Allen-Bradley CompactLogix 1769-OF4VI Module Installation Instructions
Allen-Bradley CompactLogix 1769-OF4VI Module is a compact and powerful analog output module designed for industrial applications. This module provides four isolated differential channels with flexible output ranges and a high resolution of 15 bits plus sign. It's perfect for controlling analog actuators like valves, motors, and pumps.
PDF
Download
Document
Advertisement
Advertisement
Installation Instructions Compact 1769-OF4VI Isolated Analog Output Module Catalog Number 1769-OF4VI Topic Page Important User Information 2 About the Module 4 System Assembly 6 Mounting Expansion I/O 8 Replacing a Single Module Within a System 11 Module Spare/replacement Parts 12 Grounding the Module 12 I/O Memory Mapping 17 Specifications 22 Additional Resources 27 2 Compact 1769-OF4VI Isolated Analog Output Module Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences. SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 3 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations. Informations sur l’utilisation de cet équipement en environnements dangereux. Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation. Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation. WARNING: Explosion Hazard - AVERTISSEMENT: Risque d’Explosion – • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. • Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. • Substitution of components may impair suitability for Class I, Division 2. • If this product contains batteries, they must only be changed in an area known to be nonhazardous. • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement. • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2. • S'assurer que l'environnement est classé non dangereux avant de changer les piles. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 4 Compact 1769-OF4VI Isolated Analog Output Module About the Module Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. 1 2a 3 OK Analog DANGER Do Not Remove RTB Under Power Unless Area is Non-Hazardous 10a N/C N/C V out 0 V out 0 + N/C N/C V out 1 V out 1 + N/C 10 N/C V out 2 V out 2 + N/C N/C V out 3 - 10b V out 3 + N/C N/C Ensure Adjacent Bus Lever is Unlatched/Latched Before/After Removing/Inserting Module 4 1769-OF4VI 8a 7a 7a 2b OK Analog 5a 5b 9 6 7b 7b 8b Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 5 Item Description Item Description 1 Bus lever (with locking function) 7a Upper tongue-and-groove slots 2a Upper panel mounting tab 7b Lower tongue-and-groove slots 2b Lower panel mounting tab 8a Upper DIN rail latch 3 Module status LED 8b Lower DIN rail latch 4 Module door with terminal identification label 9 Write-on label (user ID tag) 5a Movable bus connector with female pins 10 Removable terminal block (RTB) with finger-safe cover 5b Stationary bus connector with male pins 10a RTB upper retaining screw 6 Nameplate label 10b RTB lower retaining screw Prevent Electrostatic Discharge ATTENTION: Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins or the terminal block. Follow these guidelines when you handle the module: • • • • • • Touch a grounded object to discharge static potential. Wear an approved wrist-strap grounding device. Do not touch the bus connector or connector pins. Do not touch circuit components inside the module. Use a static-safe work station, if available. When not in use, keep the module in its static-shield box. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 6 Compact 1769-OF4VI Isolated Analog Output Module ATTENTION: Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by: • sending an erroneous signal to your system’s field devices, causing unintended machine motion. • causing an explosion in a hazardous environment. Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance. System Assembly The module can be attached to the controller or an adjacent I/O module before or after mounting. • For mounting instructions, see Panel Mounting on page 9, or DIN Rail Mounting on page 11. • To work with a system that is already mounted, see Replacing a Single Module Within a System on page 11. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 7 The following procedure shows you how to assemble the Compact I/O system. 