Timer Product Conversion Differences

Timer Product Conversion Differences
ABB
SSAC Product Line Conversion Notification February 11, 2005
ESD5 Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Tolerance (Factory Calibration)
Operational
Package
Environmental
Weight
0.2 s ... 1000 m in 6 adjustable ranges or fixed
+/-10 %
2005 Generation II Design
0-5 MΩ.
0.1 s ... 1000 m in 6 adjustable ranges or fixed
+/-5%
Terminal connections are different. Terminals 2,3
are input, T1 is the output
0-100 KΩ. (see notes)
Surface mount with two #8 (M4 x 0.7) screw
Onboard adjust requires VTP Plug-on
Modules
2.5 x 3.5 x 1.22 in. (63.5 x 88.9 x 31 mm)
Surface mount with one #10 (M5 x 0.8) screw
Terminals are oriented differently. Can be ordered
as onboard adjust (see notes)
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
≅ 4.8oz (136 g)
≅ 2.4 oz (68 g)
Terminals 1,3 are line input, T2 is the output.
RT Values (for external adjustment)
Mechanical
Mounting
RT Terminals
Pre 2005 Design
8
T1
Pre 2005 Design
T2
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Initiate switch
RT = External Adjustment Potentiometer(s)
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 11, 2005
ESDR Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
Tolerance (Factory Calibration)
+/-10 %
Time ranges 0 and 5 cannot be combined in
the same unit.
0-5 MΩ.
Operational
RT Values (for external adjustment)
Mechanical
Mounting
RT Terminals
Package
Environmental
Weight
(+)
(−)
4 5
< +/-5%
Time ranges can be combined in any combination.
0-100 KΩ. (see notes)
Surface mount with two #8 (M4 x 0.7) screw
Onboard adjust requires VTP Plug-on
Modules
2.5 x 3.5 x 1.22 in. (63.5 x 88.9 x 31 mm)
Surface mount with one #10 (M5 x 0.8) screw
≅ 4.8oz (136 g)
≅ 2.4 oz (68 g)
(-) Positive switching
(+) Negative switching
3 2
2005 Generation II Design
Terminals are oriented differently (see notes)
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
(+)
(−)
(-) Positive switching
(+) Negative switching
1
6 7
8
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
RT = External Adjustment Potentiometer(s)
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 28, 2005
HRD3 Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Repeat Accuracy
Tolerance (Factory Calibration)
RT Values (for external adjustment)
Input
Pre 2005 Design
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−0.5 %
+/−1%, +/−10%
0-1 MΩ.
2005 Generation II Design
0.1 s ... 100 m in 5 adjustable ranges or fixed
+/-0.5% or 20 ms, whichever is greater
+/−1%, +/−5%
0-100 KΩ. (see note)
12 VDC, 24VAC/DC: -15% … +20%
120 & 230VAC: -20%…+10%
12 VDC, 24VDC: -15% … +20%
24 … 230 VAC: -20% … +10%
Single pole, normally open, non-isolated
SPDT Non Isolated
Contact Ratings @ 125 VAC
General purpose; UL: 15A, CSA: 30A
Motor load; UL: 1HP, CSA: 1HP
N.O.
240 VAC
General purpose; UL: 10A, CSA: 10A
Motor load; UL: 1HP, CSA: 1HP
Tolerance
Output
Form
30 VDC
Resistive; UL: 20A, CSA: 20A
Mechanical -- 1 x 106, Electrical -- 1 x 105
Life
Mechanical
Mechanical
Connection
Environmental
Operating Temperature
Pre 2005 Design
SPDT-N.O. SPDT-
General Purpose 125/240 VAC
Resistive
125/240 V AC
Motor Load
28 V DC
125 V AC
240 V AC
30 A
30 A
20 A
1 hp*
2 hp**
15 A
15 A
10 A
¼ hp**
1 hp**
Mechanical -- 1 x 106;
Electrical -- 1 x 105, *3 x 104, **6,000
Terminal layout is different.
Terminal connections are different.
-20°C ... +60°C
-40°C ... +60°C
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 28, 2005
HRD9 Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Repeat Accuracy
Tolerance (Factory Calibration)
Reset Time
RT Values (for external adjustment)
Input
Tolerance
Output
Form
Contact Ratings @ 125 VAC
240 VAC
30 VDC
Pre 2005 Design
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−0.5 %
+/−1%, +/−10%
≤ 500 ms
0-1 MΩ.
0.1 s ... 100 m in 5 adjustable ranges or fixed
+/-0.5% or 20 ms, whichever is greater
+/−1%, +/−5%
≤ 150 ms
0-100 KΩ. (see note)
12 VDC, 24VAC/DC: -15% … +20%
120 & 230VAC: -20%…+10%
12 VDC, 24VDC: -15% … +20%
24 … 230 VAC: -20% … +10%
Single pole, normally open, non-isolated
General purpose; UL: 15A, CSA: 30A
Motor load; UL: 1HP, CSA: 1HP
General purpose; UL: 10A, CSA: 10A
Motor load; UL: 1HP, CSA: 1HP
SPDT Isolated
Resistive; UL: 20A, CSA: 20A
Mechanical -- 1 x 106, Electrical -- 1 x 105
Life
2005 Generation II Design
Mechanical
Mechanical
Connection
Environmental
Operating Temperature
Pre 2005 Design
SPDT-N.O.
30 A
30 A
20 A
1 hp*
2 hp**
General Purpose 125/240 VAC
Resistive
125/240 V AC
28 V DC
Motor Load
125 V AC
240 V AC
SPDT-N.O.
15 A
15 A
10 A
¼ hp**
1 hp**
Mechanical -- 1 x 106;
Electrical -- 1 x 105, *3 x 104, **6,000
Terminal layout is different.
Terminal connections are different.
-20°C ... +60°C
-40°C ... +60°C
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
UTL = Optional Untimed Load
S1 = Initiate Switch
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 28, 2005
HRDB Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Repeat Accuracy
Tolerance (Factory Calibration)
Reset Time
RT Values (for external adjustment)
Input
Tolerance
Output
Form
Contact Ratings @ 125 VAC
240 VAC
30 VDC
Pre 2005 Design
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−0.5 %
+/−1%, +/−10%
≤ 500 ms
0-1 MΩ.
0.1 s ... 100 m in 5 adjustable ranges or fixed
+/-0.5% or 20 ms, whichever is greater
+/−1%, +/−5%
≤ 150 ms
0-100 KΩ. (see note)
12 VDC, 24VAC/DC: -15% … +20%
120 & 230VAC: -20%…+10%
12 VDC, 24VDC: -15% … +20%
24 … 230 VAC: -20% … +10%
Single pole, normally open, non-isolated
General purpose; UL: 15A, CSA: 30A
Motor load; UL: 1HP, CSA: 1HP
General purpose; UL: 10A, CSA: 10A
Motor load; UL: 1HP, CSA: 1HP
SPDT Isolated
Resistive; UL: 20A, CSA: 20A
Mechanical -- 1 x 106, Electrical -- 1 x 105
Life
2005 Generation II Design
Mechanical
Mechanical
Connection
Environmental
Operating Temperature
Pre 2005 Design
SPDT-N.O.
General Purpose 125/240 VAC
Resistive
125/240 V AC
28 V DC
Motor Load
125 V AC
240 V AC
SPDT-N.O.
30 A
30 A
20 A
1 hp*
2 hp**
15 A
15 A
10 A
¼ hp**
1 hp**
Mechanical -- 1 x 106;
Electrical -- 1 x 105, *3 x 104, **6,000
Terminal layout is different.
Terminal connections are different.
-20°C ... +60°C
-40°C ... +60°C
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
UTL = Optional Untimed Load
S1 = Initiate Switch
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 28, 2005
HRDI Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Repeat Accuracy
Tolerance (Factory Calibration)
RT Values (for external adjustment)
Input
Tolerance
Output
Form
Contact Ratings @ 125 VAC
240 VAC
30 VDC
Pre 2005 Design
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−0.5 %
+/−1%, +/−10%
0-1 MΩ.
0.1 s ... 100 m in 5 adjustable ranges or fixed
+/-0.5% or 20 ms, whichever is greater
+/−1%, +/−5%
0-100 KΩ. (see note)
12 VDC, 24VAC/DC: -15% … +20%
120 & 230VAC: -20%…+10%
12 VDC, 24VDC: -15% … +20%
24 … 230 VAC: -20% … +10%
Single pole, normally open, non-isolated
General purpose; UL: 15A, CSA: 30A
Motor load; UL: 1HP, CSA: 1HP
General purpose; UL: 10A, CSA: 10A
Motor load; UL: 1HP, CSA: 1HP
SPDT Non Isolated
Resistive; UL: 20A, CSA: 20A
Mechanical -- 1 x 106, Electrical -- 1 x 105
Life
2005 Generation II Design
Mechanical
Mechanical
Connection
Environmental
Operating Temperature
Pre 2005 Design
General Purpose 125/240 VAC
Resistive
125/240 V AC
28 V DC
Motor Load
SPDT-N.O.
30 A
30 A
20 A
SPDT-N.O.
15 A
15 A
10 A
1 hp*
2 hp**
¼ hp**
1 hp**
125 V AC
240 V AC
Mechanical -- 1 x 106;
Electrical -- 1 x 105, *3 x 104, **6,000
Terminal layout is different.
Terminal connections are different.
-20°C ... +60°C
-40°C ... +60°C
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 28, 2005
HRDM Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Repeat Accuracy
Tolerance (Factory Calibration)
RT Values (for external adjustment)
Input
Tolerance
Output
Form
Contact Ratings @ 125 VAC
240 VAC
30 VDC
Pre 2005 Design
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−0.5 %
+/−1%, +/−10%
0-1 MΩ.
0.1 s ... 100 m in 5 adjustable ranges or fixed
+/-0.5% or 20 ms, whichever is greater
+/−1%, +/−5%
0-100 KΩ. (see note)
12 VDC, 24VAC/DC: -15% … +20%
120 & 230VAC: -20%…+10%
12 VDC, 24VDC: -15% … +20%
24 … 230 VAC: -20% … +10%
Single pole, normally open, non-isolated
General purpose; UL: 15A, CSA: 30A
Motor load; UL: 1HP, CSA: 1HP
General purpose; UL: 10A, CSA: 10A
Motor load; UL: 1HP, CSA: 1HP
SPDT Non Isolated
Resistive; UL: 20A, CSA: 20A
Mechanical -- 1 x 106, Electrical -- 1 x 105
Life
2005 Generation II Design
Mechanical
Mechanical
Connection
Environmental
Operating Temperature
Pre 2005 Design
General Purpose 125/240 VAC
Resistive
125/240 V AC
28 V DC
Motor Load
SPDT-N.O.
30 A
30 A
20 A
SPDT-N.O.
15 A
15 A
10 A
1 hp*
2 hp**
¼ hp**
1 hp**
125 V AC
240 V AC
Mechanical -- 1 x 106;
Electrical -- 1 x 105, *3 x 104, **6,000
Terminal layout is different.
Terminal connections are different.
-20°C ... +60°C
-40°C ... +60°C
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 28, 2005
HRDR Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Repeat Accuracy
Tolerance (Factory Calibration)
Reset Time
RT Values (for external adjustment)
Input
Tolerance
Output
Form
Contact Ratings @ 125 VAC
240 VAC
30 VDC
Pre 2005 Design
0.2 s ... 500 m in 6 adjustable ranges or fixed
+/−0.5 %
+/−10%
≤ 250 ms
0-1 MΩ.
0.1 s ... 1000 m in 6 adjustable ranges or fixed
+/-0.5% or 20 ms, whichever is greater
+/−5%
≤ 150 ms
0-100 KΩ. (see note)
12 VDC, 24VAC/DC: -15% … +20%
120 & 230VAC: -20%…+10%
12 VDC, 24VDC: -15% … +20%
24 … 230 VAC: -20% … +10%
Single pole, normally open, non-isolated
General purpose; UL: 15A, CSA: 30A
Motor load; UL: 1HP, CSA: 1HP
General purpose; UL: 10A, CSA: 10A
Motor load; UL: 1HP, CSA: 1HP
SPDT Non Isolated
Resistive; UL: 20A, CSA: 20A
Mechanical -- 1 x 106, Electrical -- 1 x 105
Life
2005 Generation II Design
Mechanical
Mechanical
Connection
Environmental
Operating Temperature
Pre 2005 Design
General Purpose 125/240 VAC
Resistive
125/240 V AC
28 V DC
Motor Load
125 V AC
240 V AC
SPDT-N.O.
30 A
30 A
20 A
SPDT-N.O.
15 A
15 A
10 A
1 hp*
2 hp**
¼ hp**
1 hp**
Mechanical -- 1 x 106;
Electrical -- 1 x 105, *3 x 104, **6,000
Terminal layout is different.
Terminal connections are different.
-20°C ... +60°C
-40°C ... +60°C
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
S1 = Optional Initiate Switch
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 28, 2005
HRDS Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Repeat Accuracy
Tolerance (Factory Calibration)
Reset Time
Initiate Time
RT Values (for external adjustment)
Input
Tolerance
Output
Form
Contact Ratings @ 125 VAC
240 VAC
30 VDC
Pre 2005 Design
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−0.5 %
+/−1%, +/−10%
≤ 500 ms
≅ 200 ms
0-1 MΩ.
0.1 s ... 100 m in 5 adjustable ranges or fixed
+/-0.5% or 20 ms, whichever is greater
+/−1%, +/−5%
≤ 150 ms
≤ 20 ms
0-100 KΩ. (see note)
12 VDC, 24VAC/DC: -15% … +20%
120 & 230VAC: -20%…+10%
12 VDC, 24VDC: -15% … +20%
24 … 230 VAC: -20% … +10%
Single pole, normally open, non-isolated
General purpose; UL: 15A, CSA: 30A
Motor load; UL: 1HP, CSA: 1HP
General purpose; UL: 10A, CSA: 10A
Motor load; UL: 1HP, CSA: 1HP
SPDT Non Isolated
Resistive; UL: 20A, CSA: 20A
Mechanical -- 1 x 106, Electrical -- 1 x 105
Life
2005 Generation II Design
Mechanical
Mechanical
Connection
Environmental
Operating Temperature
Pre 2005 Design
General Purpose 125/240 VAC
Resistive
125/240 V AC
28 V DC
Motor Load
SPDT-N.O.
30 A
30 A
20 A
SPDT-N.O.
15 A
15 A
10 A
1 hp*
2 hp**
¼ hp**
1 hp**
125 V AC
240 V AC
Mechanical -- 1 x 106;
Electrical -- 1 x 105, *3 x 104, **6,000
Terminal layout is different.
Terminal connections are different.
-20°C ... +60°C
-40°C ... +60°C
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Initiate Switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 11, 2005
HRV Series Part Numbers
Important Differences Between Product Designs
Specifications
Count Functions
Minimum Switch Closure Time
Minimum Switch Open (between closures)
Time
Time Delay
Recycle Time
Output
Pre 2005 Design
2005 Generation II Design
≥ 25 ms
≥ 20 ms
≥ 30 ms
≥ 20 ms
< 500ms
Reset Time: < 150 ms
Ratings:
Definite Purpose
125 V AC
17 FLA, 96 LRA*20 FLA, 60 LRA*
Definite Purpose
240 V AC 30 FLA, 80 LRA*20 FLA, 60 LRA*
* SPDT - N.C. Ratings: 10 A at 28 V DC (Resistive) 10 FLA, 30 LRA at 125 V AC/240 V AC
(Definite Purpose)
Definite Purpose Ratings removed
Mechanical
The Isolated SPST (not shown) will follow
the terminal layout of the Isolated SPDT
except the N.C. contact will be omitted.
Mechanical
Operational
Terminal layout and connections for Non-Isolated
SPST units are different for AC and DC voltages.
Terminal layout for Non-Isolated SPST AC
and DC voltages will be the same.
Legend
V = Input Voltage
L = Timed delayed load
UTL = Optional untimed load
UTC = Optional untimed counter
S1 = Initiate switch
Dashed lines are internal connections or optional connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
KRD3 Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Range
Tolerance (Factory Calibration)
Input
Power Consumption
Pre 2005 Design
≤ 250 ms
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−10%
12, 24 VDC≤ 0.65W; 24 VΑC: ≤ 1 VΑ;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
≤ 150 ms
0.1 s ... 100 m in 5 adjustable ranges or fixed
≤ +/- 5%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive 28 VDC; ¼ HP @ 125 VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
KRD9 Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Repeat Accuracy
Initiate Time
Input
Voltage (AC)
Tolerance
Power Consumption
Pre 2005 Design
<= 250 ms
+/-1% or 16 ms (20 ms @ 50Hz), whichever is
greater
ΑC≅ 40 ms; DC ≅ 10 ms
24 or 120 V AC; 12, 24 or 110 V DC
12 VDC, 24VAC/DC: -15% … +20%
110 VDC & 120VAC: -20%…+10%
12, 24 VDC≤ 1W; 24 VAC: ≤ 1 VA;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
<= 150 ms
+/- 0.5% or 20 ms whichever is greater
≤ 40 ms; ≤ 750 Operations per Minute
24 …240 VAC/DC; 12 … 48 VDC
12 … 48 VDC; - 15% …+ 20%
24 … 240 VAC/DC; -20% … +10%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C)
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive at 230 VAC & 28 VDC
¼ HP @ 125 VAC
Max. Switching voltage: 250VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
UTL = Optional untimed load
S1 = Initiate switch
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
KRDB Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Repeat Accuracy
Initiate Time
Input
Voltage (AC)
Tolerance
Power Consumption
Pre 2005 Design
<= 250 ms
+/-1% or 16 ms (20 ms @ 50Hz), whichever is
greater
ΑC≅ 40 ms; DC ≅ 10 ms
24 or 120 V AC; 12, 24 or 110 V DC
12 VDC, 24VAC/DC: -15% … +20%
110 VDC & 120VAC: -20%…+10%
12, 24 VDC≤ 1W; 24 VAC: ≤ 1 VA;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
<= 150 ms
+/- 0.5% or 20 ms whichever is greater
≤ 40 ms
24 …240 VAC/DC; 12 … 48 VDC
12 … 48 VDC; - 15% …+ 20%
24 … 240 VAC/DC; -20% … +10%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C)
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive at 230 VAC & 28 VDC
¼ HP @ 125 VAC
Max. Switching voltage: 250VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
UTL = Optional untimed load
S1 = Initiate switch
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
KRDI Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Range
Tolerance (Factory Calibration)
Input
Power Consumption
Pre 2005 Design
≤ 250 ms
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−10%
12, 24 VDC≤ 0.65W; 24 VΑC: ≤ 1 VΑ;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
≤ 150 ms
0.1 s ... 100 m in 5 adjustable ranges or fixed
≤ +/- 5%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C)
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive 28 VDC; ¼ HP @ 125 VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
KRDM Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Range
Tolerance (Factory Calibration)
Input
Power Consumption
Pre 2005 Design
≤ 250 ms
0.2 s ... 100 m in 5 adjustable ranges or fixed
+/−10%
12, 24 VDC≤ 0.65W; 24 VΑC: ≤ 1 VΑ;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
≤ 150 ms
0.1 s ... 100 m in 5 adjustable ranges or fixed
≤ +/- 5%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C)
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive 28 VDC; ¼ HP @ 125 VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
KRDR Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Range
Range 5
Tolerance (Factory Calibration)
Input
Power Consumption
Pre 2005 Design
≤ 250 ms
0.2 s ... 100 m in 6 adjustable ranges or fixed
Highest time range is 5 to 500 minutes.
+/−10%
12, 24 VDC≤ 0.65W; 24 VΑC: ≤ 1 VΑ;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
≤ 150 ms
0.1 s ... 100 m in 6 adjustable ranges or fixed
Highest time range is 10 to 1000 minutes.
