LENNOX CLIMATIC 10 MODBUS OPTION User manual
Below you will find brief information for CLIMATIC 10 MODBUS OPTION. This user manual discusses how to configure the CLIMATIC 10 for use with a MODBUS network, which allows you to control one or more units through the CLIMATIC 10 to a BMS system using a single network. The manual includes wiring diagrams and instructions for setting up the CLIMATIC 10 and GATEWAY, along with a detailed address map for the MODBUS network.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
8
REV 1 CLIMATIC 10 MODBUS OPTION Date : 09.11.05 1. GENERAL DESCRIPTION. 1.1 ¿How is the net composed? The purpose of this net is connecting one or several units through the CLIMATIC 10 to a BMS system. For this we use the interface GATEWAY that allows us to use a net of CLIMATIC 10 through MODBUS protocol. We can connect up to 16 units with the CLIMATIC 10 thermostat ( we can connect together different sizes ) to the same interface, and up to 16 GATEWAYs in the same net. GATEWAY nº1 GATEWAY nº2 GATEWAY nº3 (. . . . GATEWAY nº16 Ctrol 1 Ctrol 1 Ctrol 1 Ctrol 1 Ctrol 2 Ctrol 2 Ctrol 2 Ctrol 2 Ctrol 3 Ctrol 3 Ctrol 3 Ctrol 3 (...) Ctrol 16 (...) (...) Ctrol 16 Ctrol 16 (...) Ctrol 16 The CLIMATIC 10 must be specific, and substitutes the standard controller of the unit. There is not possibility of programmable option for this thermostat. In the MODBUS net , it is posible to install different controllers or devices , providing the same configuration of communication is used ( protocol RTU , same communication speed , same parity , etc……. ) and connection RS485 . 1.2 ¿What can be switched on to this net? With this system , we can control the following functions of the unit: • • • • • • • Selection of mode of functioning: OFF/AUTO/FAN/COOL/HEAT and fan mode between FAN ON/AUTO. Modify the setpoints : confort, absence and nuit Read alarm status and reset alarms Read air ambient temperature, condensing temperature ( in some programs) and outdoor ambient temperarture ( only if the optional freecooling is included) Read inlets /outlets status Register of hours of functionning (for compressor and fans) Keypad blocking /unblocking 1/8 CLIMATIC 10 MODBUS OPTION • REV 1 Date : 09.11.05 How to supply. In every installation it is necessary to include : One terminal CLIMATIC 10 with RS485 connection for each of the units connected. This CLIMATIC will be programmed according the type of unit commanded. One GATEWAY at least for every 16 units. Connections between the unit and the terminal CLIMATIC 10 must be done according the wiring diagram. GATEWAY is supplied without connecting/wiring and must be installed in an appropriate place , power supplied and communicated through bus connection. 2. WIRING. The connections between terminals CLIMATIC 10 must be done with screened cable section AWG 20 (0,5mm2) o AWG 22(0.32 ÷ 0.38 mm2) with a capacity between wires less than 100 pF/m. The screen shall be preferable of made continous wiring (Models Belden 8761 y 8762 fulfill this requirements) . In the last terminal CLIMATIC 10 a 120 Ohm resistance shall be installed. Power supply of GATEWAY is 230V , and it has to fulfill all the requirements related to electricity norm requirements. In the wiring diagram above , the connection to a net RS 485 is represented. If we want to connect only one GATEWAY directly to a computer , we can use through the MODEM connection a RS 232 wiring according the following equivalence table. It has to be taken into account that in the configuration , it has to be defined the type of connection ( RS 232 or RS 485 ) to the GATEWAY . 