SIM900D Safety Test Report

SIM900D Safety Test Report
Test Report issued under the responsibility of:
TEST REPORT
IEC 60950-1
Information technology equipment – Safety –
Part 1: General requirements
Report Reference No...................... :
SHESO10040052001
Date of issue..................................... :
2010-04-19
Total number of pages ......................
33
CB/CCA Testing Laboratory .......... :
SGS-CSTC Standards Technical Services (Shanghai) Co., Ltd.
Address ............................................ :
No. 588 West Jindu Rd, Xinqiao Town, Songjiang District 201612
Shanghai CHINA
Applicant’s name............................ :
Shanghai Simcom Ltd.
Address ............................................ :
Building A, SIM Technology Building, No.633, Jinzhong Road,
Changning District, Shanghai P.R. China
Manufacturer’s name ..................... :
Same as applicant
Address ............................................ :
Same as applicant
Factory’s name ............................... :
Same as applicant
Address ............................................ :
Same as applicant
Test specification:
Standard ........................................... :
IEC 60950-1:2005 (2nd Edition)
Non-standard test method…………..:
N/A
Test Report Form No...................... :
IEC60950_1A
Test Report Form(s) Originator ........ :
SGS Fimko Ltd
Master TRF ...................................... :
Dated 2009-09
Copyright © 2009 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from
the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme
procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended
to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
Test item description .....................:
Wireless module
Trade Mark ....................................... :
N/A
Manufacturer .................................... :
Shanghai Simcom Ltd.
Model/Type reference....................... :
SIM900D
Ratings ............................................. :
4.0Vdc
SHES-TRF-206IT
Page 3 of 33
Report No.: SHESO10040052001
Summary of testing:
These tests fulfill the requirements of standard ISO/IEC 17025.
When determining the test conclusion, the Measurement Uncertainty of test has been considered.
Unless specially specified, all accessories are tested with the appliance and are found in compliance with
the standard IEC 60950-1:2005 and EN 60950-1:2006 + A11:2009.
The EUT was tested with a test board, which can simulate the normal operation condition for the
equipment under test. The test board is provided by the applicant.
Tests performed (name of test and test clause):
Testing location:
All clause
Refer to page 1
Summary of compliance with National Differences:
European group differences and national differences (12 pages)
Copy of marking plate
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 4 of 33
Report No.: SHESO10040052001
Test item particulars .................................................. :
Equipment mobility .................................................... : [] movable [] hand-held
[] transportable
[] stationary [x] for building-in [] direct plug-in
Connection to the mains............................................ : [] pluggable equipment [] type A [] type B
[] permanent connection
[] detachable power supply cord
[] non-detachable power supply cord
[x] not directly connected to the mains
Operating condition ................................................... : [x] continuous
[] rated operating / resting time:
Access location ......................................................... : [] operator accessible
[] restricted access location
[x] assess in end equipment
Over voltage category (OVC) ................................... : [] OVC I [] OVC II [] OVC III
[x] other: Supplied by SELV
[] OVC IV
Mains supply tolerance (%) or absolute mains supply N/A
values ....................................................................... :
Tested for IT power systems .................................... : [] Yes
[x] No
IT testing, phase-phase voltage (V) .......................... : N/A
Class of equipment ................................................... : [] Class I [] Class II
[] Not classified
[x] Class III
Considered current rating (A) ................................... : P
Pollution degree (PD) ............................................... : [] PD 1
[x] PD 2
[] PD 3
IP protection class .................................................... : IPX0
Altitude during operation (m) .................................... : Up to 2000m
Altitude of test laboratory (m) ................................... : Up to 2000m
Mass of equipment (kg) ............................................ : 0.014
Possible test case verdicts:
- test case does not apply to the test object..................: N/A
- test object does meet the requirement .......................: P (Pass)
- test object does not meet the requirement .................: F (Fail)
Testing ..........................................................................:
Date of receipt of test item ............................................: 2010-04-14
Date(s) of performance of tests ....................................: 2010-04-14 to 2010-04-16
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 5 of 33
Report No.: SHESO10040052001
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Throughout this report a comma (point) is used as the decimal separator.
This document is issued by the company under its General Conditions of Service accessible at
http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of liability,
indemnification and jurisdiction issues defined therein.Any holder of this document is advised that
information contained hereon reflects the Company’s findings at the time of its intervention only and within
the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and this document
does not exonerate parties to a transaction from exercising all their rights and obligations under the
transaction documents. Any unauthorized alteration, forgery or falsification of the content or appearance of
this document is unlawful and offenders may be prosecuted to the fullest extent of the law.
Unless otherwise stated: (a) the results shown in this document refer only to the sample(s) tested and (b)
such sample(s) are retained for 3 months. This document cannot be reproduced except in full, without prior
approval of the company.
Contents:
1. Test Report – 31 pages;
2. Attachment 1 – Photos documents – 2 pages;
3. Attachment 2 – European group differences and national differences – 12 pages.
General product information:
The EUT is a Class III built-in wireless module, which supplied by 4.0Vdc and contains only SELV circuits.
The EUT is a complete Quad-band GSM / GPRS module in a SMT type with small dimensions, which deliver
GSM 900/1800MHz performance for voice, SMS, data, and fax in a small form factor and low power
consumption.
The support frequency band of EUT: GSM 900/1800
The maximum operate temperature in user manual is 80°C.
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 6 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
1
GENERAL
P
1.5
Components
P
1.5.1
General
P
Comply with IEC 60950-1 or relevant component
standard
P
1.5.2
Evaluation and testing of components
P
1.5.3
Thermal controls
No thermal controls
N/A
1.5.4
Transformers
No transformers
N/A
1.5.5
Interconnecting cables
No interconnecting cables
N/A
1.5.6
Capacitors bridging insulation
Class III equipment
N/A
1.5.7
Resistors bridging insulation
No resistors bridging
insulation
N/A
1.5.7.1
Resistors bridging functional, basic or
supplementary insulation
N/A
1.5.7.2
Resistors bridging double or reinforced insulation
between a.c. mains and other circuits
N/A
1.5.7.3
Resistors bridging double or reinforced insulation
between a.c. mains and antenna or coaxial cable
N/A
1.5.8
Components in equipment for IT power systems
Class III equipment.
N/A
1.5.9
Surge suppressors
No surge suppressors
N/A
1.5.9.1
General
N/A
1.5.9.2
Protection of VDRs
N/A
1.5.9.3
Bridging of functional insulation by a VDR
N/A
1.5.9.4
Bridging of basic insulation by a VDR
N/A
1.5.9.5
Bridging of supplementary, double or reinforced
insulation by a VDR
N/A
1.6
Power interface
N/A
1.6.1
AC power distribution systems
Class III equipment
N/A
1.6.2
Input current
Shall be evaluated in the end
product.
N/A
1.6.3
Voltage limit of hand-held equipment
Not hand-held equipment
N/A
1.6.4
Neutral conductor
Class III equipment
N/A
1.7
Marking and instructions
1.7.1
Power rating
Rated voltage(s) or voltage range(s) (V) ............... :
Symbol for nature of supply, for d.c. only ............... :
Result - Remark
Verdict
P
N/A
Not intend to connect to
mains directly.
N/A
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 7 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
Rated frequency or rated frequency range (Hz) .... :
N/A
Rated current (mA or A) ........................................ :
N/A
Manufacturer’s name or trade-mark or identification SIMCom
mark ...................................................................... :
P
Model identification or type reference ................... :
SIM900D
P
Symbol for Class II equipment only ....................... :
Class III equipment
Other markings and symbols ................................ :
See marking plate. The
additional marking does not
give rise to
misunderstandings.
N/A
P
1.7.2
Safety instructions and marking
P
1.7.2.1
General
P
1.7.2.2
Disconnect devices
Class III equipment
N/A
1.7.2.3
Overcurrent protective device
Class III equipment
N/A
1.7.2.4
IT power distribution systems
Class III equipment
N/A
1.7.2.5
Operator access with a tool
Built-in equipment. Shall be
evaluated in the end product.
N/A
1.2.7.6
Ozone
Not product ozone
N/A
1.7.3
Short duty cycles
Equipment is designed for
continuous operation.
N/A
1.7.4
Supply voltage adjustment ................................... :
No votage adjustment
N/A
Methods and means of adjustment; reference to
installation instructions ......................................... :
N/A
1.7.5
Power outlets on the equipment ........................... :
No such power outlets
N/A
1.7.6
Fuse identification (marking, special fusing
characteristics, cross-reference) .......................... :
No fuses
N/A
1.7.7
Wiring terminals
No such wiring terminals
N/A
1.7.7.1
Protective earthing and bonding terminals ........... :
Class III equipment
N/A
1.7.7.2
Terminals for a.c. mains supply conductors
Class III equipment
N/A
1.7.7.3
Terminals for d.c. mains supply conductors
Class III equipment
N/A
1.7.8
Controls and indicators
No control and indicator.
N/A
1.7.8.1
Identification, location and marking ...................... :
N/A
1.7.8.2
Colours ................................................................ :
N/A
1.7.8.3
Symbols according to IEC 60417 ......................... :
N/A
1.7.8.4
Markings using figures ....................................... :
No controls
N/A
1.7.9
Isolation of multiple power sources ..................... :
No multiple power source.
N/A
1.7.10
Thermostats and other regulating devices .......... :
No such device.
N/A
1.7.11
Durability
The marking withstands
required tests.
1.7.12
Removable parts
No removable parts
P
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 8 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
1.7.13
Replaceable batteries .......................................... :
No replaceable batteries
Language(s) ........................................................ :
N/A