≤ +/- 5%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C)
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive 28 VDC; ¼ HP @ 125 VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
KRDS Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Repeat Accuracy
Initiate Time
Input
Voltage (AC)
Tolerance
Power Consumption
Pre 2005 Design
<= 250 ms
+/-1% or 16 ms (20 ms @ 50Hz), whichever is
greater
ΑC≅ 40 ms; DC ≅ 10 ms
24 or 120 V AC; 12, 24 or 110 V DC
12 VDC, 24VAC/DC: -15% … +20%
110 VDC & 120VAC: -20%…+10%
12, 24 VDC≤ 1W; 24 VAC: ≤ 1 VA;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
<= 150 ms
+/- 0.5% or 20 ms whichever is greater
≤ 40 ms; ≤ 750 Operations per Minute
24 …240 VAC/DC; 12 … 48 VDC
12 … 48 VDC; - 15% …+ 20%
24 … 240 VAC/DC; -20% … +10%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C)
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive at 230 VAC & 28 VDC
¼ HP @ 125 VAC
Max. Switching voltage: 250VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
UTL = Optional untimed load
S1 = Initiate switch
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 4, 2005
KRPD Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Repeat Accuracy
Initiate Time
Input
Voltage (AC)
Tolerance
Power Consumption
Pre 2005 Design
<= 250 ms
+/-1% or 16 ms (20 ms @ 50Hz), whichever is
greater
ΑC≅ 40 ms; DC ≅ 10 ms
24 or 120 V AC; 12, 24 or 110 V DC
12 VDC, 24VAC/DC: -15% … +20%
110 VDC & 120VAC: -20%…+10%
12, 24 VDC≤ 1W; 24 VAC: ≤ 1 VA;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
<= 150 ms
+/- 0.5% or 20 ms whichever is greater
≤ 40 ms; ≤ 750 Operations per Minute
24 …240 VAC/DC; 12 … 48 VDC
12 … 48 VDC; - 15% … +20%
24 … 240 VAC/DC; -20% … +10%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C)
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive at 230 VAC & 28 VDC
¼ HP @ 125 VAC
Max. Switching voltage: 250VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
UTL = Optional untimed load
S1 = Initiate switch (not required for some functions)
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 4, 2005
KRPS Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Repeat Accuracy
Initiate Time
Input
Voltage (AC)
Tolerance
Power Consumption
Pre 2005 Design
<= 250 ms
+/-1% or 16 ms (20 ms @ 50Hz), whichever is
greater
ΑC≅ 40 ms; DC ≅ 10 ms
24 or 120 V AC; 12, 24 or 110 V DC
12 VDC, 24VAC/DC: -15% … +20%
110 VDC & 120VAC: -20%…+10%
12, 24 VDC≤ 1W; 24 VAC: ≤ 1 VA;
110 VDC : ≤ 2W; 120 VAC ≤ 2 VA
2005 Generation II Design
<= 150 ms
+/- 0.5% or 20 ms whichever is greater
≤ 40 ms; ≤ 750 Operations per Minute
24 …240 VAC/DC; 12 … 48 VDC
12 … 48 VDC; - 15% …+ 20%
24 … 240 VAC/DC; -20% … +10%
AC ≤ 2 VA; DC ≤ 2 W
Output
Contact Ratings (@ 40°C)
10A resistive @ 125 VAC
5A resistive @ 30 VDC; ¼ HP @ 125 VAC
Max. Switching voltage: 230 VAC (5A resistive)
10A resistive @ 125 VAC
5A resistive at 230 VAC & 28 VDC
¼ HP @ 125 VAC
Max. Switching voltage: 250VAC
Mechanical
Terminal layout is different.
Onboard adjust requires an adjustment tool.
Terminals
Pre 2005 Design
2005 Generation II Design
Legend:
V = Input voltage
UTL = Optional untimed load
S1 = Initiate switch (not required for some functions)
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
KSD1 Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Tolerance (Factory Calibration)
Operational
RT Values (for external adjustment)
Recycle Time
Mechanical
RT Terminals
Pre 2005 Design
2005 Generation II Design
0.1 s ...500 m in 6 adjustable ranges or fixed
+/-10 %
Highest time range is 5 to 500 minutes.
0-1 MΩ.
≤ 200 ms
0.1 s ... 1000 m in 6 adjustable ranges or fixed
+/-5%
Highest time range is 10 to 1000 minutes.
0-100 KΩ.(see notes)
≤ 150 ms
Onboard adjustment requires the use of a VTP
Plug-on Module.
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
Pre 2005 Design
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 4, 2005
KSD2 Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Tolerance (Factory Calibration)
Operational
RT Values (for external adjustment)
Recycle Time
Mechanical
RT Terminals
Pre 2005 Design
2005 Generation II Design
0.1 s ...500 m in 6 adjustable ranges or fixed
+/-10 %
Highest time range is 5 to 500 minutes.
0-1 MΩ.
≤ 300 ms
0.1 s ... 1000 m in 6 adjustable ranges or fixed
+/-5%
Highest time range is 10 to 1000 minutes.
0-100 KΩ.(see notes)
≤ 150 ms
Onboard adjustment requires the use of a VTP
Plug-on Module.
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
Pre 2005 Design
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 4, 2005
KSD3 Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Tolerance (Factory Calibration)
Operational
RT Values (for external adjustment)
Recycle Time
Mechanical
RT Terminals
Pre 2005 Design
2005 Generation II Design
0.1 s ...500 m in 6 adjustable ranges or fixed
+/-10 %
Highest time range is 5 to 500 minutes.
0-1 MΩ.
≤ 300 ms
0.1 s ... 1000 m in 6 adjustable ranges or fixed
+/-5%
Highest time range is 10 to 1000 minutes.
0-100 KΩ.(see notes)
≤ 150 ms
Onboard adjustment requires the use of a VTP
Plug-on Module.
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
Pre 2005 Design
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 11, 2005
KSD4 Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Range
Tolerance (Factory Calibration)
Operational
RT Values (for external adjustment)
Recycle Time
Mechanical
RT Terminals
Pre 2005 Design
2005 Generation II Design
0.1 s ...500 m in 6 adjustable ranges or fixed
+/-10 %
Highest time range is 100 to 500 minutes.
0-1 MΩ.
≤ 300 ms
0.1 s ... 1000 m in 6 adjustable ranges or fixed
+/-5%
Highest time range is 1 to 1000 minutes.
0-100 KΩ.(see notes)
≤ 150 ms
Onboard adjustment requires the use of a VTP
Plug-on Module.
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
Pre 2005 Design
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 18, 2005
KSDB Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Range
RT Values (for external adjustment)
Output
Maximum Load Current
(except) 120 V DC
Voltage Drop
Mechanical
Pre 2005 Design
2005 Generation II Design
0.1 s ... 500 m in 6 adjustable ranges or fixed
0-5 MΩ.
0.1 s ... 1000 m in 6 adjustable ranges or fixed
0-100 KΩ. (see notes)
1 A steady state, 10 A inrush at 60°C
0.5 A steady state, 5 A inrush
ΑC≅ 2.5 V at 1 A, DC ≅ 1.7 V at rated current
Mechanical
Onboard adjustment requires the use of a VTP
Plug-on Module.
Connection
Terminals 1,3 line input. Terminal 2 output.
(-)
(+)
(+)
(-)
Negative Switching
Positive Switching
Pre 2005 Design
1A Steady State, 10 A Inrush at 60°C
All Voltages
ΑC≅ 2.5 V at 1 A, DC ≅ 1V at 1 A
RT terminals are oriented differently.
Initiate terminal is in a different location.
Can be ordered as onboard adjustable. (see notes)
Terminals 3, 2 line input, Terminal T1 is output
(-)
(+) Negative Switching
(+)
(-) Positive Switching
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 4, 2005
KSDR Series Part Numbers
Important Differences Between Product Designs
Specifications
Pre 2005 Design
Time Delay
Tolerance (Factory Calibration)
RT Values (for external adjustment)
Mechanical
RT Terminals
3 2
4
5
2005 Generation II Design
+/-10 %
0-5 MΩ.
+/-5%
0-100 KΩ.(see notes)
Onboard adjustment requires the use of a VTP
Plug-on Module.
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
1
7
6
Pre 2005 Design
8
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometers
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 18, 2005
KSDS Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Range
RT Values (for external adjustment)
Tolerance (Factory Calibration)
Output
Maximum Load Current
Voltage Drop
Mechanical
Pre 2005 Design
2005 Generation II Design
0.1 s ... 500 m in 6 adjustable ranges or fixed
0-1 MΩ (ranges 0- 4). 0-3 MΩ (range 5).
≤ +/-10%
0.1 s ... 1000 m in 6 adjustable ranges or fixed
0-100 KΩ. (see notes)
≤ +/-5%
1 A steady state, 10 A inrush at 55°C
ΑC≅ 2.5 V at 1 A, DC ≅ 1.7 V at rated current
1 A steady state, 10 A inrush at 60°C
DC≅ 1 V at 1 A
Mechanical
Onboard adjustment requires the use of a VTP
Plug-on Module.
Connection
Terminals 1,3 line input. Terminal 2 output.
(-)
(+)
(+) Negative Switching
(-) Positive Switching
Pre 2005 Design
RT terminals are oriented differently.
Initiate terminal is in a different location.
Can be ordered as onboard adjustable. (see notes)
Terminals 3, 2 line input, Terminal T1 is output
(-)
(+)
(+) Negative Switching
(-) Positive Switching
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 4, 2005
KSPD Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
Repeat Accuracy
Input
Voltage
Line Frequency
Output
DC Operation
Mechanical
2005 Generation II Design
± 0.5% or 20 ms
+/−1 % or 20 ms
24, 120, or 230 V AC; 12 or 24, V DC
50 ... 60 Hz
24 to 240 V AC; 12 to 120 V DC
50 … 60 Hz/≤ 10% DC Ripple
Positive switching
Positive or negative switching
RT terminals are oriented differently.
Initiate terminal is in a different location.
RT Terminals
(+)
(-)
Positive Switching
(+)
(-)
(-)
(+)
Positive Switching
Negative Switching
V
L
3
2
1
6
8 6
S1
R T1
1
2
Pre 2005 Design
T1
T2
4
5
7
8
UTL
RT 2
Terminal Location for
External Adjustment
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch (Not required for all functions)
UTL = Optional Untimed Load
RT = External Adjustment Potentiometers
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 4, 2005
KSPS Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
Repeat Accuracy
Input
Voltage
Line Frequency
Output
DC Operation
Mechanical
2005 Generation II Design
± 0.5 or 20 ms
+/−1 % or 20ms
24, 120, or 230 V AC; 12 or 24, V DC
50 ... 60 Hz
24 to 240 V AC; 12 to 120 V DC
50 to 60 Hz/ ≤ 10% DC Ripple
Positive switching
Positive or negative switching
RT terminals are oriented differently.
Initiate terminal is in a different location.
RT Terminals
(+)
(-)
Positive Switching
Pre 2005 Design
(+)
(-)
(-) Positive Switching
(+) Negative Switching
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch (Not required for all functions)
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 18, 2005
KSPU (Positive Switching DC Voltages)
Important Differences Between Product Designs
Specification
Time Delay
Recycle Time
Setting Accuracy
Initiate Time
Max. Initiate (Count) Rate
Input
Voltage (AC)
Voltage (DC)
Pre 2005 Design
2005 Generation II Design
<= 250 ms
<= +/- 2%
40 ms
<= 10 per second
<= 150 ms
<=+/-1% or 20ms whichever is greater
<= 20 ms
<= 25 per second
24, 120, or 120/230VAC
12, 24, or 120 VDC positive switching
24 to 240 VAC
12 to 120 VDC positive or negative switching
The connection diagram is the same for both designs:
(−)
(+) Negative switching
(+)
(-) Positive switching
Legend:
V = Input voltage
L = Time delayed load
UTL = Optional untimed load
S1 = Initiate switch (not required for some functions)
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
NHPD Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
Repeat Accuracy
Input
Voltage
Output
2005 Generation II Design
± 0.5% or 20 ms
+/−1 % or 20 ms
Leakage
Mechanical
RT Terminals
24, 120, or 230 V AC
24 to 240 V AC
[email protected], [email protected],
[email protected]
≅ 5mA @ 230VAC
Vertical Orientation
Horizontal Orientation
V
L
3
2
1
6
8 6
S1
R T1
1
2
Pre 2005 Design
T1
T2
4
5
7
8
UTL
RT 2
Terminal Location for
External Adjustment
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch (Not required for all functions)
UTL = Optional Untimed Load
RT = External Adjustment Potentiometers
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
NHPS Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Repeat Accuracy
Input
Voltage
Output
Pre 2005 Design
+/−1 % or 20ms
Leakage
2005 Generation II Design
± 0.5 or 20 ms
24, 120, or 230 V AC
24 to 240 V AC
[email protected], [email protected],
[email protected]
≅ 5mA at 230VAC
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch (Not required for all functions)
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 11, 2005
NHPU Series Part Numbers
Important Differences Between Product Designs
Specification
Recycle Time
Setting Accuracy
Initiate Time
Max. Initiate (Count) Rate
Voltage (AC)
Pre 2005 Design
Time Delay
<= 250 ms
<= +/- 2%
40 ms
<= 10 per second
Input
24, 120, or 120/230VAC
2005 Generation II Design
<= 150 ms
<=+/-1% or 20ms whichever is
greater
<= 20 ms
<= 25 per second
24 to 240 VAC
The connection diagram is the same for both designs::
Legend:
V = Input voltage
L = Time delayed load
UTL = Optional untimed load
S1 = Initiate switch (not required for some functions)
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
PTHA Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
2005 Generation II Design
0-5 MΩ.
≤ 500 ms
0-100 KΩ. (see note)
≤ 150 ms
[email protected], [email protected],
[email protected]
≅ 5 mA at 230 VAC
Time Delay
RT Values (for external adjustment)
Reset Time
Output
Off State Leakage
Mechanical
RT Terminals
Connection
Package
Environmental
Weight
Terminals 2,3 line input. Terminal 1 output.
2 x 2 x 1.30 in. (50.8 x 50.8 x 33.0 mm)
Terminals are oriented differently.
Terminals 2, 3 are input; T1 is output
2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4mm)
≅ 2.9 oz (82 g)
≅ 3.9 oz (111 g)
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time Delayed Load
S1 = Optional Low Current Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic
timing may occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
PTHF Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
2005 Generation II Design
0-5 MΩ.
≤ 500 ms
0-100 KΩ. (see note)
≤ 150 ms
[email protected], [email protected],
[email protected]
≅ 5 mA at 230 VAC
Time Delay
RT Values (for external adjustment)
Reset Time
Output
Off State Leakage
Mechanical
RT Terminals
Connection
Package
Environmental
Weight
Terminals 2,3 line input. Terminal 1 output.
2 x 2 x 1.30 in. (50.8 x 50.8 x 33.0 mm)
Terminals are oriented differently.
Terminals 2, 3 are input; T1 is output
2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4mm)
≅ 2.9 oz (82 g)
≅ 3.9 oz (111 g)
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time Delayed Load
S1 = Optional Low Current Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic
timing may occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 4, 2005
RS Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Range
Range 4
Range Combination
Reset Time
Output
Minimum Holding Current
Mechanical
Mounting
Package
Connection
Environmental
Weight
Pre 2005 Design
2005 Generation II Design
0.1 s ... 255.75 h in 4 adjustable ranges
0.25 … 255.75 h in 0.25 h increments
Time ranges 1 and 4 cannot be combined in
the same unit.
100 ms
0.1 s ... 1023 h in 4 adjustable ranges
1 … 1023 h in 1 h increments
All combinations of time ranges are acceptable
5 mA
Off State Leakage; AC ≅ 5 mA; DC 1≅ mA
Surface mount with two to six #8 (M4 x 0.7)
screws
4.5 x 3.1 x 1.3 in. (114 x 79 x 34 mm)
Pre 2005 Design
≅ 7oz (198 g)
≤ 150 ms
Surface mount with one #10 (M5 x 0.8) screw
3 x 2 x 1.5 in. (76.7 x 51.3 x 38.1mm
Terminals are oriented differently.
≅ 3.9 oz (111 g)
2005 Generation II Design
Legend:
V = Input voltage
L = Time delayed load
T1 = ON Time
T2 = OFF Time
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 18, 2005
TDUB Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
Range
Tolerance (Factory Calibration)
Mechanical
Mounting
Package
Connection
Environmental
Weight
3
0.1 s ... 10230 s in 3 adjustable ranges
+/-10 %
0.1 s ... 102.3 m in 3 adjustable ranges
< +/-5%
Surface mount with two #8 (M4 x 0.7) screw
2.5 x 3.5 x 1.22 in. (63.5 x 88.9 x 31 mm)
Input Voltage T3, T1; Output T2
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
Input Voltage T3, T2; Output T1
≅ 4.8 oz (136 g)
≅ 2.4 oz (68 g)
_
+
2
2005 Generation II Design
Positive Switching
+
_
Positive Switching
1
4
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate Switch
RT = External Adjustment Potentiometer(s)
UTL = Optional Untimed Load
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 18, 2005
TDUI Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
Range
Tolerance (Factory Calibration)
Mechanical
Mounting
Package
Connection
Environmental
Weight
0.1 s ... 10230 s in 3 adjustable ranges
+/-10 %
0.1 s ... 102.3 m in 3 adjustable ranges
< +/-5%
Surface mount with two #8 (M4 x 0.7) screw
2.5 x 3.5 x 1.22 in. (63.5 x 88.9 x 31 mm)
Input Voltage T3, T1; Output T2
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
Input Voltage T3, T2; Output T1
≅ 4.8 oz (136 g)
≅ 2.4 oz (68 g)
_
+
3
2005 Generation II Design
Positive Switching
+
_
Positive Switching
2 1
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
RT = External Adjustment Potentiometer(s)
UTL = Optional Untimed Load
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 18, 2005
TDUS Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
Range
Tolerance (Factory Calibration)
Mechanical
Mounting
Package
Connection
Environmental
Weight
3
0.1 s ... 10230 s in 3 adjustable ranges
+/-10 %
0.1 s ... 102.3 m in 3 adjustable ranges
< +/-5%
Surface mount with two #8 (M4 x 0.7) screw
2.5 x 3.5 x 1.22 in. (63.5 x 88.9 x 31 mm)
Input Voltage T3, T1; Output T2
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
Input Voltage T3, T2; Output T1
≅ 4.8 oz (136 g)
≅ 2.4 oz (68 g)
_
+
2
2005 Generation II Design
Positive Switching
+
_
Positive Switching
1
4
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate Switch
RT = External Adjustment Potentiometer(s)
UTL = Optional Untimed Load
Dashed lines are internal connections
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
TH1 Series Part Numbers
Important Differences Between Product Designs
Specifications
Pre 2005 Design
Time Delay
Tolerance (Factory Calibration)
RT Values (for external adjustment)
Recycle Time
Output
Voltage Drop
2005 Generation II Design
≤ +/-10 %
0-3 MΩ (ranges 1, 2 & 3). 0-5 MΩ (range 4).
≤ 100 ms
≤ +/-5%
0-100 KΩ (see notes)
≤ 150 ms
ΑC≅ 2.0 V at rated current
[email protected], [email protected],
[email protected]
≅ 2.5 V at rated current
Onboard adjustment requires the use of a VTP
Plug-on Module.
Terminals 1,3 line input. Terminal 2 output.
RT and initiate terminals are oriented differently.
Can be ordered as onboard adjust (see notes)
Terminals 3, 2 line input, T1 is output
Leakage
≅ 5 mA at 230 VAC
Mechanical
RT Terminals
Connections
Pre 2005 Design
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Optional Low Current Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
TH2 Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Tolerance (Factory Calibration)
RT Values (for external adjustment)
Recycle Time
Output
Pre 2005 Design
2005 Generation II Design
≤ +/-10 %
0-3 MΩ (ranges 1, 2 & 3). 0-5 MΩ (range 4).
≤ 100 ms
≤ +/-5%
0-100 KΩ (see notes)
≤ 150 ms
[email protected], [email protected],
[email protected]
≅ 5 mA at 230 VAC
Onboard adjustment requires the use of a VTP
Plug-on Module.
Terminals 1,3 line input. Terminal 2 output.
RT and initiate terminals are oriented differently.
Can be ordered as onboard adjust (see notes)
Terminals 3, 2 line input, T1 is output
Leakage
Mechanical
RT Terminals
Connections
Pre 2005 Design
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Optional Low Current Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 18, 2005
THC Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Tolerance (Factory Calibration)
RT Values (for external adjustment)
Recycle Time
Output
Pre 2005 Design
2005 Generation II Design
≤ +/-10 %
0-3 MΩ (ranges 1, 2 & 3). 0-5 MΩ (range 4).
≤ 100 ms
≤ +/-5%
0-100 KΩ (see notes)
≤ 150 ms
[email protected], [email protected],
[email protected]
≅ 5 mA at 230 VAC
Onboard adjustment requires the use of a VTP
Plug-on Module.
Terminals 1,3 line input. Terminal 2 output.
RT and initiate terminals are oriented differently.
Can be ordered as onboard adjust (see notes)
Terminals 3, 2 line input, T1 is output
Leakage
Mechanical
RT Terminals
Connections
Pre 2005 Design
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 11, 2005
THD1 Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
Operational
RT Values (for external adjustment)
Mechanical
RT Terminals
Pre 2005 Design
2005 Generation II Design
Terminals 1,3 line input. Terminal 2 output.
0-5 MΩ.
Terminals 2, 3 are input; T1 is output
0-100 KΩ. (see notes)
Horizontally Aligned
Vertically Aligned (see notes)
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time Delayed Load
S1 = Optional Low Current Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
THD2 Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
RT Values (for external adjustment)
Mechanical
0-5 MΩ.
RT Terminals
Onboard adjust requires VTP Plug-on Module
Connections
Output
Terminals 1,3 line input. Terminal 2 output.
[email protected], [email protected],
[email protected]
Off State Leakage
Pre 2005 Design
2005 Generation II Design
0-100 KΩ. (see notes)
Terminals are oriented differently. Can be ordered
as onboard adjust (see notes)
Terminals 2, 3 are input; T1 is output
≅ 5mA @ 230VAC
2005 Generation II Design
Legend
V = Input voltage
L = Time Delayed Load
S1 = Optional Low Current Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
THD3 Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
RT Values (for external adjustment)
Linearity:
Output
Off State Leakage
Pre 2005 Design
2005 Generation II Design
0-5 MΩ.
≤+/−2% 10% to 100% of range
0-100 KΩ. (see notes)
Linearity not specified.
[email protected], [email protected],
[email protected]
≅ 5 mA at 230 VAC
Onboard adjust requires VTP Plug-on
Modules
Terminals 1,3 line input. Terminal 2 output.
Terminals are oriented differently. Can be ordered
as onboard adjust (see notes)
Terminals 2, 3 are input; T1 is output
Mechanical
RT Terminals
Connection
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time Delayed Load
S1 = Optional Low Current Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 18, 2005
THD4 Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
Time Delay
RT Values (for external adjustment)
Linearity:
Output
2005 Generation II Design
0-5 MΩ.
≤+/−2% 10% to 100% of range
0-100 KΩ. (see notes)
Linearity not specified.
[email protected], [email protected],
[email protected]
≅ 5mA @ 230VAC
Onboard adjustment requires the use of a VTP
Plug-on Module.
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
Leakage
Mechanical
RT Terminals
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
THDB Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
2005 Generation II Design
0-5 MΩ.
50ms
0-100 KΩ. (see notes)
20 ms
[email protected], [email protected],
[email protected]
≅ 5 mA at 230 VAC
Time Delay
RT Values (for external adjustment)
Initiate time
Output
Off State Leakage
Mechanical
RT Terminals
Terminals 1,3 line input. Terminal 2 output.
2 x 2 x 1.30 in. (50.8 x 50.8 x 33.0 mm)
Terminals are oriented differently. Can be ordered
as onboard adjust (see notes)
Terminals 2, 3 are input; T1 is output
2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4mm)
≅ 2.9 oz (82 g)
≅ 3.9 oz (111 g)
Onboard adjust requires VTP Plug-on Module
Connection
Package
Environmental
Weight
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time Delayed Load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
THDS Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
2005 Generation II Design
0-5 MΩ.
50ms
0-100 KΩ. (see notes)
≤ 20 ms
[email protected], [email protected],
[email protected]
≅ 5mA at 230 VAC
Time Delay
RT Values (for external adjustment)
Initiate time
Output
Off State Leakage
Mechanical
RT Terminals
Terminals 1,3 line input. Terminal 2 output.
2 x 2 x 1.30 in. (50.8 x 50.8 x 33.0 mm)
Terminals are oriented differently. Can be ordered
as onboard adjust (see notes)
Terminals 2, 3 are input; T1 is output
2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4mm)
≅ 2.9 oz (82 g)
≅ 3.9 oz (111 g)
Onboard adjust requires VTP Plug-on Module
Connection
Package
Environmental
Weight
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time Delayed Load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 25, 2005
THS Series Part Numbers
Important Differences Between Product Designs
Specifications
Time Delay
Tolerance (Factory Calibration)
RT Values (for external adjustment)
Recycle Time
Output
Pre 2005 Design
2005 Generation II Design
≤ +/-10 %
0-3 MΩ (ranges 1, 2 & 3). 0-5 MΩ (range 4).
≤ 100 ms
≤ +/-5%
0-100 KΩ (see notes)
≤ 150 ms
[email protected], [email protected],
[email protected]
≅ 5 mA at 230 VAC
Onboard adjustment requires the use of a VTP
Plug-on Module.
Terminals 1,3 line input. Terminal 2 output.
RT and initiate terminals are oriented differently.
Can be ordered as onboard adjust (see notes)
Terminals 3, 2 line input, T1 is output
Leakage
Mechanical
RT Terminals
Connections
Pre 2005 Design
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 18, 2005
TSB Series Part Numbers
Important Differences Between Product Designs
Specifications
Pre 2005 Design
Time Delay
Tolerance (Factory Calibration)
Terminals 4 & 5 initiate, terminals 6 & 7 for
external adjust RT.
Continues to time with complete loss of
power.
Operational
RT Values (for external adjustment)
Mechanical
RT Terminals
≤ +/-10 %
0-3 MΩ (ranges 1, 2 & 3). 0-5 MΩ (range 4).
Onboard adjust requires VTP Plug-on Module
Pre 2005 Design
2005 Generation II Design
≤ +/-5%
Terminal connections are different.
Terminals 4 & 5 for RT.
Terminal 6 takes line voltage for initiate. Doubler
terminal accessory is available to replace terminal T7.
Initiate switch S1 can be connected to an optional
untimed load.
Time delay is reset upon loss of power.
0-100 KΩ. (see notes)
Terminals are oriented differently. Onboard adjust is
now available. (see notes)
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer(s)
Dashed lines are internal connections
Note: 1.) VTR plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification April 11, 2005
TSD1 Series Part Numbers
Important Differences Between Product Designs
Specifications
Pre 2005 Design
2005 Generation II Design
Time Delay
Range
Operational
RT Values (for external adjustment)
Recycle Time
Mechanical
RT Terminals
0.2 s ...10000 m in 7 adjustable ranges or
fixed
Highest time range is 100 to 10,000 minutes.
0-1 MΩ.
≤ 200 ms
Onboard adjustment requires the use of a VTP
Plug-on Module.
Pre 2005 Design
0.1 s ... 100 h m in 7 adjustable ranges or fixed
Highest time range is 1 to 100 hours.
0-100 KΩ.(see notes)
≤ 150 ms
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 4, 2005
TSD2 Series Part Numbers
Important Differences Between Product Designs
Specifications
Pre 2005 Design
2005 Generation II Design
Time Delay
Range
Operational
RT Values (for external adjustment)
0.2 s ...10000 m in 7 adjustable ranges or
fixed
Highest time range is 100 to 10,000 minutes.
0-1 MΩ.
0.1 s ... 100 h m in 7 adjustable ranges or fixed
Highest time range is 1 to 100 hours.
0-100 KΩ.(see notes)
Mechanical
RT Terminals
Onboard adjustment requires the use of a VTP
Plug-on Module.
Pre 2005 Design
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 4, 2005
TSD3 Series Part Numbers
Important Differences Between Product Designs
Specifications
Pre 2005 Design
2005 Generation II Design
Time Delay
Range
Operational
RT Values (for external adjustment)
Mechanical
RT Terminals
0.2 s ...10000 m in 7 adjustable ranges or
fixed
Highest time range is 100 to 10,000 minutes.
0-1 MΩ.
Onboard adjustment requires the use of a VTP
Plug-on Module.
Pre 2005 Design
0.1 s ... 100 h m in 7 adjustable ranges or fixed
Highest time range is 1 to 100 hours.
0-100 KΩ.(see notes)
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 11, 2005
TSD4 Series Part Numbers
Important Differences Between Product Designs
Specification
Pre 2005 Design
2005 Generation II Design
Time Delay
Range
Operational
RT Values (for external adjustment)
Mechanical
0.2 s ... 10000 m in 7 adjustable ranges or fixed
Highest time range is 100 to 10000 minutes.
0-1 MΩ.
0.1 s ... 100 h in 7 adjustable ranges or fixed
Highest time range is 1 to 100 hours.
0-100 KΩ. (see notes)
RT Terminals
Onboard adjustment requires the use of a VTP
Plug-on Module.
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
Pre 2005 Design
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification February 11, 2005
TSD6 Series Part Numbers
Important Differences Between Product Designs
Specifications
Pre 2005 Design
2005 Generation II Design
Time Delay
Range
Operational
RT Values (for external adjustment)
Mechanical
0.2 s ...10000 m in 7 adjustable ranges or fixed
Highest time range is 100 to 10000 minutes.
0-1 MΩ.
0.1 s ... 100 h in 7 adjustable ranges or fixed
Highest time range is 1 to 100 hours.
0-100 KΩ. (see notes)
RT Terminals
Onboard adjustment requires the use of a VTP
Plug-on Module.
RT terminals are oriented differently.
Can be ordered as onboard adjustable. (see notes)
(+)
(−)
(-) Positive switching
(+) Negative switching
Pre 2005 Design
(+)
(−)
(-) Positive switching
(+) Negative switching
2005 Generation II Design
Legend
V = Input Voltage
L = Timed Delayed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 11, 2005
TSDB Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
RT Values (for external adjustment)
Input
Voltage
Output
Maximum Load Current
(except) 120 V DC
Voltage Drop
Pre 2005 Design
2005 Generation II Design
0-5 MΩ.
0-100 KΩ. (see notes)
24, 120, or 230 V AC; 12,24, or 120 V DC
12 or 24 V DC; 24, 120, or 230 V AC
1 A steady state, 10 A inrush at 60°C
0.5 A steady state, 5 A inrush
ΑC≅ 2.5 V at 1 A, DC ≅ 1.7 V at rated
current
Same
1 A steady state, 10 A inrush
AC≅ 2.5 V at 1 A, DC≅ 1 V at 1 A
Mechanical
Mechanical
Onboard adjustment requires the use of
a VTP Plug-on Module.
RT terminals are oriented differently.
Initiate terminal is in a different location.
Can be ordered as onboard adjustable. (see
notes)
Connection
Terminals 1,3 line input. Terminal 2
output.
Terminals 3, 2 line input, Terminal T1 is output
(-)
(+)
(+)
(-)
Negative Switching
Positive Switching
Pre 2005 Design
(-)
(+) Negative Switching
(+)
(-) Positive Switching
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 11, 2005
TSDS Series Part Numbers
Important Differences Between Product Designs
Specification
Time Delay
RT Values (for external adjustment)
Output
Voltage Drop
Mechanical
Pre 2005 Design
2005 Generation II Design
0-1 MΩ (ranges 0- 4). 0-3 MΩ (range 5).
0-100 KΩ. (see notes)
ΑC≅ 2.5 V at 1 A, DC ≅ 1.7 V at rated current
DC≅ 1 V at 1 A
Mechanical
Onboard adjustment requires the use of a VTP
Plug-on Module.
Connection
Terminals 1,3 line input. Terminal 2 output.
(-)
(+)
(+) Negative Switching
(-) Positive Switching
Pre 2005 Design
RT terminals are oriented differently.
Initiate terminal is in a different location.
Can be ordered as onboard adjustable. (see notes)
Terminals 3, 2 line input, Terminal T1 is output
(-)
(+)
(+) Negative Switching
(-) Positive Switching
2005 Generation II Design
Legend
V = Input voltage
L = Time delayed load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTP plug-on adjustment modules cannot be used with the 2005 Generation Design. An onboard
adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
ABB
SSAC Product Line Conversion Notification March 11, 2005
TSS Series Part Numbers
Important Differences Between Product Designs
Specifications
Pre 2005 Design
Time Delay
Tolerance (Factory Calibration)
Terminals 4 & 5 initiate, terminals 6 & 7 for
external adjust RT.
Operational
RT Values (for external adjustment)
Mechanical
RT Terminals
≤ +/-10 %
0-3 MΩ (ranges 1, 2 & 3). 0-5 MΩ (range 4).
Onboard adjust requires VTP Plug-on Module
Pre 2005 Design
2005 Generation II Design
≤ +/-5%
Terminal connections are different.
Terminals 4 & 5 for RT.
Terminal 6 takes line voltage for initiate. Doubler
terminal accessory is available to replace terminal T7.
Initiate switch S1 can be connected to an optional
untimed load.
0-100 KΩ. (see notes)
Terminals are oriented differently. Onboard adjust is
now available. (see notes)
2005 Generation II Design
Legend
V = Input Voltage
L = Timed delayed load
S1 = Initiate switch
UTL = Optional Untimed Load
RT = External Adjustment Potentiometer
Dashed lines are internal connections
Note: 1.) VTR plug-on adjustment modules cannot be used with the 2005 Generation Design. An
onboard adjustment option is available for the Generation II design.
2.) The RT Value cannot exceed 100 k ohms. If the RT exceeds 200k ohms erratic timing may
occur. This is normal and not an indication of a defective unit.
ABB SSAC, PO Box 1000, Baldwinsville, NY 13027; Technical Help 800-377-7722; Fax 315-638-0333
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TSDR
Gen 2
Range
Repeat Accuracy
Tolerance (Factory Calibration)
Recycle Time
Time Delay vs. Temperature & Voltage
Voltage
Tolerance
Line Frequency
Type
Maximum Load Current
Voltage Drop
Circuitry
Dielectric Breakdown
Insulation Resistance
Mounting
Package
Termination
Operating Temperature
Storage Temperature
Humidity
Weight
Time Delay
0.1 s ... 1000 m in 6 adjustable ranges or fixed
+/-0.5%
+/-10%
150 ms
+/-5%
Input
24, 120, or 230 V AC
+/-20%
50 ... 60 Hz
Output
Solid state
1 A steady state, 10 A inrush at 60°C
≅ 2.5 V at 1 A
Protection
Encapsulated
≥ 2000 V RMS terminals to mounting surface
≥ 100 MΩ
Mechanical
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
0.25 in. (6.35 mm) male quick connect
terminals
Environmental
-40°C ... +60°C
-40°C ... +85°C
95% relative, non-condensing
≅ 2.4 oz (68 g)
0.1 s ... 1000 m in 6 adjustable ranges or fixed
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Notable differences
Mechanical
Operational
RT Values (for external adjustment)
RT terminals are oriented differently.
Adjustable range 0 cannot be combined with
fixed times greater than 100 m.
0-5 MΩ.
0-100 KΩ.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com