Digital I/O Conversion Module
(Cat 1492-CM1771-LD011)
I. Description
This Digital I/O Conversion Module provides for the conversion of (1) 1771, 32 point I/O modules to be converted to
(1) 1756, 32 point I/O module and consists of the following:
(1) 1771 Module (32pt) to (1) 1756 Module (32pt)
(2) Conversion Module: 1492-CM1771-LD005
(1) Cable: 1492-CONCAB005Z (Table 2, Section III)
(1) Conversion Mounting Assembly: 1492-MUA… (Table 1, Section II)
This conversion is accomplished without the removal of any field wires from the existing 1771 Swing Arm. The existing 1771 Swing Arm fits directly onto the edge connector of the 1492 Conversion Module. On one end of the 1492
Cable is (1) connector for the Conversion Module. On the other end is the Removable Terminal Block (RTB) for the
1756 I/O module, as shown in the photo below. The I/O signals are routed through the 1492 Conversion Module and
the 1492 Cable to the appropriate terminals on the 1756 I/O module per the Wiring Diagrams in Section V. As standard, both portions of the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length. Refer to the footnotes in
Table 2, Section III for further details.
Conversion Compatibility and
Product I.D. Label
37-Pin Connector for cable 1492-CONCABY
1492-CM1771-LD011 Conversion Module
WARNING
PN-114283
DIR 10000060094 (Version 01)
Publication 1492-IN041B-EN-E
Printed in U.S.A.
De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O chassis,
and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any
device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.
II. Installation
The 1492 Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see Table 1 below). A
complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
1) Determine the quantity of each type of 1771 I/O modules used in the 1771 I/O Chassis to be converted.
2) Select the applicable 1492 Conversion Modules from Table 2, Section III.
3) Review the Max Slots for I/O and Chassis Width data from the Table 1 below.
4) Select a 1756 I/O Chassis which has enough I/O Slots.
NOTE: (2) I/O slots are required in the 1756 Chassis for conversions where (1) 1771 I/O module converts to (2) 1756 I/O
modules.
5) Select the 1492 Conversion Mounting Assembly which has enough Conversion Module slots.
NOTE: (2) Conversion Module slots are required in the 1492 Conversion Mounting Assembly for conversions where (2)
1771 I/O module convert to (1) 1756 I/O modules.
NOTE: The 1492 Conversion Mounting Assembly has the same Height & Width foot-print as the 1771 Chassis and is
designed to use the same mounting hardware. The combined Depth of the 1492 Conversion Mounting Assembly with the
1756 Chassis mounted on top is 10.25 inches (Controller w/key) or 10.0 inches (Controller w/o key). Dimension drawings
are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly.
Table 1: Bulletin 1771 to 1756 Chassis Conversion
1771 Chassis
Cat. No.
Max
Slots
for
I/O
1771-A1B
4
1771-A2B
8
1756 Chassis
Chassis Width
without
Power
Supply
with
Power
Supply
9.01
12.61
14.01
17.61
Conversion Mounting Assembly
Cat. No.
Max
Slots
for
I/O
Chassis
Width
Cat. No.
Max Slots
for
Conversion
Modules
Chassis
Width
1492-MUA1B-A4-A7
4
9.01
1756-A4
3
10.35
1756-A7
6
14.49
1756-A7
1756-A10
6
9
14.49
19.02
1492-MUA2B-A7-A10
8
14.01
1771-A3B1
12
19.01
1756-A10
1756-A13
9
12
19.02
23.15
1492-MUA3-A10-A13
12
19.01
1771-A4B
16
24.01
1756-A13
1756-A17
12
16
23.15
29.06
1492-MUA4-A13-A17
16
24.01
1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.
Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power
Supply. The Cover-Plate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left justified,
Right justified or Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting
Assembly.
PN-114283
DIR 10000060094 (Version 01)
Publication 1492-IN041B-EN-E
(2)
III. Compatiblity
Table 2: Bulletin 1771 to 1756 Conversion Modules and Cables
1756
1771
Digital I/O Module Digital I/O Module
1771-OW16
-
1756-OW16I
1492
Conversion Module
1492-CM1771-LD0011
1492
Cable
1492-CONCAB005Y
Foot Notes:
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific
1771 and 1756 I/O modules involved.
