Fuses - IEC and British Standard

Fuses - IEC and British Standard

IEC & British Standard Fuses

IEC and British Standard Fuses

Section Contents

Page

Application Data . . . . . . . . . . . . . . . . . . . . . 245-246

CSA Type P and Type D fuses

(CDS, CDN & PON) . . . . . . . . . . . . . . . . . . . . . . . . . . . .247

Tron ™ HRC Form II Class C fuses

(CGL Form II Class C) . . . . . . . . . . . . . . . . . . . . . . . . . . 248

HRCI Industrial ceramic body fuses (CIF21 HRCI-CA &

CIF06 HRCI-CB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249

HRCI-J Fast-acting fuses (CJ HRCI-J) . . . . . . . . . . . . . . . 250

HRCI-Miscellaneous Type K fuses (CIH, CIK &

CIL HRCI-MISC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251

HRC Form II current-limiting fuses . . . . . . . . . . . . . . . . . .252

BS 88 British Standard low voltage fuses (SSD, NSD,

ESD & STD, NITD, AAO, BAO, OSD, CEO,

DEO BS 88 Part 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .253

BS 88 British Standard low voltage fuses (AC, AD, BC,

BD, CD, DD, ED, EFS & EF, FF, FG, GF, GG,

GH BS 88) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .254

DIN Style Type D (D16, D27, D33, D125 Type D) . . . . . . 255

Neozed low voltage fuses (NZ01, NZ02 Type D0) . . . . . . 255

NH HRC Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256-259

Class gG/gL IEC Industrial ferrule fuses (C08G, C08M,

C10G, C10M, C14G, C14M, C22G, C22M) . . . . . . . . . . 260

Class aM IEC Industrial ferrule fuses (C08M, C10M,

C14M, C22M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .261

Class aM & gG/gL IEC Industrial ferrule fuses with striker

(C14G_S, C22G_S, C14M_S, C22M_S) . . . . . . . . . . . . . 262

HRC fuse holders

CAMaster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .263

SAFEloc . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .263

Scan this tag to get the latest product information for

IEC and British Standard Fuses.

Application Data

The standard range of fuses for low voltage industrial and general purpose applications meet the requirements of

BS 88 and IEC 60269. By using advanced fuse technology, current ratings up to 400A have compact dimensions, but retain standard dimensional and performance requirements.

These designs are for 315/240V systems. The standard range of fuses are available from 2-1250A in the following tag forms: Offset Blade - Offset Bolted - Center Bolted.

Supplementary ranges cover applications up to 660Vac and

500Vdc including those with nonstandard tag fixings.

Bussmann fuses are manufactured under quality systems independently assessed to BS 5750 (ISO 9002) and appropriate ratings carry the ASTA 20 endorsement.

Selecting fuses is relatively simple and effective. The following notes cover the majority of applications. For further information contact our Application Engineers at toll free phone: 855-287-7626 (855-BUSSMANN).

Circuit Loading

The current rating of the fuse should not be less than the full load current of the circuit. The circuit should be so designed that small overloads of long duration will not be of frequent occurrence.

Cable Ratings & Protection

There is an increasing move away from 70°C PVC insulation to materials that are more environmentally friendly, for example 90°C XLPE. The ratings of fusegear, switches, accessories, etc. are generally based upon the equipment being connected to conductors intended to be operated at a temperature not exceeding 70°C in normal service.

In view of the above, it is recommended that the practice of designs based upon conductor temperatures of 70°C be regarded as the norm. The equipment manufacturer should be consulted to ascertain the reduction of nominal current rating of the equipment if conductor temperatures exceeding

70°C are used. In addition, an overriding factor is often voltage drop.

Fuses with gG characteristics protect associated cables against both overload and short-circuit current, provided that the current rating of the fuse 1N is equal or less than the current carrying capacity of the cable 1z.

In motor circuits, the motor starter will provide the overload protection and the fuses will provide the short-circuit protection. The maximum fuse size that can be used depends upon the type of cable used and is determined using the appropriate K factor. The following table gives the maximum sizes of fuses that are recommended for two popular cables with copper conductors, 70°C PVC (K = 115) and 90°C thermosetting (K = 143).

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

245

IEC & British Standard Fuses

Application Data for BS Low Voltage Fuses

Cable Size (mm 2 )

Max. Fuse Rating (amps)

K = 115 K = 143

10

16

25

35

50

1

1,5

2.5

4

6

16

20

32*

50*

63*

100*

125*

200*

315*

400*

70

95

560

710

630

800

120 800 1000

* Extended Motor Circuit dual ratings can be used.

125*

160*

250*

355*

500

16

25*

32*

50*

63*

Protection Against Electrical Shock

For a TN System, a disconnecting time not exceeding 5s is permitted for a distribution circuit. The maximum values of earth fault loop impedance (Zs) of 240V for Bussmann gG fuses to BS 88: Parts 2 and 6 are:

Rating (A) Zs (Ohms) Rating (A) Zs (Ohms) Rating (A) Zs (Ohms)

6

10

16

20

25

32

40

14

7.7

4.3

3.0

2.4

1.9

1.4

50

63

80

100

125

160

200

1.1

0.86

0.60

0.44

0.35

0.27

0.20

250

315

400

500

630

800

0.16

0.13

0.096

0.073

0.054

0.044

Ambient Temperature

The derating, in terms of current, of 0.5% per °C above an ambient of 35°C is recommended.

Interrupting Rating

The standardized interrupting rating values are 80kA for voltages of 415Vac and above, and 40kA for DC applications. The 240Vac designs have an interrupting rating of 50kA.

Coordination Ratio

All fuses to BS 88 Parts 2 and 6 will give a coordination ratio of 2:1; and for most practical situations a ratio of 1.6:1 (two steps in the R10 series). Example: an upstream fuse rated at

160A will coordinate with a downstream fuse rated at 100A.

Current and Energy Limitation

The range of fuses have pre-arcing I 2 t values towards the bottom limits of BS 88 Parts 2 and 6. This ensures excellent current and energy limitation. They also have lower power losses at rated current. This assists in the appropriate interchangeability with other makes of fuses.

Transformers

When fuses are used on the primary side of transformers, the normal fuse current rating should be at least twice the nominal transformer primary current.

Fluorescent Lighting

The normal fuse current rating should be at least twice the normal full load current of the maximum number of lights to be simultaneously switched.