1.7.14
Equipment for restricted access locations ........... :
Built-in equipment. Shall be
evaluated in the end product.
N/A
2
PROTECTION FROM HAZARDS
P
2.1
Protection from electric shock and energy hazards
P
2.1.1
Protection in operator access areas
Class III equpment contains
SELV circuit only.
2.1.1.1
Access to energized parts
No energized part.
P
N/A
Test by inspection ................................................. :
N/A
Test with test finger (Figure 2A) ............................ :
N/A
Test with test pin (Figure 2B) ................................ :
N/A
Test with test probe (Figure 2C) ............................ :
N/A
2.1.1.2
Battery compartments
No battery compartment.
N/A
2.1.1.3
Access to ELV wiring
No ELV circuit
N/A
Working voltage (Vpeak or Vrms); minimum
distance through insulation (mm)

2.1.1.4
Access to hazardous voltage circuit wiring
No hazardous voltage circuit.
N/A
2.1.1.5
Energy hazards ..................................................... :
No energy hazard.
N/A
2.1.1.6
Manual controls
No such part.
N/A
2.1.1.7
Discharge of capacitors in equipment
Not intended to connect to
mains supply directly.
N/A
Measured voltage (V); time-constant (s) ................ :
2.1.1.8
Energy hazards – d.c. mains supply

Not intended to connect to
d.c. mains supply.
N/A
a) Capacitor connected to the d.c. mains supply .. :
N/A
b) Internal battery connected to the d.c. mains
supply .................................................................... :
N/A
2.1.1.9
Audio amplifiers ..................................................... :
No audio amplifiers
N/A
2.1.2
Protection in service access areas
No hazardous voltage or
energy levels exist
N/A
2.1.3
Protection in restricted access locations
Built-in equipment. Shall be
evaluated in the end product.
N/A
2.2
SELV circuits
P
2.2.1
General requirements
P
2.2.2
Voltages under normal conditions (V) ................... :
Under SELV limit.
P
2.2.3
Voltages under fault conditions (V) ....................... :
Under SELV limit.
P
2.2.4
Connection of SELV circuits to other circuits ...... :
No other circuit.
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 9 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
2.3
TNV circuits
2.3.1
Limits
Result - Remark
Verdict
N/A
No TNV circuit.
N/A
Type of TNV circuits............................................... :

2.3.2
Separation from other circuits and from accessible
parts
N/A
2.3.2.1
General requirements
N/A
2.3.2.2
Protection by basic insulation
N/A
2.3.2.3
Protection by earthing
N/A
2.3.2.4
Protection by other constructions .......................... :
N/A
2.3.3
Separation from hazardous voltages
N/A
Insulation employed ............................................... :
2.3.4

Connection of TNV circuits to other circuits
N/A
Insulation employed ............................................... :

2.3.5
Test for operating voltages generated externally
N/A
2.4
Limited current circuits
N/A
2.4.1
General requirements
2.4.2
Limit values
No limited current circuit.
N/A
N/A
Frequency (Hz)....................................................... :

Measured current (mA) .......................................... :

Measured voltage (V)............................................. :

Measured circuit capacitance (nF or µF) ............... :

2.4.3
Connection of limited current circuits to other
circuits
N/A
2.5
Limited power sources
N/A
a) Inherently limited output
No limited power source.
N/A
b) Impedance limited output
N/A
c) Regulating network limited output under normal
operating and single fault condition
N/A
d) Overcurrent protective device limited output
N/A
Max. output voltage (V), max. output current (A),
max. apparent power (VA) ..................................... :

Current rating of overcurrent protective device (A) .:

2.6
Provisions for earthing and bonding
2.6.1
Protective earthing
2.6.2
Functional earthing
N/A
Class III equipment
N/A
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 10 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
2.6.3
Protective earthing and protective bonding
conductors
N/A
2.6.3.1
General
N/A
2.6.3.2
Size of protective earthing conductors
N/A
2
Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... :
2.6.3.3
Verdict

Size of protective bonding conductors
N/A
2
Rated current (A), cross-sectional area (mm ),
AWG ...................................................................... :

Protective current rating (A), cross-sectional area
2
(mm ), AWG .......................................................... :
2.6.3.4
Resistance of earthing conductors and their
terminations; resistance (Ω), voltage drop (V), test
current (A), duration (min)...................................... :
N/A
2.6.3.5
Colour of insulation ................................................ :
N/A
2.6.4
Terminals
N/A
2.6.4.1
General
N/A
2.6.4.2
Protective earthing and bonding terminals
N/A
Rated current (A), type, nominal thread diameter
(mm)....................................................................... :

2.6.4.3
Separation of the protective earthing conductor from
protective bonding conductors
N/A
2.6.5
Integrity of protective earthing
N/A
2.6.5.1
Interconnection of equipment
N/A
2.6.5.2
Components in protective earthing conductors and
protective bonding conductors
N/A
2.6.5.3
Disconnection of protective earth
N/A
2.6.5.4
Parts that can be removed by an operator
N/A
2.6.5.5
Parts removed during servicing
N/A
2.6.5.6
Corrosion resistance
N/A
2.6.5.7
Screws for protective bonding
N/A
2.6.5.8
Reliance on telecommunication network or cable
distribution system
N/A
2.7
Overcurrent and earth fault protection in primary circuits
N/A
2.7.1
Basic requirements
N/A
Class III equipment, no
primary circuits
Instructions when protection relies on building
installation
N/A
2.7.2
Faults not simulated in 5.3.7
N/A
2.7.3
Short-circuit backup protection
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 11 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
2.7.4
Number and location of protective devices ........... :
N/A
2.7.5
Protection by several devices
N/A
2.7.6
Warning to service personnel ................................ :
N/A
2.8
Safety interlocks
N/A
2.8.1
General principles
2.8.2
Protection requirements
N/A
2.8.3
Inadvertent reactivation
N/A
2.8.4
Fail-safe operation
N/A
2.8.5
Moving parts
N/A
2.8.6
Overriding
N/A
2.8.7
Switches and relays
N/A
2.8.7.1
Contact gaps (mm) ................................................ :
N/A
2.8.7.2
Overload test
N/A
2.8.7.3
Endurance test
N/A
2.8.7.4
Electric strength test
N/A
2.8.8
Mechanical actuators
N/A
2.9
Electrical insulation
N/A
2.9.1
Properties of insulating materials
N/A
2.9.2
Humidity conditioning
N/A
No safety interlocks
N/A
Relative humidity (%), temperature (°C) ............... :
2.9.3
Grade of insulation
2.9.4
Separation from hazardous voltages

Class III equipment. Only
functional insulation.
N/A
N/A
Method(s) used ..................................................... :

2.10
Clearances, creepage distances and distances through insulation
N/A
2.10.1
General
N/A
2.10.1.1
Frequency ............................................................. :
N/A
2.10.1.2
Pollution degrees ................................................... :
N/A
2.10.1.3
Reduced values for functional insualtion
N/A
2.10.1.4
Intervening unconnected conductive parts
N/A
2.10.1.5
Insulation with varying dimensions
N/A
2.10.1.6
Special separation requirements
N/A
2.10.1.7
Insulation in circuits generating starting pulses
N/A
2.10.2
Determination of working voltage
N/A
Class III equipment. Only
functional insulation provided.
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 12 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
2.10.2.1
General
N/A
2.10.2.2
RMS working voltage
N/A
2.10.2.3
Peak working voltage
N/A
2.10.3
Clearances
N/A
2.10.3.1
General
N/A
2.10.3.2
Mains transient voltages
N/A
a) AC mains supply ............................................... :
N/A
b) Earthed d.c. mains supplies .............................. :
N/A
c) Unearthed d.c. mains supplies .......................... :
N/A
d) Battery operation ............................................... :
N/A
2.10.3.3
Clearances in primary circuits
(see appended table 2.10.3
and 2.10.4)
N/A
2.10.3.4
Clearances in secondary circuits
(see appended table 2.10.3
and 2.10.4)
N/A
2.10.3.5
Clearances in circuits having starting pulses
(see appended table 2.10.3
and 2.10.4)
N/A
2.10.3.6
Transients from a.c. mains supply ........................ :
N/A
2.10.3.7
Transients from d.c. mains supply ........................ :
N/A
2.10.3.8
Transients from telecommunication networks and
cable distribution systems ..................................... :
N/A
2.10.3.9
Measurement of transient voltage levels
N/A
a) Transients from a mains suplply
N/A
For an a.c. mains supply ....................................... :
N/A
For a d.c. mains supply ......................................... :
N/A
b) Transients from a telecommunication network :
N/A
2.10.4
Creepage distances
N/A
2.10.4.1
General
N/A
2.10.4.2
Material group and caomparative tracking index
N/A
CTI tests ................................................................. :
Material group IIIb is assumed
to be used
2.10.4.3
Minimum creepage distances
(see appended table 2.10.3
and 2.10.4)
2.10.5
Solid insulation
N/A
2.10.5.1
General
N/A
2.10.5.2
Distances through insulation
2.10.5.3
Insulating compound as solid insulation
N/A
2.10.5.4
Semiconductor devices
N/A
2.10.5.5.
Cemented joints
2.10.5.6
Thin sheet material – General
(see appended table 2.10.5)
(see appended table 2.10.3
and 2.10.4)

