ICS Triplex ICS Regent+Plus Relay Output Modules Reference Manual
ICS Triplex ICS Regent+Plus Relay Output Modules are designed to provide control over user output loads. These modules come in two variations - high and low power, offering dry contact relay closure outputs for switching AC and DC voltages to field loads. Each module features a triplicated I/O Safetybus interface, ensuring that a Regent system failure cannot unintentionally apply power to an output. Additionally, a module failure will not impact the operation of other I/O modules in the system.
PDF
Download
Document
Advertisement
Advertisement
ICS Regent+Plus ® PD-7017 Relay Output Modules Low Power and High Power (T7446L and T7446H) Issue 1, March, 06 Relay output modules provide control of eight user output loads. Two types of relay output modules are available providing dry contact relay closure outputs for switching a variety of AC and DC voltages to field loads. Each module's triplicated I/O Safetybus interface ensures that no Regent system failure can incorrectly apply power to an output and that no failure in the module can affect the operation of the Regent system or other I/O modules in the system. Features · Eight isolated, dry contact relay outputs: four Form-C, and four form-A or Form-B selectable. · Hot replaceable. · Automatic self-testing of triplicated I/O Safetybus circuits and many simplex logic circuits. · High power modules (T7446H) operate up to 250 VAC/125 VDC switching loads rated at 500 VA or 100 Watts. · Low power modules (T7446L) operate up to 125 VAC/VDC switching loads rated at 60 VA or 30 Watts. · Individual front panel indicators on each module show active and fault status, shutdown state, and output status (logic side). · TÜV certified, Risk Class 5, non-interfering. Industrial Control Services 1 Relay Output Modules (T7446L, H) Module Operation A block diagram of a typical relay output module is shown in Figure 1. The processor modules send triplicated write data commands to the output module over the I/O Safetybus. The processors’ addressing data and data write commands are voted by the module (preventing I/O Safetybus failures upstream from the module from affecting module operation). The voted result is then passed to the I/O bus interface logic. Figure 1. Block Diagram of a Relay Output Module. The voted output data from the I/O bus interface logic is then used to drive the output circuits. Logic output drive signals energize the coils of relays mounted on the printed circuit board. Relay contacts provide dry-contact switching of load devices. When the output is logically turned on, the relay coil is energized (closing the N.O. contact), and when the output is 2 Industrial Control Services (T7446L, H) Relay Output Modules logically turned off, the relay coil is de-energized (closing the N.C. contact). The relay provides logic-to-field isolation between the module’s logic and field circuits — protecting the output module from field signal over voltages, transients, and other electrical disturbances. Both types of relay output module use UL 508 approved relays. Testing and Diagnostics Each module’s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module. Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error. Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly. Front Panel Indicators The relay output module is shown in Figure 2. The front panel contains active and fault status indicators, a shutdown indicator, and output status indicators for each output circuit. Active and Fault Status Indicators These green and red LEDs indicate the overall health of the module. During normal operation the green ACTIVE indicator flashes at the controller's scan rate. If a module fault is detected the red FAULT indicator turns on and the green indicator turns off. PD-7017 Mar-06 3 Relay Output Modules (T7446L, H) Shutdown Indicator Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O assembly is set to shutdown, the red SHUTDOWN indicator will turn on when communications with the controller are lost. If the I/O assembly is set to hold, the SHUTDOWN indicator will always be off (see page 11, Fault Mode Jumper). Note: When the module is installed in the I/O chassis or when logic power (from the I/O power supply modules) is first applied to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode. Output Status Indicators The output status indicators are yellow LEDs located on the logic-side (coil) of the relay output. There are eight output status indicators — one for each output. These indicators are lit when the output relay coil is energized, closing the normally open contact. 4 Industrial Control Services (T7446L, H) Relay Output Modules Figure 2. Relay Output Module. PD-7017 Mar-06 5 Relay Output Modules (T7446L, H) Application Simplex Configuration Relay output modules provide a suitable interface to noncritical output devices. These non-critical devices typically include status alarms or other field devices that are not used for primary safety shutdown purposes. Although much of the circuitry on the relay output module is automatically tested, some logic circuits and the field-side output switch are simplex and non-tested. This simplex configuration is illustrated in Figure 3. For safety-critical outputs requiring fail-safe or fault tolerant output configurations, Guarded digital output modules should be used. Figure 3. Simplex Relay Output Configuration. Field Wiring For field wiring details, refer to PD-7901 - I/O Termination Assembly (ITA). 