Allen-Bradley ArmorBlock LP2 8 Sinking Input Module Installation Instructions
The Allen-Bradley ArmorBlock LP2 8 Sinking Input Module is a standalone 24V dc I/O product that communicates via a DeviceNet network. It features 8 sinking inputs accessed through Y splitter labels and a sealed housing that requires no enclosure. This module is designed for use in industrial environments and is compliant with relevant European Union directives.
PDF
Download
Document
Advertisement
Advertisement
Installation Instructions ArmorBlock LP2 8 Sinking Input Module (Cat. No. 1792D-8BT0LP) I-0 I-7 I-1 I-6 I-2 I-5 I-3 I-4 Network Status Module Status 42041 This ArmorBlock LP2™ I/O module (Cat. No. 1792D-8BT0LP) is a stand-alone 24V dc I/O product which communicates via a DeviceNet™ network. The sealed housing of this module requires no enclosure. This model has 8 sinking inputs accessed through Y splitter labels. Package Contents Your package contains: • • 1 ArmorBlock LP2 Module Installation Instructions Publication 1792D-5.47 - August 1999 2 ArmorBlock LP2 8 Sinking Input Module European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives. EMC Directive This product is tested to meet Council Directive 89/336/EC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial Environment • EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial Environment This product is intended for use in an industrial environment. Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publication Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1. Publication 1792D-5.47 - August 1999 ArmorBlock LP2 8 Sinking Input Module 3 Install Your ArmorBlock LP2 I/O Module To install the module: • Set the node address and baud rate. • Mount the module. • Connect the input cord sets to the LP2 module • Communicate with your ArmorBlock LP2 module. More detailed information about each of these steps is in the following procedures. Set the Node Address Set the node address using RSNetWorx for DeviceNet™ software, DeviceNetManager™ software, or another software configuration tool. The module is equipped with AutoBaud detect. AutoBaud lets the module read the settings already in use on your DeviceNet network and automatically adjusts to follow those settings. Mount the Module 1. Mount the module using the dimensions shown below. 4.72in 120mm 1.95in 49.5mm 12in 305mm 2.7in 68.5mm (width) I-0 I-7 I-1 I-6 I-2 I-5 I-3 I-4 Network Status 4.21in 107mm Module Status 0.25in 6.25mm 42041 2. Connect the grey DeviceNet cable to the DeviceNet trunk. Use the 1485P-P1R5-MN5R1 T-Part tap to make the connection to round media. Use the 1485P-P1E4-R5 to connect to the Kwik Link flat media system. Publication 1792D-5.47 - August 1999 4 ArmorBlock LP2 8 Sinking Input Module Connect the Input Cord Sets to the LP2 Module This module uses 5 pin micro (12mm) style PCB mounted connectors. Four micro caps cover the connectors on your module. Remove the caps and connect your cables to the appropriate ports. This product has two inputs per connector. Use a “Y” splitter cable for access to all input connections. For more information on these cables, see the Product Data guide, publication 1792-2.1. Use the micro caps to cover and seal unused ports. A Pinout diagram for the connector is shown below. 2 1 5 3 4 1 Input Micro-Connector (View into Sockets) Pin 1 Sensor Source Voltage Pin 2 Input B Pin 3 Return Logic Ground1 Pin 4 Input A Pin 5 Not Used 41452 Logic Ground is approximately 0.4V above DeviceNet V-measured at the module. ATTENTION: ! • • • • Make sure to connect the proper color coded cables together. DeviceNet cables should connect with DeviceNet cables. Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements. For maximum noise immunity, input cable return wires must be properly terminated. When inputs are connected in loopback, return wires should be connected together. I/O cable length should be less than 30 meters. Publication 1792D-5.47 - August 1999 ArmorBlock LP2 8 Sinking Input Module 5 Input connectors for this module are shown below. Connector A Input 0 Input 1 Connector B Input 2 Input 3 I-0 I-7 I-1 I-6 I-2 I-5 I-3 I-4 Connector D Input 7 Input 6 Connector C Network Status Module Status Input 5 Input 4 42041 Communicate with Your ArmorBlock LP2 Module This ArmorBlock module’s I/O is exchanged with the master through a poll, change of state, or cyclic connection. The module produces input data as follows: Type of I/O Connections Consumes Produces Cyclic 0 Bytes 2 Bytes Polled 0 Bytes 2 Bytes Change of State 0 Bytes 2 Bytes Cyclic - allows configuration of the block as an I/O client. The block will produce its I/O cyclically at the rate configured. Polled - a master initiates communication by sending its polled I/O message to the module. The 8 input module consumes the message, updates inputs, and producing a response. The response has input data and input faults. Publication 1792D-5.47 - August 1999 