3 4 2 1 6 1 5 Item Description Item Description 1 Tongue-and-groove slots 4 Bus lever 2 Bus connectors 5 End-cap terminator 3 Positioning tab 6 End-cap bus terminator 1. Disconnect power. 2. Check that the bus lever of the module to be installed is in the unlocked (fully right) position. 3. Use the upper and lower tongue-and-groove slots (1) to secure the modules together (or to a controller). 4. Move the module back along the tongue-and-groove slots until the bus connectors (2) line up with each other. 5. Push the bus lever back slightly to clear the positioning tab (3). Use your fingers or a small screwdriver. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 8 Compact 1769-OF4VI Isolated Analog Output Module 6. To allow communication between the controller and module, move the bus lever fully to the left (4) until it clicks. Make sure it is locked firmly in place. ATTENTION: When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection. 7. Attach an end-cap terminator (5) to the last module in the system by using the tongue-and-groove slots as before. 8. Lock the end-cap bus terminator (6). IMPORTANT A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus. Mounting Expansion I/O ATTENTION: During panel or DIN rail mounting of all devices, be sure that all debris, such as metal chips and wire strands, is kept from falling into the module. Debris that falls into the module could cause damage on power up. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 9 Minimum Spacing Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50 mm (2 in.) of space on all sides for adequate ventilation. 4 3 2 2 2 2 6 2 1 4 5 Item Description Item Description 1 Top 4 Side 2 Compact I/O modules 5 Bottom 3 End cap 6 Host controller Panel Mounting Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 10 Compact 1769-OF4VI Isolated Analog Output Module Panel Mounting Using the Dimensional Template Host Controller Spacing for single-wide modules 35mm (1.378 in.) Spacing for one-and-a half-wide modules 52.5mm (2.067 in.) Refer to host controller documentation for this dimension. Note: Overall hole spacing tolerance: ±0.4mm (0.016 in.). 30535-M Panel Mounting Procedure Using Modules as a Template The following procedure lets you use the assembled modules as a template for drilling holes in the panel. If you have sophisticated panel mounting equipment, you can use the dimensional template provided on page 10. Due to module mounting hole tolerance, it is important to follow these procedures. 1. On a clean work surface, assemble no more than three modules. 2. Using the assembled modules as a template, carefully mark the center of all module-mounting holes on the panel. 3. Return the assembled modules to the clean work surface, including any previously mounted modules. 4. Drill and tap the mounting holes for the recommended M4 or #8 screw. 5. Place the modules back on the panel, and check for proper hole alignment. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 11 6. Attach the modules to the panel using the mounting screws. TIP If mounting more modules, mount only the last one of this group and put the others aside. This reduces remounting time during drilling and tapping of the next group. 7. Repeat steps 1 … 6 for any remaining modules. DIN Rail Mounting The module can be mounted using the following DIN rails. • 35 x 7.5 mm (1.38 x 0.30 in.; EN 50 022 - 35 x 7.5) • 35 x 15 mm (1.38 x 0.59 in.; EN 50 022 - 35 x 15) Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place. Replacing a Single Module Within a System The module can be replaced while the system is mounted to a panel (or DIN rail). Follow the steps below in order: 1. Remove power. 2. On the module to be removed, remove the upper and lower mounting screws from the module (or open the DIN latches by using a screwdriver). 3. Move the bus lever to the right to disconnect (unlock) the bus. 4. On the right-side adjacent module, move its bus lever to the right (unlock) to disconnect it from the module to be removed. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 12 Compact 1769-OF4VI Isolated Analog Output Module 5. Gently slide the disconnected module forward. If you feel excessive resistance, check that the module has been disconnected from the bus, and that both mounting screws have been removed (or DIN latches opened). TIP It may be necessary to rock the module slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules. 6. Before installing the replacement module, be sure that the bus lever on the module to be installed, and on the right-side adjacent module are in the unlocked (fully right) position. 