Installation
Dataliner DL40 Plus Message Display
(Catalog No. 2706-LV2xX, -LV4xX)
Overview
This document describes how to install a Dataliner DL40 Plus display
(standard or slave version) and contains these topics:
•
•
•
•
•
Wiring and safety guidelines
Mounting and dimensions
Power connections
DIP switch settings
Specifications
For additional information, refer to:
• DL40 Plus Message Display User Manual (Publication 2706-6.1)
• DL40 Plus Slave Display User Manual (Publication 2706-6.3)
Wiring and Safety Guidelines
Install the DL40 Plus display conforming to NFPA 70E, Electrical Safety
Requirements for Employee Workplaces. In addition to the NFPA general
guidelines, refer to the following:
Careful cable routing helps minimize electrical noise. Route incoming
power to the module by a separate path from the communication cables.
Do not run communications wiring and power wiring in the same
conduit!
Where communication and wire paths must cross, make their intersection
perpendicular.
Grounding helps limit the effects of noise due to electromagnetic
interference (EMI). To avoid problems caused by EMI, properly ground all
equipment and use shielded cables.
Important: Power, input and output (I/O) wiring must be in accordance
with Class I, Division 2 wiring methods [Article 501-4(b) of the National
Electrical Code, NFPA70] and in accordance with the local authority having
jurisdiction.
2
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
Hazardous Location
Installations
!
!
!
Mounting the DL40 Plus
ATTENTION: THIS EQUIPMENT IS SUITABLE
FOR USE IN CLASS I, DIVISION 2, GROUPS A, B,
C AND D, OR NON-HAZARDOUS LOCATIONS
ONLY.
ATTENTION: EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR CLASS 1, DIVISION 2.
ATTENTION: EXPLOSION HAZARD - DO NOT
CONNECT OR DISCONNECT EQUIPMENT
UNLESS POWER HAS BEEN SWITCHED OFF OR
THE AREA IS KNOWN TO BE NON-HAZARDOUS.
The following pages provide panel cutout dimensions and overall
dimensions for the DL40 Plus displays.
You can also mount the DL40 Plus in a custom panel or enclosure. When a
DL40 Plus is properly installed, the faceplate provides a NEMA Type 12,
13, and 4X(indoor) rating. To install the DL40 Plus:
1. Cut and drill the appropriate mounting holes in the enclosure or panel.
2. Remove the six mounting nuts from the hardware bag provided with the
display.
3. Position the DL40 Plus in the panel or enclosure mounting hole.
4. Install and alternately tighten the nuts to a torque of 10in•lbs
(1.13N•m).
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
Panel Cutout Dimensions
All dimensions are in inches (millimeters)
Cutout 13.62 (345.9)
0.19 (4.8)
Cutout
3.50
(88.9)
0.19 (4.8)
6.81 (173.0)
2-Line DL40 Plus Display
(Standard or Slave)
6.94 (176.1)
3.88
(98.4)
0.25 (6.4)
Diameter Hole
6 places
13.87 (352.3)
Cutout 13.62 (345.9)
0.19 (4.8)
Cutout
5.30
(134.6)
0.19 (4.8)
6.81 (173.0)
4-Line DL40 Plus Display
(Standard or Slave)
6.94 (176.1)
5.68
(144.3)
0.25 (6.4)
Diameter Hole
6 places
13.87 (352.3)
3
4
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
Dimensions
2-Line Display
13.16
(334.2)
4.38
(111.3)
14.357 (365.0)
3.16
(80.3)
3.19
(81.0)
Dimensions are in inches (millimeters)
Dimensions
4-Line Display
6.16
(156.4)
13.16
(334.2)
14.357 (365.0)
3.16
(80.3)
Dimensions are in inches (millimeters)
3.19
(81.0)
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
Before making power connections, make sure that the power is turned off.
The DL40 Plus display requires 100-240Volts AC, 50/60 Hz, 0.60-0.25
Amperes.
!
ATTENTION: Improper wiring of the power
connections may result in damage to the DL40.
