Smart-Sensor-VAV Overview
156
Figure 7-1: Smart-Sensor-VAV
The Smart-Sensor-VAV will be referred to as the Smart-Sensor throughout this document.
The Smart-Sensor has a built-in thermistor for temperature sensing, a 2-line / 8-character LCD display and five push buttons. The Smart-Sensor measures the room temperature every few seconds, updates the value displayed on the LCD and sends the temperature to the controller.
The Smart-Sensor has a regular user mode for building occupants and a password-protected configuration mode that consists of a main configuration menu and 3 sub-menus (I/O display mode, flow configuration mode and flow calibration mode). The menu hierarchy and the options available in each menu and submenu are illustrated in Figure 7-2 .
VAV / VVT User Guide
Smart-Sensor-VAV User Guide
Figure 7-2: System Overview
VAV / VVT User Guide 157
Startup and Errors
Normally, the first time that the Smart-Sensor is powered up, i.e. connected to a VAV/VVT from which it draws power, the text
SENSOR INIT…
will appear on the LCD screen. The
Smart-Sensor will also show this text after any power cycle of the VAV signifying that it is able to communicate with the VAV and that it is being initialized.
If there is a loss of communication between the Smart-Sensor and the VAV during regular operation, or if communication cannot be established on power up, the text
SENSOR COM FAIL will appear on the LCD display. The Smart-Sensor will periodically attempt to reestablish communication with the VAV and display the text
SENSOR RETRY!
If communication cannot be established, the LCD display will alternate between these two messages.
If a communications problem is encountered, examine the wiring between the
Smart-Sensor and the VAV. Verify the polarity and ensure that the wires are properly inserted into the wire terminals and that a wire length of 15 meters (50 feet) has not been exceeded.
158 VAV / VVT User Guide
Smart-Sensor-VAV User Guide
Button Operation
Figure 7-3: Smart Sensor Push Buttons
The Smart-Sensor has five push buttons. A simple press-and-release of a button can be used to scroll through menu items or change displayed values one at a time. Alternatively, the UP or
DOWN button can be held to simulate repeated button presses, which is convenient when making changes to setpoints, adjusting the damper position, etc. In general, a single press of a button allows the user to view the status and an immediate second press allows the user to change the status.
VAV / VVT User Guide 159
User Mode
The user mode is meant to be accessible by building occupants so that they can view temperatures, adjust the setpoint and initiate an override. By default, the Smart-Sensor will display the room temperature.
Button Usage in User Mode
Not used in user mode.
Used to view the next available menu option.
Used to put the VAV into override mode. The occupancy state will temporarily change to BYPASS.
The DOWN button is used to view and decrease the setpoint.
Pressing the button once will display the setpoint. Pressing it a second time will decrease the temperature by 0.5 degrees. Holding down the button will decrease the value continuously until the button is released or the lower limit is reached.
The UP button is used to view and increase the setpoint. Pressing the button once will display the setpoint. Pressing it a second time will increase the temperature by 0.5 degrees. Holding down the button will increase the value continuously until the button is released or until the upper limit is reached.
160 VAV / VVT User Guide
Smart-Sensor-VAV User Guide
User Mode – Display Text Definitions
Displayed Text Detailed Description
RoomTemp
Setpoint
Displays the current room temperature. The room temperature is the default display screen for the Smart-Sensor.
The temperature is read from the onboard temperature sensor and written to
nvoSpaceTemp
.
(SI Units: ºC / Imperial Units: ºF)
Displays the current midpoint. The setpoint can be modified by using the UP and DOWN arrows. The midpoint is the median value between the heating and cooling setpoints.
When the midpoint is changed, the heating and cooling setpoints will change by the same value.
Pressing the UP/DOWN buttons is like rotating the knob on regular wall-mounted sensors.
The diagram below illustrates the relation between the midpoint and the heating/cooling setpoints. In this example, the range between the heating and cooling setpoints is 2ºC and the midpoint is 21 ºC.
Field
Type
Read-
Only
Editable
If the HVAC mode is in cooling, the effective setpoint, i.e. the actual setpoint, will be the cooling setpoint. Similarly, if the HVAC mode is in heating, the effective setpoint will be the heating setpoint.
If the VAV has been setup for single room control only, then the setpoint that is entered using the Smart-Sensor (when in occupied, bypass or standby modes) is written to
nvoEffectSetpt
. However
nvoEffectSetpt
will equal
nviSetpoint
if
nviSetpoint
has been assigned a value, since it overrides all other setpoint values.