N/A
N/A
N/A
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 13 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
2.10.5.7
Separable thin sheet material
Result - Remark
Verdict
N/A
Number of layers (pcs) ........................................... :

2.10.5.8
Non-separable thin sheet material
N/A
2.10.5.9
Thin sheet material – standard test procedure
N/A
Electric strength test
2.10.5.10
(see appended table 2.10.5)
Thin sheet material – alternative test procedure
Electric strength test

N/A
(see appended table 2.10.5)

2.10.5.11
Insulation in wound components
N/A
2.10.5.12
Wire in wound components
N/A
Working voltage .................................................... :
N/A
a) Basic insulation not under stress ...................... :
N/A
b) Basic, supplemetary, reinforced insulation ........ :
N/A
c) Compliance with Annex U ................................. :
N/A
Two wires in contact inside wound component;
angle between 45° and 90° ................................... :
N/A
Wire with solvent-based enamel in wound
components
N/A
2.10.5.13
Electric strength test
(see appended table 2.10.5)

Routine test
N/A
Additional insulation in wound components
N/A
Working voltage .................................................... :
N/A
- Basic insulation not under stress ........................ :
N/A
- Supplemetary, reinforced insulation .................... :
N/A
2.10.6
Construction of printed boards
N/A
2.10.6.1
Uncoated printed boards
(see appended table 2.10.3
and 2.10.4)
N/A
2.10.6.2
Coated printed boards
(see appended table 2.10.3
and 2.10.4)
N/A
2.10.6.3
Insulation between conductors on the same inner
surface of a printed board
(see appended table 2.10.3
and 2.10.4)
N/A
2.10.6.4
Insulation between conductors on different layers of
a printed board
2.10.5.14
Distance through insulation
N/A
(see appended table 2.10.5)
Number of insulation layers (pcs)........................... :
N/A
N/A
2.10.7
Component external terminations
(see appended table 2.10.3
and 2.10.4)
N/A
2.10.8
Tests on coated printed boards and coated
components
N/A
2.10.8.1
Sample preparation and preliminary inspection
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 14 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
2.10.8.2
Thermal conditioning
2.10.8.3
Electric strength test
2.10.8.4
Abrasion resistance test
N/A
2.10.9
Thermal cycling
N/A
2.10.10
Test for Pollution Degree 1 environment and
insulating compound
N/A
2.10.11
Tests for semiconductor devices and cemented
joints
N/A
2.10.12
Enclosed and sealed parts
N/A
3
WIRING, CONNECTIONS AND SUPPLY
P
3.1
General
P
3.1.1
Current rating and overcurrent protection
P
3.1.2
Protection against mechanical damage
No wireways, shall be
considered in end product
N/A
3.1.3
Securing of internal wiring
No internal wiring
N/A
3.1.4
Insulation of conductors
(see appended table 5.2)
N/A
3.1.5
Beads and ceramic insulators
N/A
3.1.6
Screws for electrical contact pressure
N/A
3.1.7
Insulating materials in electrical connections
N/A
3.1.8
Self-tapping and spaced thread screws
N/A
3.1.9
Termination of conductors
N/A
10 N pull test
N/A
3.1.10
Sleeving on wiring
N/A
3.2
Connection to a mains supply
N/A
3.2.1
Means of connection
3.2.1.1
Connection to an a.c. mains supply
N/A
3.2.1.2
Connection to a d.c. mains supply
N/A
3.2.2
Multiple supply connections
N/A
3.2.3
Permanently connected equipment
N/A
Number of conductors, diameter of cable and
conduits (mm) ....................................................... :
Result - Remark
Verdict
N/A
(see appended table 5.2)
Not intended to connected to
mains supply.
N/A
N/A

3.2.4
Appliance inlets
N/A
3.2.5
Power supply cords
N/A
3.2.5.1
AC power supply cords
N/A
Type ...................................................................... :

TRF No. IEC60950_1A
SHES-TRF-206IT
Page 15 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
2
Rated current (A), cross-sectional area (mm ),
AWG ..................................................................... :

3.2.5.2
DC power supply cords
N/A
3.2.6
Cord anchorages and strain relief
N/A
Mass of equipment (kg), pull (N) .......................... :

Longitudinal displacement (mm) ........................... :

3.2.7
Protection against mechanical damage
N/A
3.2.8
Cord guards
N/A
Diameter or minor dimension D (mm); test mass (g)
............................................................................... :

Radius of curvature of cord (mm) .......................... :

3.2.9
Supply wiring space
N/A
3.3
Wiring terminals for connection of external conductors
N/A
3.3.1
Wiring terminals
N/A
3.3.2
Connection of non-detachable power supply cords
N/A
3.3.3
Screw terminals
N/A
3.3.4
Conductor sizes to be connected
N/A
Rated current (A), cord/cable type, cross-sectional
2
area (mm )............................................................. :
3.3.5

Wiring terminal sizes
N/A
Rated current (A), type, nominal thread diameter
(mm) ..................................................................... :

3.3.6
Wiring terminal design
N/A
3.3.7
Grouping of wiring terminals
N/A
3.3.8
Stranded wire
N/A
3.4
Disconnection from the mains supply
N/A
3.4.1
General requirement
3.4.2
Disconnect devices
N/A
3.4.3
Permanently connected equipment
N/A
3.4.4
Parts which remain energized
N/A
3.4.5
Switches in flexible cords
N/A
3.4.6
Number of poles - single-phase and d.c. equipment
N/A
3.4.7
Number of poles - three-phase equipment
N/A
3.4.8
Switches as disconnect devices
N/A
3.4.9
Plugs as disconnect devices
N/A
3.4.10
Interconnected equipment
N/A
Not intended to connected to
mains supply.
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 16 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
3.4.11
Multiple power sources
N/A
3.5
Interconnection of equipment
N/A
3.5.1
General requirements
3.5.2
Types of interconnection circuits ........................... :
N/A
3.5.3
ELV circuits as interconnection circuits
N/A
3.5.4
Data ports for additional equipment
N/A
4
PHYSICAL REQUIREMENTS
4.1
Stability
Built-in components, shall be
evaluated in end product
N/A
P
N/A
Angle of 10°
Class III equipment.
N/A
Test force (N) ........................................................ :
Not floor standing equipment.
N/A
4.2
Mechanical strength
P
4.2.1
General
P
4.2.2
Steady force test, 10 N
P
4.2.3
Steady force test, 30 N
Built-in components, shall be
evaluated in end product
N/A
4.2.4
Steady force test, 250 N
Built-in components, shall be
evaluated in end product
N/A
4.2.5
Impact test
N/A
Fall test
N/A
Swing test
N/A
4.2.6
Drop test; height (mm) .......................................... :
N/A
4.2.7
Stress relief test
N/A
4.2.8
Cathode ray tubes
N/A
Picture tube separately certified ............................ :
(see separate test report or
attached certificate)
N/A
4.2.9
High pressure lamps
N/A
4.2.10
Wall or ceiling mounted equipment; force (N) ....... :
N/A
4.3
Design and construction
P
4.3.1
Edges and corners
P
4.3.2
Handles and manual controls; force (N) .............:
No such part.
N/A
4.3.3
Adjustable controls
No adjustable control.
N/A
4.3.4
Securing of parts
No parts are likely to loose
and create a hazard
N/A
4.3.5
Connection by plugs and sockets
No such part.
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 17 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
4.3.6
Direct plug-in equipment
Not direct plug-in equipment.
N/A
Torque .................................................................. :