L1
Black
(Brown)
White
(Blue)
Green
(Green/Yellow)
Three DIP switch banks are located on the back of the display. Access the
DIP switches through a cutout, as shown below. Set DIP switches using a
thin nonconductive object. Do not use a pencil (broken graphite pieces may
short out the internal circuitry).
For details on DIP switch settings, refer to the DL40 Plus User Manual
(Publication 2706-6.1).
SW1
KEYBOARD
SW2
SW3
RS-485
12VDC
DIP Switch Settings
(Remote I/O Versions)
L2N
RIO
2S1
GND
Power Connections
5
RELAY
250 VAC 3A
L1 L2N
RS-232
Remote I/O Port
Location of DIP Switches
Switch Bank #1 (SW-1) sets the rack address.
Switch Bank #2 (SW-2) controls Baud Rate, Fast Reset Sequence,
Block Transfer, Last Chassis, Keyboard Type, Handshaking, Last State,
Select Enable, No PLC Comm Error Message.
Switch Bank #3 (SW-3) sets the serial address. The serial address refers
to the address used for triggers received from the serial RS-485 port or
computer keyboard.
Important: Disconnect power from the DL40 Plus before setting any
switch except Select Enable, SW2-9. Select Enable can be changed with
the power on. Switch settings are scanned only on power-up. A new
setting for Select Enable takes effect immediately. All other switches take
effect on power-up or reset.
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
Two DIP switch banks are located on the back of the module. You can
access the DIP switches through a cutout, as shown below. Set DIP
switches using a thin nonconductive object. Do not use a pencil (broken
graphite pieces may short out the internal circuitry).
For details on DIP switch settings, refer to the DL40 Plus User Manual
(Publication No. 2706-6.1).
KEYBOARD
SW1
SW2
RS-485
GND
DIP Switch Settings
(Parallel Port Versions)
12VDC
6
RELAY
250 VAC 3A
L1 L2N
RS-232
DIP Switches
Switch Bank #1 (SW-1) controls: Debug Mode, Fast Reset Sequence,
Keyboard Type, Select Enable.
Switch Bank #2 (SW-2) sets the serial address. The serial address refers
to the address used for triggers received from the serial RS-485 port or
computer keyboard.
Important: Remove power from the DL40 Plus before setting any switch
except Select Enable, SW1-9. Select Enable can be changed with the power
ON. Switch settings are scanned only on power-up. The new setting for
Select Enable takes effect immediately. The new settings for all other
switches take effect when you power-up or reset the DL40 Plus.
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
DIP Switch Settings
(Slave Versions)
7
Access the 10-position DIP switches from the back of the display. Set DIP
switches using a thin nonconductive object. Do not use a pencil (broken
graphite pieces may short out the internal circuitry).
Changes to DIP switches take effect on powerup. The DL40 Plus slave
displays the current settings during its powerup sequence. If you make
changes with the power applied, you will have to cycle power before the
changes take effect. For details on setting DIP switches, refer to the DL40
Plus Slave User Manual (Publication 2706-6.3).
10-Position DIP Switch
O
N
1 2 3 4
5 6 7 8 9 10
↑ Up = ON
↓ Down = OFF
O
N
1 2 3 4
5 6 7 8 9 10
Positions #1 and #2 of DIP Switch #1 set the operating mode. Default
factory setting is DL Slave mode.
Positions #3 and #4 of DIP Switch #1 set the display language. Default
factory setting is English.
Positions #5 and #6 of DIP Switch #1 set the baud rate. Select the baud
rate to match the host device. Default factory setting is 9600.
Positions #7 and #8 of DIP Switch #1 determine the parity. Set the
parity to match the host device. Default factory setting is Even Parity
enabled. Positions #9 and #10 apply to Terminal mode operation.
Positions #1 through #7 of DIP Switch #2 select the serial address of
the DL40 Slave. The address is the binary sum of the value of all the
switches in the Up condition. Default factory setting is address 127.
Positions #8 to #10 are not used.
Additional Information
For additional information on communication port wiring and display
configuration, refer to the DL40 Plus User Manual (Publication 2706-6.1)
or DL40 Plus Slave User Manual (Publication 2706-6.3).
8
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
Specifications
Display Characters
Character Height
Two line display
Four line display
11.3 mm (0.44 inch)
11.3 mm (0.44 inch)
Character Set
English
Cyrillic
International
Standard & Extended ASCII Characters
Standard & Cyrillic (Russian) Characters
Standard & International ISO 8859-1 Characters
Characters per Display Line
20
Viewing Distance - Approximate
7.6 meters (25 feet)
Character Type
Vacuum fluorescent, 5 x 7 dot matrix characters.
Filtered to blue/green color.
Electrical
Input Voltage
100 - 240V AC, 50-60 Hz, 0.60 - 0.25A
Input Power
60VA
Fuse Type
Internal sealed (not user replaceable)
Annunciation Relay
AC Resistive Load
DC Resistive Load
Single N.O. contact
3 Amperes at 240V AC
3 Amperes at 30V DC
Serial Communications
Electrical Interface
RS-232 (EIA-/TIA-232-E)
RS-485 (EIA-485)
Baud Rate
300, 1200, 9600, 19200
2400, 4800 (2706-LV2S, -LV2R, -LV4S, -LV4R
only)
Data Format
7 or 8 data bits; odd, even, or no parity
PLC Remote I/O Communications Port (RIO versions only)
Electrical Interface
Allen-Bradley Remote I/O Link
Remote I/O Baud Rate
57.6K, 115.2K, or 230.4K
Maximum I/O Cable Distance
10,000 feet (2800m) for 57.6K baud
5,000 feet (1400m) for 115.2k baud
2,500 feet (700m) for 230.4K baud
Rack Sizes
1/4 1/2, 3/4, or 1 (any starting module)
Data Transfer Type
Discrete I/O or Block Transfers
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
Parallel Communications Port (Parallel Port versions only)
Electrical Interface
Parallel Input Port
Logic Low
Indeterminate
Logic High
0 to 24 VDC
High True Logic
0 - 0.8 VDC
0.8 - 3.5 VDC
3.5 - 24 VDC
Low True Logic
3.5 - 24 VDC
0.8 - 3.5 VDC
0 - 0.8 VDC
Data Lines
16 Data Lines,- plus 4 strobe lines
Input Current
5mA per data line at 12 Volts DC
Output Supply
+12 Volts DC output voltage source provided,
200mA maximum
Keyboard Port (RIO & Parallel Port Versions Only)
Electrical Interface
Standard Personal Computer Keyboard
IBM PC-XT, -AT compatible
Connector
8-pin DIN (large style connector)
Environmental
Temperature Range - Operating
0° to 60°C (+32° to 140°F)
Temperature Range - Storage
-40° to 85°C (-40° to 185°F)
Humidity
5% to 95% (non-condensing)
Shock
Operating 15G, Non-operating 30G pulses
Vibration
Operating 1.0G, Non-operating 2.5G sinusoidal
Mechanical
Enclosure Type
Weight - Approximate
Catalog No. 2706-LV2S, -LV2P, -LV2R
Catalog No. 2706-LV4S, -LV4P, -LV4R
UL listed for NEMA Type 12, 13, 4, 4X (indoor use
only) when mounted in a suitable enclosure of
Type 12, 13, 4, 4X, IP65, or IP54
3.6 lbs. (1.6 kg)
4.8 lbs. (2.2 kg)
9
10
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
Certifications
UL Listings
UL listed for UL-508 Industrial Control Equipment
Class I, Groups A, B, C, and D Division 2,
Hazardous Locations
UL Listed for Canadian Safety Standards
CSA 22.2 No. 213
European Union Directive
Electromagnetic Compatibility Directive
(89/336/EEC)
EN 50082-2
Generic Emission Standard Industrial Environment
EN 50081-2
Generic Immunity Standard Industrial Environment
IEC 1131-2 Programmable Controllers Equipment Class I
Dataliner DL40 Plus Message Display (Catalog No. 2706-LV2xX, -LV4xX)
11
41061-115-01(A)