Allen-Bradley 193 E1 PLUS PTC Thermistor Accessory Module Installation Instructions
The Allen-Bradley 193 E1 PLUS PTC Thermistor Accessory Module is a component designed for motor protection. It helps prevent damage to your motor by monitoring the temperature of the motor winding, and tripping the motor if it exceeds a pre-determined temperature threshold. The unit provides two methods of resetting the motor after a trip: manual and automatic. The module can be easily installed with a side-mount design and features remote reset capabilities.
PDF
Download
Document
Advertisement
Advertisement
1 2 A 3 4 5 6 7 8 Bulletin 193 E1 PLUS PTC Thermistor Accessory Module Application and Installation Présentation du module accessoire de thermistance CTP 193 E1 PLUS - Utilisation et installation Anwendung und Installation des PTC-Thermistor-Zusatzmoduls, Serie 193 E1 PLUS Boletín 193 E1 PLUS Instalación y aplicación de módulo accesorio de PTC termistor Boletim 193 - Aplicação e Instalação do Módulo Acessório de Termistor PTC do E1 PLUS Applicazione e installazione del modulo accessorio per termoresistenza PTC Bollettino 193 E1 PLUS (Cat 193-EPT) ATTENTION: Only personnel familiar with the side mount module and the associated application should install or service the system. Improper installation or servicing may result in property damage or severe personal injury. Follow all applicable national and local codes. This document acts as a guide for typical installation only. ATTENTION : Le module à bornes latérales doit être installé ou mis en service par un technicien agréé. Toute installation ou mise en service incorrecte est susceptible de causer des dommages matériels ou d'importantes lésions corporelles. Respectez tous les modes opératoires locaux et nationaux en vigueur. Ce document fait office de guide pour une installation standard uniquement. ACHTUNG: Das System sollte nur von Mitarbeitern installiert oder gewartet werden, die mit dem seitlich montierten Modul und zugehörigen Anwendungen vertraut sind. Die nicht ordnungsgemäße Installation oder Wartung kann zu Sachschäden und schweren Verletzungen führen. Befolgen Sie sämtliche zutreffenden nationalen und lokalen Regeln. Dieses Dokument soll nur einen Leitfaden für eine typische Installation darstellen. ATENCIÓN: La instalación y el mantenimiento del sistema deben realizarlos únicamente el personal familiarizado con el módulo de montaje lateral y la aplicación asociada. Una instalación o mantenimiento incorrectos pueden causar daños personales o a la propiedad. Cumpla con todos los códigos nacionales y locales aplicables. Este documento es sólo una guía para la instalación típica. ATENÇÃO: Somente os funcionários familiarizados com o módulo de montagem lateral e sua respectiva aplicação deverão fazer a instalação ou manutenção do sistema. A instalação ou manutenção indevida pode resultar em danos às dependências ou em graves lesões pessoais. Cumpra todas as normas nacionais e locais aplicáveis. Este documento serve de guia somente para instalações normais. ATTENZIONE: l'installazione e la manutenzione del sistema vanno effettuate solo da un tecnico che ha dimestichezza con il modulo a montaggio laterale e la relativa applicazione. L'installazione o la manutenzione non appropriate possono causare danni materiali o gravi lesioni personali. Seguire tutte le normative nazionali e locali applicabili. Questo documento rappresenta solo una guida all'installazione tipica. B C ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free from contaminants. (Follow NFPA70E requirements) ATTENTION : Avant le montage et la mise en service, couper l'alimentation secteur pour éviter toute décharge. Prévoir une mise en coffret ou armoire appropriée. Protéger le produit contre les environnements agressifs. ACHTUNG: Vor Installations- oder Servicearbeiten Stromversorgung zur Vermeidung von elektrischen Unfällen trennen. Die Geräte müssen in