246

Rating Motor

54.0

66.0

79.0

98.0

135.0

155.0

185.0

220.0

250.0

310.0

335.0

375.0

415.0

460.0

562.0

596.0

3.6

5.0

6.5

8.4

11.0

15.0

20.0

27.0

33.0

38.0

A

0.8

1.1

1.5

2.0

3 0

30.0

37.0

45.0

55.0

75.0

90.0

110.0

132.0

150.0

185.0

200.0

225.0

250.0

280.0

335.0

355.0

1.5

2.2

3.0

4.0

5.5

7.5

11.0

15.0

18.5

22.0

kW

0.25

0.37

0.55

0.75

1.1

Capacitor Circuits

For power factor correction in capacitor circuits, the fuse should be chosen with a current rating greater than 1.5 times the rated capacitor current. This takes into account the high inrush current, circuit harmonics and capacitor tolerances.

Motor Circuits

In motor circuits, the fuse has to withstand the motor's starting current and often requires a higher rating than the motor's full load current. Coordination recommendations are made by the manufacturers of motor starters in accordance with IEC 60947-4-1. To get Type 2 coordination with fuses, tests are performed with the latest gG or gM fuses to BS 88 or IEC 60269 that have pre-arcing I 2 t values towards the bottom of specified limits. This means that Bussmann fuses are suitable to provide Type 2 coordination.

Extended dual ratings of motor circuit protection fuses with gM characteristics are available in most popular fuse sizes to extend the use of associated equipment with appropriate economies. In the majority of applications, gG fuses are used. It is not essential to use gM fuses for motor circuit protection, they simply extend the utilization of standard equipment.

Below is a table of recommended fuses at 415V. In most applications, the run-up time is less than 5 seconds and duty is infrequent - no more than twice per hour. The next larger rating should be used for more demanding applications.

Direct On-line Asst. Start

Standard Motor Circuit Standard

(gG) (gM) (gG)

500

560

560

630

710

800

250

315

355

355

450

100

125

160

160

250

40

50

63

80

80

16

16

20

20

25

6

6

10

A

4

4

63M100

100M125

100M160

100M160

200M250

200M250

200M315

315M400

315M400

400M500

4 00M500

-

-

-

-

-

-

-

-

-

20M25

32M40

32M50

32M63

63M80

63M80

-

-

-

A

-

-

400

400

450

500

630

710

160

200

250

315

355

80

80

100

100

160

25

32

40

50

50

0 1

0 1

6 1

6 1

2 20

4

4

6

A

2

2

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

CSA Type P and Type D Fuses

CDS, CDN & PON Type P & D

Specifications

Description: CSA time-delay Type D & P fuses.

Dimensions: See Catalog Numbers table and Dimensions illustration.

Ratings:

Volts: — 250Vac (CDN & PON)

— 600Vac (CDS)

Amps: — 10-600A

IR: — 10kA minimum

Agency Information: CE, CSA Certified to C22.2 No. 59.1.

Features and Benefits

• Economical fuse in a variety of ratings for applications not requiring time-delay.

Typical Applications

• Lighting, heating and other circuits not subject to temporary surges and where available short-circuit current are relatively low.

Basic Catalog Numbers

Time-Delay CSA Type “D” Fuses

Catalog

Numbers Volts

Amp

Ratings

CDN

CDS

250Vac

600Vac

Below 10A use FRN-R 10, 12, 15, 20, 25, 30,

35, 40, 45, 50, 60, 70, 80, 90, 100

110, 125, 150, 175, 200, 225, 250, 300, 350, 400,

450, 500, 600

Below 10A use FRS-R 10, 12, 15, 20, 25, 30,

35, 40, 45, 50, 60

70, 80, 90, 100, 110, 125, 150, 175, 200,

225, 250, 300, 350, 400, 450, 500, 600

One-Time CSA Type “P” Fuses

Catalog

Number Volts

Amp

Ratings

PON 250Vac 15, 20, 25, 30, 35, 40, 45, 50, 60

Dimensions

A

Ferrule Design—1 through 60A

C

A

D

Knife Blade—70 through 600A

B

F

B

E

Catalog Numbers

Basic Catalog

Number and Volts

CDN/PON 250Vac

CDS 600Vac

Amp

Ratings

1-30

35-60

70-100

110-200

225-400

450-600

1-30

35-60

70-100

110-200

225-400

450-600

A

Overall

2.0 (50.8)

3.0 (76.2)

5.88 (149.4)

7.3 (185.4)

8.63 (219.2)

10.38 (263.7)

5.0 (127.0)

5.5 (139.7)

7.88 (200.2)

9.63 (244.6)

11.63 (295.4)

13.38 (339.9)

B Max

Diameter

0.56 (14.3)

0.81 (20.6)

0.81 (20.6)

1.06 (27.0)

To Order

To order, specify Basic Catalog Number and amp rating. Example: CDN-30

Dimensions in (mm)

C Min

Blade Length

1.0 (25.4)

1.38 (34.9)

1.88 (47.6)

2.25 (57.2)

1.0 (25.4)

1.38 (34.9)

1.88 (47.6)

2.25 (57.2)

D Min

Barrel Length

4.13 (104.8)

4.63 (117.5)

5.19 (131.8)

6.13 (115.6)

7.13 (118.1)

8.19 (208.0)

E

Blade Thickness

0.13 (3.2)

0.19 (4.8)

0.25 (6.4)

0.25 (6.4)

0.13 (3.2)

0.19 (4.8)

0.25 (6.4)

0.25 (6.4)

F

Blade Width

0.75 (19.1)

1.13 (28.6)

1.63 (41.3)

2 (50.8)

0.75 (19.1)

1.13 (28.6)

1.63 (41.3)

2 (50.8)

Data Sheet: 4126

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

247

IEC & British Standard Fuses

Tron

HRC Form II Class C Fuses

CGL Form II Class C

Specifications

Description: Current-limiting HRCII-C fuses designed to withstand inrush currents on typical motor start-ups while offering high current limitation in the short-circuit region.

Dimensions: See Dimensions illustrations.

Ratings:

Volts: — 600Vac/250Vdc (1-30A)

Amps: — 1-600A

IR: — 200kA (40,000A DC)

Agency Information: CE, CSA Certified,

C22.2 No. 106.