7. Slide the replacement module into the open slot. 8. Connect the modules together by locking (fully left) the bus levers on the replacement module and the right-side adjacent module. 9. Replace the mounting screws (or snap the module onto the DIN rail). Module Spare/replacement Parts • Terminal block, catalog number 1769-RTBN18 • Door, catalog number 1769-RD (2 per kit) Grounding the Module This product is intended to be mounted to a well-grounded mounting surface, such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional information. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 13 System Wiring Guidelines Consider the following when wiring your system: • Channels are isolated from each other. • Use Belden 8761, or equivalent, shielded wire. • Under normal conditions, the drain wire and shield junction must be connected to earth ground, via a panel or DIN rail mounting screw at the analog I/O module end. Keep the shield connection to ground as short as possible. TIP In environments where high frequency noise may be present, it may be necessary to ground the shield via a 0.1 µF capacitor at the load end and also ground the module end without a capacitor. • For optimum accuracy, limit overall cable impedance by keeping your cable as short as possible. Locate the I/O system as close to your sensors or actuators as your application will permit. • Load resistance for each voltage output channel must be equal to or greater than 2K Ω.. Wiring Output Devices ATTENTION: Miswiring of the module to an AC/DC source will damage the module. Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 14 Compact 1769-OF4VI Isolated Analog Output Module Labeling the Terminals A removable, write-on label is provided with the module. Remove the label from the door, mark the identification of each terminal with permanent ink, and slide the label back into the door. Your markings (ID tag) will be visible when the module door is closed. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 15 Removing the Finger-safe Terminal Block To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 N•m (4.1 in•lb). 3 1 2 Item Description 1 Wiring the finger-safe terminal block 2 Lower retaining screws 3 Upper retaining screws Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 16 Compact 1769-OF4VI Isolated Analog Output Module Wiring the Finger-safe Terminal Block When wiring the terminal block, keep the finger-safe cover in place. 1. Loosen the terminal screws to be wired. 2. Route the wire under the terminal pressure plate. You can use the bare wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug. TIP The terminal screws are non-captive. You can use a ring lug [maximum 6.35 mm (0.25 in.) o.d. with a 3.53 mm (0.139 in.) minimum i.d. (M3.5)] with the module. 3. Tighten the terminal screw making sure the pressure plate secures the wire. Recommended torque when tightening terminal screws is 0.68 N•m (6 in•lb). TIP If you need to remove the finger-safe cover, insert a screwdriver into one of the square wiring holes and gently pry the cover off. If you wire the terminal block with the finger-safe cover removed, you will not be able to put it back on the terminal block because the wires will be in the way. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 17 Wire Size and Terminal Screw Torque Each terminal accepts up to two wires with the following restrictions: Wire Type Wire Size Terminal Screw Torque Retaining Screw Torque Cu-90 °C (194°F) #14…#22 AWG 0.68 N•m (6 in•lbs) 0.46 N•m (4.1 in-•bs) Stranded Cu-90 °C (194°F) #16…#22 AWG 0.68 N•m (6 in•lbs) 0.46 N•m (4.1 in•lbs) Solid I/O Memory Mapping Output Data File For each module, slot x, words 0…3 in the output data file contain the channel 0 …channel 3 output data. Word 4 is used to unlatch any alarm condition that has been latched. Refer to your module user manual for additional details. Word Bit Position 15 0 SGN Analog Output Data Channel 0 1 SGN Analog Output Data Channel 1 2 SGN Analog Output Data Channel 2 3 SGN Analog Output Data Channel 3 4 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0 • SGN = Sign bit in two’s complement format. • UU = Unlatch under-range (or low-clamp exceeded) alarm. • UO = Unlatch over-range (or high-clamp exceeded) alarm. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 18 Compact 1769-OF4VI Isolated Analog Output Module Input Data File Word For each module, slot x, input data file words 2…5 contain the state of the module’s output data (output data echo) file words 0…3. During normal operation, these input words represent the analog values that the outputs are directed to by the control program. Bit Position 15 14 13 12 11 10 9 8 7 6 5 4 0 1 H3 U3 O3 H2 U2 O2 H1 2 Channel 0 Data Value 3 Channel 1 Data Value 4 Channel 2 Data Value 5 Channel 3 Data Value U1 O1 3 2 1 0 S3 S2 S1 S0 H0 U0 O0 • S = General status (over-range, under-range, or low/high clamp exceeded). • H = Output held bit. • U = Under-range (or low-clamp exceeded) alarm. • O = Over-range (or high-clamp exceeded) alarm. IMPORTANT The output module input data file reflects the analog output data echo of the module, not necessarily the electrical state of the output terminals. It does not reflect shorted or open outputs. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 19 Configuration Data File The manipulation of the bits from this file is normally done with programming software (for example, RSLogix 500 software or RSNetworx for DeviceNet software) during initial configuration of the system. In that case, graphical screens are provided by the programmer to simplify configuration. However, some systems, like the 1769-ADN DeviceNet Adapter, also allow the bits to be altered as part of the control program, using communication rungs. In that case, it is necessary to understand the bit arrangement. The channel configuration words, the first two words of each eight word group, are described on page 20. Refer to your module user manual for additional details. Word Description Word Description 0 Channel 0 Configuration Word 0 16 Channel 2 Configuration Word 0 1 Channel 0 Configuration Word 1 17 Channel 2 Configuration Word 1 2 Channel 0 Fault Value Word 18 Channel 2 Fault Value Word 3 Channel 0 Program Idle Mode Word 19 Channel 2 Program Idle Mode Word 4 Channel 0 Low Clamp 20 Channel 2 Low Clamp 5 Channel 0 High Clamp 21 Channel 2 High Clamp 6 Channel 0 Ramp Rate 22 Channel 2 Ramp Rate 7 Channel 0 Spare 23 Channel 2 Spare 8 Channel 1 Configuration Word 0 24 Channel 3 Configuration Word 0 9 Channel 1 Configuration Word 1 25 Channel 3 Configuration Word 1 10 Channel 1 Fault Value Word 26 Channel 3 Fault Value Word 11 Channel 1 Program Idle Mode Word 27 Channel 3 Program Idle Mode Word 12 Channel 1 Low Clamp 28 Channel 3 Low Clamp 13 Channel 1 High Clamp 29 Channel 3 High Clamp 14 Channel 1 Ramp Rate 30 Channel 3 Ramp Rate 15 Channel 1 Spare 31 Channel 3 Spare Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 20 Compact 1769-OF4VI Isolated Analog Output Module Channel Configuration Words Word/Bit 15 Word 0 E Word 1 14 13 12 11 10 9 8 Reserved Reserved 7 6 5 4 3 2 SIU SIO LA ER FM PM HI Output Data Format Select Reserved 0 1 PFE Output Type/Range • E = Channel Enable: (0 = Disabled, 1 = output Enabled, process changes) • Reserved = Set to zero • SIU = System interrupt low clamp, under-range alarms: (0 = Disabled, 1 = Enabled) • SIO = System interrupt high clamp, over-range alarms: (0 = Disabled, 1 = Enabled) • LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled, 1 = Enabled) • ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by fault states.) • FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value) • PM = Program mode: (0 = Hold Last State, 1 = User Defined Value) • HI = Hold for initialization: (0 = Disabled, 1 = Enabled) • PFE = Program/idle to fault enable: (0 = Disabled, 1 Enabled) The first two words of each eight word group in the configuration file allow you to change the parameters of each channel independently. For example, words 8 and 9 correspond to channel 1 while words 16 and 17 correspond to channel 3. Define Indicate this These bit settings 15 14 13 12 11 10 9 8 7 6 Program Program (Idle) (Idle) to Fault Mode Data Enable Applied(1) Fault Mode Data Applied(1) Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 5 4 3 2 1 