ICS Triplex ICS Regent+Plus DC Digital Input Modules 24VDC, 48VDC and 120VDC Reference Manual
ICS Triplex ICS Regent+Plus DC Digital Input Modules 24VDC, 48VDC and 120VDC are designed for input sensing for 16 field input switches. They come in three types for interfacing with inputs powered by 24, 48, or 120 VDC field power supplies. Each module's triplicated I/O Safetybus interface ensures system reliability and fault tolerance. Features include hot-replaceability, self-testing, front panel indicators, and robust isolation.
PDF
Download
Document
Advertisement
Advertisement
ICS Regent+Plus ® PD-7011 DC Digital Input Modules 24 VDC, 48 VDC and 120 VDC (T7401, T7402 and T7408) Issue 1, March, 06 DC digital input modules provide input sensing for 16 field input switches. Three types of modules are available for interfacing to inputs powered from 24, 48, or 120 VDC field power supplies. Each module's triplicated I/O Safetybus interface ensures that no failure in the module can affect the operation of the Regent system or other I/O modules in the system. Extensive fault detection and annunciation of critical redundant circuits help prevent the controllers from receiving erroneous data from a faulty input module. Features · Sixteen input circuits, configured as two isolated groups of eight circuits each. · Fault tolerant operation when connected in parallel with redundant modules of the same type. · Hot-replaceable. · Automatic self-testing of triplicated I/O Safetybus circuits and many simplex logic circuits. · Individual front panel indicators on each module show active and fault status and logic-side input on/off status. · 2500 volt minimum electrical isolation between field and logic circuits. · TÜV certified, Risk Class 5. Three DC digital input modules can be connected in parallel to obtain fault tolerant input sensing. In this triple module configuration, a failed module can be removed and replaced without interrupting the input signals. Industrial Control Services 1 DC Digital Input Modules (T7401, 02, and 08) Module Operation A block diagram of a typical DC digital input module is shown in Figure 1. Optical isolation between field wiring and the modules’ logic circuitry provides field-to-logic isolation — protecting the modules’ logic circuits from field signal over-voltages, transients, and other electrical disturbances. It also provides a safety barrier between the primary field voltages and user accessible circuits. Figure 1. Block Diagram of DC Digital Input Module. When the field switch is closed, the input to the module is on. When the field switch opens, the input to the module turns off. Data from the logic side of the optical isolators are bused to the I/O bus interface logic. The processor modules send triplicated read data requests to the input module over the I/O Safetybus. The processors’ addressing data and data read requests are voted by the 2 Industrial Control Services (T7401, 02, and 08) DC Digital Input Modules module (preventing I/O Safetybus failures upstream from the module from affecting its ability to be read). The voted result is then passed to the I/O bus interface logic. After receiving the voted data read request, the I/O bus interface logic sends its input data to the module’s three bus drivers. Each of the three bus drivers is independently powered and controlled by the I/O transceiver modules— preventing failures in a single driver from propagating to the other two busses. The bus drivers transmit the data across the backplane I/O Safetybus to the I/O transceivers which, in turn, transmit the data to the processors. Testing and Diagnostics Each module’s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module. Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate I/O module errors. Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly. Front Panel Indicators Figure 2 shows the physical features of the DC digital input modules. The front panel of each module contains active and fault status indicators and field signal status indicators for each circuit. PD-7011 Mar-06 3 DC Digital Input Modules (T7401, 02, and 08) Figure 2. DC Digital Input Module. Active and Fault Status Indicators These green and red LEDs indicate the overall health of the module. During normal operation the green ACTIVE indicator flashes at the controller's scan rate. If a module fault is detected the red FAULT indicator turns on and the green indicator turns off. 4 Industrial Control Services (T7401, 02, and 08) DC Digital Input Modules Field Status Indicators Input status