einem passenden Gehäuse eingebaut und gegen Verschmutzung geschützt werden. ATENCION: Desconéctese de la corriente eléctrica, antes de la instalación o del servicio, a fin de impedir sacudidas eléctricas. Instálelo en una caja apropiada. Manténgalo libre de contaminantes. ATENÇÃO: Para evitar choques, desconectar da corrente elétrica antes de fazer a instalação ou a manutenção. Instalar em caixa apropriada. Manter livre de contaminantes. ATTENZIONE: Per prevenire infortuni, togliere tensione prima dell'installazione o manutenzione. Installare in custodia idonea. Tenere lontano da contaminanti. D ATTENTION: Do not use automatic reset mode in applications where unexpected automatic restart of the motor can cause injury to persons ordamage to equipment. ATTENTION : N’utilisez pas le mode Remise à zéro automatique dans les applications où un redémarrage automatique inattendu du moteur pourrait provoquer des blessures personnelles ou des dégâts matériels. ACHTUNG: Der automatische Rücksetzmodus darf nicht in Anwendungen verwendet werden, in denen der unerwartete Neustart des Motors zuPersonen– oder Sachschäden führen kann. ATENCION: No use el modo de reseteo automático en aplicaciones donde el rearranque repentino del motor pueda causar lesiones personales o dañoal equipo. ATENÇÃO: não utilize o modo de reajuste automático em aplicações nas quais o reinício automático e inesperado do motor possa causar ferimentosàs pessoas ou danos ao equipamento. ATTENZIONE: non usare la modalità di ripristino automatico in applicazioni dove il riavviamento automatico improvviso del motore può provocareinfortuni o danni all’apparecchiatura. contromisure. E F 42053-005-01 (1) Printed in U.S.A. G REFERENCE REVISION AUTHORIZATION 1 1025227 BUL. 193 MCS-E1 PLUS OVERLOAD RELAY PTC THERMISTOR ACCESSORY MODULE INSTALLATION INSTRUCTION SHEET DIMENSIONS APPLY BEFORE SURFACE TREATMENT (DIMENSIONS IN INCHES) TOLERANCES UNLESS OTHERWISE SPECIFIED .XX: N/A .XXX: N/A E - DOC THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC. OR ITS SUBSIDIARIES AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION, INC. H LOCATION: MILWAUKEE, WISCONSIN U.S.A. G. Ushakow CHKD. M. Jutz APPD. G. Lehman DR. ANGLES: 42053 N/A DATE DATE DATE 1-24-07 1-24-07 1-24-07 DWG. SIZE B SHEET 1 OF 6 42053-005 B-vertical.ai 1 2 3 4 5 6 7 8 A ATTENTION: The side mount module contains ESD (electrostatic discharge)-sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, refer to Rockwell Automation publication 8000-4.5.2, "Guarding Against Electrostatic Damage", or any other applicable ESD protection handbook. ATTENTION : Le module à bornes latérales contient des pièces et des assemblages sensibles aux décharges électrostatiques. Des précautions en matière de régulation statique sont à prendre lors de l'installation, de l'essayage, de l'entretien ou de la réparation de cet appareil. Les composants peuvent être endommagés si les procédures de régulation statique ne sont pas suivies. Si vous n'êtes pas familier avec ces procédures, veuillez consulter la publication Rockwell Automation 8000-4.5.2 intitulée " Guarding Against Electrostatic Damage " ou tout autre manuel de protection contre les décharges électrostatiques approprié. ACHTUNG: Das seitlich montierbare Modul enthält Teile und Komponenten, die gegenüber elektrostatischer Entladung empfindlich sind. Bei der Installation, Erprobung, Wartung oder Reparatur dieses Moduls sind entsprechende Vorsichtsmaßnahmen zum Schutz vor elektrostatischer Entladung zu ergreifen. Wenn keine Vorsichtsmaßnahmen zum Schutz vor elektrostatischer Entladung ergriffen werden, können an Teilen Schäden entstehen. Wenn Sie mit den Vorsichtsmaßnahmen zum Schutz vor elektrostatischer Entladung nicht vertraut sind, lesen Sie die Publikation 8000-4.5.2 "Guarding Against Electrostatic Damage" (Schutz vor Schäden durch elektrostatische Entladung) von Rockwell Automation oder einen anderen Leitfaden zu diesem