Advertisement
Advertisement
ICS Regent ® PD-6015 DC Digital Output Module 24 VDC (T3441A) Issue 1, March, 06 The DC digital output module provides control of 16 user output loads. One type of module is available to interface to outputs powered from a nominal 24 VDC field power supply. Each module's triplicated I/O Safetybus interface ensures that no Regent system failure can incorrectly apply power to an output, and that no failure in the module can affect the operation of the Regent system or other I/O modules in the system. Features · Sixteen output circuits, configured as two isolated groups of eight circuits each. · Hot-replaceable. · Automatic self-testing of triplicated I/O Safetybus circuits and many simplex logic circuits. · 2 amp output circuits. · Individual front panel indicators on each module show active/fault, shutdown, blown fuse, and output on/off status (field side). · 2500 volt minimum electrical isolation between field and logic circuits. · TÜV certified, Risk Class 5, non-interfering. Industrial Control Services 1 DC Digital Output Module (T3441A) Module Operation A block diagram of a typical 24 VDC digital output module is shown in Figure 1. The processor modules send triplicated write data commands to the output module over the I/O Safetybus. The processors’ addressing data and data write commands are voted by the module (preventing I/O Safetybus failures upstream from the module from affecting module operation). The voted result is then passed to the I/O bus interface logic. Figure 1. Block Diagram of 24 VDC Digital Output Module. The voted output data from the I/O bus interface logic is then used to drive the output circuits. Power MOSFETs are used on the outputs to convert the logic level output drive signals to switch 24 VDC power to load devices. These output circuits provide a very low on state voltage drop and low off state leakage. 2 Industrial Control Services (T3441A) DC Digital Output Module When the output is logically turned on, the field device is energized, and when the output is logically turned off, the field device is de-energized. Optical isolation between the module’s logic and field circuits provides logic-to-field isolation — protecting the output module from field signal over voltages, transients, and other electrical disturbances. It also provides a safety barrier between the primary field voltages and user accessible circuits. Each output is individually fused to protect the circuits from short circuit conditions in output wiring and field devices. Testing and Diagnostics Each module’s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module. Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error. Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly. Fuses are continually checked for continuity. Field power must be connected to the output module in order for it to detect a blown fuse. Front Panel Indicators The 24 VDC digital output module is shown in Figure 2. The front panel contains active and fault status indicators, a shutdown indicator, blown fuse indicators (one per output group) and an output status indicator for each output circuit. PD-6015 Mar-06 3 DC Digital Output Module (T3441A) Active and Fault Status Indicators These green and red LEDs indicate the overall health of the module. During normal operation, the green ACTIVE indicator flashes at the controller’s scan rate. If a module fault is detected the red FAULT indicator turns on and the green ACTIVE indicator turns off. Shutdown Indicator Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O unit is set to shutdown, the red SHUTDOWN indicator will turn on when communications with the controller are lost. If the I/O unit is set to hold, the SHUTDOWN indicator will always be off (see page 8, Fault Mode Jumper). Note: When the module is installed in the I/O chassis or when logic power (from the I/O power supply modules) is first applied to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode. Output Status Indicators The output status indicators are yellow LEDs, located on the field side of the output. There are 16 output status indicators, — one for each output. These indicators are lit when the output FET is energized to turn on the load. Blown Fuse Indicators The red BLOWN FUSE indicators turn on when one of the fuses in the corresponding output group opens. A blown fuse will also cause the module’s FAULT indicator to turn on. Field power must be connected to the module for it to detect a blown fuse. Refer to Maintenance, page 12, for fuse replacement instructions. 4 Industrial Control Services (T3441A) DC Digital Output Module Figure 2. 24 VDC Digital Output Module. PD-6015 Mar-06 5 DC Digital Output Module (T3441A) Application Simplex Configuration Digital output modules provide a suitable interface to noncritical output devices. These non-critical devices typically include status alarms or other field devices that are not used for primary safety shutdown purposes. Although much of the circuitry on the digital output module is automatically tested, some logic circuits and the field-side output switch are simplex and non-tested. This simplex configuration is illustrated in Figure 3. For safety-critical outputs requiring fail-safe or fault tolerant output configurations, Guarded digital output modules should be used. Figure 3. Simplex Digital Output Configuration. Field Wiring Field wiring terminal blocks on the I/O chassis are used to connect power sources and loads to the module. The terminal blocks are located directly above and below the slot where the module is installed. Each terminal block consists of ten #6 wire clamp screw terminals capable of holding two 12 AWG wires. Each module has separate 24 VDC power terminals for each output group (group 1: channels 1-8, group 2: channels 9-16). The two groups are electrically isolated from each other (2500 volts minimum). Figure 4 shows the proper field wiring connections for the 24 VDC digital output module. 