0 0 1 Compact 1769-OF4VI Isolated Analog Output Module 21 Define Indicate this These bit settings 15 14 13 12 11 10 9 8 7 6 5 4 3 2 Hold for Disabled Initialization Enabled Program (Idle) Mode Fault Mode Enable Ramping System Interrupt High Clamp System Interrupt Low Clamp Enable Channel (1) 1 0 0 1 Hold Last State(1) 0 User-Defined Value(1) 1 Hold Last State(1) 0 User-Defined Fault Value(1) 1 Disabled 0 Enabled 1 Disabled 0 Enabled(1) 1 Disabled 0 Enabled(1) 1 Disabled 0 Enabled 1 These functions are not supported by all controllers (for example, MicroLogix 1500) using any configuration method. Refer to your controller manual for details. Define Indicate this These bit settings 15 14 13 12 11 10 9 Output Range Select Output Data Select 2 1 0 -10 …+10V DC 8 0 0 0 0…5V DC 0 0 1 0…10V DC 0 1 0 1…5V DC 0 1 1 Raw/Proportional Counts 0 0 0 Engineering Units 0 0 1 Scaled for PID 0 1 0 Percent Range 0 1 1 7 6 5 4 3 Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 22 Compact 1769-OF4VI Isolated Analog Output Module Specifications Specification 1769-OF4VI Dimensions 118 mm (height) x 87 mm (depth) x 35 mm (width) height including mounting tabs is 138 mm 4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in. Approximate Shipping Weight (with carton) 270g (0.6 lbs.) Storage Temperature -40°C to +85°C (-40°F to +185°F) Operating Temperature 0°C to +60°C (32°F to +140°F) Operating Humidity 5% to 95% non-condensing Operating Altitude 2000 meters (6561 feet) Vibration Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak Shock Operating: 30G, 11 ms panel mounted (20G, 11 ms DIN rail mounted) Non-Operating: 40G panel mounted (30G DIN rail mounted) Agency Certification •C-UL certified (under CSA C22.2 No. 142) •UL 508 listed •CE compliant for all applicable directives Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D (ISA 12.12-01, C-UL under CSA C22.2 No. 213) Radiated and Conducted Emissions IEC 61000-6-4 and CISPR 11 Group 1, class A Electrical /EMC: The module has passed testing at the following levels: •ESD Immunity (IEC 61000-4-2) •4 kV contact, 8 kV air, 4 kV indirect •Radiated Immunity (IEC 61000-4-3) •10 V/m, 80 to 1000 MHz, 80% amplitude modulation •Fast Transient Burst (IEC 61000-4-4) •2 kV, 5 kHz •Surge Immunity (IEC 61000-4-5) •1 kV galvanic gun •Conducted Immunity (IEC 61000-4-6) •10V dc, 0.15 to 80 MHz(1) Analog Normal Operating Ranges(2) ± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 23 Specification 1769-OF4VI (2) Full Scale Analog Ranges ± 10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc, 0.5 to 5.25V dc Number of Outputs 4 isolated differential Bus Current Draw (max.) 5V, 165mA 24V, 110mA Heat Dissipation 2.0 Total Watts (all points - 10V dc into 2 k - worst case calculated) Digital Resolution Across Full Range 15 bits plus sign (bipolar) ±10V dc: 15.89 bits, 330 µV/bit 0 to +5V dc: 13.89 bits, 330 µV/bit 0 to +10V dc: 14.89 bits, 330 µV/bit +1 to +5V dc: 13.57 bits, 330 µV/bit Conversion Rate (all channels) max. 120 ms Step Response to 63%(3) <2.9 ms Load Output Current 5 mA max. Load Range Output > 2K Ω Max. Capacitive Load 1 µF Field Calibration None required Overall Accuracy(4) ±0.5% full scale at 25°C (1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz. (2) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog output up to the maximum full scale range. The flag automatically resets when within the normal operating range unless configured to latch. (3) Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until the device is at 63% of full range. (4) Includes offset, gain, drift, non-linearity and repeatability error terms. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 24 Compact 1769-OF4VI Isolated Analog Output Module Specification 1769-OF4VI Accuracy Drift with Temperature ±0.0086% FS per °C Output Ripple(1) range 0 to 50 kHz (referred to output range) ±0.05% Non-linearity (in percent full scale) ±0.05% Repeatability(2) (in percent full scale) ±0.05% Output Error Over Full Temperature Range (0 to 60°C [+32 to +140°F]) ±0.8% Output Impedance <1 Ω Open and Short-Circuit Protection Yes Short-Circuit Current 35 mA typical, 42 mA max. Output Overvoltage Protection Yes Output Response at System Power Up and Power Down Power up: +1.2V dc spike for less than 0.4 ms Power down: 1.2V dc spike