Thema. ATENCIÓN: El módulo de montaje lateral contiene piezas sensibles a descargas electrostáticas (DEE). Deben adoptarse precauciones contra la electricidad estática al momento de instalar, probar, reparar o revisar esta pieza. Si no se siguen apropiadamente los procedimientos de control de descargas electrostáticas pueden producirse daños en los componentes. Si no conoce bien las precauciones contra la electricidad estática, consulte la publicación 8000-4.5.2, "Guarding Against Electrostatic Damage" ("Protección contra daños producidos por la electricidad estática") u otros manuales similares. ATENÇÃO: O módulo do suporte contém partes e montagens sensíveis à descarga eletrostática. São necessárias precauções relacionadas ao controle estático durante a instalação, teste, revisão ou reparo desta montagem. Poderão ocorrer danos ao componente, se os procedimentos para o controle da descarga eletrostática (ESD) não forem seguidos. Caso você não esteja familiarizado com os procedimentos para o controle eletrostático, consulte a publicação 8000-4.5.2, "Guarding Against Electrostatic Damage", da Rockwell Automation ou qualquer outro material relativo à ESD. ATTENZIONE: il modulo laterale contiene parti e componenti sensibili alle scariche elettrostatiche. Durante l'installazione, il collaudo e gli interventi di manutenzione di questo modulo è necessario adottare precauzioni per il controllo dell'energia elettrostatica. La mancata osservanza delle procedure di controllo delle scariche elettrostatiche può causare il danneggiamento dei componenti. Se non si ha familiarità con tali procedure consultare la pubblicazione Rockwell Automation numero 8000-4.5.2, "Guarding Against Electrostatic Damage", o qualsiasi altro manuale per la protezione dalle scariche elettrostatiche. B Rockwell Automation C Rockwell Automation Reset Operation Opération de remise à zéro Zurücksetzungsvorgang Operación de reseteo Operação de reajuste Operazione di ripristino C A Fault Reset Method Mode de remise à zéro des défauts Fehlerzurücksetzungs-Methode Método de restablecimiento de fallo Método de Redefinição de Falhas Metodo di ripristino errore Adjustment Settings Paramètres d'ajustement Einstellungen Configuración Configurações dos ajustes Impostazioni di regolazione D B D A Overload Relay / PTC Reset (SW1) Remise à zéro du relais de surcharge/thermistance CTP (SW1) PTC Trip PTC Short PTC Open Déclenchement de thermistance Thermistance en court-circuit Thermistance ouverte PTC-Auslösung PTC-Kurzsschluss PTC offen Zurücksetzung des Überlastrelais/PTC (SW1) Desconexión de PTC Cortocircuito PTC PTC abierto Restablecer relé de sobrecarga / PTC (SW1) Disparo do PTC Curto-circuito do PTC Circuito aberto do PTC Relé de Sobrecarga / Redefinição do PTC (SW1) Intervento PTC Cortocircuito PTC Circuito PTC aperto Overload Surcharge Überlast Sobrecarga Sobrecarga Sovraccarico Phase Loss Perte de phase Phasenverlust Pérdida de fase Perda de Fase Perdita di fase Ripristino relè termico/PTC (SW1) C C C C Manual Manuelle Manuell Manuale Manual Manuelle Manuell Manuale Manual Manuelle Manuell Manuale Manual Manuelle Manuell Manuale Manual Manuelle Manuell Manuale C C C Automatic Automatique Automatisch Automático Automatico Automatic / Manual Automatique/Manuelle Automatisch/manuell Automático / Manual Automatico / manuale Manual Manuelle Manuell Manuale Manual Manuelle Manuell Manuale B B D A B wird durch den DIP-Schalter 1 bei A außer Kraft gesetzt. Modo de restablecimiento B se anula con el conmutador DIP 1 en A O modo de redefinição B é substituído pela chave DIP 1 em A Il microinterruttore 1 in A ha la precedenza sulla modalità di ripristino B Zurücksetzungsmodus E C Automatic / Manual Automatique/Manuelle Automatisch/manuell Automático / Manual Automatico / manuale A is overridden by DIP switch 1 at Manual Reset mode Manuelle est neutralisé par le commutateur DIP 1 en Manuell Le mode de remise à zéro