If the VAV is being used for two room control and the Smart-Sensor is associated with the first room, i.e. it provides SPACE_TEMP_ROOM1
VAV / VVT User Guide 161
162
Cooling
Heating
OccState
Override
OutdoorTemp and is used to specify SETPOINT_ROOM1, then
nvoEffectSetpt
will equal the average of
SETPOINT_ROOM1 and
SETPOINT_ROOM2.
If there is no sensor providing a reading for
SETPOINT_ROOM2, then the controller averages SETPOINT_ROOM1 with the median of the heating and cooling setpoints stored in
nciSetPts.
(SI Units: ºC / Imperial Units: ºF)
If the HVAC mode is in cooling, the Smart-
Sensor will display the text
Cooling followed by the cooling setpoint, which is the effective setpoint at the time.
The HVAC mode is read from
nvoUnitStatus.
If the HVAC mode is in cooling, the Smart-
Sensor will display the text
Heating followed by the heating setpoint, which is the effective setpoint at the time.
The HVAC mode is read from
nvoUnitStatus.
Shows the current occupancy status.
The occupancy state is read from
nvoOccState
.
The text
Override will appear when the
Override button is pressed, and
nvoOccState
will be set to OC_BYPASS.
The controller will remain in bypass mode for the time period specified in
SCPTbypassTime
.
The outdoor temperature is only displayed if
nviOutdoorTemp
has been bound to a controller that can provide an outdoor temperature reading.
(SI Units: ºC / Imperial Units: ºF)
Read-
Only
Read-
Only
Read-
Only
Read-
Only
Read-
Only
The values that can be changed by the Smart-Sensor are read directly from the device in the
VAV Device Configuration
tool.
VAV / VVT User Guide
Smart-Sensor-VAV User Guide
Password-Protected Configuration Mode
The Smart-Sensor configuration mode is protected by a password and is hidden from building occupants. The configuration mode provides building personnel with a number of advanced configuration, monitoring and air balancing options as summarized in Figure 7-2.
Entering the Configuration Mode
To access the password-protected configuration mode, do the following:
1. Hold the and the buttons simultaneously for a few seconds. Release the buttons when you see the display screen text change to Login 5000.
2. Use the arrow keys to increase or decrease the displayed number until it matches the configured password. By default the password is 5001.
If the password has previously been changed and has been forgotten, examine the value of UCPTcomPassword or check the Password field in the
Error!
Reference source not found.
window.
3. Press the button to submit the password that was entered.
4. If the correct password has been entered, the Smart-Sensor will be in the
Srvc Pin
screen. If an incorrect password has been entered, the Smart-Sensor will display the text
Password
Failed
.
The Smart-Sensor will automatically exit the configuration mode 20 minutes after the last button press. To exit the configuration mode manually, hold the and the buttons simultaneously for a few seconds.
Button Usage in Configuration Mode
Used to access one of the three available submenus. This button will not have any effect unless the Smart-Sensor displays the text
Submenu
which indicates that it is possible to access a specific submenu.
Used to view the next available menu option.
Used like an "Enter" key on a keyboard. When this button is pressed, the value specified is sent to the controller.
Decreases the displayed parameter value.
VAV / VVT User Guide 163
Increases the displayed parameter value.
164 VAV / VVT User Guide
Smart-Sensor-VAV User Guide
Configuration Mode – Display Text Definitions
Displayed Text Detailed Description Field
Type
Editable
Srvc Pin
SI Units
Temp Cal
VAV Mode
Submenu IO
State
Submenu Flow
Cfg
Submenu Flow
Cal
This menu is used to send a service pin message over the network. Setting the value to 1 and pressing the Override button is equivalent to pressing the service pin button on the controller.
This menu is used to specify the display units for temperature values. Setting the value to 0 will cause the Smart-Sensor to display temperatures in imperial units (°F & CFM). Setting the value to 1 will cause the Smart-Sensor to display SI units (°C & LPS).
The value is written to the field of
UCPTvavOptions
.
SmartSensorInSI
This menu is used to calibrate the temperature sensor. The arrow buttons can be used to increase or decrease the temperature calibration offset value by 0.1° per button press. The offset can be up to +/- 12.7°C or +/- 22.8°F. to The value is
UCPTcomInputCfg.Offset
. written
(SI Units: ºC / Imperial Units: ºF)
This menu is used to specify whether VAV or
VVT mode is being used. This menu can also be used to put a VAV controller into VVT mode.