Features and Benefits

• Close sizing to loads allows using smaller and less costly switches

• Provides a higher degree of short-circuit protection

• Helps protect motors against burnout from overloads

Typical Applications

• For use in circuits subject to surge currents such as those caused by motors, transformers and other inductive loads

Catalog Numbers (-Amps)

CGL-1

CGL-2

CGL-3

CGL-4

CGL-6

CGL-10

CGL-15

CGL-20

CGL-25

CGL-30

CGL-35

CGL-40

CGL-45

CGL-50

CGL-60

CGL-70

CGL-80

CGL-90

CGL-100

CGL-110

CGL-125

CGL-150

CGL-175

CGL-200

CGL-225

CGL-250

CGL-300

CGL-350

CGL-400

CGL-450

CGL-500

CGL-600

Dimensions

0.22"

(5.56mm)

0.22"

(5.56mm)

0.81"

(20.64mm)

CGL 1-30

2.0"

(50.8mm)

2.80"

(71.04mm)

3.31"

(84.14mm)

0.22"

(5.56mm)

0.22"

(5.56mm)

0.34"

(8.73mm)

0.81"

(20.64mm)

0.06"

(1.59mm)

0.94"

(23.81mm)

2.0"

(50.8mm)

2.80"

(71.04mm)

3.5"

(88.9mm)

CGL 35-60

0.50"

(12.7mm)

0.343"

(8.71mm)

0.343"

(8.71mm)

1.34"

(34.04mm)

0.06"

(1.59mm)

1.06"

(26.92mm)

0.75"

(19.05mm)

0.09"

(2.29mm)

1.375"

(34.93mm)

CGL 70-100

2.39"

(60.72mm)

3.64"

(92.47mm)

4.31"

(109.54mm)

0.343"

(8.71mm)

0.343

(8.71mm)

CGL 110-200

3.00"

(76.2mm)

4.30"

(109.22mm)

5.31"

(134.87mm)

0.38"

(9.53mm)

0.75"

(19.05mm)

1.50"

(38.1mm)

0.125"

(3.18mm)

1.0"

(25.4mm)

0.19"

(4.76mm)

3.0"

(76.2mm)

5.25"

(133.35mm)

8.19"

(207.96mm)

1.0"

(25.4mm)

2.38"

(60.33mm)

CGL 225-400

0.41"

(10.32mm)

1.0"

(25.4mm)

CGL 450-600

1.0"

(25.4mm)

3.0"

(76.2mm)

5.25"

(133.35mm)

8.19"

(207.96mm)

.60"

(15.24mm)

0.375"

(9.53mm)

3.00"

(76.2mm)

Data Sheet: 4125

248

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

HRCI Industrial Ceramic Body Fuses

CIF21 HRCI-CA

Specifications

Description: The HRCI-CA fuse provides both overload and short-circuit protection to

HRCI requirements. Offset blades for bolt-on mounting. CIF21 fuse fits the Cooper

Bussmann CAMaster fuse holder (see data sheet 4132).

Dimensions: See Dimensions illustration.

Construction: Ceramic body.

Ratings:

Volts: — 600Vac/250Vdc

Amps: — 1-30A

IR: — 200kA RMS Sym.

Agency Information: CE, CSA C22.2, No. 106-M92.

Mounting: Bolt-on.

Catalog Numbers

Catalog

Numbers

Amp

Ratings

1CIF21

3CIF21

6CIF21

10CIF21

15CIF21

20CIF21

25CIF21

30CIF21

10

15

20

25

30

1

3

6

Features and Benefits

• Close sizing to loads allows using smaller and less costly switches

• Provides a higher degree of short-circuit protection

• Helps protect motors against burnout from overloads

Typical Applications

• For use in circuits subject to surge currents such as those caused by motors, transformers and other inductive loads

Dimensions - in (mm)

2.15 (54.5)

1.44 (35.5)

CIF06 HRCI-CB

Specifications

Description: A miniature industrial fuse that provides both short-circuit and overload protection and the  CIF06 fits the 30A

SAFEloc fuse holder.

Dimensions: See Dimensions illustration.

Construction: Ground ceramic body with plated end caps.

Ratings:

Volts: — 600Vac/250Vdc

Amps: — 1-30A

IR: — 200kA RMS Sym.

Agency Information: CE, CSA C22.2 No. 106-M92 (3-30A only).

Mounting: Clip-in offset blades.

Catalog Number

Catalog

Numbers

Amp

Ratings

1CIF06

3CIF06

6CIF06

10CIF06

15CIF06

20CIF06

25CIF06

30CIF06

15

20

25

30

6

10

1

3

Features and Benefits

• Close sizing to loads allows using smaller and less costly switches

• Provides a higher degree of short-circuit protection

• Helps protect motors against burnout from overloads

Typical Applications

• For use in circuits subject to surge currents such as those caused by motors, transformers and other inductive loads

Dimensions - in (mm)

2.38 (60.4)

1.44 (35.5)

0.19 (4.7)

0.54 (13.8)

0.44 (11.1) 0.54 (13.8)

0.5 (12.7)

0.03 (3.5)

1.75 (44.5)

0.03 (0.81)

0.14 (3.5)

Data Sheet: 4127

Data Sheet: 4128

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

249

IEC & British Standard Fuses

HRCI-J Fast-acting Fuses

CJ HRCI-J

Specifications

Description: HRCI-J fast-acting fuses are industrial duty fuses with the excellent current-limiting characteristics of fast-acting HRCI-J fuses to limit damage to equipment and installations by the thermal and magnetic energy associated with a large short-circuit fault current.

Overload characteristics limit cable damage due to low overload currents.

Dimensions: See Catalog Numbers table and Dimensions illustrations.

Construction: Ceramic body fuse.

Ratings:

Volts: — 600Vac (or less), 250Vdc

Amps: — 1-600A

IR: — 200kA

Agency Information: CSA C22.2 No. 106 M92; Designed to BS 88:2, IEC 60269-2.

Dimensions

1CJ to 60CJ

C

70CJ to 600CJ

E

C

B

A

B

D

J

A

K

F

H

B

G

Catalog Numbers

Catalog Numbers

Catalog

Numbers

Amp

Ratings A

1CJ

3CJ

6CJ

10CJ

15CJ

20CJ

25CJ

30CJ

35CJ

40CJ

45CJ

50CJ

60CJ

70CJ

80CJ

90CJ

100CJ

110CJ

125CJ

150CJ

175CJ

200CJ

225CJ

250CJ

300CJ

350CJ

400CJ

450CJ

500CJ

600CJ

2.25 (57)

2.38 (60)

4.63 (117)

5.75 (146)

7.13 (181)

8 (203)

70

80

90

100

110

35

40

45

50

60

10

15

20

25

30

1

3

6

250

300

350

400

450

125

150

175

200

225

500

600

B

0.5 (12.7)

0.63 (16)

3.63 (92)

4.38 (111)

5.25 (133)

6 (152)

C D

0.81 (20.6) —

1.06 (27)

1.13 (28)

1.63 (41)

2.13 (54)

2.63 (66)

0.75 (19)

1.63 (41)

2 (51)

Dimensions - in (mm)

E F

0.13 (3.2)

1.13 (28.6) 0.19 (4.8)

0.25 (6.3)

0.38 (9.5)

1 (25.4)

1.38 (35)

G

0.5 (12.7)

H

0.28 (7.1)

0.69 (17.5) 0.28 (7.1)

1.88 (47.6) 0.94 (24)

2.13 (54) 1 (25.4)

J

0.38 (9.5)

0.38 (9.5)

K

2.63 (67)

3 (76)

0.41 (10.3) 0.53 (13.5) 3.38 (86)

0.53 (13.5) 0.69 (17.5) 3.75 (96)

Data Sheet: 4129

250

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

HRCI - Miscellaneous Type K Fuses

CIH, CIK & CIL HRCI-MISC

Specifications

Description: HRI fuses provide both overload and short-circuit protection, featuring offset blades for bolt down mounting.

Dimensions: See Catalog Numbers table and

Dimensions illustration.

Construction: Ceramic body.

Ratings:

Volts: — 600V

Amps: — 1-100A

IR: — [email protected]

Agency Information: CE, CSA C22.2 No.

106 M92.

Dimensions

K

D

F

A

G

E

J

B

H

G

L

C

(The CIL14 has a rejection hole, not a slot as shown above.)

Catalog Numbers

Catalog

Numbers Ratings

1CIH07

Amp

1

A Max B Max C Max

2.25 (57) 0.94 (24) 3.38 (86)

3CIH07

6CIH07

10CIH07

15CIH07

3

6

10

15

2.25 (57) 0.94 (24) 3.38 (86)

20CIH07

25CIH07

30CIH07

35CIK07

40CIK07

50CIK07

60CIK07

80CIL14

90CIL14 90

100CIL14 100

20

25

30

35

40

50

60

80

2.28 (58)

2.28 (58)

2.75 (70)

2.75 (70)

1.06 (27)

1.06 (27)

1.44 (37)

1.44 (37)

3.56 (91)

3.56 (91)

4.38 (111)

4.38 (111)

D Nom

0.38 (9.2)

0.38 (9.2)

0.5 (12.7)

0.5 (12.7)

0.75 (19)

0.75 (19)

Dimensions - in (mm)

E Nom

0.04 (1.0)

F Nom G Nom H Nom

2.88 (73) 0.21 (5.2) 0.31 (8)

0.04 (1.0) 2.88 (73) 0.21 (5.2) 0.31 (8)

J Max

1 (25.4)

K Nom L Max

0.10 (2.6) 2.38 (60)

1 (25.4) 0.10 (2.6) 2.38 (60)

0.05 (1.2)

0.05 (1.2)

2.88 (73) 0.21 (5.2) 0.41 (10.5)

2.88 (73)

0.21 (5.2)

0.41 (10.5)

1.09 (28) 0.13 (3.2) 2.38 (61)

1.09 (28) 0.13 (3.2)

2.38 (61)

0.09 (2.5)

0.09 (2.5)

3.69 (94) 0.34 (8.7) 0.41 (10.5)

3.69 (94) 0.34 (8.7) 0.41 (10.5)

1.5 (38.5) —

1.5 (38.5)

2.91 (74)

2.91 (74)

Recommended Fuse Holders

Fuse

1-30A

35-60A

Fuse Holder

CM30CF

CM60CF

Data Sheet: 4130

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

251

IEC & British Standard Fuses

HRC Form II Current-limiting Fuses

HRC Form II

Specifications

Description: HRC Form II current-limiting fuses.

Dimensions: See Catalog

Numbers table and Dimensions illustrations.

Construction: Ceramic body.

Ratings:

Volts: — 600Vac (or less)

— 250Vdc

Amps: — 2-600A

IR: — 200kA RMS Sym.

Agency Information: CE, CSA C22.2 No.106M1992;

BS 88:2, IEC 60269:2.

Typical Applications

• Used to protect motor control circuits, together with contactors and overload protection relays to provide Type 2 coordination - per IEC 60947-4.

Catalog Numbers

Catalog Amp

Numbers Ratings

2H07C 2

4H07C

6H07C

10H07C

15H07C

4

6

10

15

20H07C

25H07C

30H07C

40K07C

50K07C

60K07C

50

60

80K07CR 80

100K07CR 100

20

25

30

40

80L14C

100L14C

80

100

125M14C 125

150M14C 150

200M14C

80L09C

200

80

100L09C 100

125M09C 125

150M09C

200M09C

250P09C

300P09C

350P09C

400P09C

250P11C

300P11C

350P11C

400P11C

450R11C

500R11C

600R11C

350

400

450

500

600

150

200

250

300

350

400

250

300

A

1.38 (35)

1.38 (35)

2.19 (56)

2.19 (56)

2.19 (56)

2.38 (60)

2.56 (65)

2.56 (65)

2.38 (60)

2.56 (65)

2.56 (65)

3.06 (178)

3.06 (178) 2.31 (59)

3.06 (178) 2.31 (59)

3.19 (81)

3.19 (81)

B

0.56 (14)

0.56 (14)

0.88 (22)

0.88 (22)

0.88 (22)

0.88 (21.4)

1.5 (38)

1.5 (38)

0.88 (21.4)

1.5 (38)

1.5 (38)

2.31 (59)

2.88 (73)

2.88 (73)

C

3.38 (85)

3.38 (85)

3.44 (87)

3.44 (87)

4.38 (111)

5 (127)

5.38 (136)

8.25 (210)

8.25 (210)

8.25 (210)

D

0.38 (9)

0.38 (9)

0.5 (13)

0.5 (13)

0.5 (13)

0.75 (19)

0.75 (19)

0.75 (19)

0.75 (19)

1 (25.4)

1 (25.4)

1 (25.4)

1 (25.4)

G

Dimensions

F

A

G

G

H

H

H

C

F

A

C

F

C

A

D

E

J

B

H07C

(Offset Blades)

D

E

D

E

J

B

B

K07C/K07CR/

L14C/M14C

(Offset Blades)

L09C/M09C/P09C

(Center Blades)

G

K

F

A

K

D

B

P11C/R11C

(Center Blades)

H

E

Dimensions - in (mm)

E

0.06 (1.2)

F

2.88 (73)

C

G

0.22 (5.6)

H

0.31 (8)

J

0.56 (14) —

K CSA Category

HRCII-C

0.56 (14)

HRCII-C

0.06 (1.2)

0.06 (1.2)

0.06 (1.2)

0.09 (2.4)

0.09 (2.4)

0.13 (3.2)

0.19 (4.8)

0.19 (4.8)

2.88 (73)

2.88 (73)

2.88 (73)

3.69 (94)

4.38 (111)

4.38 (111)

4.38 (111)