Manuale Manual Manuelle Manuell Manuale With supply voltage removed from the module, reset configuration is controlled by adjustment settings at Après avoir coupé l'alimentation du module, vous pouvez utiliser les paramètres en B B pour définir la configuration de la remise à zéro. Wenn die Stromversorgung vom Modul getrennt ist, wird die Zurücksetzungskonfiguration durch Einstellung bei B gesteuert. Con la tensión de suministro eliminada del módulo, la configuración de restablecimiento está controlada por la configuración de ajuste de Com a tensão de alimentação removida do módulo, a configuração de redefinição é controlada pelas configurações de ajuste em B B In assenza di tensione di alimentazione del modulo, la configurazione di ripristino viene controllata dalle impostazioni di regolazione in B F (2) G REFERENCE REVISION AUTHORIZATION 1 1025227 BUL. 193 MCS-E1 PLUS OVERLOAD RELAY PTC THERMISTOR ACCESSORY MODULE INSTALLATION INSTRUCTION SHEET DIMENSIONS APPLY BEFORE SURFACE TREATMENT (DIMENSIONS IN INCHES) TOLERANCES UNLESS OTHERWISE SPECIFIED .XX: N/A .XXX: N/A E - DOC THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC. OR ITS SUBSIDIARIES AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION, INC. H LOCATION: MILWAUKEE, WISCONSIN U.S.A. ----------CHKD. ----------APPD. ----------DR. ANGLES: 42053 N/A DATE DATE DATE ------------------------------- DWG. SIZE B SHEET 2 OF 6 42053-005 B-vertical.ai 1 2 3 4 5 6 7 8 A Features Caractéristiques Leistungsmerkmale Características Recursos Caratteristiche ATTENTION: Do not apply external voltage to R1, R2, IT1 and IT2. Equipment damage may occur. ATTENTION: Aucune tension d'alimentation externe ne doit être appliquée aux bornes R1, R2, IT1 et IT2. Cela pourrait causer des dommages matériels. ACHTUNG: Legen Sie an R1, R2, IT1 und IT2 keine externe Spannung an. Andernfalls können Geräteschäden verursacht werden. ATENCIÓN: No aplique tensión externa a R1, R2, IT1 y IT2. Pueden producirse daños en el equipo. ATENÇÃO: Não aplique tensão externa em R1, R2, IT1 e IT2. Há risco de danos no equipamento. ATTENZIONE: non applicare tensioni esterne a R1, R2, IT1 e IT2. Si potrebbero causare danni all'apparecchiatura. Status LED Voyant d'état Status-LED LED de estado LED de Status LED di stato I O S TU STA 1 2 3 B IT1 IT2 IT1 IT2 Remote Reset and PTC Thermistor Control Terminals Bornes de commande de remise à zéro à distance et de thermistance CTP Steuerungsklemmen für dezentrales Zurücksetzen und PTC-Thermistor Terminales de control de termistor PTC y reconexión remota Terminais de Controle de Termistor PTC e Redefinição Remota Terminali di controllo per la termoresistenza PTC e il ripristino remoto Power Supply Terminals Terminaux d'alimentation électrique Netzklemmen Terminales de alimentación eléctrica Terminais de fornecimento de energia Terminali alimentazione elettrica C D E Adjustment Settings Paramètres d'ajustement Einstellungen Configuración Overload Relay and PTC Reset Mode Mode de remise à zéro du relais de surcharge et de la thermistance CTP Überlastrelais- und PTC-Zurücksetzungsmodus Relé de sobrecarga y modo de restablecimiento de PTC Automatique: 0 SW1 Manuelle: I Protection par thermistance Désactiver: 0 SW2 Activer: I Automatic: 0 SW1 Manual: I SW2 PTC Protection Disable: 0 Enable: I SW3 Overload Relay Type 1 Phase: 0 3 Phase: I Protection anti-brouillage SW3 Monophasé: 0 Triphasé: I Configurações de Ajuste Impostazioni di regolazione Modo de Redefinição de PTC e Relé de Sobrecarga Modalità ripristino PTC e relè termico Automático: 0 SW1 Manual: I SW2 Proteção de PTC Desativar: 0 Ativar: I Tipo de Relé de Sobrecarga Monofásico: 0 Trifásico: I SW3 Automatisch: 0 SW1 Manuell: I SW2 PTC-Schutz Aktivieren: I Deaktivieren: 0 Überlastrelaistyp SW3 3-phasig: I 1-phasig: 0 SW1 Manual: I Automático: 0 SW2 Protección PTC Activar: I Desactivar: 0 Tipo de relé de sobrecarga SW3 1 fase: I 3 fases: I SW1 Manuale: I SW1 