indicators are located on the logic-side (after the signal conditioning and isolation). The field status indicators are lit when current is flowing through the input. Application Simplex Configuration Digital input modules provide a suitable interface to noncritical input signals. Although many of the circuits in the digital input modules are automatically tested and annunciated, some logic circuits and all of the field-side sensing circuits are simplex and non-tested. This simplex input configuration is illustrated in Figure 3. Figure 3. Simplex Digital Input Configuration. Fault Tolerant Connection For critical inputs, redundant input modules are used in a 2oo3 or 1oo2 fault tolerant configuration. In these configurations the redundant input modules are connected to single or multiple sensors. If redundant sensors are installed in the field, the redundant modules are connected so that each sensor connects to one of the redundant modules. These configurations are illustrated in Figure 4, showing triple redundant input modules. Each DC digital input module is hot replaceable. In triple redundant input configurations, if a fault occurs on one module, it can be removed and replaced PD-7011 Mar-06 5 DC Digital Input Modules (T7401, 02, and 08) while the system continues to sense the inputs from the remaining two input modules. Figure 4. Fault Tolerant Digital Input Configurations. Field Wiring For field wiring details, refer to PD-7901 - I/O Termination Assembly (ITA). 6 Industrial Control Services (T7401, 02, and 08) DC Digital Input Modules Keying The I/O chassis can be physically keyed to prevent accidental damage caused by inserting a module into a slot wired for a different module type. Figure 5 illustrates how the slot keys are installed on the I/O chassis slot field wiring connectors. The slot key positions for the DC digital input modules are listed in Table 1. Figure 5. Installing Slot Keys. PD-7011 Mar-06 7 DC Digital Input Modules (T7401, 02, and 08) Table 1. Slot Key Positions. Module Upper Connector Lower Connector T7401 4 15 T7402 10 15 T7408 12 15 Configuration Each input module is configured using the WINTERPRET I/O Configuration Editor. In the editor, you will perform the three steps described below to configure the input module. 1) Set the Module Type: Position the cursor on the module slot you wish to define. Choose Set Module Type from the Edit Menu and select the appropriate digital input module from the list. 2) Edit the Module Definition: Choose Edit Module Definition from the Edit Menu. A dialog box will open where you can define the input point definitions. Figure 6. Digital Input Module Definition. 8 Industrial Control Services (T7401, 02, and 08) DC Digital Input Modules 3) Edit each point: Choose Edit from the Module Definition dialog box to define a name and description for each I/O point. In the Digital Input Point dialog, enter a tag name (up to 12 characters) and a description (up to 40 characters). Figure 7. Defining a Digital Input Point. The tag names are used in the application program to represent the input state. In addition, a module tag name can be entered to represent the combined state of all 16 inputs. This module tag name represents the 16 inputs as a signed, 16-bit integer. In this format, input point one is the least significant bit (LSB) and input point 16 is the most significant bit (MSB). Programming Inputs are referenced in the application program through the tag names defined in the I/O Configuration Editor. When current flows through the input (field switch closed) the input is said to be on, or have a value of one. In ladder logic, the on state would produce power flow in a normally open (N.O.) contact. To program fault tolerant configurations using triplicated digital input modules, a voter element can be used as shown in Figure 8. PD-7011 Mar-06 9 DC Digital Input Modules (T7401, 02, and 08) Figure 8. Programming Fault Tolerant Digital Inputs. In this illustration, VOTE_A_NAME, VOTE_B_NAME, and VOTE_C_NAME represent the three digital inputs to be twoout-of-three voted. ERROR_A_NAME, ERROR_B_NAME and ERROR_C_NAME are the error bits for the digital inputs. RESULT_NAME is the result of the voter instruction. The field Msec is the time, in milliseconds, an input can be incorrect before signaling an error. RESET_NAME is the reset bit used to reset the latched error bits. The voter instruction can be used to vote digital input points or entire digital input modules. When voting digital input modules, the tag names VOTE_A_NAME, VOTE_B_NAME, and VOTE_C_NAME would be the names of the digital input modules and RESULT_NAME would be a shared variable register. After voting the modules, a block move instruction should be used to move the contents of the register RESULT_NAME into individual shared variable control relays. Refer to the WINTERPRET Help files for more information about the block move instruction and shared variable definitions. Maintenance No periodic maintenance or calibration is required for the digital input modules. There are no user replaceable parts inside these modules. In safety critical input applications, the inputs should be dynamically transitioned at a period not greater than six months. Safety Considerations The DC voltage digital input modules are TÜV certified as 10 Industrial Control Services (T7401, 02, and 08) DC Digital Input Modules non-interfering and when properly configured are also certified for Risk Class 5 safety critical inputs. Safety critical configurations include 2oo3 and 1oo2 voting methods. In safety critical input applications using a single sensor, it is important that the sensor failure modes be predictable and well understood, so there is little probability of a failed sensor not responding to a critical process condition. In such a configuration, it is important that the sensor be tested regularly, either by dynamic process conditions that are verified in the Regent, or by manual intervention testing. Redundant sensors can be used with redundant input modules to eliminate any single points of failure and extend fault tolerance to include the sensors. In all safety critical configurations and applications, the DC voltage digital input modules can be used for de-energized to trip inputs, only if the inputs are dynamically transitioned at a period not greater than six months. For additional safety considerations, please refer to the Safety Considerations section of the Regent User’s Guide. PD-7011 Mar-06 11 DC Digital Input Modules (T7401, 02, and 08) Specifications Safetybus Power 1.15 load units Number of Inputs 16 circuits divided into two groups of eight Voltage Range Turn-On Voltage Turn-Off Voltage Input Current Turn-On Delay minimum maximum T7401 T7402 T7408 14 to 30 VDC 38 to 58 VDC 95 to 150 VDC 12 VDC, min 36 VDC, min 88 VDC, min 4.7 VDC, max 11 VDC, max 28 VDC, max 8.7 mA 4.4 mA 4.4 mA 0.2 msec 0.1 msec 0.05 msec 1.8 msec 1.0 msec 0.4 msec 0.5 msec 0.15 msec 0.05 msec 2.6 msec 1.0 msec 0.5 msec 50 VAC 140 VAC 400 VAC 80 VAC, for 5 sec 220 VAC, for 5 sec 880 VAC, for 5 sec 10 Watts, 9.5 Watts, 18 Watts, 34 BTUs/hour 32 BTUs/hour 60 BTUs/hour Turn-Off Delay minimum maximum Over Voltage Protection continuous: burst: Heat Dissipation Fusing Isolation 12 None, fuse external if required 2500 volts minimum (field wiring to control logic) 2500 volts minimum (input group 1-8 to input group 9-16) Operating Temperature 0° to 60° C (32° to 140° F) Storage Temperature -40° to 85° C (-40° to 185° F) Industrial Control Services (T7401, 02, and 08) DC Digital Input Modules Operating Humidity 0 to 95% relative humidity, non-condensing Vibration 10 to 55 Hz: ±0.15mm Shock Operating: 15 g, ½ sine wave, 11 msec Electromagnetic Interference • • • IEC 801 Part 2 - Electrostatic Discharges IEC 801 Part 3 - Radiated Electromagnetic Fields ANSI/IEEE C37.90 - Surge Withstand Capability Safety Level 3: Contact discharge of 6 kV Level 3: 10 V/M, 27 MHz 500 MHz 2.5 kV damped 1 MHz sine wave 4 kV bi-directional impulse, 10 nsec rise time, fast transient (T3402, T3408 only) Certified to DIN V VDE 0801 for Risk Class 5. Also designed to meet UL 508 and CSA 22.2, No. 142-M1981 Dimensions Height: Width: Depth: Weight PD-7011 Mar-06 12.6" (320 mm) 1.27" (32 mm) 10.12" (257 mm) 3.0 lbs (1.4 kg) 13 ">
Advertisement
Key Features
- Triplicated I/O Safetybus
- Fault tolerant operation
- Hot-replaceable
- Self-testing
- Front panel indicators
- 2500 volt isolation
- TÜV certified, Risk Class 5
Frequently Answers and Questions
How many input circuits does each module have?
Each module has sixteen input circuits, organized as two isolated groups of eight circuits.
What is the purpose of the triplicated I/O Safetybus?
The triplicated I/O Safetybus ensures that no failure in the module affects the Regent system or other I/O modules. It contributes to system reliability and fault tolerance.
Can I replace a module without interrupting the input signals?
Yes, the modules are hot-replaceable, meaning you can remove and replace them without interrupting the input signals in a triple module configuration.