6 ArmorBlock LP2 8 Sinking Input Module Change of state - productions occur when an input changes or a fault condition occurs. If no input or fault condition change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new input data to the I/O block. Refer to the table below for the word/bit definitions. Bit 07 06 05 04 03 02 01 00 Produces 0 I7 I6 I5 I4 I3 I2 I1 I0 Produces 1 ISC RSVD RSVD RSVD RSVD RSVD RSVD RSVD Where: I= Input ISC=Input Short Circuit RSVD = Reserved Byte Bit Description Produces 0 00-07 Input status bits: When the bit is set (1), the input is on. Bit 00 = input 0, bit 01= input 1, bit 02 = input 2, bit 03 = input 3, bit 04 = input 4, bit 05 = input 5, bit 06 = input 6, bit 07 = input 7. Produces 1 07 Input Short Circuit The DeviceNet Network uses advanced network technology, producer/ consumer communication, to increase network functionality and throughput. Visit our web site at http://www.ab.com/networks for producer/ consumer technology information and updates. Publication 1792D-5.47 - August 1999 ArmorBlock LP2 8 Sinking Input Module 7 Troubleshoot with the Indicators This module has the following indicators: • Network status indicator • Module status indicator • Individual point status indicators for inputs 0 through 7 Point Indicators for Point Indicators for input 0 input 1 Connector A input 2 input 3 Connector B DeviceNet Indicators I-0 I-7 I-1 I-6 I-2 I-5 I-3 I-4 Network Status input 7 input 6 Connector D input 5 input 4 Connector C Module Status LED Assignments 42041 The following table describes the module status indicator. Module Status Indicator Indication Status None No Power Green Blinking Solid Needs Commissioning Operating Normal Red Blinking Solid Recoverable Fault Unrecoverable Fault Publication 1792D-5.47 - August 1999 8 ArmorBlock LP2 8 Sinking Input Module The following table describes the network status indicator. Network Status Indicator Indication Status None Not On-line Green Blinking Solid On-line/No Connections On-line/Connected Red Blink Solid Connection Timed Out Failed Communication: A duplicate node address exists or module is at the wrong baud rate. The following table describes I/O status indicators. I/O Status Indicators Function Module Status Indicator Point Indicator Condition Inputs Green Green Blinking Red None Yellow None No valid input Valid input Input Short For more information on indicators, see the Product Data publication 1792-2.1. Publication 1792D-5.47 - August 1999 ArmorBlock LP2 8 Sinking Input Module 9 Specifications 8 Input Module - Cat. No. 1792D-8BT0LP Sinking Input Specifications Max Inputs per block 8 - 3 wire or dry contact PNP devices Min Sensor Source Current (per input) 50mA - On-state Voltage 25V dc 10V dc On-state Current 10mA 2mA Off-state Voltage 5Vdc Off-state Current 1.5mA Indicators Network Status - red/green Module Status - red/green Point LED- yellow Communication Rate • • • 125Kbps @ 500 meters(1600 feet) for thick cable, flat media length 375 meters (1230 feet) 250Kbps @ 200 meters(600 feet) for thick cable, flat media length 150 meters (492 feet) 500Kbps @ 100 meters (330 feet) for thick cable, flat media length 75 meters (246 feet) DeviceNet Power Voltage Current 25V dc 125mA (no sensors) 11V dc 500mA (8 sensors @ 50mA per sensor) Dimensions (assembled to base) inches - (millimeters) 1.023H x 2.7W x 4.72D (26)H x (68.5)W x (120)D Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating Non-operating Vibration -25 to 60oC (-13 to 140oF) -25 to 80oC (-13 to 176OF) Up to 100% 30g peak acceleration, 11 (+1) ms pulse width 50g peak acceleration, 11(+1)ms pulse width Tested 10g @ 10-500Hz per IEC 68-2-6 Conductors Publication DN-6.7.2 Enclosure Meets or exceeds IP67 Agency Certification (when product is marked) • Product Data (user information) Publication 1792-2.1 CE marked for all applicable directives This product has been tested at an Open DeviceNet Vendor Association, Inc. (ODVA) authorized independent test laboratory and found to comply with ODVA Conformance Test. Please contact the ODVA website (http://www.odva.org) for listing of products tested by ODVA independent test labs for further details. Publication 1792D-5.47 - August 1999 ArmorBlock, ArmorBlock LP2 and DeviceNetManager are trademarks of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA). RSNetWorx for DeviceNet is a trademark of Rockwell Software, Inc. Publication 1792D-5.47 - August 1999 PN 955138-16 © (1999) Rockwell International Corporation.Printed in USA ">
Advertisement
Key features
- 8 sinking inputs
- DeviceNet™ network communication
- Sealed housing
- AutoBaud detect
- European Union directive compliant
- IP67 rating
- Input Short Circuit detection
Frequently asked questions
This module has 8 sinking inputs.
It communicates via a DeviceNet network.
The maximum I/O cable length is 30 meters (98 feet).
The module supports Cyclic, Polled, and Change of State communication modes.