SW1 SW2 PTC Protection Disattiva: 0 Attiva: I SW2 SW2 SW3 Tipo di relè termico Monofase: 0 Trifase: I SW3 SW3 Automatico: 0 F (3) G REFERENCE REVISION AUTHORIZATION 1 1025227 BUL. 193 MCS-E1 PLUS OVERLOAD RELAY PTC THERMISTOR ACCESSORY MODULE INSTALLATION INSTRUCTION SHEET DIMENSIONS APPLY BEFORE SURFACE TREATMENT (DIMENSIONS IN INCHES) TOLERANCES UNLESS OTHERWISE SPECIFIED .XX: N/A .XXX: N/A E - DOC THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC. OR ITS SUBSIDIARIES AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION, INC. H LOCATION: MILWAUKEE, WISCONSIN U.S.A. ----------CHKD. ----------APPD. ----------DR. ANGLES: 42053 N/A DATE DATE DATE ------------------------------- DWG. SIZE B SHEET 3 OF 6 42053-005 B-vertical.ai 1 A 2 3 4 PTC Monitoring Ratings Valeurs nominales de contrôle de thermistance PTC-Überwachungsnennwerte Type of Control Unit Maximum Number of Sensors Maximum Cold Resistance of Sensor Chain Trip Resistance Reset Resistance Short Circuit Trip Resistance B 5 6 7 8 Valores de seguimiento PTC Regime de Monitoração de PTC Valori monitoraggio PTC Type of Control Unit Open Circuit Trip Resistance Maximum Voltage at 1T1 / 1T2 (Rptc=4kΩ) Maximum Voltage at 1T1 / 1T2 (Rptc=open) PTC Response Time Mark A 6 1500 Ω 3400 Ω ± 150 Ω 1600 Ω ± 50 Ω 25 Ω ± 10 Ω Mark A > 20,000 Ω < 7.5 Vdc < 30 Vdc 500ms tο 800ms PTC Circuit Function Función de circuito PTC PTC trip delay: The delay between the occurrence of a PTC out-of-range fault and a trip of the E1 Plus varies, but is generally described by one of the following: · 500 ms ± 250 ms, typical; · < 6 seconds, for a PTC out-of-range fault present at power-up of the side mount module. Under no conditions should a PTC trip take longer than 6 seconds. Retardo de desconexión por PTC: El lapso que se produce entre el fallo fuera de rango PTC y la desconexión del E1 Plus es variable, pero suele describirse por alguna de las siguientes condiciones: · 500 ms ± 250 ms, típico; · < 6 segundos, para un fallo fuera de rango PTC presente al encender el módulo de montaje lateral; Bajo ninguna condición el retardo de desconexión por fallo a tierra debe superar los 6 segundos. Status LED: (steady green - module is powered up) The status LED will indicate the module status by flashing a red trip code. The number of flashes followed by a pause identifies the specific trip code as follows: (1) - overload trip (2) - phase loss trip (3) - PTC trip (4) - PTC open circuit (5) - PTC short circuit Fast flash - impending trip PTC Thermistor fault detected and E1 Plus not yet capable of tripping. Steady red - hardware fault Internal hardware fault detected and E1 Plus trip attempted. Recover fault by cycling SMM supply voltage. If this fault is encountered, the user should: a) verify that supply voltage is within limits; b) verify that wiring to the terminals is correct; c) verify that the pins which connect the SMM to the E1 Plus are not damaged or misaligned. LED de estado: (verde fijo - el módulo está encendido) El LED de estado indicará el estado del módulo con un código de desconexión rojo. El número de parpadeos de la luz identifica el código de desconexión de la siguiente manera: (1) - desconexión por sobrecarga (2) - desconexión por pérdida de fase (3) - desconexión por PTC (4) circuito abierto por PTC (5) - cortocircuito por PTC Encendido rápido - desconexión inminente Se ha detectado un fallo de PTC Thermistor y E1 Plus no puede realizar la desconexión. Luz roja fija - error de hardware Se ha detectado un error de hardware interno y E1 Plus ha intentado la desconexión. Recuperar el fallo mediante el ciclado de tensión de suministro SMM Si se produce un fallo, el usuario deberá: a) comprobar que la tensión de suministro se encuentre dentro de los límites; b) comprobar que el cableado de los terminales sea correcto; c) comprobar que las clavijas que conectan el SMM al E1 Plus no estén dañadas o desalineadas. Fonction de