Swegon ADAPT Free Instructions

Swegon ADAPT Free Instructions

Swegon ADAPT Free is a versatile air diffuser that can be used in a variety of applications, including offices, schools, and hospitals. It is designed to provide optimal indoor air quality and comfort by automatically adjusting the airflow rate based on the occupancy and temperature of the space.

Some of the key features of the Swegon ADAPT Free include:

  • Automatic airflow control: The diffuser uses a built-in sensor to detect the occupancy and temperature of the space, and automatically adjusts the airflow rate to maintain a comfortable environment.
  • Energy efficiency: The diffuser's energy-efficient design helps to reduce energy consumption and costs.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Swegon ADAPT Free Instructions | Manualzz

ADAPT

TM

Free d

Installation – Commissioning – Maintenance

20151013 / Art. No. 1545217

Installation

All connections to the duct system should be done with a straight duct of the same dimension as the box inlet and with a length > 2 x ØD. If a flexible duct is used, it should be stretched so it remains as straight as possible, see figure 1.

1. The commissioning box can be suspended from a ceiling and connected to a duct system.The diffuser is secured to the ceiling by connecting the M8 threaded rod (A) into the popnut on the top of the diffuser, see figure 3.

2. Make sure that the orientation of the sensor module aligns with the extension of the room, see figure 2. If the connecting duct does not enter the room as in the example in figure 4, the frontplate of the diffuser must be dismantled and rotated in a direction with the sensor module directed as shown in figure 2. Then fixate and secure the diffuser with screws or pop rivets. Readjust the hanger rods of the commissioning box if necessary .

3. The front plate is dismantled by pressing the fixing pins of the bottom plate outward, which will loosen it from the upper cone. Detach the safety cord that secures front plate to the upper cone and disconnect the connector

(C, figure 3) from the top of the front plate. When reassembling, press together the S-hook to prevent it from coming loose.

B

A

Figure 1. Using a flexible duct.

C

Figure 2. The orientation of the sensor module in a room or in an office module. The LED’s of the sensor should be aligned with the extension of the room in a straight line, facing the short sides of the room as shown by the arrow in the figure.

Figure 3. ADAPT Free, installation.

1

WISE

Figure 4. Lighting fixtures or similar objects must not be installed beneath the diffuser as this disrupts the presence detection and room temperature measurement.

Commissioning

All the ADAPT Air diffusers are delivered preset into commissioning mode, which means that the air diffuser is set to max. airflow by override control.

When the ADAPT air diffuser is in commissioning mode, the light-emitting diode shines orange. The different LED indications:

• Steady green LED: Normal operation, the air diffuser is operating normally.

• Flashing green LED: The air diffuser has just been powered on and calibration is in progress.

• Steady red LED: Function failure, see separate documentation inte the TUNE Adapt manual.

• Steady orange LED: The commissioning mode, max. airflow

• Flashing orange LED: Other commissioning modes and all the forced control situations of the feedback control system.

Maintenance

The exterior surface of the ADAPT air diffusers can be cleaned whenever necessary using lukewarm water with dishwashing detergent added.

The duct system is accessible through the air diffuser and the commissioning box.

More information about the commissioning process itself can be read in the Project Manual for the Wise system and the TUNE Adapt manual.

2

Swegon reserves the right to alter specifications. 20151013 www.swegon.com

WISE

24 V

Modbus

Figure 5. Commissioning with TUNE Adapt.

Electrical connections.

All the connections are wired to the CONNECT Adapt connection box. From there, the Master air diffuser is connected by means of the LINK Adapt (RJ45) cable included in the delivery. The slave air diffusers, if required, are connected by means of the same type of cable to their respective slave contacts. If there are more than 2 slave air diffusers, a SPLIT

Link Adapt should be used for further connection to the last slave air diffuser. See Figure 7. If SPLIT Link Adapt is used, the maximum length of LINK Adapt from the connection box to the last air diffuser is 15 meters. If ADAPT is to be connected through Modbus communication, this should be done with the LINK Modbus (RJ12) cable. The maximum length of

SPLIT Link Modbus is 10 meters from the connection box to the last air diffuser. Use double CONNECT Adapts if longer distances are required. All cables and contacts are different so that they will not be confused or incorrectly connected.

Electrical data

ADAPT is supplied with power via the connection box. See the wiring diagram in figure 7 or relevant diagram from the

Swegon Templates application, containing details for the specific installation. It is important that cables with appropriate cross-sectional area, transformers of correct size and power supply cables of correct length are selected. This can for example be carried out with the dimensioning tool

“Cable and Transformer Design”, available for download from www.swegon.com (the application is available in english and swedish language versions).

Supply voltage 24 V AC ±10 %

Max. power consumption (controller only)

Cable rating (controller only)

Ambient temperature

3 VA

0,6 A

0 °C - +50 °C

1

3

2

Figure 6. Air diffuser connections.

1. Connection for LINK Adapt cable (RJ45)

2. Connection for the LINK Modbus cable (RJ12).

3. Direct 24 V connection if a connection box is not used and the air diffuser will be completely “stand alone”.

3

Swegon reserves the right to alter specifications. 20151013 www.swegon.com

WISE

4

12

3

1

6

12

5

2

5

6

12

11

6

2

5

5

2

6

20

Master

21

Slave

22

Slave

23

Modbus

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

- + C

10

7a

G

OUT1

G0

5

1

6

7b

7c

1

3

2

Figure 7. Wiring of Master/Slave air diffusers and accessories.

1. ADAPT Master air diffuser

2. ADAPT Slave air diffusers

3. CONNECT Adapt, connection box

4. 24 V AC Transformer

5. LINK Adapt (5 m long RJ45 cable)

6. LINK Modbus (5 m long RJ12 cable)

7a. TUNE Temp (1 VA)

7b. DETECT Quality (Room version with display - Q0: 1 VA.

Room version without display Q1 and duct version - Q2: 3 VA)

7c. DETECT RH, humidity sensor (1 VA)

8. ACTUATOR, radiator control (max 3 valves at 6 VA)

9. ADAPT Relay, relay for lighting

10. Connection to main control system (Modbus RTU)

11. SPLIT Link RJ45

12. SPLIT Modbus RJ12, max. stab length, 10 m.

*) Only one of the accessories in paragraph 7 can be connected at any one time in a room installation.

4

Swegon reserves the right to alter specifications. 20151013

9

A1 A2 1 3

8 www.swegon.com