Packing Data
PK
Installation Instructions
This document describes how to install a Dataliner DL10 display in a panel or
enclosure and connect power.
•
•
•
•
•
•
•
•
European Union Directive Compliance
wiring and safety guidelines
enclosures
required tools
mounting dimensions
clearances
installing the DL10 display in a panel
connecting AC power
For more information on the Dataliner DL10 display, refer to the Dataliner DL10
User Manual (Publication 2706-800).
2
Dataliner DL10 Message Display
European Union Directive Compliance
If a Dataliner Message Display is installed within the European Union or EFTA
regions and has a CE mark, the following regulations apply.
EMC Directive
This apparatus is tested to meet Council Directive 89/336/EEC Electromagnetic
Compatibility (EMC) using a technical construction file and the following standards
in whole or in part.
• EN 50081-2
• EN 50082-2
EMC – Generic Emission Standard, Part 2 Industrial Environment
EMC – Generic Immunity Standard, Part 2 Industrial Environment
Dataliner products are intended for use in an industrial environment.
Low Voltage Directive
This apparatus is tested to meet Council Directive 73/23/EEC Low Voltage (LVD)
with amendments, including 93/68/EEC using the pertinent sections of the following
standards.
• EN 61131-2:1992
• EN 60950:1992
Programmable Controllers - Equipment
Requirements and Tests
Safety of Information Technology Equipment
Intended Use of Product
According to these Standards, the factor which determines, for EMC purposes,
whether an apparatus is deemed to be “Industrial” or “Residential, commercial
and light industrial”, is given in Clause 1 of EN50081-2 as follows:
Dataliner DL10 Message Display
3
Apparatus covered by this standard is not intended for connection to a public
mains network but is intended to be connected to a power network supplied
from a high- or medium-voltage transformer dedicated for the supply of an
installation feeding a manufacturing or similar plant.
This product is intended for use solely in an industrial environment as defined
above. When installed in Europe, any other application is in contravention of
European Union Directives, and a breach of these laws.
Wiring and Safety Guidelines
Install the Dataliner DL10 display using publication 70E, Electrical Safety
Requirements for Employee Workplaces. In addition to the NFPA general
guidelines, follow these recommendations:
• Connect the Dataliner display to its own branch circuit. The input power
source should be protected by a fuse or circuit breaker rated at no more than
15 amps.
• Route incoming power to the DL10 display by a separate path
from the communications cable.
• Where power and communication lines must cross, they should cross at right
angles. Communications lines can be installed in the same conduit as low
level DC I/O lines (less than 10 Volts).
• Grounding minimizes noise from Electromagnetic Interference (EMI) and is
a safety measure in electrical installations. To avoid EMI, shield and ground
cables appropriately.
• A source for grounding recommendations is the National Electrical Code
published by the National Fire Protection Association of Boston.
Enclosures
Mount the DL10 display in a panel or enclosure to protect the internal circuitry.
The display meets NEMA Type 12/13, 4 (indoor use), and 4X (for stainless steel
faceplate versions) ratings only when properly mounted in a panel or enclosure
with the equivalent rating.
4
Dataliner DL10 Message Display
Allow enough space within the enclosure for adequate ventilation. Consider heat
produced by other devices in the enclosure. The ambient temperature around the
display must be between 0 and 50C (32 and 122F).
Make provisions for accessing the back panel of the display for wiring,
maintenance, and troubleshooting.
Required Tools
Other than the tools required to make the panel cutout, the tools required for
installation are:
• 3/8 inch deep well socket wrench
• small slotted screwdriver
• torque wrench (in. / lbs).
Installing Display in Panel
To install the Dataliner display:
ATTENTION: Disconnect all electrical power from the panel before
!
making cutout.
Make sure the area around the panel cutout is clear.
Take precautions so that metal cuttings do not enter any components
that may already be installed in panel.
Failure to follow this warning may result in personal injury or damage
to the panel components.