protection par thermistance Função do Circuito de PTC Délai de déclenchement de thermistance Le délai entre l'apparition d'un défaut de thermistance hors limites et le déclenchement du relais E1 Plus est variable. En règle générale, il est défini comme suit : · 500 ms ± 250 ms (délai standard) ; · < 6 secondes pour un défaut de thermistance hors limite lors de la mise sous tension du module à bornes latérales. Un déclenchement de thermistance ne doit jamais dépasser 6 secondes. Atraso do disparo de PTC: O atraso entre a ocorrência de uma falha fora da faixa de PTC e um disparo do E1 Plus varia, mas em geral é descrito por uma destas condições: · 500 ms ± 250 ms, normal; · < 6 segundos, para uma falha fora da faixa de PTC ocorrida na ativação do módulo de montagem lateral. Sob hipótese alguma um disparo de PTC deve demorar mais do que 6 segundos. Voyant d'état : vert continu : le module est sous tension. Le voyant d'état indique l'état du module par des clignotements de couleur rouge (code de déclenchement). Le nombre de clignotements suivi d'une pause identifie le code de déclenchement comme suit : (1) - surcharge (2) - perte de phase (3) - thermistance (4) - thermistance ouverte (5) - thermistance en court-circuit Clignotement rapide : déclenchement imminent Une défaillance de la thermistance CPT a été détectée et le relais E1 Plus n'est pas en mesure d'activer le déclenchementchement. Continu rouge : défaut matériel Un défaut matériel interne a été détecté et le relais E1 Plus a lancé une tentative de déclenchement. Il s'agit d'un défaut de récupération détecté à la mise sous tension du module de gestion système. Si ce défaut se produit, l'utilisateur doit : a) vérifier que la tension n'est pas hors limites ; b) vérifier le bon câblage des bornes ; c) vérifier que les broches qui relient le module de gestion système au relais E1 Plus ne sont pas endommagées ou mal alignées. LED de Status: (verde constante - o módulo está ativado) Este LED indicará o status do módulo piscando um código de disparo vermelho. O número de vezes que o LED piscar seguido de uma pausa identifica o código de disparo específico da seguinte maneira: (1) - disparo de sobrecarga (2) - disparo de perda de fase (3) - disparo de PTC (4) - Circuito aberto do PTC (5) - Curto-circuito do PTC Piscada rápida - disparo iminente Falha detectada no Termistor PTC, e E1 Plus ainda incapaz de disparar. Vermelho constante - falha de hardware Falha de hardware interna detectada, e tentativa de disparo do E1 Plus. Repare a falha desligando e ligando a tensão de alimentação de SMM. Se essa falha ocorrer, o usuário deverá: a) verificar se a tensão de alimentação está dentro dos limites; b) verificar se a fiação até os terminais está correta; c) verificar se os pinos que conectam o SMM ao E1 Plus não estão danificados ou mal alinhados. PTC-Stromkreisfunktion Funzione del circuito PTC PTC-Auslösungsverzögerung: Die Verzögerung zwischen dem Auftreten eines Fehlers durch Überschreiten des zulässigen PTCBereichs und der Auslösung des E1 Plus variiert, kann jedoch grundsätzlich durch die folgenden Parameter beschrieben werden: · 500 ms ± 250 ms typisch; · < 6 s bei einem Überschreiten des zulässigen PTC-Bereichs während des Einschaltens des seitlich montierten Moduls. Unter keinen Bedingungen sollte eine PTC-Auslösung länger als 6 Sekunden dauern. Ritardo di intervento PTC: Il ritardo di intervento del relè E1 Plus a seguito del rilevamento di un valore PTC fuori intervallo è variabile, ma può essere in genere descritto in uno dei modi seguenti: · 500 ms ± 250 ms, tipico; · < 6 secondi, per un valore PTC fuori intervallo rilevato all'accensione del modulo a montaggio laterale. In nessun caso l'intervento PTC dovrebbe essere ritardato per più di 6 secondi. C D E LED di stato: (verde fisso - il modulo è acceso) Il LED di stato indica lo stato del modulo tramite un codice di intervento a luce rossa lampeggiante. Il codice