The 3 numbers indicate the cable length of each portion of the 1492 Cable. Recommended cable lengths of 0.5M
are shown. Additional cable lengths are as follows:
1.0M = 1492-CONCAB010Y
IV. Conversion Module Specifications
(Operating specifications are when installedin the Conversion System base / cover-plate assembly)
Specification
Dimensions
Approximate Shipping Weight
Storage Temperature
Operating Temperature
Operating Humidity
Shock
Non operating
Operating
Operating Vibration
Maximum Operating Voltage
Max. Module Operating Current
Per Point:
Per Module:
Value
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
238.9 g (0.53 lbs) (includes carton)
-40 to +85°C (-40 to +185°F)
0 to 60°C (32 to 140°F)
5 to 95% at 60°C (non-condensing)
50g
30g
2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)
240 Vac at 47 to 63Hz or 240 Vdc
2 Amps
12 Amps
Agency Certifications
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Pollution Degree
2
Environmental Rating
IP20
NOTICE
PN-114283
DIR 10000060094 (Version 01)
Publication 1492-IN041B-EN-E
(3)
V. Wiring Diagrams
Conversion: 1771-OW16 to 1756-OW16I
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
WARNING
Conversion Module
1492-CM1771-LD011
Output 10 (NC)
Output 11 (NC)
Output 12 (NC)
Output 13 (NC)
Common 00
Output 00
Common 01
Output 01
Common 02
Output 02
Common 03
Output 03
Common 04
Output 04
Common 05
Output 05
Common 06
Output 06
Common 07
Output 07
Common 10
Output 10 (NO)
Common 11
Output 11(NO)
Common 12
Output 12 (NO)
Common 13
Output 13 (NO)
Common 14
Output 14 (NO)
Common 15
Output 15 (NO)
Common 16
Output 16 (NO)
Common 17
L1
LOAD
L2
+
-
LOAD
Output 17 (NO)
Output 14 (NC)
Output 15 (NC)
Output 16 (NC)
Output 17 (NC)
17
20
23
26
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
19
18
22
21
25
24
28
27
31
30
34
33
37
36
40
39
29
32
35
38
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Cable
1492-CONCAB005Y
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
1756-OW16I
2
1
4
3
6
5
8
7
10
9
12
11
14
13
16
15
18
17
20
19
22
21
24
23
26
25
28
27
30
29
32
31
L1-0
OUT-0 N.O.
L1-1
OUT-1 N.O.
L1-2
OUT-2 N.O.
L1-3
OUT-3 N.O.
L1-4
OUT-4 N.O.
L1-5
OUT-5 N.O.
L1-6
OUT-6 N.O.
L1-7
OUT-7 N.O.
L1-8
OUT-8 N.O.
L1-9
OUT-9 N.O.
L1-10
OUT-10 N.O.
L1-11
OUT-11 N.O.
L1-12
OUT-12 N.O.
L1-13
OUT-13 N.O.
L1-14
OUT-14 N.O.
L1-15
OUT-15 N.O.
1771-WN Swing Arm
From 1771-OW16
Conversion Module Installation and Application Considerations
The 1771-OW16 module output resistive current limits versus 1756-OW16I limits are as follows:
1771-OW16
1756-OW16I w/ 1492-CONCAB005Y
a) Current/Point
2A @ 250V AC
2A @ 240V AC
2A @ 30V DC
2A @ 30V DC
0.3A @ 150V DC
0.25A @ 125V AC
The 1492-CONCAB005Y is limited to 3A per pin.
The 1771-OW16 has N.O. and N.C. relay contact outputs. The 1756-OW16I has N.O. relay contact outputs only. The conversion module does not convert the N.C. to N.O. contacts. If the 1771-OW16 N.C. outputs were being used, the installer must
rewire the 1771-WN swing arm and move the N.C. wires to the N.O. output terminals. In addition, the control Logix programming
will need to be changed to simulate a N.C. relay with this output.
Refer to your 1771-OW16 and 1756-OW16I Installation Manual wiring schematics and diagrams for more details.
Ensure 1756 output module ratings are not exceeded.
Reference Doc: 41170-940 (Version 01)]
PN-114283
DIR 10000060094 (Version 01)
Publication 1492-IN041B-EN-E
Printed in U.S.A.
">