Dataliner DL10 Message Display
5
Mounting the DL10
The following figures provide panel cutout dimensions and overall dimensions for
the DL10.
You can mount the DL10 in a custom panel or enclosure. Dataliner enclosure
Catalog Number 2706-NE2 (four-line display) is available. When the DL10 is
properly installed, the faceplate of the DL10 provides a NEMA Type 12/13, Type 4
(indoor use only), and 4X (for stainless steel faceplate version) enclosure integrity.
To install the DL10, perform the following steps:
1. Cut and drill the appropriate mounting holes in the enclosure or panel.
!
ATTENTION: Do not install the display in the panel or enclosure until
all cutouts and holes are completed. Metal filings accumulated when
cutting and drilling could enter ventilation holes on the display and cause
the display to fail.
2. Remove the six mounting nuts from the hardware kit included with the DL10.
3. Position the DL10 in the panel or enclosure mounting hole.
4. Install and tighten the six nuts on the mounting studs to a torque of 14 in•lbs
(1.6N•m) each.
!
ATTENTION: Mounting nuts must be tightened to a torque of 14
inch-pounds to provide a proper seal and to prevent potential damage to
the display. Allen-Bradley assumes no responsibility for water or
chemical damage to the display or other equipment within the enclosure
because of improper installation.
6
Dataliner DL10 Message Display
Mounting Dimensions
Figure 1
Four Line Dimensions
Dimensions in Inches (Millimeters)
13.30
(337.8)
0.12 Typ.
(3.2)
Top View
Six 0.50 (12.7)
Mounting
Studs
0.53
(13.5)
14.37
(365.0)
8.83
(224.3)
1.63
(4.14)
6.18
(157.0)
2.94
(74.7)
Front View
0.125 (3.2) (Gasket Thickness)
0.104 (2.6)
(Panel
Thickness)
0.53
(13.5)
5.12
(130)
Side View
4.44
(112.8)
5.11
(129.8)
0.53
(13.5)
Dataliner DL10 Message Display
7
Clearances
Allow adequate clearances for mounting, air flow, maintenance, and wiring. See
Figure 2.
Figure 2
Minimum Mounting Clearances
Side, Top and Bottom Clearances
Leave 25 mm (1 in.)
for Mounting and Air Flow
Display Cutout
Front View
Leave 25 mm (1 in.)
for Mounting and Air Flow
Leave 38 mm (1.5 in.)
for Mounting and Air Flow
Leave 25 mm (1 in.)
for Mounting and Air Flow
8
Dataliner DL10 Message Display
Cutout Dimensions
Figure 3 shows the required cut-out dimensions.
Figure 3
Dimensions in Inches (Millimeters)
Four Line DL10 Display
0.218 (5.5)
DIA. HOLE
(6 PLACES)
13.87
(352.3)
6.94 (176.1)
0.12
(3.0)
6.81 (173.0)
13.62 (345.9)
Cut Out
5.26
(133.6)
Cut Out
5.68
(144.3)
Dataliner DL10 Message Display
9
EMI Power-Line Filters (EU Installations Only)
DL10 displays intended for use in the European Union require a power-line filter.
One line filter is required for each installed display. Two filter models are available.
These filters are functionally identical, they differ only in termination style.
Schaffner Part No.
Termination Style
FN 660-3/06
Fast-On (Spade) connectors
FN 660-3/07
Wire leads
Line filters are available from an authorized Schaffner distributor.
Part Number
(FN 660-3/07)
27mm
(1.06 in.)
30mm
(1.18 in.)
12 mm
(0.47 in.)
65 mm
(2.56 in.)
75 mm
(2.95 in.)
85 mm
(3.35 in.)
Part Number
(FN 660-3/06)
5.3 mm
(0.21 in.)
54 mm
(2.13 in.)
When properly installed, power-line filters prevent interference currents in the
power lines. Interference currents can affect other devices on the same power
line and other nearby equipment. Connect the Dataliner message display to the
power-line filter as shown on the following page.