6 Industrial Control Services (T3441A) DC Digital Output Module Figure 4. Module Wiring. PD-6015 Mar-06 7 DC Digital Output Module (T3441A) Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in the lower left-hand corner of each I/O chassis. The position of the fault mode jumper determines the module's response to system level faults. The fault mode jumper’s position will cause all output modules in the I/O chassis to either shutdown (turn off all outputs) or to hold (hold the last state) after a system level failure occurs. An example of a system level failure is the failure of two processor modules. Keying The I/O chassis can be physically keyed to prevent accidental damage caused by inserting a module into a slot wired for a different module type. Figure 5 illustrates how the slot keys are installed on the I/O chassis slot field wiring connectors. The slot key positions for the DC digital output module are listed in Table 1. Table 1. Slot Key Positions. 8 Module Upper Connector Lower Connector T3441A 10 5 Industrial Control Services (T3441A) DC Digital Output Module Figure 5. Installing Slot Keys. Configuration Each output module is configured using the WINTERPRET I/O Configuration Editor. In the editor you will perform the three steps described below to configure the output module. PD-6015 Mar-06 9 DC Digital Output Module (T3441A) 1) Set the Module Type: Position the cursor on the module slot you wish to define. Choose Set Module Type from the Edit Menu and select the appropriate digital output module from the list. 2) Edit the Module Definition: Choose Edit Module Definition from the Edit Menu. A dialog box will open where you can define the output point definitions. Figure 6. Digital Output Module Definition. 3) Edit each point: Choose Edit from the Module Definition dialog box to define a name and description for each output point. In the Digital Output Point dialog, enter names and values for the configuration fields as described below. Figure 7. Defining a Digital Output Point. 10 Industrial Control Services (T3441A) DC Digital Output Module Name Also called the tag name, this is the name used in the application program to reference the output point. The name can be up to 12 characters long. Description This 40-character field provides a place to describe the output point definition. The description is used to help document your system (it does not affect application program operation). Comm Protect Marking the Comm Protect check box protects the point from changes by communications functions such as data write, forcing, and load initial value when Comm Protect is enabled. Initial Value The initial value for the output is loaded to the Regent when you load the I/O configuration and also when you load the application program that controls the output. Final Value The final value for the output is loaded to the Regent when the application program that controls the output is deleted. Unless special circumstances exist, you should always enter zero, so that the output is turned off when you delete the application program that controls it. Output Module Definition In addition to configuring output point definitions, you can configure an output module definition to represent the combined state of all sixteen output points. The module definition represents the 16 output point definitions as signed, 16-bit integers. In this format, output point 1 is the least significant bit (LSB) and output point 16 is the most significant bit (MSB). Programming Outputs are controlled by writing application programs that solve for output values. For example, placing an output tag name on a coil in ladder logic will cause the output to turn on when there is power flow to the coil in the ladder logic rung. You can also reference the logic state of the output in your PD-6015 Mar-06 11 DC Digital Output Module (T3441A) control logic by using a contact element (or similar element) with the output point name. Maintenance No periodic maintenance or calibration is required for this module. Fuses for each output are located within the module. To replace a blown fuse the output module must be removed from the I/O chassis and opened. To open the output module, remove four screws from the side of the module’s clamshell. Remove the blown fuse from its retaining clips (on the circuit board) and replace it. To prevent damage to the module, replacement fuses must be of the same rating and type (see Specifications, below). To prevent electrostatic damage to sensitive module circuits, maintenance personnel should always use the proper antistatic work areas and grounding straps when handling or working with circuit boards. Safety Considerations The DC digital output module is TÜV certified as noninterfering, and can be used in a safety system for simplex non-safety critical outputs. For safety critical outputs, guarded output modules should be used (model T3461A, T3481 or T3485 are recommended). Specifications 12 Safetybus Power 0.8 load units Number of Outputs 16 circuits divided into two groups of 8 circuits each Voltage Range 18 to 30 VDC Load Current 2 amps maximum per output 0° to 60° C Industrial Control Services (T3441A) DC Digital Output Module Minimum Load 0 mA On State Drop 0.5 volts maximum @ 2 amps Surge Current 15 amps, 20 msec Output Leakage 1 mA maximum Fusing One 3 A, 250 V, fast-acting (3AG) per output, located inside module Turn-On Delay 1.0 msec, maximum Turn-Off Delay 1.0 msec, maximum Heat Dissipation 16 Watts, 54 BTUs/hour Over voltage Protection 45 VDC, continuous Isolation 2500 volts minimum (field wiring to control logic) 2500 volts minimum (output group 1-8 to output group 916) Operating Temperature 0° to 60° C (32° to 140° F) Storage Temperature -40° to 85° C (-40° to 185° F) Operating Humidity 0 to 95% relative humidity, non-condensing Vibration 10 to 55 Hz: ±0.15mm Shock Operating: 15 g, ½ sine wave, 11 msec Electromagnetic Interference • • PD-6015 Mar-06 IEC 801 Part 2 - Electrostatic Discharges IEC 801 Part 3 - Radiated Electromagnetic Fields Level 3: Contact discharge of 6 kV Level 3: 10 V/M, 27 MHz 500 MHz 13 DC Digital Output Module (T3441A) Safety Certified to DIN V VDE 0801 (non-interfering) and designed to meet UL 508 and CSA 22.2, No. 142-M1981 Dimensions Height: Width: Depth: Weight 14 12.6" (320 mm) 1.27" (32 mm) 10.12" (257 mm) 3.5 lbs (1.6 kg) Industrial Control Services ">
Advertisement