Compliance with the relevant mains plug standard
.............................................................................. :
N/A
4.3.7
Heating elements in earthed equipment
No such elements, Class III
equipment
N/A
4.3.8
Batteries
No batteries
N/A
- Overcharging of a rechargeable battery
N/A
- Unintentional charging of a non-rechargeable
battery
N/A
- Reverse charging of a rechargeable battery
N/A
- Excessive discharging rate for any battery
N/A
4.3.9
Oil and grease
No oil and grease.
N/A
4.3.10
Dust, powders, liquids and gases
Not intend to product dust, or
using powders, liquids and
gases
N/A
4.3.11
Containers for liquids or gases
No such containers used
N/A
4.3.12
Flammable liquids ................................................ :
No flammable liquids
N/A
Quantity of liquid (l) .............................................. :
N/A
Flash point (°C) .................................................... :
N/A
4.3.13
Radiation
4.3.13.1
General
4.3.13.2
Ionizing radiation
4.3.13.3
No such radiation.
N/A
N/A
No ionizing radiation.
N/A
Measured radiation (pA/kg) .................................. :

Measured high-voltage (kV) ................................. :

Measured focus voltage (kV) ............................... :

CRT markings ...................................................... :

Effect of ultraviolet (UV) radiation on materials
No UV lamp used.
N/A
Part, property, retention after test, flammability
classification ......................................................... :
N/A
4.3.13.4
Human exposure to ultraviolet (UV) radiation ...... :
N/A
4.3.13.5
Laser (including LEDs)
(see separate test report of
IEC/EN 60825-1 /
IEC/EN 60825-2)
N/A
Laser class ........................................................... :

4.3.13.6
Other types ........................................................... :
N/A
4.4
Protection against hazardous moving parts
N/A
4.4.1
General
4.4.2
Protection in operator access areas .................... :
No hazardous moving parts
N/A
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 18 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
4.4.3
Protection in restricted access locations .............. :
N/A
4.4.4
Protection in service access areas
N/A
4.5
Thermal requirements
P
4.5.1
General
P
4.5.2
Temperature tests
P
Normal load condition per Annex L ...................... :

4.5.3
Temperature limits for materials
(see appended table 4.5)
4.5.4
Touch temperature limits
Built-in equipment, shall be
evaluated in the end product
N/A
4.5.5
Resistance to abnormal heat ............................... :
(see appended table 4.5.5)
N/A
4.6
Openings in enclosures
4.6.1
Top and side openings
N/A
Built-in equipment, shall be
evaluated in the end product
Dimensions (mm) ................................................. :
4.6.2
P
N/A

Bottoms of fire enclosures
N/A
Construction of the bottomm, dimensions (mm) .. :

4.6.3
Doors or covers in fire enclosures
N/A
4.6.4
Openings in transportable equipment
N/A
4.6.4.1
Constructional design measures
N/A
Dimensions (mm) ................................................. :

4.6.4.2
Evaluation measures for larger openings
N/A
4.6.4.3
Use of metallized parts
N/A
4.6.5
Adhesives for constructional purposes
N/A
Conditioning temperature (°C), time (weeks)........ :

4.7
Resistance to fire
N/A
4.7.1
Reducing the risk of ignition and spread of flame
Built-in equipment, shall be
evaluated in end product
N/A
Method 1, selection and application of components
wiring and materials
(see appended table 4.7)
N/A
Method 2, application of all of simulated fault
condition tests
(see appended table 5.3)
N/A
4.7.2
Conditions for a fire enclosure
N/A
4.7.2.1
Parts requiring a fire enclosure
N/A
4.7.2.2
Parts not requiring a fire enclosure
N/A
4.7.3
Materials
N/A
4.7.3.1
General
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 19 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
4.7.3.2
Materials for fire enclosures
N/A
4.7.3.3
Materials for components and other parts outside
fire enclosures
N/A
4.7.3.4
Materials for components and other parts inside fire
enclosures
N/A
4.7.3.5
Materials for air filter assemblies
N/A
4.7.3.6
Materials used in high-voltage components
N/A
5
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
N/A
5.1
Touch current and protective conductor current
N/A
5.1.1
General
5.1.2
Configuration of equipment under test (EUT)
N/A
5.1.2.1
Single connection to an a.c. mains supply
N/A
5.1.2.2
Redundant multiple connections to an a.c. mains
supply
N/A
5.1.2.3
Simultaneous multiple connections to an a.c. mains
supply
N/A
5.1.3
Test circuit
N/A
5.1.4
Application of measuring instrument
N/A
5.1.5
Test procedure
N/A
5.1.6
Test measurements
N/A
Class III equipment
Verdict
N/A
Supply voltage (V) ................................................ :

Measured touch current (mA) .............................. :

Max. allowed touch current (mA) ......................... :

Measured protective conductor current (mA) ....... :

Max. allowed protective conductor current (mA)... :

5.1.7
Equipment with touch current exceeding 3,5 mA
N/A
5.1.7.1
General ................................................................. :
N/A
5.1.7.2
Simultaneous multiple connections to the supply
N/A
5.1.8
Touch currents to telecommunication networks and
cable distribution systems and from
telecommunication networks
N/A
5.1.8.1
Limitation of the touch current to a
telecommunication network or to a cable
distribution system
N/A
5.1.8.2
Supply voltage (V) ................................................ :

Measured touch current (mA) .............................. :

Max. allowed touch current (mA) ......................... :

Summation of touch currents from
telecommunication networks
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 20 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
a) EUT with earthed telecommunication ports ..... :
N/A
b) EUT whose telecommunication ports have no
reference to protective earth
N/A
5.2
Electric strength
N/A
5.2.1
General
5.2.2
Test procedure
5.3
Abnormal operating and fault conditions
5.3.1
Protection against overload and abnormal operation (see appended table 5.3)
N/A
5.3.2
Motors
No motors
N/A
5.3.3
Transformers
No transformers
N/A
5.3.4
Functional insulation.............................................. :
Class III equipment
5.3.5
Electromechanical components
No such components
5.3.6
Audio amplifiers in ITE ......................................... :
N/A
5.3.7
Simulation of faults
N/A
5.3.8
Unattended equipment
N/A
5.3.9
Compliance criteria for abnormal operating and
fault conditions
P
5.3.9.1
During the tests
P
5.3.9.2
After the tests
P
Class III equipment, only
functional insulation.
N/A
N/A
P
P
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 21 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
6
CONNECTION TO TELECOMMUNICATION NETWORKS
N/A
6.1
Protection of telecommunication network service persons, and users of other
equipment connected to the network, from hazards in the equipment
N/A
6.1.1
Protection from hazardous voltages
N/A
6.1.2
Separation of the telecommunication network from earth
N/A
6.1.2.1
Requirements
N/A
(see appended table 5.2)
Supply voltage (V) ................................................ :

Current in the test circuit (mA) ........................... :

6.1.2.2
Exclusions ............................................................ :
N/A
6.2
Protection of equipment users from overvoltages on telecommunication networks
N/A
6.2.1
Separation requirements
N/A
6.2.2
Electric strength test procedure
N/A
6.2.2.1
Impulse test
(see appended table 5.2)
N/A
6.2.2.2
Steady-state test
(see appended table 5.2)
N/A
6.2.2.3
Compliance criteria
N/A
6.3
Protection of the telecommunication wiring system from overheating
N/A
Max. output current (A) ........................................ :

Current limiting method ........................................ :

7
CONNECTION TO CABLE DISTRIBUTION SYSTEMS
N/A
7.1
General
N/A
7.2
Protection of cable distribution system service
persons, and users of other equipment connected
to the system, from hazardous voltages in the
equipment
N/A
7.3
Protection of equipment users from overvoltages
on the cable distribution system
N/A
7.4
Insulation between primary circuits and cable
distribution systems
N/A
7.4.1
General
N/A
7.4.2
Voltage surge test
(see appended table 5.2)
N/A
7.4.3
Impulse test
(see appended table 5.2)
N/A
Not intend to connect to
distribution systems
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 22 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
A
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
N/A
A.1
Flammability test for fire enclosures of movable
equipment having a total mass exceeding 18 kg,
and of stationary equipment (see 4.7.3.2)
N/A
A.1.1
Samples ................................................................ :

Wall thickness (mm) ............................................. :

A.1.2
Conditioning of samples; temperature (°C) .......... :
N/A
A.1.3
Mounting of samples ............................................ :
N/A
A.1.4
Test flame (see IEC 60695-11-3)
N/A
Flame A, B, C or D ............................................... :

A.1.5
Test procedure
N/A
A.1.6
Compliance criteria
N/A
Sample 1 burning time (s) ..................................... :

Sample 2 burning time (s) ..................................... :

Sample 3 burning time (s) ..................................... :

A.2
Flammability test for fire enclosures of movable equipment having a total mass not
exceeding 18 kg, and for material and components located inside fire enclosures
(see 4.7.3.2 and 4.7.3.4)
A.2.1
Samples, material ................................................. :

Wall thickness (mm) ............................................. :

A.2.2
Conditioning of samples; temperature (°C) .......... :
N/A
A.2.3
Mounting of samples ............................................ :
N/A
A.2.4
Test flame (see IEC 60695-11-4)
N/A
Flame A, B or C .................................................... :
N/A

A.2.5
Test procedure
N/A
A.2.6
Compliance criteria
N/A
A.2.7
Sample 1 burning time (s) ..................................... :

Sample 2 burning time (s) ..................................... :

Sample 3 burning time (s) ..................................... :

Alternative test acc. to IEC 60695-11-5, cl. 5 and 9
N/A
Sample 1 burning time (s) ..................................... :

Sample 2 burning time (s) ..................................... :

Sample 3 burning time (s) ..................................... :

A.3
Hot flaming oil test (see 4.6.2)
N/A
A.3.1
Mounting of samples
N/A
A.3.2
Test procedure
N/A
A.3.3
Compliance criterion
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 23 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
B
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
N/A
B.1
General requirements
N/A
No motors
Position ................................................................. :

Manufacturer ........................................................ :

Type ..................................................................... :

Rated values ....................................................... :

B.2
Test conditions
N/A
B.3
Maximum temperatures
(see appended table 5.3)
N/A
B.4
Running overload test
(see appended table 5.3)
N/A
B.5
Locked-rotor overload test
N/A
Test duration (days) ............................................. :

Electric strength test: test voltage (V) .................. :

B.6
Running overload test for d.c. motors in secondary
circuits
N/A
B.6.1
General
N/A
B.6.2
Test procedure
N/A
B.6.3
Alternative test procedure
N/A
B.6.4
Electric strength test; test voltage (V) .................. :
N/A
B.7
Locked-rotor overload test for d.c. motors in
secondary circuits
N/A
B.7.1
General
N/A
B.7.2
Test procedure
N/A
B.7.3
Alternative test procedure
N/A
B.7.4
Electric strength test; test voltage (V) ................. :
N/A
B.8
Test for motors with capacitors
(see appended table 5.3)
N/A
B.9
Test for three-phase motors
(see appended table 5.3)
N/A
B.10
Test for series motors
N/A
Operating voltage (V) ........................................... :
C
ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
Position ................................................................. :
C.1

N/A
No isolation transformer.

Manufacturer ........................................................ :

Type ..................................................................... :

Rated values ....................................................... :

Method of protection ............................................. :

Overload test
(see appended table 5.3)
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 24 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
C.2
Insulation
(see appended table 5.2)
N/A
Protection from displacement of windings ............:
N/A
D
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4)
N/A
D.1
Measuring instrument
N/A
D.2
Alternative measuring instrument
N/A
E
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13)
N/A
F
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10 and Annex G)
N/A
G
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
N/A
G.1
Clearances
N/A
G.1.1
General
N/A
G.1.2
Summary of the procedure for determining
minimum clearances
N/A
G.2
Determination of mains transient voltage (V)
N/A
G.2.1
AC mains supply .................................................. :
N/A
G.2.2
Earthed d.c. mains supplies ................................. :
N/A
G.2.3
Unearthed d.c. mains supplies ............................. :
N/A
G.2.4
Battery operation .................................................. :
N/A
G.3
Determination of telecommunication network
transient voltage (V) ............................................. :
N/A
G.4
Determination of required withstand voltage (V)
N/A
G.4.1
Mains transients and internal repetitive peaks ..... :
N/A
G.4.2
Transients from telecommunication networks ..... :
N/A
G.4.3
Combination of transients
N/A
G.4.4
Transients from cable distribution systems
N/A
G.5
Measurement of transient voltages (V)
N/A
a) Transients from a mains supply
N/A
For an a.c. mains supply
N/A
For a d.c. mains supply
N/A
b) Transients from a telecommunication network
N/A
G.6
Determination of minimum clearances ................ :
N/A
H
ANNEX H, IONIZING RADIATION (see 4.3.13)
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 25 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
J
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
Verdict
N/A
Metal(s) used ....................................................... :

K
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.8)
N/A
K.1
Making and breaking capacity
N/A
K.2
Thermostat reliability; operating voltage (V) ......... :
N/A
K.3
Thermostat endurance test; operating voltage (V)
.............................................................................. :
N/A
K.4
Temperature limiter endurance; operating voltage
(V) ........................................................................ :
N/A
K.5
Thermal cut-out reliability
N/A
K.6
Stability of operation
L
ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL
BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.2)
L.1
Typewriters
N/A
L.2
Adding machines and cash registers
N/A
L.3
Erasers
N/A
L.4
Pencil sharpeners
N/A
L.5
Duplicators and copy machines
N/A
L.6
Motor-operated files
N/A
L.7
Other business equipment
M
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1)
N/A
M.1
Introduction
N/A
M.2
Method A
N/A
M.3
Method B
N/A
M.3.1
Ringing signal
N/A
M.3.1.1
Frequency (Hz) ..................................................... :

M.3.1.2
Voltage (V) ........................................................... :

M.3.1.3
Cadence; time (s), voltage (V) ............................. :

M.3.1.4
Single fault current (mA) ...................................... :

M.3.2
Tripping device and monitoring voltage ............... :
N/A
M.3.2.1
Conditions for use of a tripping device or a
monitoring voltage
N/A
M.3.2.2
Tripping device
N/A
M.3.2.3
Monitoring voltage (V) .......................................... :
N/A
(see appended table 5.3)
N/A
P
P
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 26 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
N
ANNEX N, IMPULSE TEST GENERATORS (see 1.5.7.2, 1.5.7.3, 2.10.3.9, 6.2.2.1,
7.3.2, 7.4.3 and Clause G.5)
N/A
N.1
ITU-T impulse test generators
N/A
N.2
IEC 60065 impulse test generator
N/A
P
ANNEX P, NORMATIVE REFERENCES
Q
ANNEX Q, Voltage dependent resistors (VDRs) (see 1.5.9.1)
N/A
a) Preferred climatic categories ........................... :
N/A
b) Maximum continuous voltage .......................... :
N/A
c) Pulse current .................................................... :
N/A
R
ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL
PROGRAMMES
N/A
R.1
Minimum separation distances for unpopulated
coated printed boards (see 2.10.6.2)
N/A
R.2
Reduced clearances (see 2.10.3)
N/A
S
ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3)
N/A
S.1
Test equipment
N/A
S.2
Test procedure
N/A
S.3
Examples of waveforms during impulse testing
N/A
T
ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
(see 1.1.2)
N/A

See separate test report
U
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
See separate test report

N/A

V
ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1)
N/A
V.1
Introduction
N/A
V.2
TN power distribution systems
N/A
W
ANNEX W, SUMMATION OF TOUCH CURRENTS
N/A
W.1
Touch current from electronic circuits
N/A
W.1.1
Floating circuits
N/A
W.1.2
Earthed circuits
N/A
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 27 of 33
Report No.: SHESO10040052001
IEC 60950-1
Clause
Requirement + Test
Result - Remark
Verdict
W.2
Interconnection of several equipments
N/A
W.2.1
Isolation
N/A
W.2.2
Common return, isolated from earth
N/A
W.2.3
Common return, connected to protective earth
N/A
X
ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS (see clause
C.1)
N/A
X.1
Determination of maximum input current
N/A
X.2
Overload test procedure
N/A
Y
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3)
N/A
Y.1
Test apparatus ..................................................... :
N/A
Y.2
Mounting of test samples ..................................... :
N/A
Y.3
Carbon-arc light-exposure apparatus ................... :
N/A
Y.4
Xenon-arc light exposure apparatus .................... :
N/A
Z
ANNEX Z, OVERVOLTAGE CATEGORIES (see 2.10.3.2 and Clause G.2)
N/A
AA
ANNEX AA, MANDREL TEST (see 2.10.5.8)
N/A
BB
ANNEX BB, CHANGES IN THE SECOND EDITION

TRF No. IEC60950_1A
SHES-TRF-206IT
Page 28 of 33
1.5.1
Report No.: SHESO10040052001
TABLE: List of critical components
Object/part No.
Manufacturer/
trademark
P
Type/model
Technical data
Standard
(Edition / year)
Mark(s) of
1
conformity )
PCB
CHINA
CIRCUIT
TECHNOLOGY
(SHANTOU)
CORP
6
V-0, 130°C min. UL 796
UL E99006
Alt.
Various
Various
V-0, 130°C min. UL 796
UL
1
) An asterisk indicates a mark which assures the agreed level of surveillance
Supplementary information:
1.6.2
TABLE: Electrical data (in normal conditions)
--
U (V)
I (A)
Irated (A)
P (W)
Fuse #
Ifuse (A)
Condition/status
4.0
0.28
--
1.12
--
--
Under GSM900
4.0
0.21
--
0.84
--
--
Under GSM1800
Supplementary information:
No rated input current provided. The test result just for reference.
2.10.3 and
2.10.4
TABLE: Clearance and creepage distance measurements
Clearance (cl) and creepage
distance (cr) at/of/between:
U peak
(V)
U r.m.s.
(V)
Required cl
(mm)
N/A
cl
(mm)
Required cr
(mm)
cr
(mm)
Functional:
Basic/supplementary:
Reinforced:
Supplementary information:
2.10.5
TABLE: Distance through insulation measurements
Distance through insulation (DTI) at/of:
U peak
(V)
U rms
(V)
N/A
Test
voltage
(V)
Required DTI
(mm)
DTI
(mm)
Supplementary information:
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 29 of 33
4.3.8
Report No.: SHESO10040052001
TABLE: Batteries
N/A
The tests of 4.3.8 are applicable only when appropriate battery
data is not available
Is it possible to install the battery in a reverse polarity position?
Non-rechargeable batteries
Discharging
Meas.
current
Manuf.
Specs.
Unintentional
charging
Rechargeable batteries
Charging
Meas.
current
Manuf.
Specs.
Discharging
Meas.
current
Manuf.
Specs.
Reversed
charging
Meas.
current
Manuf.
Specs.
Max.
current
during
normal
condition
Max.
current
during
fault
condition
Test results:
Verdict
- Chemical leaks
- Explosion of the battery
- Emission of flame or expulsion of molten metal
- Electric strength tests of equipment after completion of tests
Supplementary information:
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 30 of 33
4.5
Report No.: SHESO10040052001
TABLE: Thermal requirements
P
Supply voltage (V) ........................... :
4.0Vdc

Ambient Tmin (°C) ............................. :
20.0

Ambient Tmax (°C) ............................ :
20.2

T (°C)
Allowed
Tmax
(°C)
PCB
33.9
70
Metal shielding
31.8
--
Connector
29.0
--
Maximum measured temperature T of part/at::
Supplementary information:
Test condition: Input 4.0VDC under GSM900, which represnetive the worst test condition.
Only the maximum temperature is recorded in above form, because the input power values using other
bandwidths are all below the values above.
T shall not exceed (Tmax + Tamb – Tma) as it is non-temperature dependent equipment according to
clause 1.4.12.3.
Tma is 80 °C according to user’s manual.
Tamb is 20.0 °C
Allowed T of PCB of wireless CPU is 130-80+20.0 = 70 °C
Temperature T of winding:
t1 (°C)
R1 (Ω)
t2 (°C)
R2 (Ω)
T (°C)
Allowed Insulation
class
Tmax (°C)
Supplementary information:
4.5.5
TABLE: Ball pressure test of thermoplastic parts
N/A
Allowed impression diameter (mm) .....................: ≤ 2 mm
Part

Test temperature Impression diameter
(mm)
(°C)
Supplementary information:
4.7
TABLE: Resistance to fire
Part
Manufacturer of
material
N/A
Type of material
Thickness Flammability
(mm)
class
Evidence
Supplementary information:
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 31 of 33
5.2
Report No.: SHESO10040052001
TABLE: Electric strength tests, impulse tests and voltage surge tests
Test voltage applied between:
N/A
Voltage shape Test voltage Breakdown
(AC, DC,
(V)
Yes / No
impulse, surge)
Functional:
Basic/supplementary:
Reinforced:
Supplementary information:
5.3
Component
No.
TABLE: Fault condition tests
N/A
Ambient temperature (°C) ....................................:

Power source for EUT: Manufacturer, model/type,
output rating .........................................................:

Fault
Supply
voltage
(V)
Test
time
Fuse #
Fuse
current
(A)
Observation
Supplementary information:
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 32 of 33
Attachment 1
Report No. SHESO10040052001
Photo documents
Wireless module overview
Wireless module overview
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 33 of 33
Report No. SHESO10040052001
Wireless module on test board
TRF No. IEC60950_1A
SHES-TRF-206IT
Page 1 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
Verdict
ATTACHMENT TO TEST REPORT IEC 60950-1
EUROPEAN GROUP DIFFERENCES AND NATIONAL DIFFERENCES
Information technology equipment – Safety –
Part 1: General requirements
Differences according to................ :
EN 60950-1:2006 + A11:2009
Attachment Form No...................... :
EU_GD_IEC60950_1A
Attachment Originator ................... :
SGS Fimko Ltd
Master Attachment ......................... :
Date (2009-09)
Copyright © 2009 IEC System for Conformity Testing and Certification of Electrical Equipment
(IECEE), Geneva, Switzerland. All rights reserved.
EN 60950-1:2006/A11:2009 – CENELEC COMMON MODIFICATIONS
IEC 60950-1, GROUP DIFFERENCES (CENELEC common modifications
(EN))
Clause
Requirement + Test
Contents
Add the following annexes:
Annex ZA (normative)
Annex ZB (normative)
Annex ZC (informative)
General
Result - Remark
Verdict
P
Normative references to international
publications with their corresponding European
publications
Special national conditions
A-deviations
Delete all the “country” notes in the reference document according to the following
list:
1.4.8 Note 2
1.5.1
Note 2 & 3 1.5.7.1
Note
1.5.8 Note 2
1.5.9.4
Note
1.7.2.1
Note 4, 5 & 6
2.2.3 Note
2.2.4
Note
2.3.2
Note
2.3.2.1 Note 2
2.3.4
Note 2
2.6.3.3
Note 2 & 3
2.7.1 Note
2.10.3.2
Note 2
2.10.5.13
Note 3
3.2.1.1 Note
3.2.4
Note 3.
2.5.1
Note 2
4.3.6 Note 1 & 2 4.7
Note 4
4.7.2.2
Note
4.7.3.1Note 2
5.1.7.1
Note 3 & 4 5.3.7
Note 1
6
Note 2 & 5 6.1.2.1
Note 2
6.1.2.2
Note
6.2.2 Note 6.
2.2.1
Note 2
6.2.2.2
Note
7.1
Note 3
7.2
Note 7.3
Note 1 & 2
G.2.1 Note 2
Annex H
Note 2
P
Page 2 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
1.3.Z1
Add the following subclause:
1.3.Z1 Exposure to excessive sound pressure
The apparatus shall be so designed and
constructed as to present no danger when used
for its intended purpose, either in normal
operating conditions or under fault conditions,
particularly providing protection against exposure
to excessive sound pressures from headphones
or earphones.
Not produce sound pressure
Verdict
N/A
NOTE Z1 A new method of measurement is described
in EN 50332-1, Sound system equipment:
Headphones and earphones associated with portable
audio equipment - Maximum sound pressure level
measurement methodology and limit considerations Part 1: General method for “one package equipment”,
and in EN 50332-2, Sound system equipment:
Headphones and earphones associated with portable
audio equipment - Maximum sound pressure level
measurement methodology and limit considerations Part 2: Guidelines to associate sets with headphones
coming from different manufacturers.
1.5.1
Add the following NOTE:
N/A
NOTE Z1 The use of certain substances in electrical
and electronic equipment is restricted within the EU:
see Directive 2002/95/EC
1.7.2.1
Add the following NOTE:
N/A
NOTE Z1 In addition, the instructions shall include, as
far as applicable, a warning that excessive sound
pressure from earphones and headphones can cause
hearing loss
2.7.1
Replace the subclause as follows:
Class III equipment.
Basic requirements
To protect against excessive current, shortcircuits and earth faults in PRIMARY CIRCUITS,
protective devices shall be included either as
integral parts of the equipment or as parts of the
building installation, subject to the following, a), b)
and c):
a) except as detailed in b) and c), protective
devices necessary to comply with the
requirements of 5.3 shall be included as parts of
the equipment;
b) for components in series with the mains input
to the equipment such as the supply cord,
appliance coupler, r.f.i. filter and switch, shortcircuit and earth fault protection may be provided
by protective devices in the building installation;
N/A
Page 3 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
Verdict
c) it is permitted for PLUGGABLE EQUIPMENT
Class III equipment.
TYPE B or PERMANENTLY CONNECTED
EQUIPMENT, to rely on dedicated overcurrent
and short-circuit protection in the building
installation, provided that the means of protection,
e.g. fuses or circuit breakers, is fully specified in
the installation instructions.
If reliance is placed on protection in the building
installation, the installation instructions shall so
state, except that for PLUGGABLE EQUIPMENT
TYPE A the building installation shall be regarded
as providing protection in accordance with the
rating of the wall socket outlet.
N/A
2.7.2
This subclause has been declared ‘void’.
N/A
3.2.3
Delete the NOTE in Table 3A, and delete also in
this table the conduit sizes in parentheses.
3.2.5.1
Replace
“60245 IEC 53” by “H05 RR-F”;
Class III equipment.
“60227 IEC 52” by “H03 VV-F or
H03 VVH2-F”;
“60227 IEC 53” by “H05 VV-F or
H05 VVH2-F2”.
In Table 3B, replace the first four lines by the
following:
a)
Up to and including 6 |
0,75 |
b)
Over 6 up to and including 10| (0,75)
1,0 |
c)
Over 10 up to and including 16| (1,0)
1,5
|
In the conditions applicable to Table 3B delete the
a)
words “in some countries” in condition .
In NOTE 1, applicable to Table 3B, delete the
second sentence.
N/A
3.3.4
In Table 3D, delete the fourth line: conductor
Class III equipment.
sizes for 10 to 13 A, and replace with the
following:
Over 10 up to and including 16 | 1,5 to 2,5 | 1,5 to
4
|
Delete the fifth line: conductor sizes for 13 to 16 A
N/A
4.3.13.6
Add the following NOTE:
N/A
NOTE Z1 Attention is drawn to 1999/519/EC: Council
Recommendation on the limitation of exposure of the
general public to electromagnetic fields 0 Hz to 300
GHz. Standards taking into account this
Recommendation which demonstrate compliance with
the applicable EU Directive are indicated in the OJEC.
Not permanently connected
equipment.
No such radiation.
N/A
Page 4 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
Annex H
Replace the last paragraph of this annex by:
At any point 10 cm from the surface of the
OPERATOR ACCESS AREA, the dose rate shall
not exceed 1 µSv/h (0,1 mR/h) (see NOTE).
Account is taken of the background level.
Replace the notes as follows:
No ionizing radiation.
Verdict
N/A
NOTE These values appear in Directive
96/29/Euratom.
Delete NOTE 2.
Bibliography
Additional EN standards.

ZA
NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH
THEIR CORRESPONDING EUROPEAN PUBLICATIONS

ZB
ANNEX ZB, SPECIAL NATIONAL CONDITIONS (EN)
—
1.2.4.1
In Denmark, certain types of Class I appliances
(see 3.2.1.1) may be provided with a plug not
establishing earthing conditions when inserted
into Danish socket-outlets.
Class III equipment.
N/A
1.2.13.14
In Norway and Sweden, for requirements see
1.7.2.1 and 7.3 of this annex.
Not intended to be connected
to cable distribution system.
N/A
1.5.7.1
In Finland, Norway and Sweden, resistors
Class III equipment.
bridging BASIC INSULATION in CLASS I PLUGGABLE
EQUIPMENT TYPE A must comply with the
requirements in 1.5.7.1. In addition when a single
resistor is used, the resistor must withstand the
resistor test in 1.5.7.2.
N/A
1.5.8
In Norway, due to the IT power system used (see Class III equipment.
annex V, Figure V.7), capacitors are required to
be rated for the applicable line-to-line voltage
(230 V).
N/A
1.5.9.4
In Finland, Norway and Sweden, the third
dashed sentence is applicable only to equipment
as defined in 6.1.2.2 of this annex.
N/A
1.7.2.1
In Finland, Norway and Sweden, CLASS I
Class III equipment.
PLUGGABLE EQUIPMENT TYPE A intended for
connection to other equipment or a network shall,
if safety relies on connection to protective earth or
if surge suppressors are connected between the
network terminals and accessible parts, have a
marking stating that the equipment must be
connected to an earthed mains socket-outlet.
The marking text in the applicable countries shall
be as follows:
In Finland: "Laite on liitettävä suojakoskettimilla
varustettuun pistorasiaan"
No such component.
N/A
Page 5 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
In Norway: “Apparatet må tilkoples jordet
Class III equipment.
stikkontakt”
In Sweden: “Apparaten skall anslutas till jordat
uttag”
In Norway and Sweden, the screen of the cable
distribution system is normally not earthed at the
entrance of the building and there is normally no
equipotential bonding system within the building.
Therefore the protective earthing of the building
installation need to be isolated from the screen of
a cable distribution system.
It is however accepted to provide the insulation
external to the equipment by an adapter or an
interconnection cable with galvanic isolator, which
may be provided by e.g. a retailer.
The user manual shall then have the following or
similar information in Norwegian and Swedish
language respectively, depending on in what
country the equipment is intended to be used in:
“Equipment connected to the protective earthing
of the building installation through the mains
connection or through other equipment with a
connection to protective earthing – and to a cable
distribution system using coaxial cable, may in
some circumstances create a fire hazard.
Connection to a cable distribution system has
therefore to be provided through a device
providing electrical isolation below a certain
frequency range (galvanic isolator, see EN
60728-11).”
NOTE In Norway, due to regulation for installations of cable
distribution systems, and in Sweden, a galvanic isolator shall
provide electrical insulation below 5 MHz. The insulation shall
withstand a dielectric strength of 1,5 kV r.m.s., 50 Hz or 60 Hz,
for 1 min.
Translation to Norwegian (the Swedish text will
also be accepted in Norway):
“Utstyr som er koplet til beskyttelsesjord via
nettplugg og/eller via annet jordtilkoplet
utstyr – og er tilkoplet et kabel-TV nett, kan
forårsake brannfare. For å unngå dette skal det
ved tilkopling av utstyret til kabel-TV nettet
installeres en galvanisk isolator mellom utstyret
og kabel- TV nettet.”
Translation to Swedish:
”Utrustning som är kopplad till skyddsjord via
jordat vägguttag och/eller via annan
utrustning och samtidigt är kopplad till kabel-TV
nät kan i vissa fall medfőra risk főr
brand. Főr att undvika detta skall vid anslutning
av utrustningen till kabel-TV nät
galvanisk isolator finnas mellan utrustningen och
kabel-TV nätet.”
Verdict
N/A
Page 6 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
Verdict
1.7.5
In Denmark, socket-outlets for providing power to No socket-outlet provided.
other equipment shall be in accordance with the
Heavy Current Regulations, Section 107-2-D1,
Standard Sheet DK 1-3a, DK 1-5a or DK 1-7a,
when used on Class I equipment. For
STATIONARY EQUIPMENT the socket-outlet
shall be in accordance with Standard Sheet DK 11b or DK 1-5a.
For CLASS II EQUIPMENT the socket outlet shall be
in accordance with Standard Sheet DKA 1-4a.
N/A
2.2.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1
and 6.1.2.2 of this annex.
N/A
2.3.2
In Finland, Norway and Sweden there are
additional requirements for the insulation. See
6.1.2.1 and 6.1.2.2 of this annex.
No TNV circuit.
N/A
2.3.4
In Norway, for requirements see 1.7.2.1, 6.1.2.1
and 6.1.2.2 of this annex.
No TNV circuit.
N/A
2.6.3.3
In the United Kingdom, the current rating of the
circuit shall be taken as 13 A, not 16 A.
Class III equipment.
N/A
2.7.1
In the United Kingdom, to protect against
excessive currents and short-circuits in the
PRIMARY CIRCUIT of DIRECT PLUG-IN
EQUIPMENT, tests according to 5.3 shall be
conducted, using an external protective device
rated 30 A or 32 A. If these tests fail, suitable
protective devices shall be included as integral
parts of the DIRECT PLUG-IN EQUIPMENT, so
that the requirements of 5.3 are met.
Class III equipment.
N/A
2.10.5.13
In Finland, Norway and Sweden, there are
additional requirements for the insulation, see
6.1.2.1 and 6.1.2.2 of this annex.
Class III equipment, only
SELV circuit inside.
N/A
3.2.1.1
In Switzerland, supply cords of equipment having Class III equipment.
a RATED CURRENT not exceeding 10 A shall be
provided with a plug complying with SEV 1011 or
IEC 60884-1 and one of the following dimension
sheets:
SEV 6532-2.1991 Plug Type 15
3P+N+PE
250/400 V, 10 A
N/A
Page 7 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
Verdict
SEV 6533-2.1991 Plug Type 11
L+N
250 V, 10 A
SEV 6534-2.1991 Plug Type 12
L+N+PE
250 V, 10 A
In general, EN 60309 applies for plugs for
currents exceeding 10 A. However, a 16 A plug
and socket-outlet system is being introduced in
Switzerland, the plugs of which are according to
the following dimension sheets, published in
February 1998:
SEV 5932-2.1998: Plug Type 25 , 3L+N+PE
230/400 V, 16 A
SEV 5933-2.1998:Plug Type 21, L+N, 250 V, 16A
SEV 5934-2.1998: Plug Type 23, L+N+PE 250 V,
16 A
3.2.1.1
In Denmark, supply cords of single-phase
Class III equipment.
equipment having a rated current not
exceeding13 A shall be provided with a plug
according to the Heavy Current Regulations,
Section 107-2-D1.
CLASS I EQUIPMENT provided with socketoutlets with earth contacts or which are intended
to be used in locations where protection against
indirect contact is required according to the wiring
rules shall be provided with a plug in accordance
with standard sheet DK 2-1a or DK 2-5a.
If poly-phase equipment and single-phase
equipment having a RATED CURRENT
exceeding 13 A is provided with a supply cord
with a plug, this plug shall be in accordance with
the Heavy Current Regulations, Section 107-2-D1
or EN 60309-2.
N/A
3.2.1.1
In Spain, supply cords of single-phase equipment Class III equipment.
having a rated current not exceeding 10 A shall
be provided with a plug according to UNE
20315:1994.
Supply cords of single-phase equipment having a
rated current not exceeding 2,5 A shall be
provided with a plug according to UNE-EN
50075:1993.
CLASS I EQUIPMENT provided with socketoutlets with earth contacts or which are intended
to be used in locations where protection against
indirect contact is required according to the wiring
rules, shall be provided with a plug in accordance
with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply
cord with a plug, this plug shall be in accordance
with UNE-EN 60309-2.
N/A
Page 8 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
3.2.1.1
In the United Kingdom, apparatus which is fitted Class III equipment.
with a flexible cable or cord and is designed to be
connected to a mains socket conforming to BS
1363 by means of that flexible cable or cord and
plug, shall be fitted with a ‘standard plug’ in