Setting the value to 0 will put the controller into
VVT mode. Setting the value to 1 will put the controller into VAV mode.
The value is written to the
VVTmode
field of the
UCPTvavOptions
.
Pressing the Submenu button while in this menu will display the I/O state submenu.
Pressing the Submenu button while in this menu will display the flow configuration submenu.
Pressing the Submenu button while in this menu will display the flow calibration submenu.
Editable
Editable
Editable
Submenu
Link
Submenu
Link
Submenu
Link
VAV / VVT User Guide 165
I/O State Configuration Submenu - Display Text Definitions
Displayed Text Detailed Description
Trm Load
Field
Type
Read-
Only
Input N
Output N
Displays the controller's terminal load. The terminal load value is read from
nvoTerminalLoad
.
Displays the value of hardware input N (where
N is between 1 and 4).
The value is read from
nvoHwInputN
(where
N is between 1 and 4).
Displays the value of hardware output N (where
N is between 1 and 6).
The value is read from the output value.
Read-
Only
Read-
Only
166 VAV / VVT User Guide
Smart-Sensor-VAV User Guide
Flow Configuration Submenu
Displayed Text Detailed Description
Min Flow
MinFlwHt
The minimum airflow that is to be maintained by the VAV box during normal operation. The flow setpoint only falls below the minimum flow if the Use zero flow as min flow while unoccupied or standby option is selected or if the flow setpoint is overridden.
Setting the minimum flow to zero means the damper can be fully closed in which case no fresh air will be supplied to the zone that the
VAV controls.
The value entered in this field is written to
SCPTminFlow
.
(SI Units: LPS / Imperial Units: CFM )
The minimum airflow that is to be maintained by the VAV when duct heating is turned ON unless it is overridden.
In occupied mode, the VAV controller generally controls the load by modulating the air flow between the Minimum flow and the
Maximum flow. The minimum flow heat value can be used when using an electric duct heater to prevent it from overheating.
When the minimum flow heat is lower than the
Minimum flow, the VAV controller uses the minimum flow heat as a low limit to protect an electric duct heater from overheating.
When the minimum flow heat is higher than the
Minimum flow, the VAV controller controls the load by modulating the air flow between the minimum flow heat and the Maximum flow on a call for duct heating.
In any case, when the air flow read by the VAV controller is 10% smaller than the minimum flow heat the duct heating is not allowed. The duct heating can restart if the air flow returns above 5% less than the minimum flow heat.
For a water duct coil, the minimum flow heat can be set to 0 to remove this protection.
Field
Type
Editable
Editable
VAV / VVT User Guide 167
168
Max Flow
Nom Flow
DmpDrTm
Open CCW
The value entered in this field is written to
SCPTminFlowHeat
.
(SI Units: LPS / Imperial Units: CFM )
The maximum allowable airflow. The flow setpoint never exceeds this value unless overridden.
The value entered in this field is written to
SCPTmaxFlow
.
(SI Units: LPS / Imperial Units: CFM )
The expected airflow when the damper is fully open. It is also used to determine the next damper movement. If the nominal flow is unknown, it can be left at zero in which case the
Maximum flow will be used to determine the next damper movement.
The value entered in this field is written to
SCPTnomAirFlow
.
(SI Units: LPS / Imperial Units: CFM )
Used to specify the time that the damper will take to go from the fully closed position to the fully open position or vice-versa. Used only for built-in actuator.
The damper drive time can be set to between 45 seconds and 150 seconds. However, it is recommended to use the default value of 95 seconds.
The value entered in this field is written to
UCPTdamperDriveTime.
Used to specify the direction (Clockwise or
Counter Clockwise) in which the actuator rotates to open the damper. Set the value to 0 for clockwise or 1 for counter clockwise.
A binary value representing the damper direction is written to the
UCPTvavOptions.
DamperCCW
field of
Editable
Editable
Editable
Editable
VAV / VVT User Guide
Area
PitotFct
Smart-Sensor-VAV User Guide
This value is used to perform a calibration of the
VAV box without using a reference instrument, but by using the K Factor Calculator window.
The value entered in this field is written to
SCPTductArea
.
(SI Units: cm2 / Imperial Units: in2 )
Most VAV box / Pitot tube manufacturers create their Pitot tubes in a manner that it amplifies the differential pressure by a certain factor. Contact them to acquire the value of this factor if they have not provided it.
The Pitot factor is therefore a divider that is applied to the differential pressure reading that compensates for varying characteristics and flow effects in VAV box equipment and pickup probes, ie. the amplification factor. The Pitot
Factor must be entered along with the Area to ensure precise calibration.
The value entered in this field is written to
SCPTGainVAV
.
Editable
Editable
VAV / VVT User Guide 169
170
Flow Calibration Submenu
Displayed Text Detailed Description
Flow
RunNrmOp
GotoMinF
GotoMaxF
The real-time air flow that is being supplied to the zone. The flow reading will only be available if the VAV has been calibrated.
The flow value is read from
nvoAirFlow
.
(SI Units: LPS / Imperial Units: CFM )
Terminates calibration mode and puts the VAV controller back into normal operation.
Calibration mode is activated as soon as a command is sent from the flow calibration submenu and it ends automatically when the
Smart-Sensor returns to user mode or the
RunNrmOp command is sent to the VAV.
While the controller is in calibration mode it will not respond to control demands.
Only use this button if the VAV is already calibrated. When this button is pressed, the VAV automatically maintains the Minimum Flow that was specified in the
Min Flow
screen of the
Flow Configuration Submenu , by adjusting the damper position. The VAV will dynamically compensate for changes in air pressure to ensure that the minimum airflow is maintained.
The VAV will continue to maintain the minimum airflow until the
RunNrmOp command is sent to the VAV or the passwordprotected menu is exited.
Only use this button if the VAV is already calibrated. When this button is pressed, the VAV automatically maintains the Maximum Flow that was specified in the
Max Flow
screen of the
Flow Configuration Submenu, by adjusting the damper position. The VAV will dynamically compensate for changes in air pressure to ensure that the maximum airflow is maintained.
The VAV will continue to maintain the minimum airflow until the
RunNrmOp command is sent to the VAV or the password- protected menu is exited.
Field
Type
Read
Only
Editable
Editable
Editable
VAV / VVT User Guide
Dmp Cmd
Dmp Pos
DifPress
CalLoVal
CalHiVal
CalToMin
CalToMax
VAV / VVT User Guide
Smart-Sensor-VAV User Guide
Moves the damper to the position that you specify in this screen. The damper can open between 0% (fully closed) and 100% (fully open).
The damper will remain at the position specified until the
RunNrmOp command is sent to the
VAV or the password-protected menu is exited.
Displays the current damper position (in %).
Editable
Read-
Only
Read-
Only
Displays the current differential pressure reading.
(SI Units: PA / Imperial Units: "WC)
When this option is used, the VAV can be calibrated based on an airflow that is close to the minimum flow that was specified in the
Min
Flow
screen of the Flow Configuration Submenu .
Adjust the damper until the flow hood (capture hood) reading is close to the minimum flow.
Enter the flow hood reading then press the
Override button. This is quicker than making micro adjustments to the damper as required when using the
CalToMin
option.
When this option is used, the VAV can be calibrated based on an airflow that is close to the maximum flow that was specified in the
Max
Flow
screen of the Flow Configuration Submenu .
Adjust the damper until the flow hood reading is close to the maximum flow. Enter the flow hood reading then press the Override button. This is quicker than making micro adjustments to the damper as required when using the
CalToMax option.
When this option is used, the VAV can be calibrated to the exact airflow that was specified in the
Min Flow
screen of the Flow Configuration
Submenu . Adjust the damper until the flow hood reading is equal to the minimum flow, change the onscreen value from 0 to 1 then press the
Override button.
When this option is used, the VAV can be calibrated to the exact airflow that was specified in the
Max Flow
screen of the Flow Configuration
Submenu.
Adjust the damper until the flow hood reading is equal to the maximum flow, change the onscreen value from 0 to 1 then press the
Editable
Editable
Editable
Editable
171
DoAutoCal
NOT CALIBRAT
Override button.
Performs an automatic calibration of the VAV.
Depending on whether or not the duct area has been entered in the
Area
screen of the Flow
Configuration Submenu, the VAV will use one of two automatic calibration methods. A detailed description of these methods is provided in the
K Factor/Pitot Factor Calibration section.
Displayed if the VAV has not been calibrated.
However if the VAV has been calibrated, it will show the calibration code that is stored in
nviCalibCode
.
Editable
Read-
Only
The values that can be changed by the Smart-Sensor are read directly from the device in the
VAV Device Configuration
window.
172 VAV / VVT User Guide