for less than 21 ms Rated Working Voltage(3) 30V ac/30V dc Output Group to Bus Isolation 500V ac or 710V dc for 1 minute (qualification test) 30V ac/30V dc working voltage (IEC Class 2 reinforced insulation) Module OK LED On: module has power, has passed internal diagnostics, and is communicating over the bus. Off: Any of the above is not true. Channel Diagnostics Over- or under-range by bit reporting (1) Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature. (2) Repeatability is the ability of the output module to reproduce output readings when the same controller value is applied to it consecutively, under the same conditions and in the same direction. (3) Rated working voltage is the maximum continuous voltage that can be applied at the output terminal, including the output signal and the value that floats above ground potential (for example, 10V dc output signal and 20V dc potential above ground). Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 25 Specification 1769-OF4VI System Power Supply Distance Rating The module may not be more than 8 modules away from the system power supply. Recommended Cable Belden 8761 (shielded) Vendor I.D. Code 1 Product Type Code 10 Product Code 42 Input Words 6 Output Words 5 Configuration Words 32 Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following ATTENTION statement applies to use in hazardous locations. WARNING: EXPLOSION HAZARD • Substitution of components may impair suitability for Class I, Division 2. • When in hazardous locations, turn off power before wiring or replacing modules. • Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. • This product must be installed in an enclosure. • All wiring must comply with N.E.C. article 501-4(b). Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 26 Compact 1769-OF4VI Isolated Analog Output Module Environnements dangereux Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux. AVERTISSEMENT: DANGER D’EXPLOSION La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe 1, Division 2. Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée et que l'environnement est classé non dangereux. Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée ou que l'environnement est classé non dangereux. Ce produit doit être installé dans une armoire. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Compact 1769-OF4VI Isolated Analog Output Module 27 Additional Resources These documents contain additional information concerning related Rockwell Automation products. Resource Description Compact I/O Analog Modules User Manual, publication 1769-UM002 Provides detailed information on installing, programming, and troubleshooting Compact analog I/O modules. MicroLogix 1500 Programmable Controllers User Manual, publication 1764-UM001 Provides a detailed description for installing and using Compact I/O modules with a MicroLogix 1500 programmable controller. 1769-ADN DeviceNet Adapter User Manual, publication 1769-UM001 Provides a detailed description of how to install and use Compact I/O modules with the 1769-ADN DeviceNet Adapter. Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system. Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative. Rockwell Automation Publication 1769-IN076B-EN-P - August 2010 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/. Installation Assistance If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Outside United States Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Compact I/O, CompactLogix, MicroLogix, RSLogix, RSLogix 500, RSNetWorx, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 1769-IN076B-EN-P - August 2010 Supersedes Publication 1769-IN076A-EN-P - July 2005 PN-83820 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">
Advertisement
Key features
- 4 isolated channels
- Flexible output ranges
- High resolution
- Compact size
- Class I, Division 2 certified
Frequently asked questions
The maximum output current for each channel is 5 mA
The minimum load range for each channel is 2K Ω
The maximum capacitive load for each channel is 1 μF
Yes, the module accepts up to a 6.35 mm (0.25 in.) spade lug.
This module is compatible with MicroLogix 1500, but some functions, such as program/idle to fault enable, may not be supported by all configurations. Refer to your controller manual for details.