2/8 CLIMATIC 10 MODBUS OPTION REV 1 Date : 09.11.05 3. CONFIGURATION 3.1 CLIMATIC 10 – GATEWAY. There is some parameters in CLIMATIC 10 that control the communication L1: Adress 1..16. Every CLIMATIC 10 connected to a GATEWAY must have an address between 1 and 16 . L6: Protocol mode. Communication protocol with the net. Its value must be L6=1 for connecting with the GATEWAY. L7: Speed. Communicating speed between GATEWAY and CLIMATIC 10 controls. Set up at L7=3 (9600 bauds). This parameter must not be misunderstood with the communication speed between the system and the GATEWAY. 3.2 GATEWAY – BMS. The configuration of the GATEWAY allow reading and writing the following parameters, which are necessary to get settled for a correct operation of the device. The configuration is done through a software supplied together with the GATEWAY. • • • • Adress of the GATEWAY in the MODBUS net Number of terminals in the CLIMATIC 10 net. Communication speed between the GATEWAY and the CLIMATIC 10 Communication parameters between the GATEWAY and the supervisión net ( speed, word lenght, stopping bits , parity) To use this configuration software it is necessary to wire a cable from the “config” connection of the GATEWAY to the computer RS232 port, like the one shown in the following diagram. Once made the configuration , this connection must be removed. To read the configuration of the GATEWAY , the following program has to be executed A:>readmb0 /Com /Com = /COM1,/COM2, is the port in which the GATEWAY is connected. Following data will appear in the display: RDMOD32 Version 2.0 - 2002 Carel Software VERSION : MB0 3.1 14/07/04 ADDRESS : 01 SLAVES : 01 MODBUS PORT PARAMETER bauds : 9600 bits : 8 stop : 1 parity : NONE CAREL PORT BAUD RATE : 9600 Mode: Rs485 Software Version Adress MODBUS of GATEWAY Number of CLIMATIC 10 connected Communication MODBUS configuration Communication CLIMATIC 10 configuration net 3/8 CLIMATIC 10 MODBUS OPTION REV 1 Date : 09.11.05 To change this configuration we use: A:>writemb0 /Com Modbus_address num_of_slave Carel_baud Modbus_baud stop_bit parity /Com = /COM1,/COM2 Modbus_address = 1..16 num_of_slave = 1..16 Carel_baud = 300, 600, 1200, 2400, 4800, 9600, 19200 Modbus_baud = 600, 1200, 2400, 4800, 9600 stop_bit = 1, 2 parity = ODD, EVEN, MARK, SPACE, NONE Port connection for GATEWAY GATEWAY address in the MODBUS net Number of thermostats to connect Communication speed between GATEWAY and CLIMATIC 10( it has to be the same value than the parameter L7 of CLIMATIC 10 and it is set up with the value 9600) Configuration of the net MODBUS connection For example , to configurate through port com1, the GATEWAY with adress 1, which is connected at the same time to 4 CLIMATIC 10 with a speed of 9600 bauds, and to the MODBUS net through 9600 bauds, 1 bit stop and NONE parity , it has to be written: Writemb0 /com1 1 4 9600 9600 1 NONE The CLIMATIC mode of communications has to be configurated through jumpers , as shown in the following chart: A: GATEWAY communication (1-2) RS 232 (2-3) RS 422-RS 485 B: GATEWAY communication (1-2) RS 485 (2-3) RS 422 (Not used) C: Communication with CLIMATIC 10 (1-2) RS 485 (necessary selection) (2-3) RS 422 (Not used in CLIMATIC 10) D: Relay signal ( not used) (1-2) Normally open (2-3) Normally closed 4/8 CLIMATIC 10 MODBUS OPTION REV 1 Date : 09.11.05 4. ADRESS MAP. There are two kind of addresses: Digital addresses : they have to be read with MODBUS functions 01 or 02 and written with functions 05 or 15. Analogic adresses :that have to be read with the MODBUS functions 03 or 04 , and written with functions 06 or 16. Adresses shown with “R” digit are readable , those shown with “W” are writable and those shown as “R/W” are both