accordance with Statutory Instrument 1768:1994 The Plugs and Sockets etc. (Safety) Regulations
1994, unless exempted by those regulations.
Verdict
N/A
NOTE ‘Standard plug’ is defined in SI 1768:1994 and
essentially means an approved plug conforming to BS
1363 or an approved conversion plug.
3.2.1.1
In Ireland, apparatus which is fitted with a flexible Class III equipment.
cable or cord and is designed to be connected to
a mains socket conforming to I.S. 411 by means
of that flexible cable or cord and plug, shall be
fitted with a 13 A plug in accordance with
Statutory Instrument 525:1997 - National
Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic
Use) Regulations 1997.
N/A
3.2.4
In Switzerland, for requirements see 3.2.1.1 of
this annex.
N/A
3.2.5.1
In the United Kingdom, a power supply cord with Class III equipment.
conductor of 1,25 mm2 is allowed for equipment
with a rated current over 10 A and up to and
including 13 A.
N/A
3.3.4
In the United Kingdom, the range of conductor
Class III equipment.
sizes of flexible cords to be accepted by terminals
for equipment with a RATED CURRENT of over
10 A up to and including 13 A is:
2
2
• 1,25 mm to 1,5 mm nominal cross-sectional
area.
N/A
4.3.6
In the United Kingdom, the torque test is
Not intended for direct plug-in.
performed using a socket outlet complying with
BS 1363 part 1:1995, including Amendment
1:1997 and Amendment 2:2003 and the plug part
of DIRECT PLUG-IN EQUIPMENT shall be
assessed to BS 1363: Part 1, 12.1, 12.2, 12.3,
12.9, 12.11, 12.12, 12.13, 12.16 and 12.17,
except that the test of 12.17 is performed at not
less than 125 °C. Where the metal earth pin is
replaced by an Insulated Shutter Opening Device
(ISOD), the requirements of clauses 22.2 and 23
also apply.
N/A
4.3.6
In Ireland, DIRECT PLUG-IN EQUIPMENT is
Not intended for direct plug-in.
known as plug similar devices. Such devices shall
comply with Statutory Instrument 526:1997 National Standards Authority of Ireland (Section
28) (Electrical plugs, plug similar devices and
sockets for domestic use) Regulations, 1997.
N/A
No appliance inlet.
Page 9 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
Verdict
5.1.7.1
In Finland, Norway and Sweden TOUCH
Class III equipment.
CURRENT measurement results exceeding 3,5
mA r.m.s. are permitted only for the following
equipment:
• STATIONARY PLUGGABLE EQUIPMENT
TYPE A that
○
is intended to be used in a RESTRICTED
ACCESS LOCATION where equipotential
bonding has been applied, for example, in a
telecommunication centre; and
○
has provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR; and
○
is provided with instructions for the
installation of that conductor by a SERVICE
PERSON;
• STATIONARY PLUGGABLE EQUIPMENT
TYPE B;
• STATIONARY PERMANENTLY CONNECTED
EQUIPMENT.
N/A
6.1.2.1
In Finland, Norway and Sweden, add the
No TNV circuit.
following text between the first and second
paragraph of the compliance clause:
If this insulation is solid, including insulation
forming part of a component, it shall at least
consist of either
two layers of thin sheet material, each of
which shall pass the
electric strength test
below, or
one layer having a distance through
insulation of at least 0,4 mm,
which shall pass
the electric strength test below.
If this insulation forms part of a semiconductor
component (e.g. an optocoupler), there is no
distance through insulation requirement for the
insulation consisting of an insulating compound
completely filling the casing, so that
CLEARANCES and CREEPAGE DISTANCES do
not exist, if the component passes the electric
strength test in accordance with the compliance
clause below and in addition
passes the tests and inspection criteria of
2.10.11 with an electric
strength test of 1,5 kV
multiplied by 1,6 (the electric strength test of
2.10.10 shall be performed using 1,5 kV), and
is subject to ROUTINE TESTING for
electric strength during
manufacturing, using a
test voltage of 1,5 kV.
N/A
Page 10 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
Verdict
It is permitted to bridge this insulation with a
capacitor complying with EN 132400:1994,
subclass Y2.
A capacitor classified Y3 according to EN
132400:1994, may bridge this insulation under
the following conditions:
the insulation requirements are satisfied by
having a capacitor classified Y3 as defined by
EN 132400, which in addition to the Y3 testing, is
tested with an impulse test of 2,5 kV defined in
EN 60950- 1:2006, 6.2.2.1;
the additional testing shall be performed on
all the test specimens as
described in EN 132400;
the impulse test of 2,5 kV is to be
performed before the endurance test in
EN 132400, in the sequence of tests as described
in EN 132400.
6.1.2.2
In Finland, Norway and Sweden, the exclusions No TNV circuit.
are applicable for PERMANENTLY CONNECTED
EQUIPMENT, PLUGGABLE EQUIPMENT TYPE
B and equipment intended to be used in a
RESTRICTED ACCESS LOCATION where
equipotential bonding has been applied, e.g. in a
telecommunication centre, and which has
provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR and is
provided with instructions for the installation of
that conductor by a SERVICE PERSON.
N/A
7.2
In Finland, Norway and Sweden, for
Not intended to be connected
requirements see 6.1.2.1 and 6.1.2.2 of this
to cable distribution system.
annex.
The term TELECOMMUNICATION NETWORK in
6.1.2 being replaced by the term CABLE
DISTRIBUTION SYSTEM.
N/A
7.3
In Norway and Sweden, for requirements see
1.2.13.14 and 1.7.2.1 of this annex.
Not intended to be connected
to cable distribution system.
N/A
7.3
In Norway, for installation conditions see EN
60728-11:2005.
Not intended to be connected
to cable distribution system.
N/A
ZC
ANNEX ZC, NATIONAL DEVIATIONS (EN).
A-DEVIATIONS (informative)
1.5.1
Sweden (Ordinance 1990:944)
Add the following:
NOTE In Sweden, switches containing mercury are not
permitted.
—
No switch.
N/A
Page 11 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
1.5.1
Switzerland (Ordinance on environmentally
hazardous substances SR 814.081, Annex 1.7,
Mercury - Annex 1.7 of SR 814.81 applies for
mercury.)
Add the following:
No switch.
Verdict
N/A
NOTE In Switzerland, switches containing mercury
such as thermostats, relays and level controllers are
not allowed.
1.7.2.1
Denmark (Heavy Current Regulations)
Supply cords of CLASS I EQUIPMENT, which is
delivered without a plug, must be provided with a
visible tag with the following text:
Vigtigt!
Lederen med grøn/gul isolation
må kun tilsluttes en klemme mærket
eller
If essential for the safety of the equipment, the
tag must in addition be provided with a diagram,
which shows the connection of the other
conductors, or be provided with the following text:
“For tilslutning af de øvrige ledere, se
medfølgende installationsvejledning.”
N/A
1.7.2.1
Germany (Gesetz über technische Arbeitsmittel
und Verbraucherprodukte (Geräte- und
Produktsicherheitsgesetz – GPSG) [Law on
technical labour equipment and consumer
products], of 6th January 2004, Section 2, Article
4, Clause (4), Item 2).
If for the assurance of safety and health certain
rules during use, amending or maintenance of a
technical labour equipment or readymade
consumer product are to be followed, a manual in
German language has to be delivered when
placing the product on the market.
Of this requirement, rules for use even only by
SERVICE PERSONS are not exempted.
N/A
1.7.5
Denmark (Heavy Current Regulations)
With the exception of CLASS II EQUIPMENT
provided with a socket outlet in accordance with
the Heavy Current Regulations, Section 107-2D1, Standard Sheet DK 1-4a, CLASS II
EQUIPMENT shall not be fitted with socketoutlets for providing power to other equipment.
N/A
1.7.13
Switzerland (Ordinance on chemical hazardous
risk reduction SR 814.81, Annex 2.15 Batteries)
Annex 2.15 of SR 814.81 applies for batteries.
N/A
Page 12 of 12
Report No.: SHESO10040052001
IEC60950_1A - ATTACHMENT
Clause
Requirement + Test
Result - Remark
5.1.7.1
Denmark (Heavy Current Regulations, Chapter
707, clause 707.4)
TOUCH CURRENT measurement results
exceeding 3,5 mA r.m.s. are permitted only for
PERMANENTLY CONNECTED EQUIPMENT
and PLUGGABLE EQUIPMENT TYPE B.
******END OF REPORT******
Verdict
N/A
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement