Allen-Bradley ArmorBlock MaXum 8 In/8 Out Module Installation Instructions
Allen-Bradley ArmorBlock MaXum 8 In/8 Out Module is a stand-alone 24V dc I/O product, which communicates via a DeviceNet network. Its sealed housing eliminates the need for an enclosure. This module is equipped with 8 shielded input channels, 8 self-protected output channels, and it features short circuit, open wire, and no load detection. It also includes local logic control and an external ground lug.
PDF
Download
Document
Advertisement
Advertisement
Installation Instructions ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug Cat. No. 1792D-8BT8PE Ground lug 43881 This ArmorBlock MaXum I/O module (Cat. No. 1792D-8BT8PE) is a stand-alone 24V dc I/O product, which communicates via a DeviceNet network. The sealed housing of this module requires no enclosure. This module has 8 inputs and 8 outputs accessed through Y splitter cables. Inputs are 24V dc devices. Eight self-protected 24V dc outputs can provide up to 0.5 amp each. Diagnostic features are short circuit, open wire, and no load detection reported to the connector level on inputs and point level on outputs. Local logic control has been included. An external lug exists to ground the block. Publication 1792D-IN055A-EN-P - October 2004 2 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited. Throughout this manual, when necessary we use notes to make you aware of safety considerations. WARNING IMPORTANT ATTENTION Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: • identify a hazard • avoid a hazard • recognize the consequence SHOCK HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present. BURN HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures. Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 3 ATTENTION Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as "open type" equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment. Package Contents Your package contains: • 1 ArmorBlock MaXum module • these installation instructions (Note: Cable bases are ordered and shipped separately.) Publication 1792D-IN055A-EN-P - October 2004 4 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug Install Your ArmorBlock MaXum I/O Module To install the ArmorBlock MaXum module: • Set the node address • Mount the module to the cable base • Connect the cord sets • Communicate with the module Each of these steps is explained in the following procedures. ATTENTION Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • If available, use a static-safe workstation. • When not in use, store the equipment in appropriate static-safe packaging. Set the Node Address Valid node addresses are 00 through 63. Set the node address using the rotary switches, RSNetWorx for DeviceNet, DeviceNetManager, or another software configuration tools. Setting the switches to a number from 64 through 99 lets the software have address control. Each module is shipped set for node address 63. The switches are located on the underside of the module. The two switches are: • MSD (most significant digit) • LSD (least significant digit) Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 5 To reset the node address, use a small blade screwdriver to rotate the switches. Line up the small black dot on the switch with the number setting you wish to use. The rotary switches are read at module power up only. Settings from 64 through 99 cause the module to use the last valid node address stored internally. For example, the last setting was 40. If a change is made to 68, and then you power up, the address will default to 40. Refer to the following illustration of the node address. NODE ADDRESS (00-63 PGM) 9 0 1 8 7 6 5 4 2 3 MSD 9 0 1 8 7 6 5 4 2 3 Node Address is set at 62; see small black dots. LSD Bottom View of Module 41462 The module is equipped with AutoBaud detect. AutoBaud lets the module read the settings already in use on your DeviceNet network and automatically adjusts to follow those settings. Install the Module This module mounts to the following cable bases: • 1792D-CBFM for KwikLink™ flat media installation • 1792D-CB12 for 12mm drop cable installation • 1792D-CB18P for round media DeviceNet and output power • other optional cable base assembly. IMPORTANT The cable base should already be installed. For more information about the cable base, see publication 1792D-IN036 (CB18P) or 1792D-IN009 (CBFM, CB12). Publication 1792D-IN055A-EN-P - October 2004 6 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug To install the module: IMPORTANT Proper alignment of the screws is necessary to complete the connections between the module contacts and the cable contacts. 1. Position the module over the mounted cable base. Align the three captive screws in the module with the accepting receptacles in the base. 2. Tighten the screws with a torque of 8 inch-pounds to secure the module to the base. Note: Dimensions change according to the cable base and module combination used. 2.7in. (68.6mm) 6.85in. (174mm) Align the screws to properly secure the module to the base. 1.9in. (48.26mm) Cable Base 1792D-CBFM is used for this example. Ground lug WARNING 43875 When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes. Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 7 Connect the Input / Output Cord Sets to the MaXum Module This module uses 5 pin micro (12mm) style PCB mounted connectors. Eight micro caps cover the connectors on your module. Remove the caps and connect your cord sets to the appropriate ports. This product has two inputs or outputs per I/O connector. Use a “Y” splitter cable for access to all I/O connections. Use the micro caps to cover and seal unused ports. The following illustration shows pinout diagrams for the connectors. Input Micro-Connector (view into socket) Pin 1 Sensor Source voltage Pin 2 Input B Pin 3 Pin 4 Pin 5 Return Logic Ground1 Input A PE Output Micro-Connector (view into socket) Pin 1 Not Used Pin 2 Output B Pin 3 Auxiliary Power Ground Pin 4 Output A Pin 5 PE 41452 1Logic Ground is approximately 0.4V above DeviceNet V- measured at the module. WARNING If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Publication 1792D-IN055A-EN-P - October 2004 8 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug Refer to publication 889-5.0 for Rockwell Automation cables and cord sets offerings. WARNING IMPORTANT ATTENTION Use supply wires suitable for 30°C above surrounding ambient. If the devices (sensors) connected to the input connections require Class 2 power to operate, the DeviceNet connections of this equipment must be powered by a Class 2 source. • Make sure all connections and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements. • For maximum noise immunity, input and output cable return wires must be properly terminated. When inputs and outputs are connected in loopback, return wires should be connected together. • I/O cable length should be less than 30 meters. Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 9 I/O connectors for this module are shown below. Connector A Input 0 Input 1 Connector B Input 2 Input 3 Connector C Input 4 Input 5 Connector D Input 6 Input 7 I-0 O-0 I-1 O-1 I-2 O-2 I-3 O-3 I-4 O-4 I-5 O-5 I-6 O-6 I-7 O-7 Output 0 Output 1 Connector E Output 2 Output 3 Connector F Output 4 Output 5 Connector G Output 6 Output 7 Connector H Auxilary Power Logic Status Net/Mod Status 41517 WARNING If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Output Power and DeviceNet Cables Output power and DeviceNet cables are described in the installation publications for the cable base assembly of your choice. Refer to the following publications: • 1792D-IN009 ArmorBlock MaXum Cable Base Installation Instructions • DN-6.7.2 DeviceNet Cable Planning and Installation Manual Publication 1792D-IN055A-EN-P - October 2004 10 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug Communicate With Your ArmorBlock MaXum I/O Module This ArmorBlock module’s I/O is exchanged with the master through a cyclic, poll, or change-of-state connection. The module consumes and produces I/O data as follows: Type of I/O Connections Consumes Produces Cyclic 1 Byte 4 Bytes Polled 1 Byte 4 Bytes Change-of-State 1 Byte 4 Bytes Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured. Polled - a master initiates communication by sending its polled I/O message to the module. The 8 input / 8 output module consumes the message, updates outputs, and produces a response. The response has input data, input faults, output faults, and the status of the auxiliary power. Change-of-State - productions occur when an input changes or a fault condition occurs. If no input or fault condition change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Refer to the table below for the word/bit definitions. Bit 07 06 05 04 03 02 01 00 Produces 0 I7 I6 I5 I4 I3 I2 I1 I0 Produces 1 OW-D OW-C OW-B OW-A ISC-D ISC-C ISC-B ISC-A Produces 2 OFLT7 OFLT6 OFLT5 OFLT4 OFLT3 OFLT2 OFLT1 OFLT0 Produces 3 RSVD OPWR RSVD RSVD RSVD RSVD RSVD RSVD Consumes 0 O7 O6 O5 O4 O3 O2 O1 O0 Where: I = Input, OW= Off Wire, ISC=Input Short Circuit in Sensor Source Voltage, OFLT = Output fault, RSVD= Reserved, OPWR= Output Power (auxiliary power), O = Output Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 11 The DevicLogix Product assembly for the 1792D-8BT8DPE is as follows: Bit 07 06 05 04 03 02 01 00 Produces 0 I7 I6 I5 I4 I3 I2 I1 I0 Produces 1 OW-D OW-C OW-B OW-A ISC-D ISC-C ISC-B ISC-A Produces 2 OFLT7 OFLT6 OFLT5 OFLT4 OFLT3 0FLT2 OFLT1 OFLT0 Produces 3 OPWR Logic Ena Produces 4 O7 O6 O5 O4 O3 O2 O1 O0 Produces 5 PNB7 PNB6 PNB5 PNB4 PNB3 PNB2 PNB1 PNB0 Where: I = Input, OW = Off Wire ISC=Input Short Circuit in Sensor Source Voltage, OFLT = Output fault, OPWR= Output Power (auxiliary power), Logic Ena = DeviceLogix enabled, O = Output, PNB = Produced Network Bit (Network Output) Publication 1792D-IN055A-EN-P - October 2004 12 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug Byte Bit Description Produces 0 00-07 Input Status bits: When the bit is set (1), the input is on. Bit 00 = input 0, bit 01 = input 1, bit 02 = input 2, and so on to bit 07 = input 7. Produces 1 00-03 Input short circuit fault: ISC-A = a short circuit for connector A Input short circuit fault: ISC-B = a short circuit for connector B Input short circuit fault: ISC-C = a short circuit for connector C Input short circuit fault: ISC-D = a short circuit for connector D Input off wire fault: OW-A = an off-wire fault for connector A Input off wire fault: OW-B = an off-wire fault for connector B Input off wire fault: OW-C = an off-wire fault for connector C Input off wire fault: OW-D = an off-wire fault for connector D 04-07 Produces 2 00-07 Output no load or overload fault (OFLT): - When the bit is set (1) an output fault has occurred. OFLT0 = output 0, OFLT1 = output 1, OFLT2 = output 2, and so on to OFLT7 = output 7. Produces 3 00-05 06 RSVD = Reserved Output Power Fault (OPWR): When the bit is set (1) auxiliary power is not present. RSVD = Reserved 07 Consumes 0 00-07 Output bits: When the bit is set (1), the output will be turned on. Bit O0 = output O0, bit 01 = output O1, bit 02 = output O2, and so on to bit O7 = output O7. The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our web site at http://www.ab.com/networks for producer/consumer technology information and updates. Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 13 Troubleshoot With the Indicators This module has the following indicators: • Network and Module status indicator • Logic status indicator • Auxiliary power indicator • Individual I/O status indicators for inputs 0 through 7 and outputs 0 through 7. Point indicators for inputs 0 and 1 Connector A Point indicators for inputs 2 and 3 Connector B Point indicators for inputs 4 and 5 Connector C Point indicators for inputs 6 and 7 Connector D I-0 O-0 I-1 O-1 I-2 O-2 I-3 O-3 I-4 O-4 I-5 O-5 I-6 O-6 I-7 O-7 Point indicators for outputs 0 and 1 Connector E Point indicators for outputs 2 and 3 Connector F Point indicators for outputs 4 and 5 Connector G Point indicators for outputs 6 and 7 Connector H Auxilary Power Module Status Indicators Logic Status Net/Mod Status 41517 LED Assignments Publication 1792D-IN055A-EN-P - October 2004 14 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug The following table describes the network and module status indicator. Net/Mod Status Indicator Indicator Status Off No power or auto bauding Flashing Green/Off On line but not connected Solid Green On line, link OK, connected Flashing Red Recoverable fault - module configuration error I/O connection fault - one or more I/O connections in the timed-out state Solid Red Unrecoverable fault Communication failure - duplicate node address present or incorrect baud rate Green to Red to Off At powerup only - LED test The following table describes the logic status indicator. Logic Status Indicators Indicator Status Off Logic is disabled Solid Green Logic is enabled Flashing Green Local forces are applied and local logic is enabled The following table describes the auxiliary power indicator. Auxiliary Power Indicator Status None No auxiliary Power Solid Green Auxiliary Power Present Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 15 The following table describes individual I/O status indicators. I/O Status Indicators Function Module Status Indicator Point Indicator1 Status Outputs Green Green Module Status blink red Module Status blink red Module Status blink red Module Status blink red None Yellow Orange Red Orange Red Output not energized Output energized Output shorted - auto restart Output shorted - latching Output no load - auto restart Output no load - latching Inputs Green Green Module Status blink red Module Status blink red None Yellow Red Blink red No valid input Valid input Short on input connector1 Off wire on input connector 1Only the first LED of each input connector will light as red when twin inputs are used. Specifications 8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE Input Specifications Maximum Minimum Inputs per block 8 - 3 wire or dry contact PNP devices or 4 - 4 wire PNP devices Sensor Source Current (per connector) 100mA total - Off-wire Sense Current 0.5mA - On-state Voltage 25V dc 10V dc On-state Current 10mA 2mA Off-state Voltage 5V dc - Off-state Current - 1.5mA Output Specifications Maximum Minimum Outputs per block 8 sourcing outputs labeled O0 through O7 Off Peak Blocking Voltage 30V 10V On-state Voltage Drop 1V - On-state Current 0.5A - Off-state Leakage 1.5mA - Module Current (all outputs) 4.0A - Surge Current - for 10ms, repeatable every 2s 2.4A - No Load Sense Current (On-state) 0.18A - Publication 1792D-IN055A-EN-P - October 2004 16 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE General Specifications Maximum Minimum DeviceNet Power Voltage Current 25V dc max 150mA max (no sensors) 11V dc min up to 1.4A (8 sensors @ 50mA per sensor) Auxiliary Power Voltage Current 30V dc max 4A max 10V dc min 4A max Indicators Net/Mod Status - red/green Logic Status - green Auxiliary Power - green Point LED - yellow/orange/red Communication Rate • • • 125Kbps @ 500 meters(1600 feet) for thick cable, flat media length 375 meters (1230 feet) 250Kbps @ 200 meters(600 feet) for thick cable, flat media length 150 meters (492 feet) 500Kbps @ 100 meters (330 feet) for thick cable, flat media length 75 meters (246 feet) Dimensions (assembled to base) inches - (Millimeters) 1.9H x 2.7W x 6.9D (48)H x (69)W x (174)D Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -25 to 60° (-13 to 140°F) Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): -25 to 80° (-13 to 176°F) Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 5 to 95% non-condensing Vibration IEC 60068-2-6 (Test Fc, Operating): 10g @ 10-500 Hz Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 17 8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE General Specifications (continued) Operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30g Non-Operating Shock IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50g Emissions CISPR 11: Group 1, Class A ESD Immunity IEC 61000-4-2: 6kV contact discharges 8kV air discharges Radiated RF Immunity IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900MHz| 10V/m with 200Hz 50% Pulse 100%AM at 1890MHz EFT/B Immunity IEC 61000-4-4: ±2kV at 5kHz on power ports ±2kV at 5kHz on signal ports ±2kV at 5kHz on communications ports Surge Transient Immunity IEC 61000-4-5: ±1kV line-line(DM) and ±2 line-earth(CM) on power ports ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports ±2kV line-earth(CM) on communications ports Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz Conductors Publication DN-6.7.2 Enclosure Meets IP67 Supply Voltages/Voltage Ranges DNet Power: 11V dc to 25V dc; Auxiliary Power: 10V dc to 30V dc Supply Power/Current Ratings DNet current:1.6A; Input current: 50mA; Output power: 60VA DC-13/SQ; Outputs 4A total; Auxiliary current:4A Isolation voltage (continuous-voltage withstand rating) Tested to withstand 750V dc for 60 seconds Wire Size Use 14-22 AWG wire with insulation temperature rating of 75°C min.See Publication DN-6.7.2; Category: 2. Wiring Category1 2 - on signal ports 2 - on power ports 2 - on communications ports Publication 1792D-IN055A-EN-P - October 2004 18 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 8 Input / 8 Output Module - Cat. No. 1792D-8BVT8PE General Specifications (continued) Certifications:2 (when product is marked) CSA CSA CE C-Tick ODVA CSA Certified Process Control Equipment CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions ODVA conformance tested to DeviceNet specifications 1. Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, "Industrial Automation Wiring and Grounding Guidelines". 2. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details. This product has been tested at an Open DeviceNet Vendor Association, Inc. (ODVA) authorized independent test laboratory and found to comply with ODVA Conformance Test. Please contact the ODVA web site (http://www.odva.org) for listing of products tested by ODVA independent test labs for further details. Publication 1792D-IN055A-EN-P - October 2004 ArmorBlock MaXum 8 Input / 8 Output Module With Ground Lug 19 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l'utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation. Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation. WARNING • • • • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. Substitution of components may impair suitability for Class I, Division 2. If this product contains batteries, they must only be changed in an area known to be nonhazardous. AVERTISSEMENT • • • • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement. Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2. S'assurer que l'environnement est classé non dangereux avant de changer les piles. ArmorBlock, ArmorBlock MaXum, RSNetWorx for DeviceNet, DeviceNetManager, and KwikLink are trademarks of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA). Publication 1792D-IN055A-EN-P - October 2004 Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com. Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running: United States 1.440.646.3223 Monday – Friday, 8am – 5pm EST Outside United States Please contact your local Rockwell Automation representative for any technical support issues. New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned: United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process. Outside United States Please contact your local Rockwell Automation representative for return procedure. Publication 1792D-IN055A-EN-P - October 2004 PN 957928-10 Copyright © 2004 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">
Advertisement
Key features
- 24V dc I/O
- DeviceNet network
- Sealed housing
- 8 Inputs
- 8 Outputs
- 0.5A output current
- Local logic control
- Ground lug
- Diagnostic features
Frequently asked questions
The ArmorBlock MaXum module communicates via the DeviceNet network.
This module has 8 input channels and 8 output channels.
Each of the 8 output channels can provide up to 0.5 amps.
The module has diagnostic features for short circuits, open wires, and no load detection on both inputs and outputs.
No, this module is sealed and does not require a separate enclosure.