di intervento specifico è identificato dal numero di lampeggi seguiti da una pausa. (1) - intervento da sovraccarico (2) - intervento da perdita di fase (3) - Intervento PTC (4) - Circuito PTC aperto (5) - Cortocircuito PTC Lampeggio rapido - intervento imminente Rilevato un guasto della termoresistenza PTC, il rel EE1 Plus non Eancora in grado di intervenire. Luce rossa fissa - guasto hardware Rilevato un guasto hardware interno, tentato intervento del relè E1 Plus. Ripristinare il funzionamento spegnendo e riaccendendo il modulo. In caso di guasto, verificare quanto segue: a) la tensione di alimentazione deve rientrare nei limiti previsti; b) il cablaggio dei terminali è corretto; c) i piedini del connettore tra il modulo e il relè non sono danneggiati o disallineati. Status-LED: (durchgängig grün - Modul ist eingeschaltet) Die Status-LED zeigt den Modulstatus durch rotes Blinken nach einem Auslösungscode an. Durch die Anzahl der Leuchtphasen, gefolgt von einer Pause, kann der genaue Auslösungscode wie folgt ermittelt werden: (1) - Überlastauslösung (2) - Phasenverlustauslösung (3) - PTC-Auslösung (4) - offener PTCStromkreis (5) - PTC-Kurzschluss Schnelles Blinken - Auslösung steht bevor Fehler am PTC-Thermistor wurde erkannt, und E1 Plus kann noch nicht ausgelöst werden. Durchgängig rot - Hardwarefehler Ein interner Hardwarefehler wurde erkannt, und es wurde versucht, das E1 Plus auszulösen. Beseitigen Sie diesen Fehler, indem Sie die SMM-Versorgungsspannung trennen und wieder zuschalten. Wenn dieser Fehler auftritt, sollte der Anwender folgendermaßen vorgehen: a) sicherstellen, dass die Versorgungsspannung im zulässigen Bereich liegt; b) sicherstellen, dass die Klemmen ordnungsgemäß verdrahtet sind; c) sicherstellen, dass die Anschlussstifte der Verbindung zwischen SMM und E1 Plus nicht beschädigt oder falsch ausgerichtet sind. F (4) G REFERENCE REVISION AUTHORIZATION 1 1025227 BUL. 193 MCS-E1 PLUS OVERLOAD RELAY PTC THERMISTOR ACCESSORY MODULE INSTALLATION INSTRUCTION SHEET DIMENSIONS APPLY BEFORE SURFACE TREATMENT (DIMENSIONS IN INCHES) TOLERANCES UNLESS OTHERWISE SPECIFIED .XX: N/A .XXX: N/A E - DOC THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC. OR ITS SUBSIDIARIES AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION, INC. H LOCATION: MILWAUKEE, WISCONSIN U.S.A. ----------CHKD. ----------APPD. ----------DR. ANGLES: 42053 N/A DATE DATE DATE ------------------------------- DWG. SIZE B SHEET 4 OF 6 42053-005 B-vertical.ai 1 2 3 4 5 6 7 8 A B Installation Instalación C Instalação Installazione 1 2 #2 Driver 1 0.7 - 1.1 N.m (6 - 10 lb-in) D 2 0.6mm X 3.5mm Blade (.02 in X .14 in Blade) 7mm (.28 in) 0.5 - 0.6 N.m (4.4 - 5.3 lb-in) Wiring Diagram Schéma de câblage E Verkabelungsschema Diagrama de cableado Diagrama de circuito Schema elettrico Recommened use of twisted pair and shielded cable for PTC thermistor, #24 AWG Minimum L'utilisation d'une paire torsadée et d'un câble blindé est recommandée pour la thermistance CTP (diamètre minimum : 24 AWG/0,5 mm). Für den PTC-Thermistor wird die Verwendung von abgeschirmten, verdrillten Doppelleitungen, mindestens AWG 24, empfohlen. Se recomienda el uso de un cable de par trenzado y blindado para el termistor R1 PTC, mínimo #24 AWG. Recomendamos o uso de no mínimo um cabo em par trançado para redefinição remota e o termistor PTC AWG nº 24. R2 Diametro minimo consigliato per il doppino intrecciato e il cavo schermato della IT1 termoresistenza PTC: n. 24 AWG 1X 24.....12 AWG 2X 24.....16 AWG 1X 0.2......2.5 mm2 2X 0.25.......1 mm2 IT1 IT2 R1 R2 Wire Size and Torque Specifications 5 lb-in IT2 0.2.....2.5 mm2 2X 0.2........1 mm2 A2 1X A2 A1 0.55 N.m A1 (24 - 240V, 47 - 63HZ or DC) 0.55 N.m F (5) G REFERENCE REVISION AUTHORIZATION 1 1025227 BUL. 193 MCS-E1 PLUS OVERLOAD RELAY PTC THERMISTOR ACCESSORY MODULE INSTALLATION INSTRUCTION SHEET DIMENSIONS APPLY BEFORE SURFACE TREATMENT (DIMENSIONS IN INCHES) TOLERANCES