6 Industrial Control Services (T7446L, H) Relay Output Modules Relay Operation The relays used on the T7446L contain SPDT contacts. For the Form-A or Form-B selectable outputs, a jumper in the module is used to select Form-A (N.O.) or Form-B (N.C.) action. The relays used on the T7446H contain two SPST contacts (one normally closed and one normally open). Jumpers within the module are also used to select the relay form. On the Form-C output, there is no guarantee for make-before-break or break-before-make. Output Form Selection Two sets of jumper posts are used to select the output form for the selectable relays. The jumper locations are shown in Figure 4. The jumper post designations are shown in Table 1. Only one jumper shunt can be installed for each relay. The modules are shipped with the jumpers positioned for normally open contact outputs. Table 1. Jumper Designations. PD-7017 Mar-06 Jumper Form Description E110 NO1 Selects normally open for relay 1 E111 NC1 Selects normally closed for relay 1 E120 NO2 Selects normally open for relay 2 E121 NC2 Selects normally closed for relay 2 E170 NO7 Selects normally open for relay 7 E171 NC7 Selects normally closed for relay 7 E180 NO8 Selects normally open for relay 8 E181 NC8 Selects normally closed for relay 8 7 Relay Output Modules (T7446L, H) Figure 4. Jumper Locations. Operating Envelope Figure 5 shows the voltage and current operating envelopes for the T7446L and T7446H. The T7446L relays are initially gold clad and have an initial resistance of 50 mOhm maximum. However, operation at high voltages and currents will remove the gold and the closed resistance will increase substantially. This increased resistance reduces its ability to subsequently switch very low power loads. 8 Industrial Control Services (T7446L, H) Relay Output Modules As with any relay, operating at higher voltages and currents will result in decreased relay life. Figure 6 shows the voltage and current versus service life for the relays. Figure 5. Voltage and Current Operating Envelopes. PD-7017 Mar-06 9 Relay Output Modules (T7446L, H) 100000 10000 1000 100 10 0 0.4 0.8 1.2 1.6 2 2.4 0 0.4 0.8 1.2 1.6 2 2.4 100000 10000 1000 100 10 Figure 6. Voltage and Current vs. Service Life. Relay Protection Each relay circuit must be fused externally to protect the relay and the load. Modules are also fused internally with factory-replaceable fuses to protect the I/O assembly and the module’s printed circuit board. If an inductive load is connected, a suitable snubber must be externally provided. 10 Industrial Control Services (T7446L, H) Relay Output Modules Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in the lower left-hand corner of each I/O chassis. The position of the fault mode jumper determines the module's response to system level faults. The fault mode jumper’s position will cause all output modules in the I/O chassis to either shutdown (turn off all outputs) or to hold (hold the last state) after a system level failure occurs. An example of a system level failure is the failure of two processor modules. Keying The I/O chassis can be physically keyed to prevent accidental damage caused by inserting a module into a slot wired for a different module type. Figure 7 illustrates how the slot keys are installed on the I/O chassis slot field wiring connectors. The slot key positions for the relay output module are listed in Table 2. Both versions of the relay output module use the same slot key positions. Table 2. Slot Key Positions. PD-7017 Mar-06 Module Upper Connector Lower Connector T7446H T7446L 17 2 11 Relay Output Modules (T7446L, H) Figure 7. Installing Slot Keys. Configuration Each output module is configured using the WINTERPRET I/O Configuration Editor. In the editor you will perform the three steps described below to configure the output module. 12 Industrial Control Services (T7446L, H) Relay Output Modules 1) Set the Module Type: Position the cursor on the module slot you wish to define. Choose Set Module Type from the Edit Menu and select the relay output module from the list. 2) Edit the Module Definition: Choose Edit Module Definition from the Edit Menu. A dialog box will open where you can define the output point definitions. Figure 8. Relay Output Module Definition. 3) Edit each point: Choose Edit from the Module Definition dialog box to define a name and description for each output point. In the Digital Output Point dialog, enter names and values for the configuration fields as described below. Figure 9. Defining a Digital Output Point. PD-7017 Mar-06 13 Relay Output Modules (T7446L, H) Name Also called the tag name, this is the name used in the application program to reference the output point. The name can be up to 12 characters long. Description This 40-character field provides a place to describe the output point definition. The description is used to help document your system (it does not affect application program operation). Comm Protect Marking the Comm Protect check box protects the point from changes by communications functions such as data write, forcing, and load initial value when Comm Protect is enabled. Initial Value The initial value for the output is loaded to the Regent when you load the I/O configuration and also when you load the application program that controls the output. Final Value The final value for the output is loaded to the Regent when the application program that controls the output is deleted. Unless special circumstances exist, you should always enter zero, so that the output is turned off when you delete the application program that controls it. Output Module Definition In addition to configuring output point definitions, you can configure an output module definition to represent the combined state of all eight output points. The module definition represents the eight output point definitions as signed, 16-bit integers. In this format, the eight outputs are the least significant bits with output point 1 as the LSB. The eight most significant bits are always zero. Programming Outputs are controlled by writing application programs that solve for output values. For example, placing an output tag name on a coil in ladder logic will cause the output to turn on when there is power flow to the coil in the ladder logic rung. You can also reference the logic state of the output in your 14 Industrial Control Services (T7446L, H) Relay Output Modules control logic by using a contact element (or similar element) with the output point name. Maintenance No periodic maintenance or calibration is required for this module. If a module is to be replaced, verify the replacement module’s relay form configuration matches the original relay output module. Fuses for each output are located inside the module. These fuses are for protection of the I/O chassis connectors and module circuit board only, and are not field-replaceable. Should an internal fuse blow, it indicates that the module is being used for output loads in excess of the safe rating of the module and the I/O chassis. Modules with blown fuses should be returned to ICS for repair or replacement. Safety Considerations The relay output modules are TÜV certified as noninterfering, and can be used in a safety system for simplex non-safety critical outputs. For safety critical outputs, guarded output modules should be used (model T7481, T7484, T7485 or T7488 are recommended). PD-7017 Mar-06 15 Relay Output Modules (T7446L, H) Specifications Safetybus Power 1.0 load units Number of Outputs Eight isolated circuits (four Form-C contacts, four selectable N.O. or N.C. contacts) Voltage Range Load Current Minimum Load Surge Current Over Voltage Protection T7446L 0.1 to 125 VAC/DC 2.0 amps 0.1 VDC/10 mA 20 amps, 16 msec T7446H 5 to 250 VAC 5 to 125 VDC 2.0 amps 5 VDC/10 mA 20 amps, 16 msec 750 VAC, 1 minute 1000 VAC, 1 minute 110 VAC, 0.3 amps 24 VDC, 1 amp 110 VAC, 0.2 amps 24 VDC, 0.3 amp 250 VAC, 2 amps 50 VDC, 2 amps 250 VAC, 2 amps 30 VDC, 2 amps 60 VA, 30 W 20 VA, 10 W 500 VA, 100 W 500 VA, 60 W 50 mOhms, initial 30 mOhms, initial Rated Load resistive inductive Maximum Switching resistive inductive Contact Resistance Breakdown Voltage Logic to field 1000 VAC 750 VAC Chnl to chnl 2500 VAC Turn-On Delay 5 msec Turn-Off Delay 2 msec Heat Dissipation 4.5 Watts, 15 BTUs/hour Same channel 16 Industrial 2000 VAC 1000 VAC 2500 VAC 10 msec 10 msec 4.5 Watts, 15 BTUs/hour Control Services (T7446L, H) Relay Output Modules Fusing (internal) Operating Temperature One 3.5 A, slow blow per output Note: Internal fuses are for protection of the printed circuit board only. Each output should be individually fused outside the module with a fuse rated for the output load. 0° to 60° C (32° to 140° F) Storage Temperature -40° to 85° C (-40° to 185° F) Operating Humidity 0 to 95% relative humidity, non-condensing Vibration 10 to 55 Hz: ±0.15mm Shock Operating: 15 g, ½ sine wave, 11 msec Electromagnetic Interference • • • IEC 801 Part 2 - Electrostatic Discharges IEC 801 Part 3 - Radiated Electromagnetic Fields ANSI/IEEE C37.90 - Surge Withstand Capability Safety Level 3: Contact discharge of 6 kV Level 3: 10 V/M, 27 MHz 500 MHz 1 kV damped 1 MHz sine wave Certified to DIN V VDE 0801 (non-interfering) and designed to meet UL 508 and CSA 22.2, No. 142-M1981 Dimensions Height: Width: Depth: Weight PD-7017 Mar-06 12.6" (320 mm) 1.27" (32 mm) 10.12" (257 mm) 4.0 lbs (1.8 kg) 17 Relay Output Modules (T7446L, H) 18 Industrial Control Services ">
Advertisement
Key Features
- Eight isolated relay outputs
- Hot replaceable
- Triplicated I/O Safetybus interface
- Automatic self-testing
- High power (T7446H) and low power (T7446L) options
- Front panel indicators
- TÜV certified
Frequently Answers and Questions
What is the voltage range for the high power module (T7446H)?
The high power module (T7446H) can operate up to 250 VAC or 125 VDC.
What is the main purpose of the triplicated I/O Safetybus interface?
The triplicated I/O Safetybus interface ensures that a system failure won't incorrectly apply power to an output and that a module failure won't affect the operation of the Regent system.
How do the output status indicators work?
The output status indicators are yellow LEDs that light up when the corresponding relay coil is energized, closing the normally open contact.