10
Dataliner DL10 Message Display
Connecting AC Power
The table below shows the electrical ratings for the Dataliner DL10 display.
Catalog Number
Supply Voltage
Power Consumption
2706-A41C
2706-A41J
120V ac, 60 Hz
55 VA maximum
2706-A42C
2706-A42J
240V ac, 50 Hz
55 VA maximum
!
ATTENTION: Terminal 3 (Protective Earth) must be connected to a
reliable low impedance earth ground to protect the display from electrical
noise. This ground connection will also protect personnel from electrical
shock if the electronics short to the DL10 case.
!
ATTENTION: The Dataliner DL10 display is designed for safe use
when installed in a suitably rated NEMA Type 12, 13, 4X (indoor use
only), IP54 or IP65 enclosure.
ATTENTION: Do not apply power to the display until all wiring
!
connections have been made. Failure to do so may result in electrical
shock.
Dataliner DL10 Message Display
11
Wiring Guidelines (EU Installations Only)
10 cm (4 in.) Maximum
L1
To
Dataliner
AC Input
L2N
L1
L2N
To
AC Mains
Supply
For installations within the European Union use the following guidelines to minimize
Radio Frequency Interference (RFI) and achieve maximum Electromagnetic
Compatibility (EMC).
• Follow all local safety regulations regarding proper grounding.
• Output leads from the power-line filter to the Dataliner must be 10 cm (4 in.) or
less.
• Both Dataliner and power-line filter must be connected to a low impedance earth
ground.
• All parts of the grounding system must be connected together with low
impedance connections. Keep all ground connections as short as possible.
• Power-line filter must be connected to earth ground before connecting the power
source.
• Do not run signal wiring and power wiring in the same conduit.
• When control or communication wires must cross, they should cross at an angle
as close to 90 degrees as possible.
• Follow Dataliner display shielded cable requirements as specified in the user
manual.
• Make sure cable shielding connections and terminations are connected as
specified in the appropriate Dataliner User Manual.
• Keep the filter line side leads well separated from the load side leads.
12
Dataliner DL10 Message Display
Wiring Diagram
The following diagram shows how to connect the power-line filter for
installations within the European Union. For non-European Union installations,
the power-line filter can be omitted. For all other wiring connections refer to the
DL10 User Manual (Publication 2706-800).
240 VAC
L1 L2N
1
2
3
10 cm (4 in.)
Maximum
LOAD
FN 660
LINE
FILTER
LINE
L1
L2N
RS-232
RS-422
IN
4
–
+
OUT
–
+
5
6
7
8
9
I
N
O
U
T
G
N
D
10
11
12
Dataliner DL10 Message Display
13
Fuse Replacement
The four line Series B and later DL10 display has two fuses. To determine if one
of the fuses is bad, remove power to the display and then remove the top cover of
the display by loosening the three cover screws. Check and replace one or both
fuses if necessary.
Main Fuse – 1.5 Amp, Type MDL, 250V ac
FU1 on Auxiliary Power Supply – 0.375 Amp, Type MDL, 250V ac.
Top View (cover off)
Main Fuse
Auxiliary Power
Supply Board
Auxiliary Power
Supply Fuse
(FU1)
Display Front
14
Dataliner DL10 Message Display
AC Power Connections
Connection
120/240V ac, 3 Wire
U.S. Color Code
120/240V ac, 3 Wire
European Harmonized Color Code
L1
Black (Line)
Brown (Line)
L2N
White (Neutral)
Blue (Neutral)
P.E.
Green (Earth Ground)
Green/Yellow (Protective Earth)
Additional Information
For additional information on communication port wiring and display
configuration, refer to the Dataliner DL10 User Manual (Publication 2706-800).
Dataliner DL10 Message Display
Notes:
15
Worldwide representation.
Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC •
Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador •
Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India •
Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia •
Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal •
Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South
Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates •
United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1)
414 382-2000 Fax: (1) 414 382-4444
41061-017-01(B)
Copyright 1999 Allen-Bradley Company, Inc. Printed in USA
">