power supplies and one 1606-XLSRED40 redundancy module. Fig. 17-1 Wiring diagram, 1+1 Redundancy, 20A output current Failure Monitor + - + - ++ - - ++ - - Input Input 2 1 DC24V,20A OK DC24V,20A OK 1606XLSRED40 Power Supply Power Supply Redundancy Module Output + L1 L2 L3 PE - L1 L2 L3 PE 20A Load I I I I I I L1 L2 L3 PE Note: Use separate mains systems for each power supply whenever possible. 17.5. N+1 Redundancy, Example with 60A N+1 Redundancy up to 60A requires four 20A power supplies and two 1606-XLSRED40 redundancy modules. Fig. 17-2 Wiring diagram, n+1 Redundancy, 60A output current Failure Monitor ++ - - DC24V,20A OK + - + - Input Input 2 1 1606XLSRED40 Power Supply Redundancy Module ++ - - DC24V,20A OK Power Supply ++ - - DC24V,20A OK 1606XLSRED40 Power Supply Redundancy Module Output L1 L2 L3 PE + - + - + - Input Input 2 1 Output L1 L2 L3 PE L1 L2 L3 PE + - ++ - - DC24V,20A OK Power Supply L1 L2 L3 PE 60A Load I I I I I I I I I I I I L1 L2 L3 PE Note: Use separate mains systems for each power supply whenever possible. 16 All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 Bulletin 1606 Switched Mode Power Supplies 17.6. Mounting Orientations Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous operation can be found below: Curve A1 Curve A2 Recommended output current. Max allowed output current (results in approximately half the lifetime expectancy of A1). Fig. 17-3 Mounting Orientation A (Standard orientation) Output Current 40A INPUT A1 30 Redundancy Module 20 10 Ambient Temperature 0 OUTPUT 20 Fig. 17-4 Mounting Orientation B (Upside down) 30 40 60 50 70°C Output Current 40A A1 OUTPUT 30 Redundancy Module 20 10 Ambient Temperature INPUT 0 20 Fig. 17-5 Mounting Orientation C (Table-top mounting) 30 40 50 60 70°C Output Current 40A 30 A2 20 A1 10 Ambient Temperature 0 20 40 50 60 70°C Output Current 40A INPUT Redundancy Module OUTPUT Fig. 17-6 Mounting Orientation D (Horizontal cw) 30 30 A2 20 A1 10 Ambient Temperature 0 20 Fig. 17-7 Mounting Orientation E (Horizontal ccw) 30 40 50 60 70°C Output Current OUTPUT Redundancy Module INPUT 40A 30 A2 20 A1 10 Ambient Temperature 0 20 30 40 50 60 70°C All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM010A-EN-P — February 2014 17 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http:// www.rockwellautomation.com/knowledgebase for FAQs, technical information, support chat and forums, software updates, and to sign up for product notification updates. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnectSM support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/. Installation Assistance If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Outside United States Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http:// literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf. Publication 1606-RM010A-EN-P — February 2014 Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">

Download
Just a friendly reminder. You can view the document right here. But most importantly, our AI has already read it. It can explain complex things in simple terms, answer your questions in any language, and help you quickly navigate even the longest or most compilcated documents.
Advertisement
Key features
- Dual Input
- Single Output
- Mosfet Redundancy
- Low Voltage Drop
- Low Power Loss
- Peak Load Capability
- Reverse Input Polarity Protection
- Wide Temperature Range
- Compact Size
- Easy Wiring
Frequently asked questions
The maximum output current of the 1606-XLSRED40 redundancy module is 40A.
The typical voltage drop between input and output is 72mV at 2x10A input current and 140mV at 2x20A input current.
It is desirable to set the output voltages of all power supplies to the same value.
The maximum operational temperature is +70°C. See Section 10 for derating requirements.
Recommended clearances include 40mm on top, 20mm on the bottom, and 5mm on the left and right sides when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source.
The 1606-XLSRED40 redundancy module has various certifications including CE, UL, CSA, ATEX, and marine certifications. For a complete list and documentation, visit www.ab.com/certifications.