UNLESS OTHERWISE SPECIFIED .XX: N/A .XXX: N/A E - DOC THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC. OR ITS SUBSIDIARIES AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION, INC. H LOCATION: MILWAUKEE, WISCONSIN U.S.A. ----------CHKD. ----------APPD. ----------DR. ANGLES: 42053 N/A DATE DATE DATE ------------------------------- DWG. SIZE B SHEET 5 OF 6 42053-005 B-vertical.ai 1 2 3 A 4 J 5 6 H 7 8 A F G E K B D B L C CONTACTOR CAT. NO. 100-C09, -C12, -C16, -C23 193*-EE_B 100-C30, -C37 C 193*-EE_D 100-C43 100-C60, -C72, -C85 Accessory Accessoire mm (in) A 63 (2.48) B 148 (5.83) C 85.2 (3.35) D 24.5 (.96) E 13.9 (.55) F 35 (1.38) G 60 (2.36) H 86.5 (3.40) J 2 (.08) K 4.5 (.17) L 18 (.71) mm (in) 63 (2.48) 148 (5.83) 101.2 (3.98) 24.5 (.96) 13.9 (.55) 35 (1.38) 60 (2.36) 104 (4.09) 2 (.08) 4.5 (.17) 18 (.71) mm (in) 67.5 (2.66) 148 (5.83) 101.2 (3.98) 24.5 (.96) 18.4 (.74) 45 (1.77) 60 (2.36) 104 (4.09) 2 (.08) 4.5 (.17) 18 (.71) mm (in) 90 (3.54) 191.6 (7.54) 120.4 (4.74) 29 (1.14) 23.8 (.94) 55 (2.16) 100 (3.94) 126 (4.94) 2 (.08) 5.4 (.21) 18 (.71) E1 PLUS CAT. NO. Zubehör Accesorio 193*-EE_E Acessório Accessori Cat 193-EMC Adjustment Cover Couvercle de réglage Abdeckung für Einstellelemente Cubierta de los ajustes Tampa do ajuste Copertura pannello di regolazione D Specifications Caractéristiques Spezifikationen Características Rated Insulation Voltage (Ui) Tension d'isolation nominale (Ui) Nennprüfspannung (Ui) Tensión nominal de aislamiento (Ui) Voltaggio di isolamento nominale (Ui) Voltagem Nominal de Isolamento (Ui) (Ui) E Specifiche Especificações 300V Power at Rated Operating Voltage Puissance à la tension nominale de service Leistung bei Nennbetriebsspannung Alimentación en tensión nominal de trabajo Alimentação na voltagem nominal de operação Corrente alla tensione nominale di esercizio (Ui) 24 VAC 120 VAC 240 VAC Rated Operating Voltage (Ue) Tension d'emploi assignée (Ue) Nennbetriebsspannung (Ue) Tensión nominal de trabajo (Ue) Voltaggio di isolamento di esercizio (Ue) Voltagem Nominal de Operação (Ue) (Ue) (Ue) 0.8 W 0.8 W 1.0 W 2.5 kV Rated Impulse Withstand Voltage (U imp) Tension de tenue aux ondes de choc (U imp) Nennimpulsspannungsfestigkeit (U imp) Tensión nominal no disruptiva de impulso (U imp) Voltagem (U imp) nominal resistente ao impulso Tensione nominale di tenuta a impulso (U imp) (U imp) (U imp) 24 - 240 VAC, 50/60 Hz 24 - 240 VDC 42053-005-01 (1) F Printed in U.S.A. GE 1 PA GE PA -01 1 G TWO SIDES PRINTED BODY STOCK WHITE BODY INK BLACK 4-1/4" W x 2-3/4" H 25-1/2" W x 11" H GE 11 PART CHG. NO. CHAR. FLAT MATERIAL 1 1025227 BUL. 193 MCS-E1 PLUS OVERLOAD RELAY PTC THERMISTOR ACCESSORY MODULE INSTALLATION INSTRUCTION SHEET DIMENSIONS APPLY BEFORE SURFACE TREATMENT (DIMENSIONS IN INCHES) TOLERANCES UNLESS OTHERWISE SPECIFIED .XX: N/A .XXX: N/A PA GE 5 GE 4 PA 3 " /2" 8-1 8-1 /2" /2" 8-1 SIZE REFERENCE REVISION AUTHORIZATION FOLD 2 PA GE PA 6 E - DOC THIS DRAWING IS THE PROPERTY OF ROCKWELL AUTOMATION, INC. OR ITS SUBSIDIARIES AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING BY ROCKWELL AUTOMATION, INC. H LOCATION: MILWAUKEE, WISCONSIN U.S.A. ----------CHKD. ----------APPD. ----------DR. ANGLES: 42053 N/A DATE DATE DATE ------------------------------- DWG. SIZE B SHEET 6 OF 6 42053-005 B-vertical.ai ">
Advertisement
Key features
- Motor protection
- PTC thermistor monitoring
- Remote reset
- Manual and automatic reset
- Side-mount design
Frequently asked questions
The module monitors the temperature of the motor winding using a PTC thermistor. If the temperature exceeds a pre-determined threshold, the module will trip the motor to prevent damage.
The module offers both manual and automatic reset options. The reset method can be configured using the DIP switches on the module.
The maximum number of sensors that can be connected depends on the type of control unit. Refer to the table in the manual for specific details.