4.38 (111)

0.22 (5.6)

0.22 (5.6)

0.22 (5.6)

0.34 (8.7)

0.34 (8.7)

0.34 (8.7)

0.34 (8.7)

0.34 (8.7)

0.34 (8.7)

0.31 (8)

0.31 (8)

0.31 (8)

0.44 (11)

0.44 (11)

0.44 (11)

0.88 (22) —

0.88 (22)

0.88 (22) —

1 (25.4)

0.44 (11)

0.56 (14)

0.56 (14)

0.5 (13)

0.5 (13)

HRCII-C

HRCII-MISC

HRCII-MISC

HRCII-MISC

HRCII-C

HRCII-C

HRCII-MISC

HRCII-MISC

0.19 (5)

0.19 (5)

5.25 (133) 0.41 (10)

0.25 (6.3)

0.25 (6.3)

5.25 (133)

5.25 (133)

0.41 (10)

0.41 (10)

0.63 (16) —

0.63 (16)

0.63 (16) —

1 (25) HRCII-C

1 (25)

HRCII-C

1 (25) HRCII-C

1 (25)

Data Sheet: 4131

252

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

BS 88 British Standard Low Voltage Fuses

SSD, NSD, ESD BS 88 Part 1

Specifications

Description: The NSD and ESD are low voltage fuses complying with general purpose gG characteristics.

Construction: Ceramic body.

Ratings:

Volts: — 240-550Vac (See Catalog Numbers table)

Amps: — 2-63A (See Catalog Numbers table)

— 20M25-63M100A Motor Starter ratings

(See Catalog Numbers table)

IR: — 33kA (SSD)

— 80kA (NSD, ESD)

Agency Information: CE, Meets the requirements of

BS 88 Part 1 and IEC 60269-1.

Mounting: Offset blades.

Basic Catalog Numbers

Basic

Catalog Amp

Numbers Ratings

SSD

NSD

2, 4, 6, 10, 16, 20, 25, 32

2, 4, 6, 10, 16, 20, 25, 32,

20M25*, 20M32*, 20M36*, 32M36*, 32M40*,

ESD

32M50*, 32M63*

2, 4, 6, 10, 16, 25, 32

40, 50, 63, 63M80, 63M100*

*“M” indicates motor starter ratings.

Max AC

Voltage

Ratings

240

550

415

415

550

415

To Order

To order, specify Basic Catalog Number and amp rating. Example: SSD-20

BS 88

Ref.

E1

F1

F1

F1

F2

F2

Recommended Fuse Holders

Basic Fuse Holder Catalog

Catalog Numbers Numbers

NSD

ESD

32NNSF

63ENSF

STD, NITD, AAO, BAO, OSD, CEO, DEO

BS 88 Part 1

Specifications

Description: The STD to DEO types are low voltage fuses complying with general purpose gG characteristics.

Construction: Ceramic body.

Ratings:

Volts: — 240-550Vac (See Catalog Numbers table)

Amps: — 2-200A (See Catalog Numbers table)

— 20M25-200M315A Motor Starter ratings

(See Catalog Numbers table)

IR: — 33kA (STD)

— 80kA (NITD, AAO, BAO, CEO, DEO)

Agency Information: CE, Meets the requirements of

BS 88 Part 1 and IEC 60269-1.

Mounting: Offset bolted blades.

Typical Applications

• The STD type are used in 240V street lighting cut-outs

• NITD to DEO types used for industrial and general purpose applications

Basic Catalog Numbers

Basic

Catalog Amp

Numbers Ratings

STD

NITD

2, 4, 6, 10, 16, 20, 25, 32

2, 4, 6, 10, 16, 20, 25, 32

20M25*, 20M32*, 32M40*, 32M50*, 32M63*

AAO

BAO

CEO

2, 4, 6, 10, 16, 20, 25, 32, 32M40*, 32M50*, 32M63*

40, 50, 63, 63M80*, 63M100*

32, 40, 50, 63, 80, 100

100M125*, 100M160*, 100M200*

125, 160, 200, 200M250*, 200M315* DEO

OSD 80, 100

100M125*, 100M160*

*“M” indicates motor starter ratings.

Max AC

Voltage BS 88

Ratings Ref.

240

550

415

550

550

550

415

415

550

415

A3

A4

A4

To Order

To order, specify Basic Catalog Number and amp rating. Example: BAO-16

Recommended Fuse Blocks & Holders

Basic Fuse Block/Holder

Catalog Numbers Catalog Numbers

NITD CM32FC

AAO

BAO

OSD

CEO

CM32F

CM63F

CM100F

BH-0111

Data Sheets 4105 (SSD), 4100 (NSD) and 4101 (ESD)

Data Sheets 4123 (STD), 4106 (NITD), 4109 (AAO), 4112

(BAO), 4107 (OSD), 4115 (CEO) and 4117 (DEO)

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

253

IEC & British Standard Fuses

BS 88 British Standard Low Voltage Fuses

AC, AD, BC, BD, CD, DD, ED, EFS BS 88

Specifications

Description: Low voltage fuses that comply with general purpose gG characteristics and available up to 400A with two hole mount and up to 1250A with four hole mount.

Construction: Ceramic body.

Ratings:

Volts: — 415/550Vac, 250Vdc (See

Catalog Numbers table)

Amps: — 2-400A (See Catalog Numbers table)

— 63M80-400M500A Motor Starter ratings (See

Catalog Numbers table)

IR: — See Catalog Numbers table

Agency Information: CE, Meets the requirements of

BS 88 Parts 1 and 2 and IEC 60269-1.

Mounting: Center bolted blades, two-hole mount.

Basic Catalog Numbers

Basic

Catalog Amp

Numbers Ratings

Interrupting

Ratings

AC DC

AC

AD

BC

2, 4, 6, 10, 16, 20, 25, 32

2, 4, 6, 10, 16, 20, 25, 32

40, 50, 63

63M80*, 63M100*

40, 50, 63

80kA 40kA

80kA 40kA

80kA 40kA

80kA —

80kA 40kA BD

CD

DD

80, 100, 100M125*, 100M160*,

100M200*, 100M200*

125, 160, 200,

200M250*, 200M315*

80kA

80kA

250, 315, 355, 400, 315M400* 80kA — ED

EFS

400M500*

125, 160, 200, 250, 315

*“M” indicates motor starter ratings.

80kA

80kA

Max Voltage

Ratings

AC DC

550 250

550 250

550 250

550 —

550 250

BS 88

Ref.

415 — B1

415 —

415 —

550 —

415 —

B2

B3

B4

To Order

To order, specify Basic Catalog Number and amp rating. Example: BC-40

Recommended Fuse Blocks & Holder

Basic Fuse Block/Holder

Catalog Numbers Catalog Numbers

AC BH-0111 Modular fuse block

AD

BC

BD

CD

DD

ED

200DF Fuse holder

BH-0111 Modular fuse block

200DF-L

200DF-L

200DF-L

BH-1131 Modular fuse block

EF, FF, FG, GF, GG, GH

BS 88

Specifications

Description: Low voltage fuses complying with general purpose gG characteristics and available up to

400A with two hole mount and up to 1250A with four hole mount.

Construction: Ceramic body.

Ratings:

Volts: — 415/550Vac, 250/400Vdc

(See Catalog Numbers table for details)

Amps: — 355-1250

IR: — See Catalog Numbers table

Agency Information: CE, Meets the requirements of

BS 88 Parts 1 and 2 and IEC269-1.

Mounting: Center bolted blades, four-hole mount.

Basic Catalog Numbers

Basic

Catalog Amp

Numbers Ratings

Interrupting

Ratings

AC DC

Max Voltage

Ratings

AC

EF

FF

FG

GF

GG

355, 400

400M500*

450, 500, 560, 630

450, 500, 560, 630

710, 800

710, 800

1000, 1250

80kA

80kA

80kA

80kA

80kA

80kA

80kA

40kA

40kA

40kA

40kA

415

550

GH 710, 800, 1000, 1250 80kA —

*

“M” indicates motor starter ratings.

*

“M” indicates motor starter ratings.

550

550

550

550

550

550

DC

400

400

250

250

BS 88

Ref.

C1

C2

C3

To Order

To order, specify Basic Catalog Number and amp rating. Example: FG-450

Data Sheets 4110 (AC), 4111 (AD), 4113 (BC), 4114 (BD),

4116 (CD), 4118 (DD), 4119 (ED) and 4121 (EFS)

254

Data Sheets 4120 (EF), 4102 (FF), 4122 (FG), 4103 (GF), 4104

(GG) and 4108 (GH)

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

DIN Style Type D and Neozed Low Voltage Fuses

D16, D27, D33, D125 Type D

Specifications

Description: DIN style Type D low voltage fuses.

Dimensions: See Catalog

Numbers table and Dimensions illustrations.

Construction: Ceramic body.

Ratings:

Volts: — 500Vac

Amps: — 2-100A

IR: — 100kA

Agency Information: CE, “D” type fuses complying with

DIN 49360 Part 2 and DIN 49515, operating class gL.

Catalog Numbers

Catalog

Numbers

Amp

Ratings

Dimension

“D” (mm)

Color

Code

Figure

Number

2D16

4D16

6D16

10D16

16D16

20D16

10

16

20

2

4

6

8

10

12

6

6

6

Pink

Brown

Green

Red

Grey

Blue

1

25D16

2D27

4D27

6D27

10D27

16D27

20D27

25D27

35D33

50D33

16

20

25

35

50

25

2

4

6

10

10

12

14

16

18

14

6

6

6

8

Yellow

Pink

Brown

Green

Red

Grey

Blue

Yellow

Black

White

2

3

63D33

80D125

63

80

20

5

Copper

Silver 4

100D125 100 7 Red

Additional Fuse links: Quick acting fuselinks in body sized D16, D27, D33 and

D125 rated 2-100A. Reference number suffixed Q, i.e. 10D27Q. Voltage rating 500V.

Gauge rings and keys can also be supplied.

Dimensions - mm

NZ01, NZ02 Type D0

Catalog

Numbers

2NZ01

4NZ01

6NZ01

10NZ01

16NZ01

20NZ02

25NZ02

35NZ02

50NZ02

63NZ02

Specifications

Description: Low voltage Neozed fuses suitable for use on 250Vdc systems.

Dimensions: See Catalog Numbers table and

Dimensions illustration.

Construction: Ceramic body.

Ratings:

Volts: — 400Vac

Amps: — 2-63A

IR: — 100kA

Agency Information: CE

Catalog Numbers

Amp

Ratings

2

10

16

4

6

20

25

35

50

63

Dimension

“D” (mm)

11

11

11

11

11

15

15

15

15

15

Color

Code

Pink

Brown

Green

Red

Grey

Blue

Yellow

Black

White

Copper

Dimensions - mm

D

36

Figure 1 Figure 2 Figure 3 Figure 4

Data Sheet: 4124 Data Sheet: 4124

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

255

IEC & British Standard Fuses

NH HRC Fuses

___NHG___B

Specifications

Class: gG/gL

Description: DIN square bodied, dual indication industrial fuses.

Construction: Steatite insulator, corrosionproof (aluminum) metal parts with full-contact, silver-plated copper blades.

Sizes: DIN 000 to 4.

Selectivity Ratio: 1:1.6 up to 500Vac.

Dimensions - mm

Fuse

Size

3

4

1

02

2

03

000

00

0

01

a

1

78.5 ± 1.5

78.5 ± 1.5

125 ± 2.5

135 ± 2.5

135 ± 2.5

150 ± 2.5

150 ± 2.5

150 ± 3

150 ± 3

200

a

2

(max)

75

75

75

75

54

54

68

75

75

84

a

3

45 ± 1.5

45 ± 1.5

62 +3/-1.5

62 ± 2.5

62 ± 2.5

62 ± 2.5

62 ± 2.5

62 ± 2.5

62 ± 2.5

80

a

4

49 ± 1.5

49 ± 1.5

68 +1.5/-3

68 ± 2.5

68 ± 2.5

68 ± 2.5

68 ± 2.5

68 ± 2.5

68 ± 2.5

90

b

(nom)

20

20

25

25

15

15

15

15

32

50

c

1

(± 8)

40

48

48

60

35

35

35

40

60

85

c

2

(nom)

11

11

11

11

10

11

11

11

11

11

Ratings:

Volts: — 500Vac/250Vdc

— 690Vac/250Vdc

Amps: — 2-1250A

IR: — 120kA

Frequency: — 50Hz

Operating Frequency: — 45-62Hz

Agency Information: IEC 60269, VDE0636, DIN 43620

Part 1 to 4, VDE Mark and CE.

Fuse Blocks

SB00-D

SB1-D

SB2-D

Size

000-00

1*, 1

02, 2, 03, 3

D

(nom)

2 ± 0.5

7.0 ± 0.5

2.5 ± 0.5

2.5 ± 0.5

2.5 ± 0.5

2.5 ± 0.5

2.5 ± 0.5

2.5 ± 0.5

3.0 ± 0.5

3

e

1 e

2

(max) (max)

53

53

61

61

41

48

48

48

75

120

52

52

60

60

21

30

30

30

70

87

e

3

(max)

25

25

25

25

16

25

25

25

25

e

4

(nom)

6

6

6

6

6

8

6

6

6

6

f

(max)

15

15

15

15

8

15

15

15

18

30

Data Sheet 4173

256

For detailed information, visit the Electrical IEC section at www.cooperbussmann.com

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

NH HRC Fuses

500Vac / 250Vdc Size

000

00

0

01

1

02

2

03

3

4

Single Indicator

Slotted End

Tags

Rated

Current

(Amps)

2 gG/gL Dual Indicator

Voltage Conducting

Metal Gripping Lugs

2NHG000B

224

250

315

355

400

80

100

125

160

200

250

35

40

50

63

100

125

160

200

224

250

315

355

400

500

630

500

630

800

1000

1250

35

40

50

63

80

10

16

20

25

32

63

80

100

125

160

25

32

35

40

50

16

20

25

32

35

4

6

10

4NHG000B

6NHG000B

10NHG000B

16NHG000B

20NHG000B

25NHG000B

32NHG000B

35NHG000B

40

50

63

80

100

40NHG000B

50NHG000B

63NHG000B

80NHG000B

100NHG000B

125 125NHG00B

160 160NHG00B

10

16

20

10NHG0B

16NHG0B

20NHG0B

25NHG0B

32NHG0B

35NHG0B

40NHG0B

50NHG0B

63NHG0B

80NHG0B

100NHG0B

125NHG0B

160NHG0B

10NHG01B

16NHG01B

20NHG01B

25NHG01B

32NHG01B

35NHG01B

40NHG01B

50NHG01B

63NHG01B

80NHG01B

100NHG01B

125NHG01B

160NHG01B

200NHG1B

224NHG1B

250NHG1B

35NHG02B

40NHG02B

50NHG02B

63NHG02B

80NHG02B

100NHG02B

125NHG02B

160NHG02B

200NHG02B

224NHG02B

250NHG02B

315NHG2B

355NHG2B

400NHG2B

250NHG03B

315NHG03B

355NHG03B

400NHG03B

500NHG3B

630NHG3B

500NHG4G

630NHG4G

800NHG4G

1000NHG4G

1250NHG4G

Carton

Quantity

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

1

1

3

1

1

1

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

For detailed information, visit the Electrical IEC section at www.cooperbussmann.com

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

257

IEC & British Standard Fuses

NH HRC Fuses

690Vac / 250Vdc Size

000

00

0

1

2

3 gG/gL Dual Indicator

Voltage Conducting

Metal Gripping Lugs

40NHG0B-690

50NHG0B-690

63NHG0B-690

80NHG0B-690

100NHG0B-690

50NHG1B-690

63NHG1B-690

80NHG1B-690

100NHG1B-690

125NHG1B-690

160NHG1B-690

200NHG1B-690

63NHG2B-690

80NHG2B-690

100NHG2B-690

125NHG2B-690

160NHG2B-690

200NHG2B-690

224NHG2B-690

250NHG2B-690

315NHG2B-690

250NHG3B-690

315NHG3B-690

355NHG3B-690

400NHG3B-690

425NHG3B-690

500NHG3B-690

2NHG000B-690

4NHG000B-690

6NHG000B-690

10NHG000B-690

16NHG000B-690

20NHG000B-690

25NHG000B-690

32NHG000B-690

35NHG000B-690

40NHG000B-690

50NHG00B-690

63NHG00B-690

80NHG00B-690

100NHG00B-690

6NHG0B-690

10NHG0B-690

16NHG0B-690

20NHG0B-690

25NHG0B-690

32NHG0B-690

35NHG0B-690

Rated

Current

(Amps)

125

160

200

224

250

160

200

63

80

100

315

250

315

355

400

425

500

50

63

80

100

125

40

50

63

80

100

16

20

25

32

35

63

80

100

6

10

25

32

35

40

50

2

4

6

10

16

20

Carton

Quantity

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

258

For detailed information, visit the Electrical IEC section at www.cooperbussmann.com

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

NH Fuse Bases

SB*-D, SB*-S

Up to 690V / 160 - 1250A

Sizes 00, 0, 1, 2, 3, 4

Description: NH fuse bases with thermoplastic

bodies. DIN-Rail and screw mounting (siz e 4 screw fix). Range of protection accesories for live parts in order to obtain IP20 protection standard.

Ratings:

• Volts: up to 690Vac

• Amps: 2 to 1250A

Applications: Protection of industrial circuits and

electrical apparatus

Standards and Approvals: IEC 60269, DIN 43620

Size

NH00

NH0

NH1

NH2

NH3

NH4

Part Numbers

1

3

1

3

1

3

1

3

1

3

Size Poles

Current

(Amps)

00

0

1

2

3

4 1

160A

160A

250A

400A

630A

1250A

Part Numbers

Carton

Quantity

Compatible

Fuse Size

DIN Screw

SB00-D

TB00-D

TB00-D-IP20

SB0-D

TB0-D

SB1-D

TB1-D

SB2-D

TB2-D

SB3-D

TB3-D

SB4-S (

Screw

Connection only)

3

1

3

1

3

1

3

1

3

1

3

000 & 00

0

01 & 1

02 & 2

03 & 3

4

Neutral

Current

(Amps)

160

160

250

400

630

1000

Part Ref

Carton

Quantity

SL00

SL0

SL1

SL2

SL3

SL4

3

Fuse extraction handle

Size

C00-3

Part Ref

FEH

Carton

Quantity

1

Protection accessories

Size

NH00*

NH0

NH1

NH2

NH3

Current

(Amps)

160A

160A

250A

400A

630A

Separation Partition

4

Part

Ref

Carton

Quantity

SP00*

SP0

SP1-2

SP1-2

SP3

2

2

2

2

2

* For single pole only

Fuse Casing

5

Part

Ref

Carton

Quantity

FC00*

FC0

FC1-2

FC1-2

FC3

3

3

3

3

3

Microswitch IP Protection Kits

Part Reference

TB00-D-IP20

FPK0-3P

FPK1-3P

FPK2-3P

FPK3-3P

Description

Complete triple pole fuse base IP20 rated

IP20 kit for TB0-D fuse base

IP20 kit for TB1-D fuse base

IP20 kit for TB2-D fuse base

IP20 kit for TB3-D fuse base

Terminal Cover

1

Part

Ref

Carton

Quantity

CS00*

CS0

CS1

CS2

CS3

6

6

6

6

6

Separator

3

Part

Ref

Carton

Quantity

BC00*

BC0

BC1-2

BC1-2

BC3

2

2

2

2

2

Part Ref Carton Quantity

BVL-50 1

Microswitch suitable for the following NH Fuse links:

