H-Frame Circuit Breaker Instruction Leaflet for Fixed and AdjustableThermal Trip 1 Warning OFF DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING. 2 40752-001 Effective 02/02 3 10 in-lb (0.2 N⋅m) 10 in-lb (0.2 N ⋅m) Note: Mounting hardware included. Use nuts (provided) if not threading holes in mounting surface. 4 34-38 in-lb (3.8-4.3 N⋅m) H Frame Collar Torque Values Wire Size Torque 2 AWG (mm ) In-lb 14-10 8 6-4 3-3/0 (2.5-6) (10) (16-25) (35-95) 35 40 45 50 (N⋅m) (4.0) (4.5) (5.1) (5.6) Warning INSTALL WIRE APPLICABLE TO THE HIGHEST RATING SHOWN ON BREAKER. Note: Endcap is sold separately. 5 Optional thermal adjustment 6 ON Note: If cover must be removed for accessory installation, torque cover mounting screws to 6-8 in-lb (.7-.9 N m). TRIP OFF RESET Push to trip 40752-001 Effective 02/02 Effective 01/01 ">