Circuit Breaker and Accessory Installation Instructions for
Bulletin 503, 503L, 507, 513, 523, 533, 543, 1233X, 1243, 1273 and 1283
ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing. Install in
suitable enclosure. Keep free from contaminants.
Horsepower Rating
For Combination Starters
Circuit
Breaker
Rating
Circuit
Breaker Field
Kit Catalog
Number
0...1/3 HP @ 200V & 230V
3A
1401-N60
0...1 HP @ 460V & 575V
3A
1401-N60
1/2...1 HP @ 200V & 230V
7A
1401-N61
1-1/2...3 HP @ 460V & 575V
7A
1401-N61
1-1/2...3 HP @ 200V & 230V
15A
1401-N62
5 HP @ 460V & 575V
15A
1401-N62
0...1/3 HP @ 200V & 230V
3A
1401-N60
0...1 HP @ 460V & 575V
3A
1401-N60
1/2...1 HP @ 200V & 230V
7A
1401-N61
1-1/2...3 HP @ 460V & 575V
7A
1401-N61
1-1/2...3 HP @ 200V & 230V
15A
1401-N62
5 HP @ 200V
30A
1401-N63
5...7-1/2 HP @ 460V & 575V
15A
1401-N62
5...7-1/2 HP @ 230V
30A
1401-N63
5...7-1/2 HP @ 200V
50A
1401-N64
10 HP @ 460V & 575V
30A
1401-N63
10 HP @ 200V & 230V
50A
1401-N64
15 HP @ 460V & 575V
30A
1401-N63
15 HP @ 230V
100A
1401-N65
20...25 HP @ 460V & 575V
50A
1401-N64
15...25 HP @ 200V
100A
1401-N65
20...25 HP @ 230V
100A
1401-N65
30 HP @ 575V
50A
1401-N64
30 HP @ 230V
150A
1401-N66
30...50 HP @ 460V
100A
1401-N65
40...50 HP @ 575V
100A
1401-N65
0-4
Mechanism - 150 Amp Frame
Circuit Breaker
150A
1494D-MB150
4-5
Mechanism - 250 Amp Frame
Circuit Breaker
250A
1494D-MB250
5
Mechanism - 400 Amp Frame
Circuit Breaker
400A
1494D-MB400
150A - 400A
1494F-M1
150A - 400A
1494F-P1
150A - 400A
1494F-S1
NEMA
Starter
Size(s)
B
150 Amp Circuit Breaker
0
C
1
250 Amp / 400 Amp Circuit Breaker
D
2
3
L Bracket and Bail Assembly
E
Circuit Breaker and Disconect Handle
0-5
0-5
0-5
F
5-1/2" Painted Metal
Disconnect Handle
5-1/2" Molded
Disconnect Handle
5-1/2" Stainless Steel
Disconnect Handle
G
REFERENCE
REVISION
AUTHORIZATION
1
155-01-1
2
1009161
DIMENSIONS APPLY BEFORE
SURFACE TREATMENT
THIS DRAWING IS THE PROPERTY OF
ROCKWELL INTERNATIONAL CORPORATION
OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,
USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY
ROCKWELL INTERNATIONAL CORPORATION
(DIMENSIONS IN INCHES)
TOLERANCES UNLESS
OTHERWISE SPECIFIED
.XX:
N/A
.XXX:
N/A
E - DOC
CIRCUIT BREAKER AND ACCESSORY
INSTALLATION INSTRUCTION SHEET
H
LOCATION: MILWAUKEE, WISCONSIN U.S.A.
G. Ushakow
CHKD. M. Jutz
APPD. J. Koziczkowski
DR.
ANGLES:
42052
N/A
DATE
DATE
DATE
7-25-04
7-25-04
7-25-04
DWG.
SIZE
B
SHEET
1
OF
4
42052-043
B-vertical.ai
1
A
2
3
4
5
6
7
8
Handle Installation
2
1
7-11 lb-in
B
3
4
1
2
C
D
5
E
2
1
F
23-37 lb-in
G
REFERENCE
REVISION
AUTHORIZATION
1
155-01-1
2
1009161
DIMENSIONS APPLY BEFORE
SURFACE TREATMENT
THIS DRAWING IS THE PROPERTY OF
ROCKWELL INTERNATIONAL CORPORATION
OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,
USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY
ROCKWELL INTERNATIONAL CORPORATION
(DIMENSIONS IN INCHES)
TOLERANCES UNLESS
OTHERWISE SPECIFIED
.XX:
N/A
.XXX:
N/A
E - DOC
CIRCUIT BREAKER AND ACCESSORY
INSTALLATION INSTRUCTION SHEET
H
LOCATION: MILWAUKEE, WISCONSIN U.S.A.
-------CHKD. - - - - - - - APPD. - - - - - - - DR.
ANGLES:
42052
N/A
DATE
DATE
DATE
----------------------
DWG.
SIZE
B
SHEET
2
OF 4
42052-043
B-vertical.ai
1
A
2
3
4
5
6
7
8
Circuit Breaker (150 Amp Frame Size) Installation
2
1
Threaded Rod
2
16 - 22 lb-in
3
1
B
+/- 1 Thread
(Sizes 3, 4, 5)
.75
(Sizes 0, 1, 2)
4
3
C
2
22 - 37 lb-in
3
4
1
D
Hitch Pin
5
2
E
1
3
F
(3)
G
REFERENCE
REVISION
AUTHORIZATION
1
155-01-1
2
1009161
DIMENSIONS APPLY BEFORE
SURFACE TREATMENT
THIS DRAWING IS THE PROPERTY OF
ROCKWELL INTERNATIONAL CORPORATION
OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,
USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY
ROCKWELL INTERNATIONAL CORPORATION
(DIMENSIONS IN INCHES)
TOLERANCES UNLESS
OTHERWISE SPECIFIED
.XX:
N/A
.XXX:
N/A
E - DOC
CIRCUIT BREAKER AND ACCESSORY
INSTALLATION INSTRUCTION SHEET
H
LOCATION: MILWAUKEE, WISCONSIN U.S.A.
DR.
ANGLES:
42052
N/A
CHKD.
APPD.
----------------------
DATE
DATE
DATE
----------------------
DWG.
SIZE
B
SHEET
3
OF
4
42052-043
B-vertical.ai
1
2
A
3
4
5
6
7
8
Circuit Breaker (150 Amp Frame Size) Installation (Cont'd)
6
7
Note: Only Cutler-Hammer circuit breakers can be used in
Allen-Bradley combination starters.
2
16 - 20 lb-in
On
Off
B
Toggle
Adjustment
Plate
Toggle
Adjustment
Plate
UP
1
25 - 30 lb-in
3
8
C
2
1
D
Testing of Circuit Breaker
1. Verify that the circuit breaker can be turned on by moving the defeater lever downward and moving the disconnect handle to the ON position.
2. If the circuit breaker does not turn on, loosen the (2) screws and adjust the toggle adjustment plates toward the line terminals until the circuit
breaker turns on when the disconnect handle is in the ON position. Tighten the (2) toggle adjustment plate screws to 25 - 30 lb-in.
3. If the circuit breaker still can not be turned on unhook the spring, remove hitch pin and separate threaded rod and handle link. Turn threaded rod
one full turn counterclockwise. Reattach threaded rod and handle link, hitch pin and spring. Repeat Step 1 and if necessary Step 2.
4. Verify that the circuit breaker can be turned off by moving the disconnect handle to the OFF position.
5. If the circuit breaker can not be turned off, loosen the (2) screws and adjust the toggle adjustment plates toward the load terminals until the
circuit breaker turns off when the disconnect handle is in the OFF position. Tighten the (2) toggle adjustment plate screws to 25 - 30 lb-in.
6. If the circuit breaker still can not be turned off and if no adjustment of the threaded rod was made in Step 3 then unhook the spring, separate
threaded rod and handle link and remove hitch pin. Turn threaded rod one full turn clockwise. Reattach threaded rod and handle link, hitch pin
and spring. Repeat Step 4 and if necessary Step 5.
7. Verify that the circuit breaker can be reset after manually tripping when circuit breaker is in the ON position.
8. Manually trip the circuit breaker while in the ON position, then move the disconnect handle to the Off-Reset position.
9. If the circuit breaker does not reset, loosen the (2) screws and adjust the toggle adjustment plates in small increments toward the load terminals.
Note: Repeat this procedure until the circuit breaker can be reset.
Note: Do not adjust the toggle adjustment plate too far: this will prevent the disconnect handle from moving to the full OFF-Reset position.
10.Tighten the (2) adjustment plate screws to 25 - 30 lb-in.
11.Verify that the circuit breaker can still be turned on following the above steps.
Note: Twisting of the bail mechanism is acceptable when the handle is in the full ON and full OFF position.
E
F
42052-043-01 (2)
Printed in U.S.A.
-01
G
2
TWO SIDES PRINTED
BODY STOCK WHITE
BODY INK BLACK
PART CHG.
NO. CHAR.
MATERIAL
1
155-01-1
2
1009161
4 - 1/4" W x 5 - 1/2" H
FLAT
FOLD
SIZE
REFERENCE
REVISION
AUTHORIZATION
17" W x 11" H
DIMENSIONS APPLY BEFORE
SURFACE TREATMENT
THIS DRAWING IS THE PROPERTY OF
ROCKWELL INTERNATIONAL CORPORATION
OR ITS SUBSIDIARIES AND MAY NOT BE COPIED,
USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY
ROCKWELL INTERNATIONAL CORPORATION
(DIMENSIONS IN INCHES)
TOLERANCES UNLESS
OTHERWISE SPECIFIED
.XX:
N/A
.XXX:
N/A
E - DOC
CIRCUIT BREAKER AND ACCESSORY
INSTALLATION INSTRUCTION SHEET
H
LOCATION: MILWAUKEE, WISCONSIN U.S.A.
-------CHKD. - - - - - - - APPD. - - - - - - - DR.
ANGLES:
42052
N/A
DATE
DATE
DATE
----------------------
DWG.
SIZE
B
SHEET
4
OF 4
42052-043
B-vertical.ai
">