readable and writable. For CLIMATIC 10 adressed with “n” ( from 1 to 16) inside the GATEWAY , adresses are the following : DIGITALS 1+200*(n-1) ID1 value ( if it is available) R 2+200*(n-1) ID2 value ( if it is available) R 3+200*(n-1) ID3 value ( if it is available) R 4+200*(n-1) Alarm reset W 9+200*(n-1) ON/OFF 16+200*(n-1) Alarm ANALOGICAS 1+256*(n-1) 2+256*(n-1) 3+256*(n-1) 4+256*(n-1) 5+256*(n-1) 6+256*(n-1) 7+256*(n-1) 8+256*(n-1) 33+256*(n-1) 34+256*(n-1) 37+256*(n-1) Temperature value B1 Temperature value B2 Temperature value B3 Actual Setpoint Absence Setpoint Confort Setpoint Night setpoint Differential Hours counter compressor 1 Hours counter compressor 2 Hours counter fan 129+256*(n-1) Outlet status (relays ) 135+256*(n-1) 136+256*(n-1) R/W R R R R R/W R/W R/W R/W R/W R R R R Unit functionning mode R/W Fan functionning mode R/W 5/8 0: open 1: closed 0: open 1: closed 0: open 1: closed 1: Reset 0: OFF 1: ON 0=no 1=yes Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 Value in K hours multiplied by 10 Value in K hours multiplied by 10 Value in K hours multiplied by 10 Bit 0: Relay 7 Bit 1: Relay 6 Bit 2: Relay 5 Bit 3: Relay 4 Bit 4: Relay 3 Bit 5: Relay 2 Bit 6: Relay 1 0: AUTO 1: COOL 2: HEAT 3: FAN 0: OFF 1: AUTO 2: SPEED1 3: SPEED2 4: SPEED3 CLIMATIC 10 MODBUS OPTION 137+256*(n-1) Alarm 1 R 138+256*(n-1) Alarm 2 R 142+256*(n-1) 143+256*(n-1) 186+256*(n-1) Setpoint category R/W Automatic mode of functioning R Keypad blocking R/W REV 1 Date : 09.11.05 Bit 0: HR 1 Bit 1: HR 2 Bit 2: HR F Bit 3: HI T Bit 4: LO T Bit 5: E ID Bit 6: REM Bit 7: E DF Bit 8: EE Bit 9: EE Bit 10: n/u Bit 11: E SR Bit 12: E TR Bit 13: E1 Bit 14: E2 Bit 15: E3 Bit 0: P AL Bit 1: Th F Bit 2: n/u Bit 3: n/u Bit 4: HI T Bit 5: LO H Bit 6: LO P 0: ABSENCE 1: CONFORT 2: NIGHT 3: STAND-BY 0: AUTO 1: COOL 2: HEAT 3: FAN ONLY 0:Not blocked 1:Blocked 5. COMMANDS DESCRIPTION. The actions done from the MODBUS commands MODBUS , they are reflected automatically in the CLIMATIC 10 and viceversa. The handling through the Terminal is operative unless the keypad is blocked. 5.1 FUNCTIONNING With digital adress 9+200*(n-1) we start and stop the unit. This is a readable/writable parameter. With 1 value we start the unit and with 0 value we stop the unit. With analogic adress 135+256*(n-1) we can see /select the mode of functionning . The way of selecting the different modes of functioning is writing the values : 0 Auto, 1 : Cool , 2: Heat and 3 : Fan. In the analogic adress 143+256*(n-1) we can see the real mode of functionning if we have previously selected automatic. This address will show 1 if the unit works in cooling mode, 2 if the unit works in heating mode and 3 if the unit works in fan mode. With digital adress 136+256*(n-1) we can change fan status between 1: Auto and 2 :Continuous 6/8 CLIMATIC 10 MODBUS OPTION REV 1 Date : 09.11.05 5.2 SETPOINTS With the analogic adress 142+256*(n-1) we can select or see the actual setpoint . The way of selecting the different setpoints is introducing the following values : 0; Absence, 1; Confort ; 2 Night and 3 Stand-by Set points can be modified in the following addresses: . 4+256*(n-1) 5+256*(n-1) 6+256*(n-1) 7+256*(n-1) 8+256*(n-1) Actual Setpoint Absence Setpoint Confort Setpoint Nigth Setpoint Differential R/W R/W R/W R/W R/W Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 5.3 ALARMS. Digital adress 16+200*(n-1) will have value when there is an alarm. This adress is readable only. This alarm can be reset by writing 1 in the digital adress 4+200*(n-1) . This address is only writable. Reset will be made if the default reason has been solve. The value will reset to 0 after alarm reset. In the analogic adresses 137+256*(n-1) and 138+256*(n-1) we can get the alarms detailed in binary code . The meaning of each bit is shown in the following table. This parameters are only readable. 137+256*(n-1) Alarm 1 R 138+256*(n-1) Alarm 2 R Bit 0: HR 1 Bit 1: HR 2 Bit 2: HR F Bit 3: HI T Bit 4: LO T Bit 5: E ID Bit 6: REM Bit 7: E DF Bit 8: EE Bit 9: EE Bit 10: n/u Bit 11: E SR Bit 12: E TR Bit 13: E1 Bit 14: E2 Bit 15: E3 Bit 0: P AL Bit 1: Th F Bit 2: n/u Bit 3: n/u Bit 4: HI T Bit 5: LO H Bit 6: LO P 5.4 HOURS COUNTER In the analogic adresses we can see the hours of functioning of each compressor and fan. 33+256*(n-1) 34+256*(n-1) 37+256*(n-1) Hours counter compressor 1 Hours counter compressor 2 Hour counter fan 7/8 CLIMATIC 10 MODBUS OPTION REV 1 Date : 09.11.05 These adresses can only be readable , and show the hours of functioning in Khours x 10. So if one of the adresses show 12 , that means 1200 hours. 5.5 KEYPAD BLOCKING Analogic adress “186+256*(n-1)” allow the blocking of the keypad CLIMATIC 10. With value 1 , the keypad gets blocked and with value 0 the keypad comes again operative. 5.6 INLETS/OUTLETS Digital inlets can be displayed in the following adresses : 1+200*(n-1) ID1 value (if it is available) R 2+200*(n-1) ID2 value ( if it is available) R 3+200*(n-1) ID3 value ( if it is available) R 0: open 1: closed 0: open 1: closed 0: open 1: closed Inlet sensors values can be displayed in the following analogical adresses: 1+256*(n-1) 2+256*(n-1) 3+256*(n-1) Temperature value B1 Temperature value B2 Temperature value B3 R R R Value multiplied by 10 Value multiplied by 10 Value multiplied by 10 The relays outlet status can be displayed in the following analogic adress , according the following meanings: 129+256*(n-1) Outlet status (relays) R 8/8 Bit 0: Relay 7 Bit 1: Relay 6 Bit 2: Relay 5 Bit 3: Relay 4 Bit 4: Relay 3 Bit 5: Relay 2 Bit 6: Relay 1
advertisement
Key Features
- Connect up to 16 units with the CLIMATIC 10 thermostat to the same interface
- Connect up to 16 GATEWAYs in the same net
- Control units through the CLIMATIC 10 to a BMS system
- Control various functions of the unit such as setpoints, alarms, and fan modes
- Use a MODBUS network for communication
- Install different controllers and devices on the same MODBUS network
- Configure the GATEWAY for reading and writing specific parameters
- Read and write digital and analogic addresses using MODBUS functions
- Block the keypad of the CLIMATIC 10 remotely
- Monitor inlets/outlets status
Frequently Answers and Questions
How is the CLIMATIC 10 net composed?
The CLIMATIC 10 net is composed of one or more units connected to a BMS system using the GATEWAY interface. This interface allows for a network of CLIMATIC 10 units to communicate using the MODBUS protocol. You can connect up to 16 units with the CLIMATIC 10 thermostat and up to 16 GATEWAYs in the same network.
What can be switched on to this net?
You can control various functions of the unit through the CLIMATIC 10 net, including selection of mode of functioning, modification of setpoints, reading alarm status and resetting alarms, reading air ambient temperature, condensing temperature, and outdoor ambient temperarture, reading inlets/outlets status, registering hours of functioning for compressor and fans, and keypad blocking/unblocking.
What is the function of the GATEWAY in the CLIMATIC 10 net?
The GATEWAY serves as an interface between the CLIMATIC 10 units and the BMS system. It allows communication between the units and the BMS using the MODBUS protocol. It also handles the configuration of communication parameters between the CLIMATIC 10 units and the BMS system.