- 400 Volts gG/gL

- 500 Volts gG/gL and aM

- 690 Volts gG/gL and aM

For detailed information, visit the Electrical IEC section at www.cooperbussmann.com

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

259

IEC & British Standard Fuses

Class gG/gL IEC 60269 Industrial Ferrule Fuses

8 x 31mm: 400Vac, 0.5 - 25A

10 x 38mm: 500Vac, 0.5 - 32A

14 x 51mm: 400Vac - 500Vac - 690Vac, 1 - 50A

22 x 58mm: 400Vac - 500Vac - 690Vac, 2 - 125A

260

For detailed information, visit the Electrical IEC section at www.cooperbussmann.com

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

Class aM IEC Industrial Ferrule Fuses - Class aM IEC

60269

8 x 31mm: 400Vac, 1 - 8A

10 x 38mm: 400Vac - 550Vac, 0.16 - 25A

14 x 51mm: 690Vac - 500Vac, 0.25 - 50A

22 x 58mm: 400Vac - 500Vac - 690Vac, 2 - 125A

Neutral Links

For detailed information, visit the Electrical IEC section at www.cooperbussmann.com

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

261

IEC & British Standard Fuses

Class aM & gG/gL IEC Industrial Ferrule Fuses with

Striker

14 X 51

22 X 58

Class gG/gL with Striker

Catalog Number

With Striker

C14G2S

C14G4S

C14G6S

C14G8S

C14G10S

C14G12S

C14G16S

C14G20S

C14G25S

C14G32S

C14G40S

C14G50S

Catalog Number

With Striker

C22G4S

C22G6S

C22G8S

C22G10S

C22G12S

C22G16S

C22G20S

C22G25S

C22G32S

C22G40S

C22G50S

C22G63S

C22G80S

C22G100S

C22G125S

Amp

Rating

12

16

20

25

32

6

8

2

4

10

40

50

Amp

Rating

16

20

25

32

40

8

10

4

6

12

50

63

80

100

125

Watts Loss

(W)

0.24

0.45

0.42

0.70

0.53

0.88

1.16

1.23

1.46

2.04

3.34

3.04

Watts Loss

(W)

0.48

0.47

0.73

0.74

0.83

1.21

1.29

1.53

2.13

3.40

3.48

4.46

5.86

6.61

8.42

Voltage

(AC)

500

500

400

Voltage

(AC)

690

690

400

Interrupting

Rating (kA)

120

120

Interrupting

Rating (kA)

80

80

14 X 51

22 X 58

Class aM with Striker

With Striker

C22M2S

C22M4S

C22M6S

C22M8S

C22M10S

C22M12S

C22M16S

C22M20S

C22M25S

C22M32S

C22M40S

C22M50S

C22M63S

C22M80S

C22M100S

C22M125S

Catalog Number

With Striker

C14M1S

C14M2S

C14M4S

C14M6S

C14M8S

C14M10S

C14M12S

C14M16S

C14M20S

C14M25S

C14M32S

C14M40S

C14M50S

Catalog Number

Amp

Rating

20

25

32

40

50

Amp

10

12

6

8

16

1

2

4

Rating

2

4

6

8

63

80

100

125

10

12

16

20

25

32

40

50

Watts Loss

(W)

0.14

0.24

0.45

0.42

0.70

0.53

0.88

1.16

1.23

1.46

2.04

3.34

3.04

Watts Loss

(W)

0.29

0.48

0.47

0.73

0.74

0.83

1.21

1.29

1.53

2.13

3.40

3.48

4.46

5.86

6.61

8.42

Voltage

(AC)

500

Interrupting

Rating (kA)

120

500

400

Voltage

(AC)

690

Interrupting

Rating (kA)

80

690

400

120

80

120

120

262

For detailed information, visit the Electrical IEC section at www.cooperbussmann.com

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

IEC & British Standard Fuses

HRC Fuse Holders

CAMaster

Specifications

Catalog Symbol:

See table below.

Description: The

CAMaster HRC fuse holder features a unique cam-action for easy fuse removal while allowing significantly improved contact pressure between fuse carrier and base contact that enhances electrical performance. A range of lockable safety carriers for the fuse holder (catalog reference: LSC), are available.

Ratings:

Volts: — 690V

Amps: — 30-100A (See Catalog Number table for details)

Agency Information: CE, CSA C22.2 No. 39; IEC 269

AND BS 88.

Mounting: 35mm DIN-Rail or single screw mounting.

Catalog Numbers

Catalog

Numbers

CM20CF

CM30CF

CM60CF

CM100CF

Amp

Ratings Details For:

30 HRCI-CA Applications

30

60

100

HRCII Applications

Fuse

Accepted

_CIF21

_H07C

_K07C

_K07CR

Accessory Catalog Numbers for CAMaster Units

Catalog Amp

Numbers

20BS

32BS

60/100BS

GLP

NI

Ratings

30

30

60/100

All

All

20LSC

30LSC

30

30

60/100LSC 60/100A

Details

Back Stud

Ganging Link Kit

660V Neon Indicator

Security Carrier with Clip

Fuse Holder

Accepted

CM20CF

CM30CF

CM60/100CF

3-Pole

CM20CF

CM30CF

CM60/100CF

SAFEloc

Specifications

Catalog

Symbol:

See table below.

Description: The

SAFEloc HRC fuse holders (for use with HRCI-CB fuses) provides a positive, stressfree fuse fitting and locks it in position to ensure safe insertion and withdrawal from the base. Base contacts are fully shrouded to help protect against electric shock. Shrouds utilize simple slide/snap action allowing access to the contact terminal screws.

Ratings:

Volts: — 600V

Amps: — 30-60A (See Catalog Number table for details)

Agency Information: CE, Designed to accommodate the compact range of offset blade fuse to CSA C22.2 No. 106,

HRCI-CB.

Mounting: 35mm DIN-Rail or single screw mounting.

Catalog Numbers*

Catalog Amp

Numbers

C30F

Ratings Connection

Front

C30BS

C30FBS

C60F

C60BS

30 Back

Front-Back

Front

Back 60

C60FBS Front-Back

*For use with HRCI-CB Fuses.

Fuse

Accepted

_CIF06

EK-Amp

Data Sheet: 4132

Data Sheet: 4133

For product data sheets, visit www.cooperbussmann.com/DatasheetsEle

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

263

Quik-Spec coordination panelboards

The new Quik-Spec coordination panelboard with a footprint up to 40% smaller than other fusible panelboards is now available up to 1200A

264

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement